Section 11 · AE

Air-side equipment

Air-side HVAC systems at steady state: coil loads and the air state at each point of the system, compared with a quasi-analytical solution.

Cases run
24
Values compared
1371
Outside example range
249
Harness checks passed
1130 of 1132
Run date
2026-10-03
AE coil and zone loads24 rows
CaseQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE101Sensible Heating Load (QZHsensible) (kWh/h)2.9312.9302.9312.9312.931In range
AE101Sensible Cooling Load (QZClatent) (kWh/h)00000In range
AE101Latent Load (QZlatent) (kWh/h)0.58610.58610.58670.58620.5861In range
AE101Coil Load (QH) (kWh/h)8.4048.3728.7688.4848.420In range
AE101Loads Sensible (QCsensible) (kWh/h)00000In range
AE101Latent (QClatent) (kWh/h)00000In range
AE101Total (QCtotal) (kWh/h)00000In range
AE101Outlet RH (RHcco) (%)6.3866.3536.8676.5456.385In range
AE103Sensible Heating Load (QZHsensible) (kWh/h)00000In range
AE103Sensible Cooling Load (QZClatent) (kWh/h)1.4651.4651.4671.4651.465In range
AE103Latent Load (QZlatent) (kWh/h)0.58610.58600.58970.58660.5861In range
AE103Coil Load (QH) (kWh/h)00000In range
AE103Loads Sensible (QCsensible) (kWh/h)0.78320.75230.78410.77120.7835In range
AE103Latent (QClatent) (kWh/h)000.010330.0014760In range
AE103Total (QCtotal) (kWh/h)0.78320.76200.78410.77270.7835In range
AE103Outlet RH (RHcco) (%)32.83331.65433.03032.58132.843In range
AE104Sensible Heating Load (QZHsensible) (kWh/h)00000In range
AE104Sensible Cooling Load (QZClatent) (kWh/h)2.9312.9302.9312.9312.931In range
AE104Latent Load (QZlatent) (kWh/h)0.58610.58580.58610.58610.5861In range
AE104Coil Load (QH) (kWh/h)00000In range
AE104Loads Sensible (QCsensible) (kWh/h)3.4923.3893.5433.4883.497In range
AE104Latent (QClatent) (kWh/h)2.0572.0122.2932.1402.054In range
AE104Total (QCtotal) (kWh/h)5.5495.5335.8365.6285.551In range
AE104Outlet RH (RHcco) (%)99.88498.66010099.748100In range
AE node states105 rows · 25 outside
CaseQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE101DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)−29.000−29−29−29−29In range
AE101DRY BULB TEMPERATURE (°C) · Mixed Air (ma)4.0034.0034.4544.2954.003In range
AE101DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)29.32428.99429.32629.14729.316In range
AE101DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)29.32428.99429.32629.14729.316In range
AE101DRY BULB TEMPERATURE (°C) · Supply Air (sa)29.93029.22229.93329.65529.922In range
AE101DRY BULB TEMPERATURE (°C) · Zone Air (z1)21.11121.09921.11821.11121.111In range
AE101DRY BULB TEMPERATURE (°C) · Return Air (ra)21.11121.09921.11821.11121.111In range
AE101HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)2.59e-42.59e-43.44e-42.78e-42.59e-4In range
AE101HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0016060.0015950.0016960.0016310.001604In range
AE101HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.0016060.0015950.0016960.0016310.001604In range
AE101HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0016060.0015950.0016960.0016310.001604In range
AE101HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0016060.0015950.0016960.0016310.001604In range
AE101HUMIDITY RATIO (G/GDA) · Zone Air (z1)0.0023060.0022000.0023730.0023080.002304In range
AE101HUMIDITY RATIO (G/GDA) · Return Air (ra)0.0023060.0022000.0023740.0023100.002304In range
AE101SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)692.65691.84833.33776.09691.93In range
AE101SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)787.91787.06833.33814.18787.16In range
AE101SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)859.85830.35859.03842.94859.06Above range
AE101SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)859.85830.35859.03842.94859.06Above range
AE101SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)861.57830.35860.69842.78860.78Above range
AE101SPECIFIC VOLUME (L/KGDA) · Zone Air (z1)837.45830.35836.69833.99836.69Above range
AE101SPECIFIC VOLUME (L/KGDA) · Return Air (ra)837.45830.35836.69833.34836.69Above range
AE101ENTHALPY (J/GDA) · Location Outdoor Air (oa)−28.507−28.540−28.330−28.472−28.540In range
AE101ENTHALPY (J/GDA) · Mixed Air (ma)8.0508.0318.6808.4468.051In range
AE101ENTHALPY (J/GDA) · Heat Coil Outlet (hco)33.56833.30933.56233.46033.592Above range
AE101ENTHALPY (J/GDA) · Cool Coil Outlet (cco)33.56833.30933.56233.46033.592Above range
AE101ENTHALPY (J/GDA) · Supply Air (sa)34.18033.90034.17334.05734.203Above range
AE101ENTHALPY (J/GDA) · Zone Air (z1)27.07127.03427.26327.12127.091In range
AE101ENTHALPY (J/GDA) · Return Air (ra)27.07127.03427.26327.12127.091In range
AE101MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.11270.11280.11950.11410.1128Below range
AE101MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.32930.32960.35860.33980.3296Below range
AE101MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.32930.32960.35860.33980.3296Below range
AE101MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.32930.32960.35860.33980.3296Below range
AE101MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.32930.32960.35860.33980.3296Below range
AE101MASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE101MASS FLOW RATE (KGDA/S) · Return Air (ra)0.21660.21680.23910.22710.2168Below range
AE103DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)15.50015.50015.50015.50015.500In range
AE103DRY BULB TEMPERATURE (°C) · Mixed Air (ma)20.77420.68920.77420.73220.774In range
AE103DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)20.77420.72121.27820.81620.774In range
AE103DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)18.50018.4621918.57318.504In range
AE103DRY BULB TEMPERATURE (°C) · Supply Air (sa)19.0851919.10119.07419.088In range
AE103DRY BULB TEMPERATURE (°C) · Zone Air (z1)23.33323.32923.34823.33423.333In range
AE103DRY BULB TEMPERATURE (°C) · Return Air (ra)23.33323.32923.34823.33523.333In range
AE103HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.0029330.0028950.0029480.0029280.002936In range
AE103HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0043240.0042840.0043550.0043110.004325In range
AE103HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.0043240.0042840.0043550.0043110.004325In range
AE103HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0043240.0042840.0043550.0043110.004325In range
AE103HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0043240.0042840.0043550.0043110.004325In range
AE103HUMIDITY RATIO (G/GDA) · Zone Air (z1)0.0050010.0049600.0050590.0049970.005002In range
AE103HUMIDITY RATIO (G/GDA) · Return Air (ra)0.0050010.0049600.0050590.0050030.005002In range
AE103SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)822.32821.41833.33827.93821.57In range
AE103SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)839.20830.35838.44834.68838.44Above range
AE103SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)839.20830.35838.44834.68838.44Above range
AE103SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)832.71830.35833.33832.09831.96In range
AE103SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)834.38829.58833.45831.94833.63Above range
AE103SPECIFIC VOLUME (L/KGDA) · Zone Air (z1)847.42830.35846.66837.97846.65Above range
AE103SPECIFIC VOLUME (L/KGDA) · Return Air (ra)847.42830.35846.66835.84846.65Above range
AE103ENTHALPY (J/GDA) · Location Outdoor Air (oa)22.99622.99623.03223.01523.020In range
AE103ENTHALPY (J/GDA) · Mixed Air (ma)31.85631.70631.89031.78731.883In range
AE103ENTHALPY (J/GDA) · Heat Coil Outlet (hco)31.85631.70631.89031.78731.883In range
AE103ENTHALPY (J/GDA) · Cool Coil Outlet (cco)29.55329.46129.59829.52029.582In range
AE103ENTHALPY (J/GDA) · Supply Air (sa)30.14530.05230.19030.11530.174In range
AE103ENTHALPY (J/GDA) · Zone Air (z1)36.17136.06236.26036.15636.200In range
AE103ENTHALPY (J/GDA) · Return Air (ra)36.17136.06236.26036.15636.200In range
AE103MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.11140.11150.11370.11270.1115Below range
AE103MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.34010.33720.34100.33980.3404In range
AE103MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.34010.33720.34100.33980.3404In range
AE103MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.34010.33720.34100.33980.3404In range
AE103MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.34010.33720.34100.33980.3404In range
AE103MASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE103MASS FLOW RATE (KGDA/S) · Return Air (ra)0.22870.22480.22890.22680.2289In range
AE104DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)26.90026.88926.90026.89726.900In range
AE104DRY BULB TEMPERATURE (°C) · Mixed Air (ma)24.86824.86424.90624.88724.868In range
AE104DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)24.86824.86425.50024.97224.868In range
AE104DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)14.92914.70115.22214.92714.939In range
AE104DRY BULB TEMPERATURE (°C) · Supply Air (sa)15.50615.22215.52515.42615.514In range
AE104DRY BULB TEMPERATURE (°C) · Zone Air (z1)23.88923.87623.89023.88723.889In range
AE104DRY BULB TEMPERATURE (°C) · Return Air (ra)23.88923.87623.89023.88623.889In range
AE104HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.016770.016760.016850.016800.01677In range
AE104HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.013040.012950.013200.013080.01305In range
AE104HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.013040.012950.013200.013080.01305In range
AE104HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.010590.010300.010800.010580.01060In range
AE104HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.010590.010300.010800.010580.01060In range
AE104HUMIDITY RATIO (G/GDA) · Zone Air (z1)0.011260.010990.011500.011260.01128In range
AE104HUMIDITY RATIO (G/GDA) · Return Air (ra)0.011260.010990.011500.011260.01128In range
AE104SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)873.71830.35872.93848.48872.92Above range
AE104SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)862.73830.35861.98844.10861.96Above range
AE104SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)862.73830.35861.98844.10861.96Above range
AE104SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)830.75829.89833.33831.33830.03In range
AE104SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)832.41827.67833.33831.18831.69In range
AE104SPECIFIC VOLUME (L/KGDA) · Zone Air (z1)857.49830.35856.76842.01856.73Above range
AE104SPECIFIC VOLUME (L/KGDA) · Return Air (ra)857.49830.35856.76838.36856.73Above range
AE104ENTHALPY (J/GDA) · Location Outdoor Air (oa)69.81469.79569.99469.86369.851In range
AE104ENTHALPY (J/GDA) · Mixed Air (ma)58.21157.97058.38258.24358.268In range
AE104ENTHALPY (J/GDA) · Heat Coil Outlet (hco)58.21157.97058.38258.24358.268In range
AE104ENTHALPY (J/GDA) · Cool Coil Outlet (cco)41.77840.79041.87441.53241.845In range
AE104ENTHALPY (J/GDA) · Supply Air (sa)42.36941.40042.46542.13142.436In range
AE104ENTHALPY (J/GDA) · Zone Air (z1)52.67751.94052.77452.49652.744In range
AE104ENTHALPY (J/GDA) · Return Air (ra)52.67751.94052.77452.49652.744In range
AE104MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.11010.10930.11370.11190.1102In range
AE104MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.34090.32790.34120.33870.3412In range
AE104MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.34090.32790.34120.33870.3412In range
AE104MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.34090.32790.34120.33870.3412In range
AE104MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.34090.32790.34120.33870.3412In range
AE104MASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE104MASS FLOW RATE (KGDA/S) · Return Air (ra)0.23080.21860.23100.22610.2310In range
AE SZ coil and zone loads56 rows · 2 outside
CaseQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE201Sensible Heating Load (QZHsensible) (kWh/h)2.9312.9302.9312.9312.931In range
AE201Sensible Cooling Load (QZClatent) (kWh/h)00000In range
AE201Latent Load (QZlatent) (kWh/h)0.58610.58610.59000.58670.5861In range
AE201Coil Load (QH) (kWh/h)8.3448.3028.7098.4198.360In range
AE201Loads Sensible (QCsensible) (kWh/h)008.05e-81.15e-80In range
AE201Latent (QClatent) (kWh/h)001.84e-52.63e-60In range
AE201Total (QCtotal) (kWh/h)001.85e-52.64e-60In range
AE201Outlet RH (RHcco) (%)6.3866.3536.8716.5816.385In range
AE203Sensible Heating Load (QZHsensible) (kWh/h)00000In range
AE203Sensible Cooling Load (QZClatent) (kWh/h)1.4651.4651.4671.4651.465In range
AE203Latent Load (QZlatent) (kWh/h)0.58610.58600.58970.58660.5861In range
AE203Coil Load (QH) (kWh/h)00000In range
AE203Loads Sensible (QCsensible) (kWh/h)0.85580.81910.85300.83900.8561Above range
AE203Latent (QClatent) (kWh/h)000.011250.0016070In range
AE203Total (QCtotal) (kWh/h)0.85580.83000.85300.84060.8561Above range
AE203Outlet RH (RHcco) (%)32.83332.51533.03032.74032.843In range
AE204Sensible Heating Load (QZHsensible) (kWh/h)00000In range
AE204Sensible Cooling Load (QZClatent) (kWh/h)2.9312.9302.9312.9312.931In range
AE204Latent Load (QZlatent) (kWh/h)0.58610.58580.58610.58610.5861In range
AE204Coil Load (QH) (kWh/h)00000In range
AE204Loads Sensible (QCsensible) (kWh/h)3.5703.4563.6083.5573.574In range
AE204Latent (QClatent) (kWh/h)2.0572.0542.2892.1552.054In range
AE204Total (QCtotal) (kWh/h)5.6265.6235.8975.7125.628In range
AE204Outlet RH (RHcco) (%)99.88498.62010099.751100In range
AE205Sensible Heating Load (QZHsensible) (kWh/h)00000In range
AE205Sensible Cooling Load (QZClatent) (kWh/h)1.4651.4641.4701.4661.465In range
AE205Latent Load (QZlatent) (kWh/h)0.58610.58610.59000.58670.5861In range
AE205Coil Load (QH) (kWh/h)00000In range
AE205Loads Sensible (QCsensible) (kWh/h)1.9141.8801.9291.9101.916In range
AE205Latent (QClatent) (kWh/h)000.031090.0044410In range
AE205Total (QCtotal) (kWh/h)1.9141.9081.9291.9141.916In range
AE205Outlet RH (RHcco) (%)44.49544.11144.85344.49544.561In range
AE206Sensible Heating Load (QZHsensible) (kWh/h)00000In range
AE206Sensible Cooling Load (QZClatent) (kWh/h)1.4651.4641.4701.4661.465In range
AE206Latent Load (QZlatent) (kWh/h)0.58610.58610.59000.58670.5861In range
AE206Coil Load (QH) (kWh/h)00000In range
AE206Loads Sensible (QCsensible) (kWh/h)1.7041.6461.7311.6991.706In range
AE206Latent (QClatent) (kWh/h)0.97690.96321.0871.0170.9704In range
AE206Total (QCtotal) (kWh/h)2.6812.6642.8182.7172.677In range
AE206Outlet RH (RHcco) (%)99.87799.02510099.759100In range
AE226Sensible Heating Load (QZHsensible) (kWh/h)00000In range
AE226Sensible Cooling Load (QZClatent) (kWh/h)1.4651.4641.4661.4651.465In range
AE226Latent Load (QZlatent) (kWh/h)0.58610.58610.58970.58660.5861In range
AE226Coil Load (QH) (kWh/h)00000In range
AE226Loads Sensible (QCsensible) (kWh/h)1.5601.5031.5971.5601.562In range
AE226Latent (QClatent) (kWh/h)1.8201.7782.0501.8581.800In range
AE226Total (QCtotal) (kWh/h)3.3803.3353.6433.4183.362In range
AE226Outlet RH (RHcco) (%)99.87799.65010099.913100In range
AE245Sensible Heating Load (QZHsensible) (kWh/h)00000In range
AE245Sensible Cooling Load (QZClatent) (kWh/h)1.4651.4641.5641.4791.465In range
AE245Latent Load (QZlatent) (kWh/h)0.58610.58610.58970.58660.5861In range
AE245Coil Load (QH) (kWh/h)00000In range
AE245Loads Sensible (QCsensible) (kWh/h)2.2042.1712.2162.2002.208In range
AE245Latent (QClatent) (kWh/h)000.030610.0043740In range
AE245Total (QCtotal) (kWh/h)2.2042.1882.2162.2052.208In range
AE245Outlet RH (RHcco) (%)34.01633.83934.33034.09734.091In range
AE SZ node states280 rows · 69 outside
CaseQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE201DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)−29.000−29−29−29−29In range
AE201DRY BULB TEMPERATURE (°C) · Mixed Air (ma)4.1834.1854.6484.4934.183Below range
AE201DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)29.32428.66729.32629.06729.316In range
AE201DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)29.32428.66729.32629.06729.316In range
AE201DRY BULB TEMPERATURE (°C) · Supply Air (sa)29.93029.57629.93329.72729.922In range
AE201DRY BULB TEMPERATURE (°C) · Zone Air (z1)21.11121.09921.11921.11121.111In range
AE201DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)21.11121.09921.11921.11121.111In range
AE201DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)21.38421.38621.40821.39921.383Below range
AE201HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)2.59e-42.59e-43.44e-42.78e-42.59e-4In range
AE201HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0016060.0015950.0016980.0016320.001604In range
AE201HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.0016060.0015950.0016980.0016320.001604In range
AE201HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0016060.0015950.0016980.0016320.001604In range
AE201HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0016060.0015950.0016980.0016320.001604In range
AE201HUMIDITY RATIO (G/GDA) · Zone Air (z1)0.0023060.0022000.0023740.0023090.002304In range
AE201HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0023060.0022000.0023740.0023090.002304In range
AE201HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0023060.0022000.0023740.0023090.002304In range
AE201SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)692.65691.84833.33776.09691.93In range
AE201SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)788.42787.61833.33814.39787.67In range
AE201SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)859.85830.35859.03842.94859.06Above range
AE201SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)859.85830.35859.03842.94859.06Above range
AE201SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)861.57830.35860.69842.78860.78Above range
AE201SPECIFIC VOLUME (L/KGDA) · Zone Air (z1)837.45830.35836.69833.99836.69Above range
AE201SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)837.45830.35836.69833.99836.69Above range
AE201SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)838.23830.35837.42833.93837.46Above range
AE201ENTHALPY (J/GDA) · Location Outdoor Air (oa)−28.507−28.540−28.330−28.472−28.543In range
AE201ENTHALPY (J/GDA) · Mixed Air (ma)8.2318.2128.8928.6428.232In range
AE201ENTHALPY (J/GDA) · Heat Coil Outlet (hco)33.56833.30933.56233.46233.594Above range
AE201ENTHALPY (J/GDA) · Cool Coil Outlet (cco)33.56833.30933.56233.46233.594Above range
AE201ENTHALPY (J/GDA) · Supply Air (sa)34.18033.90034.17334.05834.206Above range
AE201ENTHALPY (J/GDA) · Zone Air (z1)27.07127.03527.26627.12327.093In range
AE201ENTHALPY (J/GDA) · Return Fan Inlet (rfi)27.07127.03527.26627.12327.093In range
AE201ENTHALPY (J/GDA) · Return Fan Outlet (rfo)27.34627.32727.56427.41127.367In range
AE201MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.11270.11280.11970.11410.1128Below range
AE201MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.32930.32960.35910.33980.3296Below range
AE201MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.32930.32960.35910.33980.3296Below range
AE201MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.32930.32960.35910.33980.3296Below range
AE201MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.32930.32960.35910.33980.3296Below range
AE201MASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE201MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.21660.21680.23940.22570.2168Below range
AE201MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.21660.21680.23940.22570.2168Below range
AE203DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)15.50015.50015.50015.50015.500In range
AE203DRY BULB TEMPERATURE (°C) · Mixed Air (ma)20.98520.88920.98320.93120.985Above range
AE203DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)20.98520.88920.98320.93120.985Above range
AE203DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)18.50018.44418.51918.49418.504In range
AE203DRY BULB TEMPERATURE (°C) · Supply Air (sa)19.08519.05219.10119.08719.088In range
AE203DRY BULB TEMPERATURE (°C) · Zone Air (z1)23.33323.32923.34823.33523.333In range
AE203DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.33323.32923.34823.33523.333In range
AE203DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)23.64623.61123.64823.62923.646In range
AE203HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.0029330.0028950.0029480.0029280.002936In range
AE203HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0043240.0042840.0043550.0043110.004325In range
AE203HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.0043240.0042840.0043550.0043110.004325In range
AE203HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0043240.0042840.0043550.0043110.004325In range
AE203HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0043240.0042840.0043550.0043110.004325In range
AE203HUMIDITY RATIO (G/GDA) · Zone Air (z1)0.0050010.0049600.0050590.0049970.005002In range
AE203HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0050010.0049600.0050590.0049970.005002In range
AE203HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0050010.0049600.0050590.0049970.005002In range
AE203SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)822.32821.41833.33827.93821.57In range
AE203SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)839.80830.35839.04834.91839.04Above range
AE203SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)839.80830.35839.04834.91839.04Above range
AE203SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)832.71830.35833.33832.09831.96In range
AE203SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)834.38829.59833.45831.94833.63Above range
AE203SPECIFIC VOLUME (L/KGDA) · Zone Air (z1)847.42830.35846.67837.97846.65Above range
AE203SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)847.42830.35846.67837.97846.65Above range
AE203SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)848.31830.35847.33837.88847.54Above range
AE203ENTHALPY (J/GDA) · Location Outdoor Air (oa)22.99622.99623.03223.01523.022In range
AE203ENTHALPY (J/GDA) · Mixed Air (ma)32.06931.90332.10631.98832.099In range
AE203ENTHALPY (J/GDA) · Heat Coil Outlet (hco)32.06931.90332.10631.98832.099In range
AE203ENTHALPY (J/GDA) · Cool Coil Outlet (cco)29.55329.46129.60129.52029.583In range
AE203ENTHALPY (J/GDA) · Supply Air (sa)30.14530.05230.19330.11530.175In range
AE203ENTHALPY (J/GDA) · Zone Air (z1)36.17136.06136.26036.15736.202In range
AE203ENTHALPY (J/GDA) · Return Fan Inlet (rfi)36.17136.06136.26036.15736.202In range
AE203ENTHALPY (J/GDA) · Return Fan Outlet (rfo)36.48936.35736.56036.46036.520In range
AE203MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.11140.11150.11370.11270.1115Below range
AE203MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.34010.33770.34100.33980.3404In range
AE203MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.34010.33770.34100.33980.3404In range
AE203MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.34010.33770.34100.33980.3404In range
AE203MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.34010.33770.34100.33980.3404In range
AE203MASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE203MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.22870.22510.22890.22710.2289In range
AE203MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.22870.22510.22890.22710.2289In range
AE204DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)26.90026.88926.90026.89726.900In range
AE204DRY BULB TEMPERATURE (°C) · Mixed Air (ma)25.08825.06525.11125.08925.088In range
AE204DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)25.08825.06525.11125.08925.088In range
AE204DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)14.92914.61114.94914.84314.939In range
AE204DRY BULB TEMPERATURE (°C) · Supply Air (sa)15.50615.31215.52515.46315.514In range
AE204DRY BULB TEMPERATURE (°C) · Zone Air (z1)23.88923.88223.89723.88923.889In range
AE204DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.88923.88223.89723.88923.889In range
AE204DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)24.21624.16724.21724.18524.215In range
AE204HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.016770.016760.016850.016800.01677In range
AE204HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.013040.012950.013140.013050.01305In range
AE204HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.013040.012950.013140.013050.01305In range
AE204HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.010590.010310.010610.010520.01060In range
AE204HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.010590.010310.010610.010520.01060In range
AE204HUMIDITY RATIO (G/GDA) · Zone Air (z1)0.011260.011000.011290.011210.01128In range
AE204HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.011260.011000.011290.011210.01128In range
AE204HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.011260.011100.011320.011250.01128In range
AE204SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)873.71830.35872.93848.48872.92Above range
AE204SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)863.36830.35862.62844.34862.60Above range
AE204SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)863.36830.35862.62844.34862.60Above range
AE204SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)830.75829.89833.33831.33830.03In range
AE204SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)832.41827.67833.33831.18831.69In range
AE204SPECIFIC VOLUME (L/KGDA) · Zone Air (z1)857.49830.35856.76842.01856.73Above range
AE204SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)857.49830.35856.76842.01856.73Above range
AE204SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)858.43830.35857.47841.91857.67Above range
AE204ENTHALPY (J/GDA) · Location Outdoor Air (oa)69.81469.79569.99469.86369.854In range
AE204ENTHALPY (J/GDA) · Mixed Air (ma)58.43858.20058.58158.45858.497In range
AE204ENTHALPY (J/GDA) · Heat Coil Outlet (hco)58.43858.20058.58158.45858.497In range
AE204ENTHALPY (J/GDA) · Cool Coil Outlet (cco)41.77840.84041.87441.54641.846In range
AE204ENTHALPY (J/GDA) · Supply Air (sa)42.36941.44042.46542.14342.437In range
AE204ENTHALPY (J/GDA) · Zone Air (z1)52.67751.99052.77552.51152.746In range
AE204ENTHALPY (J/GDA) · Return Fan Inlet (rfi)52.67751.99052.77552.51152.746In range
AE204ENTHALPY (J/GDA) · Return Fan Outlet (rfo)53.01252.29053.10952.81953.081In range
AE204MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.11010.10950.11370.11190.1102In range
AE204MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.34090.32840.34120.33870.3412In range
AE204MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.34090.32840.34120.33870.3412In range
AE204MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.34090.32840.34120.33870.3412In range
AE204MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.34090.32840.34120.33870.3412In range
AE204MASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE204MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.23080.21900.23100.22680.2310In range
AE204MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.23080.21900.23100.22680.2310In range
AE205DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)24.90024.88924.90024.89724.900In range
AE205DRY BULB TEMPERATURE (°C) · Mixed Air (ma)24.05624.04124.05624.04924.056Above range
AE205DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)24.05624.04124.05624.04924.056Above range
AE205DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)18.50218.44418.52418.49818.506In range
AE205DRY BULB TEMPERATURE (°C) · Supply Air (sa)19.08719.05319.10919.09119.090In range
AE205DRY BULB TEMPERATURE (°C) · Zone Air (z1)23.33323.33023.34823.33423.333In range
AE205DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.33323.33023.34823.33423.333In range
AE205DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)23.64623.62023.66723.63623.646In range
AE205HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.0044810.0044570.0045100.0044910.004491In range
AE205HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0058750.0058320.0059160.0058750.005884In range
AE205HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.0058750.0058320.0059160.0058750.005884In range
AE205HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0058750.0058320.0059160.0058750.005884In range
AE205HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0058750.0058320.0059160.0058750.005884In range
AE205HUMIDITY RATIO (G/GDA) · Zone Air (z1)0.0065540.0065070.0066200.0065620.006562In range
AE205HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0065540.0065070.0066200.0065620.006562In range
AE205HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0065540.0065070.0066200.0065610.006562In range
AE205SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)851.19830.35850.44839.47850.43Above range
AE205SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)850.66830.35849.90839.26849.91Above range
AE205SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)850.66830.35849.90839.26849.91Above range
AE205SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)834.78830.35834.06832.92834.04Above range
AE205SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)836.45830.35835.55832.77835.71Above range
AE205SPECIFIC VOLUME (L/KGDA) · Zone Air (z1)849.52830.35848.76838.81848.76Above range
AE205SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)849.52830.35848.76838.81848.76Above range
AE205SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)850.41830.35849.45838.72849.65Above range
AE205ENTHALPY (J/GDA) · Location Outdoor Air (oa)36.43536.43536.50036.47436.491In range
AE205ENTHALPY (J/GDA) · Mixed Air (ma)39.12839.00839.18339.10539.180In range
AE205ENTHALPY (J/GDA) · Heat Coil Outlet (hco)39.12839.00839.18339.10539.180In range
AE205ENTHALPY (J/GDA) · Cool Coil Outlet (cco)33.48733.39933.54933.46933.536In range
AE205ENTHALPY (J/GDA) · Supply Air (sa)34.08133.99034.14234.06434.130In range
AE205ENTHALPY (J/GDA) · Zone Air (z1)40.12239.99940.23040.11340.172In range
AE205ENTHALPY (J/GDA) · Return Fan Inlet (rfi)40.12239.99940.23040.11340.172In range
AE205ENTHALPY (J/GDA) · Return Fan Outlet (rfo)40.44040.29540.53040.41640.490In range
AE205MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.11110.11110.11370.11240.1112In range
AE205MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.33920.33330.34100.33900.3395In range
AE205MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.33920.33330.34100.33900.3395In range
AE205MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.33920.33330.34100.33900.3395In range
AE205MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.33920.33330.34100.33900.3395In range
AE205MASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE205MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.22810.22220.22840.22650.2283In range
AE205MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.22810.22220.22840.22650.2283In range
AE206DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)23.0002323.0002323.000In range
AE206DRY BULB TEMPERATURE (°C) · Mixed Air (ma)23.43423.40723.44423.42223.434In range
AE206DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)23.43423.40723.44423.42223.434In range
AE206DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)18.51018.44418.58918.51718.514In range
AE206DRY BULB TEMPERATURE (°C) · Supply Air (sa)19.09419.04519.16519.11219.097In range
AE206DRY BULB TEMPERATURE (°C) · Zone Air (z1)23.33323.33023.33823.33423.333In range
AE206DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.33323.33023.33823.33423.333In range
AE206DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)23.64523.61123.64823.62723.645In range
AE206HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.015570.015520.015630.015580.01556In range
AE206HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.014540.014480.014620.014540.01455In range
AE206HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.014540.014480.014620.014540.01455In range
AE206HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.013350.013230.013420.013340.01337In range
AE206HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.013350.013230.013420.013340.01337In range
AE206HUMIDITY RATIO (G/GDA) · Zone Air (z1)0.014040.013920.014130.014030.01405In range
AE206HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.014040.013920.014130.014030.01405In range
AE206HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.014040.013920.014130.014030.01405In range
AE206SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)860.73830.35859.94843.28859.94Above range
AE206SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)860.60830.35859.84843.24859.83Above range
AE206SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)860.60830.35859.84843.24859.83Above range
AE206SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)844.74830.35844.05836.92844.00Above range
AE206SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)846.43830.35845.57836.77845.69Above range
AE206SPECIFIC VOLUME (L/KGDA) · Zone Air (z1)859.63830.35858.91842.87858.88Above range
AE206SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)859.63830.35858.91842.87858.88Above range
AE206SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)860.54830.35859.62842.78859.78Above range
AE206ENTHALPY (J/GDA) · Location Outdoor Air (oa)62.70562.66362.85162.73262.710In range
AE206ENTHALPY (J/GDA) · Mixed Air (ma)60.54260.36060.62560.50660.590In range
AE206ENTHALPY (J/GDA) · Heat Coil Outlet (hco)60.54260.36060.62560.50660.590In range
AE206ENTHALPY (J/GDA) · Cool Coil Outlet (cco)52.45152.06052.68352.42452.520In range
AE206ENTHALPY (J/GDA) · Supply Air (sa)53.05252.67053.29053.02653.121In range
AE206ENTHALPY (J/GDA) · Zone Air (z1)59.16658.85059.30259.10559.235In range
AE206ENTHALPY (J/GDA) · Return Fan Inlet (rfi)59.16658.85059.30259.10559.235In range
AE206ENTHALPY (J/GDA) · Return Fan Outlet (rfo)59.48859.16059.60659.41359.557In range
AE206MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.10980.10980.11370.11190.1099Below range
AE206MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.33520.32950.34100.33730.3355In range
AE206MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.33520.32950.34100.33730.3355In range
AE206MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.33520.32950.34100.33730.3355In range
AE206MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.33520.32950.34100.33730.3355In range
AE206MASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE206MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.22540.21970.22730.22540.2256In range
AE206MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.22540.21970.22730.22540.2256In range
AE226DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)23.0002323.0002323.000In range
AE226DRY BULB TEMPERATURE (°C) · Mixed Air (ma)23.0002323.0002323.000In range
AE226DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)23.0002323.0002323.000In range
AE226DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)18.51018.44418.59018.51518.514In range
AE226DRY BULB TEMPERATURE (°C) · Supply Air (sa)19.09419.03419.16519.11019.097In range
AE226DRY BULB TEMPERATURE (°C) · Zone Air (z1)23.33323.32723.33323.33223.333In range
AE226DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.33323.32723.33323.33223.333In range
AE226DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)23.64523.61623.66723.63323.645In range
AE226HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.015570.015520.015630.015580.01556In range
AE226HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.015570.015520.015630.015580.01556In range
AE226HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.015570.015520.015630.015580.01556In range
AE226HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.013350.013260.013420.013360.01337In range
AE226HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.013350.013260.013420.013360.01337In range
AE226HUMIDITY RATIO (G/GDA) · Zone Air (z1)0.014040.013950.014130.014070.01405In range
AE226HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.014040.013950.014130.014070.01405In range
AE226HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.014040.013950.014130.014070.01405In range
AE226SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)860.73830.35859.94843.28859.94Above range
AE226SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)860.73830.35859.94843.28859.94Above range
AE226SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)860.73830.35859.94843.28859.94Above range
AE226SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)844.74830.35844.03836.92844.00Above range
AE226SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)846.43830.35845.57836.77845.69Above range
AE226SPECIFIC VOLUME (L/KGDA) · Zone Air (z1)859.63830.35858.89842.87858.88Above range
AE226SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)859.63830.35858.89842.87858.88Above range
AE226SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)860.54830.35859.62842.78859.78Above range
AE226ENTHALPY (J/GDA) · Location Outdoor Air (oa)62.70562.66362.85162.73262.710In range
AE226ENTHALPY (J/GDA) · Mixed Air (ma)62.70562.66362.85162.73262.710In range
AE226ENTHALPY (J/GDA) · Heat Coil Outlet (hco)62.70562.66362.85162.73262.710In range
AE226ENTHALPY (J/GDA) · Cool Coil Outlet (cco)52.45152.13052.68352.50852.520In range
AE226ENTHALPY (J/GDA) · Supply Air (sa)53.05252.74053.29053.11053.121In range
AE226ENTHALPY (J/GDA) · Zone Air (z1)59.16658.92059.30259.18959.235In range
AE226ENTHALPY (J/GDA) · Return Fan Inlet (rfi)59.16658.92059.30259.18959.235In range
AE226ENTHALPY (J/GDA) · Return Fan Outlet (rfo)59.48858.92059.60659.41959.557In range
AE226MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.33520.32940.34100.33730.3355In range
AE226MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.33520.32940.34100.33730.3355In range
AE226MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.33520.32940.34100.33730.3355In range
AE226MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.33520.32940.34100.33730.3355In range
AE226MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.33520.32940.34100.33730.3355In range
AE226MASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE226MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.22540.21960.22730.22540.2256In range
AE226MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.22540.21960.22730.22540.2256In range
AE245DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)24.90024.88924.90024.89724.900In range
AE245DRY BULB TEMPERATURE (°C) · Mixed Air (ma)24.90024.88924.90024.89724.900In range
AE245DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)24.90024.88924.90024.89724.900In range
AE245DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)18.50018.44418.51918.49318.504In range
AE245DRY BULB TEMPERATURE (°C) · Supply Air (sa)19.08519.05319.10119.08719.088In range
AE245DRY BULB TEMPERATURE (°C) · Zone Air (z1)23.33323.32323.34823.33323.333In range
AE245DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.33323.32323.34823.33323.333In range
AE245DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)23.64623.62123.66723.63523.646In range
AE245HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.0044810.0044570.0045100.0044910.004491In range
AE245HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0044810.0044570.0045100.0044910.004491In range
AE245HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.0044810.0044570.0045100.0044910.004491In range
AE245HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0044810.0044570.0045100.0044910.004491In range
AE245HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0044810.0044570.0045100.0044910.004491In range
AE245HUMIDITY RATIO (G/GDA) · Zone Air (z1)0.0051590.0051340.0052120.0051770.005168In range
AE245HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0051590.0051340.0052120.0051770.005168In range
AE245HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0051590.0051340.0052120.0051770.005168In range
AE245SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)851.19830.35850.44839.47850.43Above range
AE245SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)851.19830.35850.44839.47850.43Above range
AE245SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)851.19830.35850.44839.47850.43Above range
AE245SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)832.92830.35833.33832.18832.18In range
AE245SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)834.59829.76833.70832.03833.85Above range
AE245SPECIFIC VOLUME (L/KGDA) · Zone Air (z1)847.63830.35846.85838.05846.88Above range
AE245SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)847.63830.35846.85838.05846.88Above range
AE245SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)848.52830.35847.57837.96847.77Above range
AE245ENTHALPY (J/GDA) · Location Outdoor Air (oa)36.43536.43536.51036.47736.491In range
AE245ENTHALPY (J/GDA) · Mixed Air (ma)36.43536.43536.51036.47736.491In range
AE245ENTHALPY (J/GDA) · Heat Coil Outlet (hco)36.43536.43536.51036.47736.491In range
AE245ENTHALPY (J/GDA) · Cool Coil Outlet (cco)29.95129.96229.99729.98330.003Below range
AE245ENTHALPY (J/GDA) · Supply Air (sa)30.54330.55330.58930.57830.596Below range
AE245ENTHALPY (J/GDA) · Zone Air (z1)36.57136.56236.70036.62036.624In range
AE245ENTHALPY (J/GDA) · Return Fan Inlet (rfi)36.57136.56236.70036.62036.624In range
AE245ENTHALPY (J/GDA) · Return Fan Outlet (rfo)36.88936.70036.93436.84836.942In range
AE245MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.34000.33310.34100.33920.3403In range
AE245MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.34000.33310.34100.33920.3403In range
AE245MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.34000.33310.34100.33920.3403In range
AE245MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.34000.33310.34100.33920.3403In range
AE245MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.34000.33310.34100.33920.3403In range
AE245MASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE245MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.22860.22210.22890.22670.2288In range
AE245MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.22860.22210.22890.22670.2288In range
AE CV coil and zone loads91 rows · 2 outside
CaseQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE301Sensible Heating Load (QZH1sensible) (kWh/h)2.9312.9302.9312.9312.931In range
AE301Sensible Cooling Load (QZC1sensible) (kWh/h)00000In range
AE301Latent Load (QZ1latent) (kWh/h)0.58610.58610.59000.58680.5861In range
AE301Sensible Heating Load (QZH2sensible) (kWh/h)2.3452.3452.3502.3462.345In range
AE301Sensible Cooling Load (QZC2sensible) (kWh/h)00000In range
AE301Latent Load (QZ2latent) (kWh/h)0.87920.87920.88000.87930.8792In range
AE301Coil Load (QHpreheat) (kWh/h)2.9412.9473.7883.4182.947Below range
AE301Loads Sensible (QCsensible) (kWh/h)00000In range
AE301Latent (QClatent) (kWh/h)00000In range
AE301Total (QCtotal) (kWh/h)00000In range
AE301Coil Outlet RH (RHcco) (%)24.74823.89124.73324.37424.733Above range
AE301Reheat Coil Load (QH1reheat) (kWh/h)7.6997.4727.7097.6077.713In range
AE301Reheat Coil Load (QH2reheat) (kWh/h)8.3728.0778.3848.2548.389In range
AE303Sensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE303Sensible Cooling Load (QZC1sensible) (kWh/h)1.4651.4651.4671.4651.465In range
AE303Latent Load (QZ1latent) (kWh/h)0.58610.58600.58970.58670.5861In range
AE303Sensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE303Sensible Cooling Load (QZC2sensible) (kWh/h)2.3452.3452.3462.3452.345In range
AE303Latent Load (QZ2latent) (kWh/h)0.87920.87900.89090.88110.8792In range
AE303Coil Load (QHpreheat) (kWh/h)00000In range
AE303Loads Sensible (QCsensible) (kWh/h)6.7226.4206.7266.5456.735In range
AE303Latent (QClatent) (kWh/h)00000In range
AE303Total (QCtotal) (kWh/h)6.7226.4206.7266.5456.735In range
AE303Coil Outlet RH (RHcco) (%)48.12547.45748.22047.91548.150In range
AE303Reheat Coil Load (QH1reheat) (kWh/h)2.2522.1362.2552.1942.258In range
AE303Reheat Coil Load (QH2reheat) (kWh/h)2.4502.3002.4542.3752.457In range
AE304Sensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE304Sensible Cooling Load (QZC1sensible) (kWh/h)2.9312.9312.9342.9312.931In range
AE304Latent Load (QZ1latent) (kWh/h)0.58610.58610.59270.58720.5861In range
AE304Sensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE304Sensible Cooling Load (QZC2sensible) (kWh/h)3.5173.5163.5173.5173.517In range
AE304Latent Load (QZ2latent) (kWh/h)0.87920.87920.89390.88160.8792In range
AE304Coil Load (QHpreheat) (kWh/h)00000In range
AE304Loads Sensible (QCsensible) (kWh/h)10.2999.89010.31510.11810.320In range
AE304Latent (QClatent) (kWh/h)6.2586.2147.0116.5056.258In range
AE304Total (QCtotal) (kWh/h)16.55716.10417.07016.62316.578In range
AE304Coil Outlet RH (RHcco) (%)99.88695.49010099.102100In range
AE304Reheat Coil Load (QH1reheat) (kWh/h)0.98820.79770.99150.91570.9933In range
AE304Reheat Coil Load (QH2reheat) (kWh/h)1.5131.2681.5241.4221.519In range
AE305Sensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE305Sensible Cooling Load (QZC1sensible) (kWh/h)1.4651.4651.4661.4651.465In range
AE305Latent Load (QZ1latent) (kWh/h)0.58610.58610.58970.58670.5861In range
AE305Sensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE305Sensible Cooling Load (QZC2sensible) (kWh/h)2.3452.3442.3452.3452.345In range
AE305Latent Load (QZ2latent) (kWh/h)0.87920.87910.89090.88110.8792In range
AE305Coil Load (QHpreheat) (kWh/h)00000In range
AE305Loads Sensible (QCsensible) (kWh/h)9.3648.9299.3739.2049.383In range
AE305Latent (QClatent) (kWh/h)00000In range
AE305Total (QCtotal) (kWh/h)9.3648.9299.3739.2049.383In range
AE305Coil Outlet RH (RHcco) (%)65.60764.90965.84065.48965.719In range
AE305Reheat Coil Load (QH1reheat) (kWh/h)2.2542.0722.2572.1842.260In range
AE305Reheat Coil Load (QH2reheat) (kWh/h)2.4522.2232.4562.3622.459In range
AE306Sensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE306Sensible Cooling Load (QZC1sensible) (kWh/h)1.4651.4651.4661.4651.465In range
AE306Latent Load (QZ1latent) (kWh/h)0.58610.58610.58970.58670.5861In range
AE306Sensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE306Sensible Cooling Load (QZC2sensible) (kWh/h)2.3452.3452.3452.3452.345In range
AE306Latent Load (QZ2latent) (kWh/h)0.87920.87920.89090.88110.8792In range
AE306Coil Load (QHpreheat) (kWh/h)00000In range
AE306Loads Sensible (QCsensible) (kWh/h)8.9038.5988.9158.7468.921In range
AE306Latent (QClatent) (kWh/h)5.4525.4346.1035.6545.443In range
AE306Total (QCtotal) (kWh/h)14.35514.03114.80214.40014.364In range
AE306Coil Outlet RH (RHcco) (%)99.88696.21010099.243100In range
AE306Reheat Coil Load (QH1reheat) (kWh/h)2.2562.1112.2622.1952.262In range
AE306Reheat Coil Load (QH2reheat) (kWh/h)2.4552.2702.4622.3762.462In range
AE326Sensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE326Sensible Cooling Load (QZC1sensible) (kWh/h)1.4651.4651.4661.4651.465In range
AE326Latent Load (QZ1latent) (kWh/h)0.58610.58610.58970.58670.5861In range
AE326Sensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE326Sensible Cooling Load (QZC2sensible) (kWh/h)2.3452.3452.3452.3452.345In range
AE326Latent Load (QZ2latent) (kWh/h)0.87920.87920.89090.88110.8792In range
AE326Coil Load (QHpreheat) (kWh/h)00000In range
AE326Loads Sensible (QCsensible) (kWh/h)8.4448.0968.4708.2528.461In range
AE326Latent (QClatent) (kWh/h)12.32411.71212.87912.38812.302In range
AE326Total (QCtotal) (kWh/h)20.76819.94420.99320.64020.763In range
AE326Coil Outlet RH (RHcco) (%)99.88698.89010099.803100In range
AE326Reheat Coil Load (QH1reheat) (kWh/h)2.2562.1262.2672.1982.262In range
AE326Reheat Coil Load (QH2reheat) (kWh/h)2.4552.2892.4682.3802.462In range
AE345Sensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE345Sensible Cooling Load (QZC1sensible) (kWh/h)1.4651.4651.4661.4651.465In range
AE345Latent Load (QZ1latent) (kWh/h)0.58610.58610.58970.58670.5861In range
AE345Sensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE345Sensible Cooling Load (QZC2sensible) (kWh/h)2.3452.3442.3452.3452.345In range
AE345Latent Load (QZ2latent) (kWh/h)0.87920.87910.89090.88110.8792In range
AE345Coil Load (QHpreheat) (kWh/h)00000In range
AE345Loads Sensible (QCsensible) (kWh/h)9.6839.2859.7079.5319.703In range
AE345Latent (QClatent) (kWh/h)00000In range
AE345Total (QCtotal) (kWh/h)9.6839.2859.7079.5319.703In range
AE345Coil Outlet RH (RHcco) (%)50.96650.70751.33051.06351.089In range
AE345Reheat Coil Load (QH1reheat) (kWh/h)2.2532.0892.2612.1862.259In range
AE345Reheat Coil Load (QH2reheat) (kWh/h)2.4502.2412.4612.3642.457In range
AE CV node states385 rows · 80 outside
CaseQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE301DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)−29.000−29−29−29−29In range
AE301DRY BULB TEMPERATURE (°C) · Mixed Air (ma)3.4322.3583.4302.7983.432Above range
AE301DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)7.2227.2207.2227.2217.222In range
AE301DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)7.2227.2207.2227.2217.222In range
AE301DRY BULB TEMPERATURE (°C) · Supply Air (sa)7.7857.7787.8107.7947.784In range
AE301DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)29.28729.27029.67029.49129.279In range
AE301DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)27.82727.81028.08927.96827.823In range
AE301DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)21.11121.11021.13021.11421.111In range
AE301DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)22.22222.21722.24822.22522.222In range
AE301DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)21.67121.66621.70921.68121.671In range
AE301DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)22.01921.94422.01621.97822.019Above range
AE301HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)2.59e-42.59e-43.00e-42.66e-42.59e-4In range
AE301HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0015500.0014960.0015490.0015280.001548Above range
AE301HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.0015500.0014960.0015490.0015280.001548Above range
AE301HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0015500.0014960.0015490.0015280.001548Above range
AE301HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0015500.0014960.0015490.0015280.001548Above range
AE301HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0015500.0014960.0015490.0015280.001548Above range
AE301HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0015500.0014960.0015490.0015280.001548Above range
AE301HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0021990.0021720.0022530.0022070.002197In range
AE301HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.0023840.0023650.0024540.0023990.002382In range
AE301HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0022920.0022000.0023540.0022870.002290In range
AE301HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0022920.0022000.0023540.0022870.002290In range
AE301SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)692.65691.84833.33761.86691.93In range
AE301SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)786.22785.27833.33808.60785.47In range
AE301SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)796.98796.13833.33814.01796.23In range
AE301SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)796.98796.13833.33814.01796.23In range
AE301SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)798.58793.92833.33813.83797.83In range
AE301SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)859.67830.35858.84845.33858.87Above range
AE301SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)855.52830.35854.70843.26854.74Above range
AE301SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)837.31830.35836.54834.16836.55Above range
AE301SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)840.72830.35839.93835.86839.95Above range
AE301SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)839.03830.35838.25835.02838.26Above range
AE301SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)840.02830.35838.99834.87839.25Above range
AE301ENTHALPY (J/GDA) · Location Outdoor Air (oa)−28.507−28.540−28.507−28.519−28.543In range
AE301ENTHALPY (J/GDA) · Mixed Air (ma)7.3346.1787.3166.5787.335Above range
AE301ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)11.15411.01611.14011.08911.159Above range
AE301ENTHALPY (J/GDA) · Cool Coil Outlet (cco)11.15411.01611.14011.08911.159Above range
AE301ENTHALPY (J/GDA) · Supply Air (sa)11.72111.60611.71011.67411.726Above range
AE301ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)33.38933.38633.74033.58033.414In range
AE301ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)31.91831.91332.14032.03231.945In range
AE301ENTHALPY (J/GDA) · Zone 1 Air (z1)26.79926.75026.86626.80326.821In range
AE301ENTHALPY (J/GDA) · Zone 2 Air (z2)28.39028.36828.48528.41128.413In range
AE301ENTHALPY (J/GDA) · Return Fan Inlet (rfi)27.60127.55927.74027.63027.622In range
AE301ENTHALPY (J/GDA) · Return Fan Outlet (rfo)27.95327.85528.04027.94627.974In range
AE301MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.28110.28140.29650.28500.2814Below range
AE301MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.76980.73620.77090.75390.7705In range
AE301MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.76980.73620.77090.75390.7705In range
AE301MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.76980.73620.77090.75390.7705In range
AE301MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.76980.73620.77090.75390.7705In range
AE301MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.35530.33980.35580.34800.3556In range
AE301MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.41450.39640.41510.40600.4149In range
AE301MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE301MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE301MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.48870.45310.48920.46890.4891In range
AE301MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.48870.45310.48920.46890.4891In range
AE303DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)15.50015.50015.50015.50015.500In range
AE303DRY BULB TEMPERATURE (°C) · Mixed Air (ma)21.01920.83321.01520.90121.018Above range
AE303DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)21.01920.83321.01520.90121.018Above range
AE303DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.20512.16712.21512.19812.207In range
AE303DRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.77812.79512.78312.778In range
AE303DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)19.17619.05019.18019.12219.180In range
AE303DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)18.74318.57018.75018.66818.748In range
AE303DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.33323.32823.33923.33323.333In range
AE303DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)24.44424.43924.45224.44424.444In range
AE303DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.89223.88723.94623.90223.892In range
AE303DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)24.23224.17824.24124.20724.232In range
AE303HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.0029330.0028950.0029480.0029270.002936In range
AE303HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0042300.0041680.0042360.0042110.004231In range
AE303HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.0042300.0041680.0042360.0042110.004231In range
AE303HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0042300.0041680.0042360.0042110.004231In range
AE303HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0042300.0041680.0042360.0042110.004231In range
AE303HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0042300.0041680.0042360.0042110.004231In range
AE303HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0042300.0041680.0042360.0042110.004231In range
AE303HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0048920.0048440.0049380.0048930.004893In range
AE303HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.0050810.0050360.0051390.0050880.005081In range
AE303HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0049870.0049400.0050400.0049930.004988In range
AE303HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0049870.0049400.0050390.0049850.004988In range
AE303SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)822.32821.41833.33826.66821.57In range
AE303SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)839.77830.35839.01835.37839.01Above range
AE303SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)839.77830.35839.01835.37839.01Above range
AE303SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)814.63813.71833.33822.83813.87In range
AE303SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)816.26811.55833.33822.64815.50In range
AE303SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)834.51830.35833.78832.76833.76Above range
AE303SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)833.28830.35833.33832.15832.53In range
AE303SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)847.27830.35846.51839.13846.50Above range
AE303SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)850.70830.35849.93840.85849.93Above range
AE303SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)848.99830.35848.23839.99848.23Above range
AE303SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)849.97830.35848.91839.85849.20Above range
AE303ENTHALPY (J/GDA) · Location Outdoor Air (oa)22.99622.99623.03223.01623.022In range
AE303ENTHALPY (J/GDA) · Mixed Air (ma)31.86331.54031.90031.72331.893In range
AE303ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)31.86331.54031.90031.72331.893In range
AE303ENTHALPY (J/GDA) · Cool Coil Outlet (cco)22.93822.77522.97822.90122.958In range
AE303ENTHALPY (J/GDA) · Supply Air (sa)23.51823.36523.55723.49123.537In range
AE303ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)29.99829.76630.03929.89530.028In range
AE303ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)29.55929.29929.60429.43429.591In range
AE303ENTHALPY (J/GDA) · Zone 1 Air (z1)35.89335.77535.99035.90035.924In range
AE303ENTHALPY (J/GDA) · Zone 2 Air (z2)37.50037.39337.63037.52337.532In range
AE303ENTHALPY (J/GDA) · Return Fan Inlet (rfi)36.70236.58436.89036.74036.733In range
AE303ENTHALPY (J/GDA) · Return Fan Outlet (rfo)37.04736.88037.19037.05337.078In range
AE303MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.27780.27810.28420.28140.2781Below range
AE303MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.75310.73190.75400.74180.7538In range
AE303MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.75310.73190.75400.74180.7538In range
AE303MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.75310.73190.75400.74180.7538In range
AE303MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.75310.73190.75400.74180.7538In range
AE303MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.34760.33780.34800.34240.3479In range
AE303MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.40550.39410.40600.39950.4059In range
AE303MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE303MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE303MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.47530.45040.47580.46050.4758In range
AE303MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.47530.45040.47580.46050.4758In range
AE304DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)26.90026.88926.90026.89626.900In range
AE304DRY BULB TEMPERATURE (°C) · Mixed Air (ma)25.57425.54125.59625.56825.573In range
AE304DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)25.57425.54125.59625.56825.573In range
AE304DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.20612.19912.22212.20812.207In range
AE304DRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.77812.83312.79112.778Below range
AE304DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)15.58215.31015.59015.47815.590In range
AE304DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)16.45916.18516.48016.35516.464In range
AE304DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.88923.88123.89123.88823.889In range
AE304DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)25.0002525.00525.00125In range
AE304DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)24.44824.44524.50224.45824.448In range
AE304DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)24.79124.72224.79724.75424.790In range
AE304HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.016770.016770.016850.016800.01677In range
AE304HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.012240.012180.012440.012310.01225In range
AE304HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.012240.012180.012440.012310.01225In range
AE304HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0088440.0084430.0089000.0087850.008852In range
AE304HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0088440.0084430.0089000.0087850.008852In range
AE304HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0088440.0084430.0089000.0087850.008852In range
AE304HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0088440.0084430.0089000.0087850.008852In range
AE304HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0095110.0091400.0095950.0094450.009518In range
AE304HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.0097010.0093400.0097960.0096400.009708In range
AE304HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0096070.0092500.0097000.0095710.009614In range
AE304HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0096070.0092500.0097000.0095710.009614In range
AE304SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)873.71830.35872.93852.35872.92Above range
AE304SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)863.68830.35862.92847.33862.91Above range
AE304SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)863.68830.35862.92847.33862.91Above range
AE304SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)820.63819.77833.33825.84819.88In range
AE304SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)822.27817.53833.33825.66821.52In range
AE304SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)830.33829.47833.33830.69829.60In range
AE304SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)832.85830.35833.33831.96832.11In range
AE304SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)855.11830.35854.34843.06854.35Above range
AE304SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)858.57830.35857.83844.80857.80Above range
AE304SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)856.85830.35856.09843.94856.09Above range
AE304SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)857.83830.35856.83843.79857.07Above range
AE304ENTHALPY (J/GDA) · Location Outdoor Air (oa)69.81469.81469.99469.88669.854In range
AE304ENTHALPY (J/GDA) · Mixed Air (ma)56.90356.75057.10656.93856.949In range
AE304ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)56.90356.75057.10656.93856.949In range
AE304ENTHALPY (J/GDA) · Cool Coil Outlet (cco)34.58333.56034.63034.19634.621In range
AE304ENTHALPY (J/GDA) · Supply Air (sa)35.16734.16035.21434.78835.204In range
AE304ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)38.03136.73038.08537.52238.080In range
AE304ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)38.92737.62038.99538.42138.974In range
AE304ENTHALPY (J/GDA) · Zone 1 Air (z1)48.21347.26048.26947.86148.263In range
AE304ENTHALPY (J/GDA) · Zone 2 Air (z2)49.83348.90549.90549.49749.884In range
AE304ENTHALPY (J/GDA) · Return Fan Inlet (rfi)49.02848.17049.09248.71049.079In range
AE304ENTHALPY (J/GDA) · Return Fan Outlet (rfo)49.37948.47049.44249.02649.429In range
AE304MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.27530.27350.28420.27920.2755In range
AE304MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.74760.71110.74840.73650.7483In range
AE304MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.74760.71110.74840.73650.7483In range
AE304MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.74760.71110.74840.73650.7483In range
AE304MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.74760.71110.74840.73650.7483In range
AE304MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.34510.32820.34540.33990.3454In range
AE304MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.40260.38290.40300.39660.4029In range
AE304MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE304MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE304MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.47230.43760.47280.45730.4728In range
AE304MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.47230.43760.47280.45730.4728In range
AE305DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)24.90024.88924.90024.89624.900In range
AE305DRY BULB TEMPERATURE (°C) · Mixed Air (ma)24.47824.44424.48524.46124.478In range
AE305DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)24.47824.44424.48524.46124.478In range
AE305DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.20612.19912.27812.21712.207In range
AE305DRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.77812.88912.80112.778In range
AE305DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)19.17819.05119.18019.12519.181In range
AE305DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)18.74518.57218.75018.67218.750In range
AE305DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.33323.32723.33923.33323.333In range
AE305DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)24.44424.43724.45224.44424.444In range
AE305DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.89223.88523.94623.90123.892In range
AE305DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)24.23224.16724.24124.19824.232In range
AE305HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.0044810.0044570.0045100.0044910.004491In range
AE305HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0057800.0057160.0058000.0057760.005789In range
AE305HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.0057800.0057160.0058000.0057760.005789In range
AE305HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0057800.0057160.0058000.0057760.005789In range
AE305HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0057800.0057160.0058000.0057760.005789In range
AE305HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0057800.0057160.0058000.0057760.005789In range
AE305HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0057800.0057160.0058000.0057760.005789In range
AE305HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0064450.0063910.0064990.0064520.006453In range
AE305HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.0066340.0065840.0067000.0066480.006642In range
AE305HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0065400.0064870.0066020.0065600.006548In range
AE305HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0065400.0064870.0066020.0065600.006548In range
AE305SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)851.19830.35850.44841.09850.43Above range
AE305SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)851.74830.35850.99841.35850.99Above range
AE305SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)851.74830.35850.99841.35850.99Above range
AE305SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)816.64815.75833.33823.84815.90In range
AE305SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)818.28813.57833.33823.66817.53In range
AE305SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)836.59830.35835.85833.80835.84Above range
AE305SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)835.35830.35834.62833.18834.61Above range
AE305SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)849.37830.35848.61840.19848.61Above range
AE305SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)852.80830.35852.04841.90852.05Above range
AE305SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)851.10830.35850.34841.05850.34Above range
AE305SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)852.07830.35851.03840.91851.31Above range
AE305ENTHALPY (J/GDA) · Location Outdoor Air (oa)36.43536.43536.50636.47736.491In range
AE305ENTHALPY (J/GDA) · Mixed Air (ma)39.31639.13339.37439.28939.368In range
AE305ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)39.31639.13339.37439.28939.368In range
AE305ENTHALPY (J/GDA) · Cool Coil Outlet (cco)26.85226.68226.90826.82726.891In range
AE305ENTHALPY (J/GDA) · Supply Air (sa)27.43327.27327.49027.41727.471In range
AE305ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)33.93333.70333.99233.84533.982In range
AE305ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)33.49433.24033.55533.38533.544In range
AE305ENTHALPY (J/GDA) · Zone 1 Air (z1)39.84339.71339.96039.85839.893In range
AE305ENTHALPY (J/GDA) · Zone 2 Air (z2)41.45541.33441.61041.48741.506In range
AE305ENTHALPY (J/GDA) · Return Fan Inlet (rfi)40.65440.52340.86040.70040.704In range
AE305ENTHALPY (J/GDA) · Return Fan Outlet (rfo)41.00040.81941.16041.01341.050In range
AE305MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.27710.27740.28420.28050.2774Below range
AE305MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.75130.72130.75210.73940.7520In range
AE305MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.75130.72130.75210.73940.7520In range
AE305MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.75130.72130.75210.73940.7520In range
AE305MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.75130.72130.75210.73940.7520In range
AE305MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.34670.33290.34710.34130.3471In range
AE305MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.40450.38840.40500.39820.4049In range
AE305MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE305MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE305MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.47410.44390.47470.45900.4746In range
AE305MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.47410.44390.47470.45900.4746In range
AE306DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)23.0002323.0002323.000In range
AE306DRY BULB TEMPERATURE (°C) · Mixed Air (ma)23.77423.72223.77423.74223.774Above range
AE306DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)23.77423.72223.77423.74223.774Above range
AE306DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.20612.17612.22212.20312.207In range
AE306DRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.76612.78412.77812.778In range
AE306DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)19.18119.02519.19019.12719.184In range
AE306DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)18.74918.54018.76018.67518.754In range
AE306DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.33323.33123.33923.33423.333In range
AE306DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)24.44424.44224.45224.44524.444In range
AE306DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.89223.88723.91723.89723.892In range
AE306DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)24.23224.16724.23124.19324.232Above range
AE306HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.015570.015520.015630.015580.01556In range
AE306HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.011800.011750.012000.011870.01181In range
AE306HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.011800.011750.012000.011870.01181In range
AE306HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0088440.0084920.0089000.0087950.008852In range
AE306HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0088440.0084920.0089000.0087950.008852In range
AE306HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0088440.0084920.0089000.0087950.008852In range
AE306HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0088440.0084920.0089000.0087950.008852In range
AE306HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0095110.0091900.0095920.0094570.009519In range
AE306HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.0097010.0093900.0097930.0096520.009709In range
AE306HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0096070.0092960.0097000.0095800.009614In range
AE306HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0096070.0095560.0097000.0096430.009614In range
AE306SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)860.73830.35859.94845.85859.94Above range
AE306SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)857.89830.35857.12844.43857.11Above range
AE306SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)857.89830.35857.12844.43857.11Above range
AE306SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)820.63819.77833.33825.84819.88In range
AE306SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)822.27817.53833.33825.66821.52In range
AE306SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)840.68830.35839.96835.86839.93Above range
AE306SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)839.44830.35839.81835.55838.69In range
AE306SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)853.51830.35852.77842.27852.75Above range
AE306SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)856.97830.35856.22844.00856.20Above range
AE306SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)855.25830.35854.50843.14854.49Above range
AE306SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)856.23830.35855.23843.00855.46Above range
AE306ENTHALPY (J/GDA) · Location Outdoor Air (oa)62.70562.70562.85162.75562.710In range
AE306ENTHALPY (J/GDA) · Mixed Air (ma)53.93553.77054.04253.93053.968In range
AE306ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)53.93553.77054.04253.93053.968In range
AE306ENTHALPY (J/GDA) · Cool Coil Outlet (cco)34.58333.66034.63634.24134.621In range
AE306ENTHALPY (J/GDA) · Supply Air (sa)35.16734.26035.22034.83335.204In range
AE306ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)41.70640.65041.76941.31041.755In range
AE306ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)41.26640.15041.33040.84441.315In range
AE306ENTHALPY (J/GDA) · Zone 1 Air (z1)47.64546.81047.70947.34647.695In range
AE306ENTHALPY (J/GDA) · Zone 2 Air (z2)49.26648.47049.33148.98349.316In range
AE306ENTHALPY (J/GDA) · Return Fan Inlet (rfi)48.46047.69048.52548.18348.510In range
AE306ENTHALPY (J/GDA) · Return Fan Outlet (rfo)48.80847.99048.87248.49748.858In range
AE306MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.27580.27540.28420.27970.2761In range
AE306MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.74760.71600.74840.73730.7483In range
AE306MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.74760.71600.74840.73730.7483In range
AE306MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.74760.71600.74840.73730.7483In range
AE306MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.74760.71600.74840.73730.7483In range
AE306MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.34510.33050.34540.34030.3454In range
AE306MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.40260.38550.40300.39700.4029In range
AE306MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE306MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE306MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.47180.44060.47230.45770.4723In range
AE306MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.47180.44060.47230.45770.4723In range
AE326DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)23.0002323.0002323.000In range
AE326DRY BULB TEMPERATURE (°C) · Mixed Air (ma)23.0002323.0002323.000In range
AE326DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)23.0002323.0002323.000In range
AE326DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.20612.19912.22212.20612.207In range
AE326DRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.77012.79412.78012.778In range
AE326DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)19.18119.05219.19019.13219.184In range
AE326DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)18.74918.56818.76018.68018.754In range
AE326DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.33323.33123.33923.33423.333In range
AE326DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)24.44424.44224.45224.44524.444In range
AE326DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.89223.88723.94523.90223.892In range
AE326DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)24.23224.16724.24024.19824.232In range
AE326HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.015570.015520.015630.015580.01556In range
AE326HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.015570.015520.015630.015580.01556In range
AE326HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.015570.015520.015630.015580.01556In range
AE326HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0088440.0087470.0089090.0088500.008852In range
AE326HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0088440.0087470.0089090.0088500.008852In range
AE326HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0088440.0087470.0089090.0088500.008852In range
AE326HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0088440.0087470.0089090.0088500.008852In range
AE326HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0095110.0094420.0096130.0095220.009519In range
AE326HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.0097010.0096500.0098140.0097190.009709In range
AE326HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0096070.0095520.0097130.0096350.009614In range
AE326HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0096070.0095520.0097130.0096350.009614In range
AE326SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)860.73830.35859.94845.85859.94Above range
AE326SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)860.73830.35859.94845.85859.94Above range
AE326SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)860.73830.35859.94845.85859.94Above range
AE326SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)820.63819.77833.33825.83819.88In range
AE326SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)822.27817.48833.33825.65821.52In range
AE326SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)840.68830.35839.95835.86839.93Above range
AE326SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)839.44830.35838.71835.24838.69Above range
AE326SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)853.51830.35852.76842.27852.75Above range
AE326SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)856.97830.35856.20843.99856.20Above range
AE326SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)855.25830.35854.49843.14854.49Above range
AE326SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)856.23830.35855.23843.00855.46Above range
AE326ENTHALPY (J/GDA) · Location Outdoor Air (oa)62.70562.70562.85162.75562.710In range
AE326ENTHALPY (J/GDA) · Mixed Air (ma)62.70562.70562.85162.75562.710In range
AE326ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)62.70562.70562.85162.75562.710In range
AE326ENTHALPY (J/GDA) · Cool Coil Outlet (cco)34.58334.33034.60234.50434.621In range
AE326ENTHALPY (J/GDA) · Supply Air (sa)35.16734.93035.18535.09635.204In range
AE326ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)41.70641.32041.74941.57841.755In range
AE326ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)41.26640.82841.30941.11541.315In range
AE326ENTHALPY (J/GDA) · Zone 1 Air (z1)47.64547.45047.68847.60447.695In range
AE326ENTHALPY (J/GDA) · Zone 2 Air (z2)49.26649.14049.31049.25149.316In range
AE326ENTHALPY (J/GDA) · Return Fan Inlet (rfi)48.46048.37048.50448.45448.510In range
AE326ENTHALPY (J/GDA) · Return Fan Outlet (rfo)48.80848.37048.85148.66848.858In range
AE326MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.74760.71370.74840.73700.7483In range
AE326MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.74760.71370.74840.73700.7483In range
AE326MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.74760.71370.74840.73700.7483In range
AE326MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.74760.71370.74840.73700.7483In range
AE326MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.74760.71370.74840.73700.7483In range
AE326MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.34510.32940.34540.34010.3454In range
AE326MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.40260.38430.40300.39680.4029In range
AE326MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE326MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE326MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.47180.43920.47230.45740.4723In range
AE326MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.47180.43920.47230.45740.4723In range
AE345DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)24.90024.88924.90024.89624.900In range
AE345DRY BULB TEMPERATURE (°C) · Mixed Air (ma)24.90024.88924.90024.89624.900In range
AE345DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)24.90024.88924.90024.89624.900In range
AE345DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.20612.19712.22212.20512.207In range
AE345DRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.77112.79512.78012.778In range
AE345DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)19.17719.05219.18019.12219.180In range
AE345DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)18.74318.57218.75018.66918.748In range
AE345DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.33323.32823.33923.33323.333In range
AE345DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)24.44424.43824.45224.44424.444In range
AE345DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.89223.88723.94623.90123.892In range
AE345DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)24.23224.16724.24124.19824.232In range
AE345HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.0044810.0044570.0045100.0044910.004491In range
AE345HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0044810.0044570.0045100.0044910.004491In range
AE345HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.0044810.0044570.0045100.0044910.004491In range
AE345HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0044810.0044570.0045100.0044910.004491In range
AE345HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0044810.0044570.0045100.0044910.004491In range
AE345HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0044810.0044570.0045100.0044910.004491In range
AE345HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0044810.0044570.0045100.0044910.004491In range
AE345HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0051440.0051190.0052120.0051690.005153In range
AE345HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.0053330.0053080.0054130.0053650.005342In range
AE345HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0052390.0052140.0053150.0052740.005248In range
AE345HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0052390.0052140.0053150.0052740.005248In range
AE345SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)851.19830.35850.44841.09850.43Above range
AE345SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)851.19830.35850.44841.09850.43Above range
AE345SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)851.19830.35850.44841.09850.43Above range
AE345SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)814.95814.06833.33822.99814.21In range
AE345SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)816.59811.84833.33822.80815.84In range
AE345SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)834.85830.35834.12832.94834.11Above range
AE345SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)833.61830.35833.33832.32832.88Above range
AE345SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)847.61830.35846.85839.31846.86Above range
AE345SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)851.04830.35850.28841.02850.28Above range
AE345SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)849.33830.35848.57840.17848.58Above range
AE345SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)850.31830.35849.27840.03849.55Above range
AE345ENTHALPY (J/GDA) · Location Outdoor Air (oa)36.43536.43536.50636.47736.491In range
AE345ENTHALPY (J/GDA) · Mixed Air (ma)36.43536.43536.50636.47736.491In range
AE345ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)36.43536.43536.50636.47736.491In range
AE345ENTHALPY (J/GDA) · Cool Coil Outlet (cco)23.57323.56423.64023.60423.615In range
AE345ENTHALPY (J/GDA) · Supply Air (sa)24.15324.15524.24024.19424.194Below range
AE345ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)30.63630.55030.68730.60030.688In range
AE345ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)30.19730.07030.25130.13930.251In range
AE345ENTHALPY (J/GDA) · Zone 1 Air (z1)36.53436.57136.68036.61236.587Below range
AE345ENTHALPY (J/GDA) · Zone 2 Air (z2)38.14138.19038.33038.23938.196Below range
AE345ENTHALPY (J/GDA) · Return Fan Inlet (rfi)37.34337.38137.59037.45637.396Below range
AE345ENTHALPY (J/GDA) · Return Fan Outlet (rfo)37.68837.59037.74137.66937.741In range
AE345MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.75280.72170.75370.74000.7535In range
AE345MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.75280.72170.75370.74000.7535In range
AE345MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.75280.72170.75370.74000.7535In range
AE345MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.75280.72170.75370.74000.7535In range
AE345MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.75280.72170.75370.74000.7535In range
AE345MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.34750.33310.34780.34160.3478In range
AE345MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.40540.38860.40580.39850.4057In range
AE345MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE345MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE345MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.47510.44410.47570.45940.4756In range
AE345MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.47510.44410.47570.45940.4756In range
AE VAV coil and zone loads91 rows · 4 outside
CaseQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE401Sensible Heating Load (QZH1sensible) (kWh/h)2.9312.9302.9312.9312.931In range
AE401Sensible Cooling Load (QZC1sensible) (kWh/h)00000In range
AE401Latent Load (QZ1latent) (kWh/h)0.58610.58610.59000.58680.5861In range
AE401Sensible Heating Load (QZH2sensible) (kWh/h)2.3452.3452.3502.3462.345In range
AE401Sensible Cooling Load (QZC2sensible) (kWh/h)00000In range
AE401Latent Load (QZ2latent) (kWh/h)0.87920.87920.88000.87930.8792In range
AE401Coil Load (QHpreheat) (kWh/h)10.23710.24810.81810.40510.260Below range
AE401Loads Sensible (QCsensible) (kWh/h)00000In range
AE401Latent (QClatent) (kWh/h)00000In range
AE401Total (QCtotal) (kWh/h)00000In range
AE401Coil Outlet RH (RHcco) (%)4.1434.1464.8024.2834.145Below range
AE401Reheat Coil Load (QH1reheat) (kWh/h)4.4854.4894.5844.5164.499Below range
AE401Reheat Coil Load (QH2reheat) (kWh/h)4.8634.8695.0154.9134.877Below range
AE403Sensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE403Sensible Cooling Load (QZC1sensible) (kWh/h)1.4651.4651.4671.4651.465In range
AE403Latent Load (QZ1latent) (kWh/h)0.58610.58600.58970.58670.5861In range
AE403Sensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE403Sensible Cooling Load (QZC2sensible) (kWh/h)2.3452.3452.3462.3452.345In range
AE403Latent Load (QZ2latent) (kWh/h)0.87920.87900.89090.88110.8792In range
AE403Coil Load (QHpreheat) (kWh/h)00000In range
AE403Loads Sensible (QCsensible) (kWh/h)1.4531.3991.4661.4261.458In range
AE403Latent (QClatent) (kWh/h)00000In range
AE403Total (QCtotal) (kWh/h)1.4531.3991.4661.4261.458In range
AE403Coil Outlet RH (RHcco) (%)36.35634.29036.39035.81536.395In range
AE403Reheat Coil Load (QH1reheat) (kWh/h)00000In range
AE403Reheat Coil Load (QH2reheat) (kWh/h)00000In range
AE404Sensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE404Sensible Cooling Load (QZC1sensible) (kWh/h)2.9312.9312.9342.9312.931In range
AE404Latent Load (QZ1latent) (kWh/h)0.58610.58610.59270.58720.5861In range
AE404Sensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE404Sensible Cooling Load (QZC2sensible) (kWh/h)3.5173.5163.5173.5173.517In range
AE404Latent Load (QZ2latent) (kWh/h)0.87920.87920.89390.88160.8792In range
AE404Coil Load (QHpreheat) (kWh/h)00000In range
AE404Loads Sensible (QCsensible) (kWh/h)7.3867.3337.4597.3957.399In range
AE404Latent (QClatent) (kWh/h)5.9245.9176.5816.1715.924In range
AE404Total (QCtotal) (kWh/h)13.31013.30814.03113.56613.323In range
AE404Coil Outlet RH (RHcco) (%)99.88697.24010099.324100In range
AE404Reheat Coil Load (QH1reheat) (kWh/h)00000In range
AE404Reheat Coil Load (QH2reheat) (kWh/h)00000In range
AE405Sensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE405Sensible Cooling Load (QZC1sensible) (kWh/h)1.4651.4651.4661.4651.465In range
AE405Latent Load (QZ1latent) (kWh/h)0.58610.58610.58970.58670.5861In range
AE405Sensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE405Sensible Cooling Load (QZC2sensible) (kWh/h)2.3452.3442.3452.3452.345In range
AE405Latent Load (QZ2latent) (kWh/h)0.87920.87910.89090.88110.8792In range
AE405Coil Load (QHpreheat) (kWh/h)00000In range
AE405Loads Sensible (QCsensible) (kWh/h)4.0924.0914.1434.1104.102In range
AE405Latent (QClatent) (kWh/h)00000In range
AE405Total (QCtotal) (kWh/h)4.0924.0914.1434.1104.102In range
AE405Coil Outlet RH (RHcco) (%)53.33851.85553.52052.96853.463In range
AE405Reheat Coil Load (QH1reheat) (kWh/h)00000In range
AE405Reheat Coil Load (QH2reheat) (kWh/h)00000In range
AE406Sensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE406Sensible Cooling Load (QZC1sensible) (kWh/h)1.4651.4651.4661.4651.465In range
AE406Latent Load (QZ1latent) (kWh/h)0.58610.58610.58970.58670.5861In range
AE406Sensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE406Sensible Cooling Load (QZC2sensible) (kWh/h)2.3452.3452.3452.3452.345In range
AE406Latent Load (QZ2latent) (kWh/h)0.87920.87920.89090.88110.8792In range
AE406Coil Load (QHpreheat) (kWh/h)00000In range
AE406Loads Sensible (QCsensible) (kWh/h)3.6263.5673.6803.6163.635In range
AE406Latent (QClatent) (kWh/h)4.5964.4954.9694.7284.588In range
AE406Total (QCtotal) (kWh/h)8.2228.1758.5968.3448.223In range
AE406Coil Outlet RH (RHcco) (%)99.88599.38010099.857100In range
AE406Reheat Coil Load (QH1reheat) (kWh/h)00000In range
AE406Reheat Coil Load (QH2reheat) (kWh/h)00000In range
AE426Sensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE426Sensible Cooling Load (QZC1sensible) (kWh/h)1.4651.4651.4661.4651.465In range
AE426Latent Load (QZ1latent) (kWh/h)0.58610.58610.58970.58670.5861In range
AE426Sensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE426Sensible Cooling Load (QZC2sensible) (kWh/h)2.3452.3452.3452.3452.345In range
AE426Latent Load (QZ2latent) (kWh/h)0.87920.87920.89090.88110.8792In range
AE426Coil Load (QHpreheat) (kWh/h)00000In range
AE426Loads Sensible (QCsensible) (kWh/h)3.5853.5163.6423.5703.594In range
AE426Latent (QClatent) (kWh/h)5.2445.1895.6335.3595.237In range
AE426Total (QCtotal) (kWh/h)8.8298.8059.2078.9288.830In range
AE426Coil Outlet RH (RHcco) (%)99.88599.58010099.922100In range
AE426Reheat Coil Load (QH1reheat) (kWh/h)00000In range
AE426Reheat Coil Load (QH2reheat) (kWh/h)00000In range
AE445Sensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE445Sensible Cooling Load (QZC1sensible) (kWh/h)1.4651.4651.4661.4651.465In range
AE445Latent Load (QZ1latent) (kWh/h)0.58610.58610.58970.58670.5861In range
AE445Sensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE445Sensible Cooling Load (QZC2sensible) (kWh/h)2.3452.3442.3452.3452.345In range
AE445Latent Load (QZ2latent) (kWh/h)0.87920.87910.89090.88110.8792In range
AE445Coil Load (QHpreheat) (kWh/h)00000In range
AE445Loads Sensible (QCsensible) (kWh/h)4.1464.1454.1914.1624.157In range
AE445Latent (QClatent) (kWh/h)00000In range
AE445Total (QCtotal) (kWh/h)4.1464.1454.1914.1624.157In range
AE445Coil Outlet RH (RHcco) (%)49.45249.24249.78049.54849.575In range
AE445Reheat Coil Load (QH1reheat) (kWh/h)00000In range
AE445Reheat Coil Load (QH2reheat) (kWh/h)00000In range
AE VAV node states385 rows · 67 outside
CaseQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE401DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)−29.000−29−29−29−29In range
AE401DRY BULB TEMPERATURE (°C) · Mixed Air (ma)−29.000−29−28.996−28.999−29In range
AE401DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)7.2227.2037.2227.2187.222In range
AE401DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)7.2227.2037.2227.2187.222In range
AE401DRY BULB TEMPERATURE (°C) · Supply Air (sa)7.2977.2787.3107.2987.297In range
AE401DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)46.88046.50546.94846.76746.920In range
AE401DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)36.01935.76636.05535.93036.039In range
AE401DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)21.11121.11021.14521.11721.111In range
AE401DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)22.22222.22122.25922.22822.222In range
AE401DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)n/a
AE401DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)n/a
AE401HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)2.59e-42.59e-43.00e-42.66e-42.59e-4In range
AE401HUMIDITY RATIO (G/GDA) · Mixed Air (ma)2.59e-42.59e-43.00e-42.67e-42.59e-4Below range
AE401HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)2.59e-42.59e-43.00e-42.67e-42.59e-4Below range
AE401HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)2.59e-42.59e-43.00e-42.67e-42.59e-4Below range
AE401HUMIDITY RATIO (G/GDA) · Supply Air (sa)2.59e-42.59e-43.00e-42.66e-42.59e-4In range
AE401HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)2.59e-42.59e-43.00e-42.67e-42.59e-4In range
AE401HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)2.59e-42.59e-43.00e-42.66e-42.59e-4In range
AE401HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0023060.0022690.0023740.0023140.002304In range
AE401HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.0023120.0022870.0023740.0023180.002310In range
AE401HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)n/a
AE401HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)n/a
AE401SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)692.65691.84833.33761.86691.93In range
AE401SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)692.65691.85833.33761.87691.93In range
AE401SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)795.33794.48833.33813.19794.59In range
AE401SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)795.33794.48833.33813.19794.59In range
AE401SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)795.55794.28833.33813.17794.80In range
AE401SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)907.76830.35907.05869.40907.09Above range
AE401SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)876.97830.35876.18854.00876.25Above range
AE401SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)837.45833.33836.66835.52836.69Above range
AE401SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)840.62833.33839.83837.64839.86Above range
AE401SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)n/a
AE401SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)n/a
AE401ENTHALPY (J/GDA) · Location Outdoor Air (oa)−28.507−28.540−28.507−28.519−28.543In range
AE401ENTHALPY (J/GDA) · Mixed Air (ma)−28.507−28.538−28.507−28.519−28.543In range
AE401ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)7.9087.8897.9147.9057.917In range
AE401ENTHALPY (J/GDA) · Cool Coil Outlet (cco)7.9087.8897.9147.9057.917In range
AE401ENTHALPY (J/GDA) · Supply Air (sa)7.9837.97787.9897.992In range
AE401ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)47.77747.59347.79147.71547.876In range
AE401ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)36.85836.72736.86936.79936.923In range
AE401ENTHALPY (J/GDA) · Zone 1 Air (z1)27.07127.00627.13827.06927.093In range
AE401ENTHALPY (J/GDA) · Zone 2 Air (z2)28.20828.17428.25228.20328.231In range
AE401ENTHALPY (J/GDA) · Return Fan Inlet (rfi)n/a
AE401ENTHALPY (J/GDA) · Return Fan Outlet (rfo)n/a
AE401MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.28110.28140.29710.28510.2814Below range
AE401MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.28110.28140.29710.28510.2814Below range
AE401MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.28110.28140.29710.28510.2814Below range
AE401MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.28110.28140.29710.28510.2814Below range
AE401MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.28110.28140.29710.28510.2814Below range
AE401MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.11270.11280.11880.11410.1128Below range
AE401MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.16840.16860.17820.17100.1686Below range
AE401MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE401MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE401MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)00000In range
AE401MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)00000In range
AE403DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)15.50015.50015.50015.50015.500In range
AE403DRY BULB TEMPERATURE (°C) · Mixed Air (ma)16.95216.77616.96216.85616.955In range
AE403DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)16.95216.77616.96216.85616.955In range
AE403DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.66412.64712.67012.66212.664In range
AE403DRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.77812.79512.78212.778In range
AE403DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)12.78312.77812.79512.78312.778In range
AE403DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)12.78312.77812.79512.78312.778In range
AE403DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.33323.33023.34423.33423.333In range
AE403DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)24.44424.43924.46124.44624.444In range
AE403DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.95023.93624.00523.95823.950In range
AE403DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)23.95423.94424.00923.96523.955In range
AE403HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.0029330.0028950.0029480.0029270.002936In range
AE403HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0032880.0031000.0032910.0032400.003291In range
AE403HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.0032880.0031000.0032910.0032400.003291In range
AE403HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0032880.0031000.0032900.0032390.003291In range
AE403HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0032880.0031000.0032890.0032390.003291In range
AE403HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0032900.0031000.0032890.0032390.003291Above range
AE403HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0032900.0031000.0032890.0032390.003291Above range
AE403HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0049720.0049250.0050210.0049720.004970In range
AE403HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.0050310.0049850.0050840.0050350.005029In range
AE403HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0050050.0041000.0050400.0048530.005003In range
AE403HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0050050.0041000.0050550.0048560.005003In range
AE403SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)822.32821.41833.33826.66821.57In range
AE403SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)826.92826.04833.33828.97826.18In range
AE403SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)826.92826.04833.33828.97826.18In range
AE403SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)814.71813.75833.33822.85813.96In range
AE403SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)815.03813.51833.33822.83814.28In range
AE403SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)815.05814.12833.33823.03814.28In range
AE403SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)815.05814.12833.33823.03814.28In range
AE403SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)847.38830.35846.63839.19846.61Above range
AE403SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)850.63830.35849.88840.81849.86Above range
AE403SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)849.18830.35848.43840.09848.41Above range
AE403SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)849.20830.35848.41840.11848.43Above range
AE403ENTHALPY (J/GDA) · Location Outdoor Air (oa)22.99622.99623.03223.01623.022In range
AE403ENTHALPY (J/GDA) · Mixed Air (ma)25.36125.07725.37725.25125.392In range
AE403ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)25.36125.07725.37725.25125.392In range
AE403ENTHALPY (J/GDA) · Cool Coil Outlet (cco)21.02620.90321.05220.99521.049In range
AE403ENTHALPY (J/GDA) · Supply Air (sa)21.14121.02421.16321.11621.164In range
AE403ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)21.15121.02421.16321.11621.164In range
AE403ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)21.15121.02421.16321.11621.164In range
AE403ENTHALPY (J/GDA) · Zone 1 Air (z1)36.09635.98936.16236.10036.121In range
AE403ENTHALPY (J/GDA) · Zone 2 Air (z2)37.37337.27337.47037.39537.401In range
AE403ENTHALPY (J/GDA) · Return Fan Inlet (rfi)36.80536.68736.95036.83636.831In range
AE403ENTHALPY (J/GDA) · Return Fan Outlet (rfo)36.81036.69136.95036.83936.836In range
AE403MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.27780.27810.28600.28210.2781Below range
AE403MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.33520.33350.33850.33580.3357In range
AE403MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.33520.33350.33850.33580.3357In range
AE403MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.33520.33350.33850.33580.3357In range
AE403MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.33520.33350.33850.33580.3357In range
AE403MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.13690.13620.13830.13720.1371In range
AE403MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.19830.19730.20020.19860.1985In range
AE403MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE403MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE403MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.057390.050550.057970.053700.05760In range
AE403MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.057390.050370.057970.053730.05760In range
AE404DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)26.90026.88926.90026.89626.900In range
AE404DRY BULB TEMPERATURE (°C) · Mixed Air (ma)25.72625.72125.91025.76825.726In range
AE404DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)25.72625.72125.91025.76825.726In range
AE404DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.48012.44412.49112.46712.481In range
AE404DRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.77812.79212.78212.778In range
AE404DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)12.77812.77812.79212.78412.778In range
AE404DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)12.77812.77812.79212.78412.778In range
AE404DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.88923.88323.90023.89123.889In range
AE404DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)25.00024.99925.01725.00325In range
AE404DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)24.37924.36824.48024.39824.379In range
AE404DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)24.48624.47424.58224.50024.486In range
AE404HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.016770.016770.016850.016800.01677In range
AE404HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.013480.013450.013640.013520.01349In range
AE404HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.013480.013450.013640.013520.01349In range
AE404HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0090070.0087490.0090560.0089540.009015In range
AE404HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0090070.0087490.0090560.0089530.009015In range
AE404HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0090070.0087490.0090560.0089540.009015In range
AE404HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0090070.0087490.0090560.0089540.009015In range
AE404HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0099000.0096510.0099800.0098470.009908In range
AE404HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.010230.0099980.010330.010190.01024In range
AE404HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.010050.0098320.010130.010020.01005In range
AE404HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.010050.0098320.010130.010020.01005In range
AE404SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)873.71830.35872.93852.35872.92Above range
AE404SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)865.80830.35865.04848.41865.03Above range
AE404SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)865.80830.35865.04848.41865.03Above range
AE404SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)821.63820.70833.33826.33820.88In range
AE404SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)822.49819.66833.33826.24821.73In range
AE404SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)822.49821.61833.33826.77821.73In range
AE404SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)822.49821.61833.33826.77821.73In range
AE404SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)855.64830.35854.88843.33854.87Above range
AE404SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)859.29830.35858.56845.16858.53Above range
AE404SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)857.25830.35856.48844.13856.49Above range
AE404SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)857.56830.35856.69844.10856.79Above range
AE404ENTHALPY (J/GDA) · Location Outdoor Air (oa)69.81469.81469.99469.88669.854In range
AE404ENTHALPY (J/GDA) · Mixed Air (ma)60.20760.15060.40560.27460.255In range
AE404ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)60.20760.15060.40560.27460.255In range
AE404ENTHALPY (J/GDA) · Cool Coil Outlet (cco)35.27434.60035.33734.97335.312In range
AE404ENTHALPY (J/GDA) · Supply Air (sa)35.57834.93035.62435.28435.616In range
AE404ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)35.57934.93035.64035.29035.616In range
AE404ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)35.57934.93035.64035.29035.616In range
AE404ENTHALPY (J/GDA) · Zone 1 Air (z1)49.20348.56049.28048.92349.253In range
AE404ENTHALPY (J/GDA) · Zone 2 Air (z2)51.19350.58051.28850.93251.242In range
AE404ENTHALPY (J/GDA) · Return Fan Inlet (rfi)50.08049.63050.14749.85850.131In range
AE404ENTHALPY (J/GDA) · Return Fan Outlet (rfo)50.18949.73050.25649.95850.240In range
AE404MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.27510.27290.28420.27900.2753In range
AE404MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.53890.53540.54920.54050.5392In range
AE404MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.53890.53540.54920.54050.5392In range
AE404MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.53890.53540.54920.54050.5392In range
AE404MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.53890.53540.54920.54050.5392In range
AE404MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.25780.25540.26280.25850.2579In range
AE404MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.28110.28000.28640.28200.2813In range
AE404MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE404MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE404MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.26380.25430.26610.26150.2639In range
AE404MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.26380.25430.26610.26150.2639In range
AE405DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)24.90024.88924.90024.89624.900In range
AE405DRY BULB TEMPERATURE (°C) · Mixed Air (ma)24.73824.72224.75824.74324.738In range
AE405DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)24.73824.72224.75824.74324.738In range
AE405DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.66412.64712.67012.66212.664In range
AE405DRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.77812.79512.78212.778Below range
AE405DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)12.78312.77812.79512.78312.778In range
AE405DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)12.78312.77812.79512.78312.778In range
AE405DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.33323.33223.34423.33523.333In range
AE405DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)24.44424.44024.46124.44624.444In range
AE405DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.94923.93623.99623.95623.949In range
AE405DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)23.95423.94424.00023.95923.954In range
AE405HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.0044810.0044570.0045100.0044910.004491In range
AE405HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0048360.0047000.0048510.0048020.004846In range
AE405HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.0048360.0047000.0048510.0048020.004846In range
AE405HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0048360.0047000.0048510.0048010.004846In range
AE405HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0048360.0047000.0048510.0048020.004846In range
AE405HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0048380.0047000.0048510.0048020.004846In range
AE405HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0048380.0047000.0048510.0048020.004846In range
AE405HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0065250.0064730.0065820.0065290.006530In range
AE405HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.0065840.0065330.0066450.0065930.006590In range
AE405HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0065570.0059000.0066160.0064530.006563In range
AE405HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0065570.0059000.0066160.0064530.006563In range
AE405SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)851.19830.35850.44841.09850.43Above range
AE405SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)851.20830.35850.45841.10850.45Above range
AE405SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)851.20830.35850.45841.10850.45Above range
AE405SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)816.73815.78833.33823.86815.98In range
AE405SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)817.05815.52833.33823.84816.31In range
AE405SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)817.07816.16833.33824.04816.31In range
AE405SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)817.07816.16833.33824.04816.31In range
AE405SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)849.48830.35848.73840.24848.72Above range
AE405SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)852.74830.35851.98841.87851.98Above range
AE405SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)851.28830.35850.53841.15850.52Above range
AE405SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)851.30830.35850.51841.15850.54Above range
AE405ENTHALPY (J/GDA) · Location Outdoor Air (oa)36.43536.43536.50636.47736.491In range
AE405ENTHALPY (J/GDA) · Mixed Air (ma)37.17437.06237.21637.16037.230In range
AE405ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)37.17437.06237.21637.16037.230In range
AE405ENTHALPY (J/GDA) · Cool Coil Outlet (cco)24.93424.79924.97024.90724.975In range
AE405ENTHALPY (J/GDA) · Supply Air (sa)25.04924.91925.10025.02925.090In range
AE405ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)25.05824.91925.10025.02925.090In range
AE405ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)25.05824.91925.10025.02925.090In range
AE405ENTHALPY (J/GDA) · Zone 1 Air (z1)40.04739.92640.11640.04940.091In range
AE405ENTHALPY (J/GDA) · Zone 2 Air (z2)41.32741.21441.45041.35141.374In range
AE405ENTHALPY (J/GDA) · Return Fan Inlet (rfi)40.75740.62540.92040.78740.802In range
AE405ENTHALPY (J/GDA) · Return Fan Outlet (rfo)40.76240.62840.92040.79040.807In range
AE405MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.27710.27740.28420.28050.2774Below range
AE405MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.33430.33350.33830.33520.3347In range
AE405MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.33430.33350.33830.33520.3347In range
AE405MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.33430.33350.33830.33520.3347In range
AE405MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.33430.33350.33830.33520.3347In range
AE405MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.13650.13620.13830.13690.1368In range
AE405MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.19770.19730.20000.19820.1980In range
AE405MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE405MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE405MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.057120.049610.058300.054610.05733In range
AE405MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.057120.049970.058300.054670.05733In range
AE406DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)23.0002323.0002323.000In range
AE406DRY BULB TEMPERATURE (°C) · Mixed Air (ma)23.16123.13423.16723.15523.161In range
AE406DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)23.16123.13423.16723.15523.161In range
AE406DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.66512.64712.66912.66112.665In range
AE406DRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.77112.79412.78012.778In range
AE406DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)12.78312.77112.79412.78212.778In range
AE406DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)12.78312.77112.79412.78212.778In range
AE406DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.33323.31823.34423.33223.333In range
AE406DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)24.44424.43124.46124.44524.444In range
AE406DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.94923.93524.00423.95423.949In range
AE406DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)23.95423.93924.00823.95823.954In range
AE406HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.015570.015520.015630.015580.01556In range
AE406HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.014760.014700.014910.014810.01475In range
AE406HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.014760.014700.014910.014810.01475In range
AE406HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0091180.0090680.0092000.0091310.009126In range
AE406HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0091180.0090680.0092000.0091310.009126In range
AE406HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0091180.0090680.0092000.0091310.009126In range
AE406HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0091180.0090680.0092000.0091310.009126In range
AE406HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.010820.010780.010930.010830.01082In range
AE406HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.010880.010850.010990.010900.01088In range
AE406HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.010850.010300.010970.010770.01086In range
AE406HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.010850.010300.010970.010770.01086In range
AE406SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)860.73830.35859.94845.85859.94Above range
AE406SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)860.11830.35859.33845.55859.32Above range
AE406SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)860.11830.35859.39845.56859.32Above range
AE406SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)822.31821.38833.33826.65821.55In range
AE406SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)822.63821.07833.33826.63821.88In range
AE406SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)822.65821.76833.33826.83821.88In range
AE406SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)822.65821.76833.33826.83821.88In range
AE406SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)855.28830.35854.50843.14854.51Above range
AE406SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)858.56830.35857.79844.78857.80Above range
AE406SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)857.10830.35856.32844.05856.33Above range
AE406SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)857.11830.35856.30844.05856.35Above range
AE406ENTHALPY (J/GDA) · Location Outdoor Air (oa)62.70562.70562.85162.75562.710In range
AE406ENTHALPY (J/GDA) · Mixed Air (ma)60.83260.86261.12861.00760.839Below range
AE406ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)60.83260.95661.12861.03860.839Below range
AE406ENTHALPY (J/GDA) · Cool Coil Outlet (cco)35.74435.62035.76435.69935.781In range
AE406ENTHALPY (J/GDA) · Supply Air (sa)35.86035.74035.87935.81735.897In range
AE406ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)35.86635.74035.87935.81735.897In range
AE406ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)35.86635.74035.87935.81735.897In range
AE406ENTHALPY (J/GDA) · Zone 1 Air (z1)50.97150.85051.03550.94251.015In range
AE406ENTHALPY (J/GDA) · Zone 2 Air (z2)52.26252.18052.33552.25252.308In range
AE406ENTHALPY (J/GDA) · Return Fan Inlet (rfi)51.68751.64451.75551.68351.731In range
AE406ENTHALPY (J/GDA) · Return Fan Outlet (rfo)51.69251.64751.76051.68651.736In range
AE406MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.27530.27470.28420.27940.2755In range
AE406MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.33170.32970.33840.33280.3321In range
AE406MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.33170.32970.33840.33280.3321In range
AE406MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.33170.32970.33840.33280.3321In range
AE406MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.33170.32970.33840.33280.3321In range
AE406MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.13550.13460.13820.13600.1357In range
AE406MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.19620.19510.20010.19690.1964In range
AE406MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE406MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE406MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.056410.047270.056970.053440.05661In range
AE406MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.056410.047270.056970.053440.05661In range
AE426DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)23.0002323.0002323.000In range
AE426DRY BULB TEMPERATURE (°C) · Mixed Air (ma)23.0002323.0002323.000In range
AE426DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)23.0002323.0002323.000In range
AE426DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.66512.64712.67012.66112.665In range
AE426DRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.77812.78212.78012.778Below range
AE426DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)12.78312.77812.79012.78212.778In range
AE426DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)12.78312.77812.79012.78212.778In range
AE426DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.33323.32923.34423.33423.333In range
AE426DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)24.44424.44224.46124.44624.444In range
AE426DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.94923.93623.99223.95423.949In range
AE426DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)23.95423.94423.99723.95823.954In range
AE426HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.015570.015520.015630.015580.01556In range
AE426HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.015570.015520.015630.015580.01556In range
AE426HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.015570.015520.015630.015580.01556In range
AE426HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0091180.0090800.0092000.0091390.009126In range
AE426HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0091180.0090800.0092000.0091390.009126In range
AE426HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0091180.0090800.0092000.0091390.009126In range
AE426HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0091180.0090800.0092000.0091390.009126In range
AE426HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.010820.010790.010940.010840.01082In range
AE426HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.010880.010860.011000.010910.01088In range
AE426HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.010850.010400.010970.010800.01086In range
AE426HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.010850.010400.010970.010800.01086In range
AE426SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)860.73830.35859.94845.85859.94Above range
AE426SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)860.73830.35859.94845.85859.94Above range
AE426SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)860.73830.35859.94845.85859.94Above range
AE426SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)822.31821.38833.33826.66821.55In range
AE426SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)822.63821.11833.33826.64821.88In range
AE426SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)822.65821.76833.33826.84821.88In range
AE426SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)822.65821.76833.33826.84821.88In range
AE426SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)855.28830.35854.53843.15854.51Above range
AE426SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)858.56830.35857.83844.79857.80Above range
AE426SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)857.10830.35856.36844.06856.33Above range
AE426SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)857.11830.35856.34844.06856.35Above range
AE426ENTHALPY (J/GDA) · Location Outdoor Air (oa)62.70562.70562.85162.75562.710In range
AE426ENTHALPY (J/GDA) · Mixed Air (ma)62.70562.70562.85162.75562.710In range
AE426ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)62.70562.70562.85162.75562.710In range
AE426ENTHALPY (J/GDA) · Cool Coil Outlet (cco)35.74435.63035.79335.72735.781In range
AE426ENTHALPY (J/GDA) · Supply Air (sa)35.86035.76035.90835.84835.897In range
AE426ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)35.86635.76035.90835.85235.897In range
AE426ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)35.86635.76035.90835.85235.897In range
AE426ENTHALPY (J/GDA) · Zone 1 Air (z1)50.97150.88051.06150.98051.015In range
AE426ENTHALPY (J/GDA) · Zone 2 Air (z2)52.26252.20852.36152.28952.308In range
AE426ENTHALPY (J/GDA) · Return Fan Inlet (rfi)51.68751.67051.78151.71751.731In range
AE426ENTHALPY (J/GDA) · Return Fan Outlet (rfo)51.69251.67051.78651.72051.736In range
AE426MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.33170.32940.33840.33280.3321In range
AE426MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.33170.32940.33840.33280.3321In range
AE426MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.33170.32940.33840.33280.3321In range
AE426MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.33170.32940.33840.33280.3321In range
AE426MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.33170.32940.33840.33280.3321In range
AE426MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.13550.13450.13820.13590.1357In range
AE426MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.19620.19490.20010.19680.1964In range
AE426MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE426MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE426MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.056410.047260.056970.053420.05661In range
AE426MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.056410.047260.056970.053420.05661In range
AE445DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)24.90024.88924.90024.89624.900In range
AE445DRY BULB TEMPERATURE (°C) · Mixed Air (ma)24.90024.88924.90024.89624.900In range
AE445DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)24.90024.88924.90024.89624.900In range
AE445DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.66412.65212.67012.66312.664In range
AE445DRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.77812.79512.78212.778Below range
AE445DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)12.78312.77812.79512.78312.778In range
AE445DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)12.78312.77812.79512.78312.778In range
AE445DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.33323.33223.34423.33523.333In range
AE445DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)24.44424.44224.46124.44624.444In range
AE445DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.94923.93624.00523.95823.949In range
AE445DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)23.95423.94424.00923.96123.954In range
AE445HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.0044810.0044570.0045100.0044910.004491In range
AE445HUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0044810.0044570.0045100.0044910.004491In range
AE445HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.0044810.0044570.0045100.0044910.004491In range
AE445HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0044810.0044570.0045100.0044910.004491In range
AE445HUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0044810.0044570.0045100.0044910.004491In range
AE445HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0045190.0044570.0045100.0044910.004491Above range
AE445HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0045190.0044570.0045100.0044910.004491Above range
AE445HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0062050.0061390.0062640.0061960.006174In range
AE445HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.0062640.0061970.0063270.0062600.006234In range
AE445HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0062380.0057000.0062980.0061430.006207In range
AE445HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0062380.0057000.0062980.0061430.006207In range
AE445SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)851.19830.35850.44841.09850.43Above range
AE445SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)851.19830.35850.44841.09850.43Above range
AE445SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)851.19830.35850.44841.09850.43Above range
AE445SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)816.26815.32833.33823.64815.52In range
AE445SPECIFIC VOLUME (L/KGDA) · Supply Air (sa)816.59815.07833.33823.61815.84In range
AE445SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)816.65815.69833.33823.81815.84In range
AE445SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)816.65815.69833.33823.81815.84In range
AE445SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)849.04830.35848.26840.00848.23Above range
AE445SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)852.30830.35851.52841.63851.49Above range
AE445SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)850.85830.35850.07840.91850.04Above range
AE445SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)850.87830.35850.05840.91850.06Above range
AE445ENTHALPY (J/GDA) · Location Outdoor Air (oa)36.43536.43536.50636.47736.491In range
AE445ENTHALPY (J/GDA) · Mixed Air (ma)36.43536.43536.50636.47736.491In range
AE445ENTHALPY (J/GDA) · Preheat Coil Outlet (pco)36.43536.43536.50636.47736.491In range
AE445ENTHALPY (J/GDA) · Cool Coil Outlet (cco)24.03824.03424.11024.07624.079In range
AE445ENTHALPY (J/GDA) · Supply Air (sa)24.15324.15524.24024.19824.194Below range
AE445ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)24.25424.15524.24024.19824.194Above range
AE445ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)24.25424.15524.24024.19824.194Above range
AE445ENTHALPY (J/GDA) · Zone 1 Air (z1)39.23439.15339.26039.21439.185In range
AE445ENTHALPY (J/GDA) · Zone 2 Air (z2)40.51440.44140.58040.51140.467In range
AE445ENTHALPY (J/GDA) · Return Fan Inlet (rfi)39.94439.85240.05039.94739.896In range
AE445ENTHALPY (J/GDA) · Return Fan Outlet (rfo)39.94939.85640.06039.95339.901In range
AE445MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.33450.33350.33830.33520.3350In range
AE445MASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.33450.33350.33830.33520.3350In range
AE445MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.33450.33350.33830.33520.3350In range
AE445MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.33450.33350.33830.33520.3350In range
AE445MASS FLOW RATE (KGDA/S) · Supply Air (sa)0.33450.33350.33830.33520.3350In range
AE445MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.13660.13620.13820.13690.1368In range
AE445MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.19780.19730.20010.19830.1981In range
AE445MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE445MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE445MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.057180.049790.058290.054660.05740In range
AE445MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.057180.050090.058290.054710.05740In range

Min, Max and Mean describe the example programs published with the standard. Analytical is the closed-form or quasi-analytical solution where the standard gives one.