Section 11 · AE
Air-side equipment
Air-side HVAC systems at steady state: coil loads and the air state at each point of the system, compared with a quasi-analytical solution.
- Cases run
- 24
- Values compared
- 1371
- Outside example range
- 249
- Harness checks passed
- 1130 of 1132
- Run date
- 2026-10-03
Cases
Each case page shows its results, where they sit in the reference range, and the input file.
AE coil and zone loads24 rows
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| AE101 | Sensible Heating Load (QZHsensible) (kWh/h) | 2.931 | 2.930 | 2.931 | 2.931 | 2.931 | In range |
| AE101 | Sensible Cooling Load (QZClatent) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE101 | Latent Load (QZlatent) (kWh/h) | 0.5861 | 0.5861 | 0.5867 | 0.5862 | 0.5861 | In range |
| AE101 | Coil Load (QH) (kWh/h) | 8.404 | 8.372 | 8.768 | 8.484 | 8.420 | In range |
| AE101 | Loads Sensible (QCsensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE101 | Latent (QClatent) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE101 | Total (QCtotal) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE101 | Outlet RH (RHcco) (%) | 6.386 | 6.353 | 6.867 | 6.545 | 6.385 | In range |
| AE103 | Sensible Heating Load (QZHsensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE103 | Sensible Cooling Load (QZClatent) (kWh/h) | 1.465 | 1.465 | 1.467 | 1.465 | 1.465 | In range |
| AE103 | Latent Load (QZlatent) (kWh/h) | 0.5861 | 0.5860 | 0.5897 | 0.5866 | 0.5861 | In range |
| AE103 | Coil Load (QH) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE103 | Loads Sensible (QCsensible) (kWh/h) | 0.7832 | 0.7523 | 0.7841 | 0.7712 | 0.7835 | In range |
| AE103 | Latent (QClatent) (kWh/h) | 0 | 0 | 0.01033 | 0.001476 | 0 | In range |
| AE103 | Total (QCtotal) (kWh/h) | 0.7832 | 0.7620 | 0.7841 | 0.7727 | 0.7835 | In range |
| AE103 | Outlet RH (RHcco) (%) | 32.833 | 31.654 | 33.030 | 32.581 | 32.843 | In range |
| AE104 | Sensible Heating Load (QZHsensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE104 | Sensible Cooling Load (QZClatent) (kWh/h) | 2.931 | 2.930 | 2.931 | 2.931 | 2.931 | In range |
| AE104 | Latent Load (QZlatent) (kWh/h) | 0.5861 | 0.5858 | 0.5861 | 0.5861 | 0.5861 | In range |
| AE104 | Coil Load (QH) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE104 | Loads Sensible (QCsensible) (kWh/h) | 3.492 | 3.389 | 3.543 | 3.488 | 3.497 | In range |
| AE104 | Latent (QClatent) (kWh/h) | 2.057 | 2.012 | 2.293 | 2.140 | 2.054 | In range |
| AE104 | Total (QCtotal) (kWh/h) | 5.549 | 5.533 | 5.836 | 5.628 | 5.551 | In range |
| AE104 | Outlet RH (RHcco) (%) | 99.884 | 98.660 | 100 | 99.748 | 100 | In range |
AE node states105 rows · 25 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| AE101 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | −29.000 | −29 | −29 | −29 | −29 | In range |
| AE101 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 4.003 | 4.003 | 4.454 | 4.295 | 4.003 | In range |
| AE101 | DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco) | 29.324 | 28.994 | 29.326 | 29.147 | 29.316 | In range |
| AE101 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 29.324 | 28.994 | 29.326 | 29.147 | 29.316 | In range |
| AE101 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 29.930 | 29.222 | 29.933 | 29.655 | 29.922 | In range |
| AE101 | DRY BULB TEMPERATURE (°C) · Zone Air (z1) | 21.111 | 21.099 | 21.118 | 21.111 | 21.111 | In range |
| AE101 | DRY BULB TEMPERATURE (°C) · Return Air (ra) | 21.111 | 21.099 | 21.118 | 21.111 | 21.111 | In range |
| AE101 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 2.59e-4 | 2.59e-4 | 3.44e-4 | 2.78e-4 | 2.59e-4 | In range |
| AE101 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.001606 | 0.001595 | 0.001696 | 0.001631 | 0.001604 | In range |
| AE101 | HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco) | 0.001606 | 0.001595 | 0.001696 | 0.001631 | 0.001604 | In range |
| AE101 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.001606 | 0.001595 | 0.001696 | 0.001631 | 0.001604 | In range |
| AE101 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.001606 | 0.001595 | 0.001696 | 0.001631 | 0.001604 | In range |
| AE101 | HUMIDITY RATIO (G/GDA) · Zone Air (z1) | 0.002306 | 0.002200 | 0.002373 | 0.002308 | 0.002304 | In range |
| AE101 | HUMIDITY RATIO (G/GDA) · Return Air (ra) | 0.002306 | 0.002200 | 0.002374 | 0.002310 | 0.002304 | In range |
| AE101 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 692.65 | 691.84 | 833.33 | 776.09 | 691.93 | In range |
| AE101 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 787.91 | 787.06 | 833.33 | 814.18 | 787.16 | In range |
| AE101 | SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco) | 859.85 | 830.35 | 859.03 | 842.94 | 859.06 | Above range |
| AE101 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 859.85 | 830.35 | 859.03 | 842.94 | 859.06 | Above range |
| AE101 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 861.57 | 830.35 | 860.69 | 842.78 | 860.78 | Above range |
| AE101 | SPECIFIC VOLUME (L/KGDA) · Zone Air (z1) | 837.45 | 830.35 | 836.69 | 833.99 | 836.69 | Above range |
| AE101 | SPECIFIC VOLUME (L/KGDA) · Return Air (ra) | 837.45 | 830.35 | 836.69 | 833.34 | 836.69 | Above range |
| AE101 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | −28.507 | −28.540 | −28.330 | −28.472 | −28.540 | In range |
| AE101 | ENTHALPY (J/GDA) · Mixed Air (ma) | 8.050 | 8.031 | 8.680 | 8.446 | 8.051 | In range |
| AE101 | ENTHALPY (J/GDA) · Heat Coil Outlet (hco) | 33.568 | 33.309 | 33.562 | 33.460 | 33.592 | Above range |
| AE101 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 33.568 | 33.309 | 33.562 | 33.460 | 33.592 | Above range |
| AE101 | ENTHALPY (J/GDA) · Supply Air (sa) | 34.180 | 33.900 | 34.173 | 34.057 | 34.203 | Above range |
| AE101 | ENTHALPY (J/GDA) · Zone Air (z1) | 27.071 | 27.034 | 27.263 | 27.121 | 27.091 | In range |
| AE101 | ENTHALPY (J/GDA) · Return Air (ra) | 27.071 | 27.034 | 27.263 | 27.121 | 27.091 | In range |
| AE101 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.1127 | 0.1128 | 0.1195 | 0.1141 | 0.1128 | Below range |
| AE101 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3293 | 0.3296 | 0.3586 | 0.3398 | 0.3296 | Below range |
| AE101 | MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco) | 0.3293 | 0.3296 | 0.3586 | 0.3398 | 0.3296 | Below range |
| AE101 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3293 | 0.3296 | 0.3586 | 0.3398 | 0.3296 | Below range |
| AE101 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3293 | 0.3296 | 0.3586 | 0.3398 | 0.3296 | Below range |
| AE101 | MASS FLOW RATE (KGDA/S) · Zone Air (z1) | n/a* | |||||
| AE101 | MASS FLOW RATE (KGDA/S) · Return Air (ra) | 0.2166 | 0.2168 | 0.2391 | 0.2271 | 0.2168 | Below range |
| AE103 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 15.500 | 15.500 | 15.500 | 15.500 | 15.500 | In range |
| AE103 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 20.774 | 20.689 | 20.774 | 20.732 | 20.774 | In range |
| AE103 | DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco) | 20.774 | 20.721 | 21.278 | 20.816 | 20.774 | In range |
| AE103 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 18.500 | 18.462 | 19 | 18.573 | 18.504 | In range |
| AE103 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 19.085 | 19 | 19.101 | 19.074 | 19.088 | In range |
| AE103 | DRY BULB TEMPERATURE (°C) · Zone Air (z1) | 23.333 | 23.329 | 23.348 | 23.334 | 23.333 | In range |
| AE103 | DRY BULB TEMPERATURE (°C) · Return Air (ra) | 23.333 | 23.329 | 23.348 | 23.335 | 23.333 | In range |
| AE103 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.002933 | 0.002895 | 0.002948 | 0.002928 | 0.002936 | In range |
| AE103 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.004324 | 0.004284 | 0.004355 | 0.004311 | 0.004325 | In range |
| AE103 | HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco) | 0.004324 | 0.004284 | 0.004355 | 0.004311 | 0.004325 | In range |
| AE103 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.004324 | 0.004284 | 0.004355 | 0.004311 | 0.004325 | In range |
| AE103 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.004324 | 0.004284 | 0.004355 | 0.004311 | 0.004325 | In range |
| AE103 | HUMIDITY RATIO (G/GDA) · Zone Air (z1) | 0.005001 | 0.004960 | 0.005059 | 0.004997 | 0.005002 | In range |
| AE103 | HUMIDITY RATIO (G/GDA) · Return Air (ra) | 0.005001 | 0.004960 | 0.005059 | 0.005003 | 0.005002 | In range |
| AE103 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 822.32 | 821.41 | 833.33 | 827.93 | 821.57 | In range |
| AE103 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 839.20 | 830.35 | 838.44 | 834.68 | 838.44 | Above range |
| AE103 | SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco) | 839.20 | 830.35 | 838.44 | 834.68 | 838.44 | Above range |
| AE103 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 832.71 | 830.35 | 833.33 | 832.09 | 831.96 | In range |
| AE103 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 834.38 | 829.58 | 833.45 | 831.94 | 833.63 | Above range |
| AE103 | SPECIFIC VOLUME (L/KGDA) · Zone Air (z1) | 847.42 | 830.35 | 846.66 | 837.97 | 846.65 | Above range |
| AE103 | SPECIFIC VOLUME (L/KGDA) · Return Air (ra) | 847.42 | 830.35 | 846.66 | 835.84 | 846.65 | Above range |
| AE103 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 22.996 | 22.996 | 23.032 | 23.015 | 23.020 | In range |
| AE103 | ENTHALPY (J/GDA) · Mixed Air (ma) | 31.856 | 31.706 | 31.890 | 31.787 | 31.883 | In range |
| AE103 | ENTHALPY (J/GDA) · Heat Coil Outlet (hco) | 31.856 | 31.706 | 31.890 | 31.787 | 31.883 | In range |
| AE103 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 29.553 | 29.461 | 29.598 | 29.520 | 29.582 | In range |
| AE103 | ENTHALPY (J/GDA) · Supply Air (sa) | 30.145 | 30.052 | 30.190 | 30.115 | 30.174 | In range |
| AE103 | ENTHALPY (J/GDA) · Zone Air (z1) | 36.171 | 36.062 | 36.260 | 36.156 | 36.200 | In range |
| AE103 | ENTHALPY (J/GDA) · Return Air (ra) | 36.171 | 36.062 | 36.260 | 36.156 | 36.200 | In range |
| AE103 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.1114 | 0.1115 | 0.1137 | 0.1127 | 0.1115 | Below range |
| AE103 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3401 | 0.3372 | 0.3410 | 0.3398 | 0.3404 | In range |
| AE103 | MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco) | 0.3401 | 0.3372 | 0.3410 | 0.3398 | 0.3404 | In range |
| AE103 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3401 | 0.3372 | 0.3410 | 0.3398 | 0.3404 | In range |
| AE103 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3401 | 0.3372 | 0.3410 | 0.3398 | 0.3404 | In range |
| AE103 | MASS FLOW RATE (KGDA/S) · Zone Air (z1) | n/a* | |||||
| AE103 | MASS FLOW RATE (KGDA/S) · Return Air (ra) | 0.2287 | 0.2248 | 0.2289 | 0.2268 | 0.2289 | In range |
| AE104 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 26.900 | 26.889 | 26.900 | 26.897 | 26.900 | In range |
| AE104 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 24.868 | 24.864 | 24.906 | 24.887 | 24.868 | In range |
| AE104 | DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco) | 24.868 | 24.864 | 25.500 | 24.972 | 24.868 | In range |
| AE104 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 14.929 | 14.701 | 15.222 | 14.927 | 14.939 | In range |
| AE104 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 15.506 | 15.222 | 15.525 | 15.426 | 15.514 | In range |
| AE104 | DRY BULB TEMPERATURE (°C) · Zone Air (z1) | 23.889 | 23.876 | 23.890 | 23.887 | 23.889 | In range |
| AE104 | DRY BULB TEMPERATURE (°C) · Return Air (ra) | 23.889 | 23.876 | 23.890 | 23.886 | 23.889 | In range |
| AE104 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.01677 | 0.01676 | 0.01685 | 0.01680 | 0.01677 | In range |
| AE104 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.01304 | 0.01295 | 0.01320 | 0.01308 | 0.01305 | In range |
| AE104 | HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco) | 0.01304 | 0.01295 | 0.01320 | 0.01308 | 0.01305 | In range |
| AE104 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.01059 | 0.01030 | 0.01080 | 0.01058 | 0.01060 | In range |
| AE104 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.01059 | 0.01030 | 0.01080 | 0.01058 | 0.01060 | In range |
| AE104 | HUMIDITY RATIO (G/GDA) · Zone Air (z1) | 0.01126 | 0.01099 | 0.01150 | 0.01126 | 0.01128 | In range |
| AE104 | HUMIDITY RATIO (G/GDA) · Return Air (ra) | 0.01126 | 0.01099 | 0.01150 | 0.01126 | 0.01128 | In range |
| AE104 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 873.71 | 830.35 | 872.93 | 848.48 | 872.92 | Above range |
| AE104 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 862.73 | 830.35 | 861.98 | 844.10 | 861.96 | Above range |
| AE104 | SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco) | 862.73 | 830.35 | 861.98 | 844.10 | 861.96 | Above range |
| AE104 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 830.75 | 829.89 | 833.33 | 831.33 | 830.03 | In range |
| AE104 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 832.41 | 827.67 | 833.33 | 831.18 | 831.69 | In range |
| AE104 | SPECIFIC VOLUME (L/KGDA) · Zone Air (z1) | 857.49 | 830.35 | 856.76 | 842.01 | 856.73 | Above range |
| AE104 | SPECIFIC VOLUME (L/KGDA) · Return Air (ra) | 857.49 | 830.35 | 856.76 | 838.36 | 856.73 | Above range |
| AE104 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 69.814 | 69.795 | 69.994 | 69.863 | 69.851 | In range |
| AE104 | ENTHALPY (J/GDA) · Mixed Air (ma) | 58.211 | 57.970 | 58.382 | 58.243 | 58.268 | In range |
| AE104 | ENTHALPY (J/GDA) · Heat Coil Outlet (hco) | 58.211 | 57.970 | 58.382 | 58.243 | 58.268 | In range |
| AE104 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 41.778 | 40.790 | 41.874 | 41.532 | 41.845 | In range |
| AE104 | ENTHALPY (J/GDA) · Supply Air (sa) | 42.369 | 41.400 | 42.465 | 42.131 | 42.436 | In range |
| AE104 | ENTHALPY (J/GDA) · Zone Air (z1) | 52.677 | 51.940 | 52.774 | 52.496 | 52.744 | In range |
| AE104 | ENTHALPY (J/GDA) · Return Air (ra) | 52.677 | 51.940 | 52.774 | 52.496 | 52.744 | In range |
| AE104 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.1101 | 0.1093 | 0.1137 | 0.1119 | 0.1102 | In range |
| AE104 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3409 | 0.3279 | 0.3412 | 0.3387 | 0.3412 | In range |
| AE104 | MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco) | 0.3409 | 0.3279 | 0.3412 | 0.3387 | 0.3412 | In range |
| AE104 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3409 | 0.3279 | 0.3412 | 0.3387 | 0.3412 | In range |
| AE104 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3409 | 0.3279 | 0.3412 | 0.3387 | 0.3412 | In range |
| AE104 | MASS FLOW RATE (KGDA/S) · Zone Air (z1) | n/a* | |||||
| AE104 | MASS FLOW RATE (KGDA/S) · Return Air (ra) | 0.2308 | 0.2186 | 0.2310 | 0.2261 | 0.2310 | In range |
AE SZ coil and zone loads56 rows · 2 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| AE201 | Sensible Heating Load (QZHsensible) (kWh/h) | 2.931 | 2.930 | 2.931 | 2.931 | 2.931 | In range |
| AE201 | Sensible Cooling Load (QZClatent) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE201 | Latent Load (QZlatent) (kWh/h) | 0.5861 | 0.5861 | 0.5900 | 0.5867 | 0.5861 | In range |
| AE201 | Coil Load (QH) (kWh/h) | 8.344 | 8.302 | 8.709 | 8.419 | 8.360 | In range |
| AE201 | Loads Sensible (QCsensible) (kWh/h) | 0 | 0 | 8.05e-8 | 1.15e-8 | 0 | In range |
| AE201 | Latent (QClatent) (kWh/h) | 0 | 0 | 1.84e-5 | 2.63e-6 | 0 | In range |
| AE201 | Total (QCtotal) (kWh/h) | 0 | 0 | 1.85e-5 | 2.64e-6 | 0 | In range |
| AE201 | Outlet RH (RHcco) (%) | 6.386 | 6.353 | 6.871 | 6.581 | 6.385 | In range |
| AE203 | Sensible Heating Load (QZHsensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE203 | Sensible Cooling Load (QZClatent) (kWh/h) | 1.465 | 1.465 | 1.467 | 1.465 | 1.465 | In range |
| AE203 | Latent Load (QZlatent) (kWh/h) | 0.5861 | 0.5860 | 0.5897 | 0.5866 | 0.5861 | In range |
| AE203 | Coil Load (QH) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE203 | Loads Sensible (QCsensible) (kWh/h) | 0.8558 | 0.8191 | 0.8530 | 0.8390 | 0.8561 | Above range |
| AE203 | Latent (QClatent) (kWh/h) | 0 | 0 | 0.01125 | 0.001607 | 0 | In range |
| AE203 | Total (QCtotal) (kWh/h) | 0.8558 | 0.8300 | 0.8530 | 0.8406 | 0.8561 | Above range |
| AE203 | Outlet RH (RHcco) (%) | 32.833 | 32.515 | 33.030 | 32.740 | 32.843 | In range |
| AE204 | Sensible Heating Load (QZHsensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE204 | Sensible Cooling Load (QZClatent) (kWh/h) | 2.931 | 2.930 | 2.931 | 2.931 | 2.931 | In range |
| AE204 | Latent Load (QZlatent) (kWh/h) | 0.5861 | 0.5858 | 0.5861 | 0.5861 | 0.5861 | In range |
| AE204 | Coil Load (QH) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE204 | Loads Sensible (QCsensible) (kWh/h) | 3.570 | 3.456 | 3.608 | 3.557 | 3.574 | In range |
| AE204 | Latent (QClatent) (kWh/h) | 2.057 | 2.054 | 2.289 | 2.155 | 2.054 | In range |
| AE204 | Total (QCtotal) (kWh/h) | 5.626 | 5.623 | 5.897 | 5.712 | 5.628 | In range |
| AE204 | Outlet RH (RHcco) (%) | 99.884 | 98.620 | 100 | 99.751 | 100 | In range |
| AE205 | Sensible Heating Load (QZHsensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE205 | Sensible Cooling Load (QZClatent) (kWh/h) | 1.465 | 1.464 | 1.470 | 1.466 | 1.465 | In range |
| AE205 | Latent Load (QZlatent) (kWh/h) | 0.5861 | 0.5861 | 0.5900 | 0.5867 | 0.5861 | In range |
| AE205 | Coil Load (QH) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE205 | Loads Sensible (QCsensible) (kWh/h) | 1.914 | 1.880 | 1.929 | 1.910 | 1.916 | In range |
| AE205 | Latent (QClatent) (kWh/h) | 0 | 0 | 0.03109 | 0.004441 | 0 | In range |
| AE205 | Total (QCtotal) (kWh/h) | 1.914 | 1.908 | 1.929 | 1.914 | 1.916 | In range |
| AE205 | Outlet RH (RHcco) (%) | 44.495 | 44.111 | 44.853 | 44.495 | 44.561 | In range |
| AE206 | Sensible Heating Load (QZHsensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE206 | Sensible Cooling Load (QZClatent) (kWh/h) | 1.465 | 1.464 | 1.470 | 1.466 | 1.465 | In range |
| AE206 | Latent Load (QZlatent) (kWh/h) | 0.5861 | 0.5861 | 0.5900 | 0.5867 | 0.5861 | In range |
| AE206 | Coil Load (QH) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE206 | Loads Sensible (QCsensible) (kWh/h) | 1.704 | 1.646 | 1.731 | 1.699 | 1.706 | In range |
| AE206 | Latent (QClatent) (kWh/h) | 0.9769 | 0.9632 | 1.087 | 1.017 | 0.9704 | In range |
| AE206 | Total (QCtotal) (kWh/h) | 2.681 | 2.664 | 2.818 | 2.717 | 2.677 | In range |
| AE206 | Outlet RH (RHcco) (%) | 99.877 | 99.025 | 100 | 99.759 | 100 | In range |
| AE226 | Sensible Heating Load (QZHsensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE226 | Sensible Cooling Load (QZClatent) (kWh/h) | 1.465 | 1.464 | 1.466 | 1.465 | 1.465 | In range |
| AE226 | Latent Load (QZlatent) (kWh/h) | 0.5861 | 0.5861 | 0.5897 | 0.5866 | 0.5861 | In range |
| AE226 | Coil Load (QH) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE226 | Loads Sensible (QCsensible) (kWh/h) | 1.560 | 1.503 | 1.597 | 1.560 | 1.562 | In range |
| AE226 | Latent (QClatent) (kWh/h) | 1.820 | 1.778 | 2.050 | 1.858 | 1.800 | In range |
| AE226 | Total (QCtotal) (kWh/h) | 3.380 | 3.335 | 3.643 | 3.418 | 3.362 | In range |
| AE226 | Outlet RH (RHcco) (%) | 99.877 | 99.650 | 100 | 99.913 | 100 | In range |
| AE245 | Sensible Heating Load (QZHsensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE245 | Sensible Cooling Load (QZClatent) (kWh/h) | 1.465 | 1.464 | 1.564 | 1.479 | 1.465 | In range |
| AE245 | Latent Load (QZlatent) (kWh/h) | 0.5861 | 0.5861 | 0.5897 | 0.5866 | 0.5861 | In range |
| AE245 | Coil Load (QH) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE245 | Loads Sensible (QCsensible) (kWh/h) | 2.204 | 2.171 | 2.216 | 2.200 | 2.208 | In range |
| AE245 | Latent (QClatent) (kWh/h) | 0 | 0 | 0.03061 | 0.004374 | 0 | In range |
| AE245 | Total (QCtotal) (kWh/h) | 2.204 | 2.188 | 2.216 | 2.205 | 2.208 | In range |
| AE245 | Outlet RH (RHcco) (%) | 34.016 | 33.839 | 34.330 | 34.097 | 34.091 | In range |
AE SZ node states280 rows · 69 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| AE201 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | −29.000 | −29 | −29 | −29 | −29 | In range |
| AE201 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 4.183 | 4.185 | 4.648 | 4.493 | 4.183 | Below range |
| AE201 | DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco) | 29.324 | 28.667 | 29.326 | 29.067 | 29.316 | In range |
| AE201 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 29.324 | 28.667 | 29.326 | 29.067 | 29.316 | In range |
| AE201 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 29.930 | 29.576 | 29.933 | 29.727 | 29.922 | In range |
| AE201 | DRY BULB TEMPERATURE (°C) · Zone Air (z1) | 21.111 | 21.099 | 21.119 | 21.111 | 21.111 | In range |
| AE201 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 21.111 | 21.099 | 21.119 | 21.111 | 21.111 | In range |
| AE201 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 21.384 | 21.386 | 21.408 | 21.399 | 21.383 | Below range |
| AE201 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 2.59e-4 | 2.59e-4 | 3.44e-4 | 2.78e-4 | 2.59e-4 | In range |
| AE201 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.001606 | 0.001595 | 0.001698 | 0.001632 | 0.001604 | In range |
| AE201 | HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco) | 0.001606 | 0.001595 | 0.001698 | 0.001632 | 0.001604 | In range |
| AE201 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.001606 | 0.001595 | 0.001698 | 0.001632 | 0.001604 | In range |
| AE201 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.001606 | 0.001595 | 0.001698 | 0.001632 | 0.001604 | In range |
| AE201 | HUMIDITY RATIO (G/GDA) · Zone Air (z1) | 0.002306 | 0.002200 | 0.002374 | 0.002309 | 0.002304 | In range |
| AE201 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.002306 | 0.002200 | 0.002374 | 0.002309 | 0.002304 | In range |
| AE201 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.002306 | 0.002200 | 0.002374 | 0.002309 | 0.002304 | In range |
| AE201 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 692.65 | 691.84 | 833.33 | 776.09 | 691.93 | In range |
| AE201 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 788.42 | 787.61 | 833.33 | 814.39 | 787.67 | In range |
| AE201 | SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco) | 859.85 | 830.35 | 859.03 | 842.94 | 859.06 | Above range |
| AE201 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 859.85 | 830.35 | 859.03 | 842.94 | 859.06 | Above range |
| AE201 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 861.57 | 830.35 | 860.69 | 842.78 | 860.78 | Above range |
| AE201 | SPECIFIC VOLUME (L/KGDA) · Zone Air (z1) | 837.45 | 830.35 | 836.69 | 833.99 | 836.69 | Above range |
| AE201 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 837.45 | 830.35 | 836.69 | 833.99 | 836.69 | Above range |
| AE201 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 838.23 | 830.35 | 837.42 | 833.93 | 837.46 | Above range |
| AE201 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | −28.507 | −28.540 | −28.330 | −28.472 | −28.543 | In range |
| AE201 | ENTHALPY (J/GDA) · Mixed Air (ma) | 8.231 | 8.212 | 8.892 | 8.642 | 8.232 | In range |
| AE201 | ENTHALPY (J/GDA) · Heat Coil Outlet (hco) | 33.568 | 33.309 | 33.562 | 33.462 | 33.594 | Above range |
| AE201 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 33.568 | 33.309 | 33.562 | 33.462 | 33.594 | Above range |
| AE201 | ENTHALPY (J/GDA) · Supply Air (sa) | 34.180 | 33.900 | 34.173 | 34.058 | 34.206 | Above range |
| AE201 | ENTHALPY (J/GDA) · Zone Air (z1) | 27.071 | 27.035 | 27.266 | 27.123 | 27.093 | In range |
| AE201 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 27.071 | 27.035 | 27.266 | 27.123 | 27.093 | In range |
| AE201 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 27.346 | 27.327 | 27.564 | 27.411 | 27.367 | In range |
| AE201 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.1127 | 0.1128 | 0.1197 | 0.1141 | 0.1128 | Below range |
| AE201 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3293 | 0.3296 | 0.3591 | 0.3398 | 0.3296 | Below range |
| AE201 | MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco) | 0.3293 | 0.3296 | 0.3591 | 0.3398 | 0.3296 | Below range |
| AE201 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3293 | 0.3296 | 0.3591 | 0.3398 | 0.3296 | Below range |
| AE201 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3293 | 0.3296 | 0.3591 | 0.3398 | 0.3296 | Below range |
| AE201 | MASS FLOW RATE (KGDA/S) · Zone Air (z1) | n/a* | |||||
| AE201 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.2166 | 0.2168 | 0.2394 | 0.2257 | 0.2168 | Below range |
| AE201 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.2166 | 0.2168 | 0.2394 | 0.2257 | 0.2168 | Below range |
| AE203 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 15.500 | 15.500 | 15.500 | 15.500 | 15.500 | In range |
| AE203 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 20.985 | 20.889 | 20.983 | 20.931 | 20.985 | Above range |
| AE203 | DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco) | 20.985 | 20.889 | 20.983 | 20.931 | 20.985 | Above range |
| AE203 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 18.500 | 18.444 | 18.519 | 18.494 | 18.504 | In range |
| AE203 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 19.085 | 19.052 | 19.101 | 19.087 | 19.088 | In range |
| AE203 | DRY BULB TEMPERATURE (°C) · Zone Air (z1) | 23.333 | 23.329 | 23.348 | 23.335 | 23.333 | In range |
| AE203 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.333 | 23.329 | 23.348 | 23.335 | 23.333 | In range |
| AE203 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 23.646 | 23.611 | 23.648 | 23.629 | 23.646 | In range |
| AE203 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.002933 | 0.002895 | 0.002948 | 0.002928 | 0.002936 | In range |
| AE203 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.004324 | 0.004284 | 0.004355 | 0.004311 | 0.004325 | In range |
| AE203 | HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco) | 0.004324 | 0.004284 | 0.004355 | 0.004311 | 0.004325 | In range |
| AE203 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.004324 | 0.004284 | 0.004355 | 0.004311 | 0.004325 | In range |
| AE203 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.004324 | 0.004284 | 0.004355 | 0.004311 | 0.004325 | In range |
| AE203 | HUMIDITY RATIO (G/GDA) · Zone Air (z1) | 0.005001 | 0.004960 | 0.005059 | 0.004997 | 0.005002 | In range |
| AE203 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.005001 | 0.004960 | 0.005059 | 0.004997 | 0.005002 | In range |
| AE203 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.005001 | 0.004960 | 0.005059 | 0.004997 | 0.005002 | In range |
| AE203 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 822.32 | 821.41 | 833.33 | 827.93 | 821.57 | In range |
| AE203 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 839.80 | 830.35 | 839.04 | 834.91 | 839.04 | Above range |
| AE203 | SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco) | 839.80 | 830.35 | 839.04 | 834.91 | 839.04 | Above range |
| AE203 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 832.71 | 830.35 | 833.33 | 832.09 | 831.96 | In range |
| AE203 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 834.38 | 829.59 | 833.45 | 831.94 | 833.63 | Above range |
| AE203 | SPECIFIC VOLUME (L/KGDA) · Zone Air (z1) | 847.42 | 830.35 | 846.67 | 837.97 | 846.65 | Above range |
| AE203 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 847.42 | 830.35 | 846.67 | 837.97 | 846.65 | Above range |
| AE203 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 848.31 | 830.35 | 847.33 | 837.88 | 847.54 | Above range |
| AE203 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 22.996 | 22.996 | 23.032 | 23.015 | 23.022 | In range |
| AE203 | ENTHALPY (J/GDA) · Mixed Air (ma) | 32.069 | 31.903 | 32.106 | 31.988 | 32.099 | In range |
| AE203 | ENTHALPY (J/GDA) · Heat Coil Outlet (hco) | 32.069 | 31.903 | 32.106 | 31.988 | 32.099 | In range |
| AE203 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 29.553 | 29.461 | 29.601 | 29.520 | 29.583 | In range |
| AE203 | ENTHALPY (J/GDA) · Supply Air (sa) | 30.145 | 30.052 | 30.193 | 30.115 | 30.175 | In range |
| AE203 | ENTHALPY (J/GDA) · Zone Air (z1) | 36.171 | 36.061 | 36.260 | 36.157 | 36.202 | In range |
| AE203 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 36.171 | 36.061 | 36.260 | 36.157 | 36.202 | In range |
| AE203 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 36.489 | 36.357 | 36.560 | 36.460 | 36.520 | In range |
| AE203 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.1114 | 0.1115 | 0.1137 | 0.1127 | 0.1115 | Below range |
| AE203 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3401 | 0.3377 | 0.3410 | 0.3398 | 0.3404 | In range |
| AE203 | MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco) | 0.3401 | 0.3377 | 0.3410 | 0.3398 | 0.3404 | In range |
| AE203 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3401 | 0.3377 | 0.3410 | 0.3398 | 0.3404 | In range |
| AE203 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3401 | 0.3377 | 0.3410 | 0.3398 | 0.3404 | In range |
| AE203 | MASS FLOW RATE (KGDA/S) · Zone Air (z1) | n/a* | |||||
| AE203 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.2287 | 0.2251 | 0.2289 | 0.2271 | 0.2289 | In range |
| AE203 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.2287 | 0.2251 | 0.2289 | 0.2271 | 0.2289 | In range |
| AE204 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 26.900 | 26.889 | 26.900 | 26.897 | 26.900 | In range |
| AE204 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 25.088 | 25.065 | 25.111 | 25.089 | 25.088 | In range |
| AE204 | DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco) | 25.088 | 25.065 | 25.111 | 25.089 | 25.088 | In range |
| AE204 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 14.929 | 14.611 | 14.949 | 14.843 | 14.939 | In range |
| AE204 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 15.506 | 15.312 | 15.525 | 15.463 | 15.514 | In range |
| AE204 | DRY BULB TEMPERATURE (°C) · Zone Air (z1) | 23.889 | 23.882 | 23.897 | 23.889 | 23.889 | In range |
| AE204 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.889 | 23.882 | 23.897 | 23.889 | 23.889 | In range |
| AE204 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 24.216 | 24.167 | 24.217 | 24.185 | 24.215 | In range |
| AE204 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.01677 | 0.01676 | 0.01685 | 0.01680 | 0.01677 | In range |
| AE204 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.01304 | 0.01295 | 0.01314 | 0.01305 | 0.01305 | In range |
| AE204 | HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco) | 0.01304 | 0.01295 | 0.01314 | 0.01305 | 0.01305 | In range |
| AE204 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.01059 | 0.01031 | 0.01061 | 0.01052 | 0.01060 | In range |
| AE204 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.01059 | 0.01031 | 0.01061 | 0.01052 | 0.01060 | In range |
| AE204 | HUMIDITY RATIO (G/GDA) · Zone Air (z1) | 0.01126 | 0.01100 | 0.01129 | 0.01121 | 0.01128 | In range |
| AE204 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.01126 | 0.01100 | 0.01129 | 0.01121 | 0.01128 | In range |
| AE204 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.01126 | 0.01110 | 0.01132 | 0.01125 | 0.01128 | In range |
| AE204 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 873.71 | 830.35 | 872.93 | 848.48 | 872.92 | Above range |
| AE204 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 863.36 | 830.35 | 862.62 | 844.34 | 862.60 | Above range |
| AE204 | SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco) | 863.36 | 830.35 | 862.62 | 844.34 | 862.60 | Above range |
| AE204 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 830.75 | 829.89 | 833.33 | 831.33 | 830.03 | In range |
| AE204 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 832.41 | 827.67 | 833.33 | 831.18 | 831.69 | In range |
| AE204 | SPECIFIC VOLUME (L/KGDA) · Zone Air (z1) | 857.49 | 830.35 | 856.76 | 842.01 | 856.73 | Above range |
| AE204 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 857.49 | 830.35 | 856.76 | 842.01 | 856.73 | Above range |
| AE204 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 858.43 | 830.35 | 857.47 | 841.91 | 857.67 | Above range |
| AE204 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 69.814 | 69.795 | 69.994 | 69.863 | 69.854 | In range |
| AE204 | ENTHALPY (J/GDA) · Mixed Air (ma) | 58.438 | 58.200 | 58.581 | 58.458 | 58.497 | In range |
| AE204 | ENTHALPY (J/GDA) · Heat Coil Outlet (hco) | 58.438 | 58.200 | 58.581 | 58.458 | 58.497 | In range |
| AE204 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 41.778 | 40.840 | 41.874 | 41.546 | 41.846 | In range |
| AE204 | ENTHALPY (J/GDA) · Supply Air (sa) | 42.369 | 41.440 | 42.465 | 42.143 | 42.437 | In range |
| AE204 | ENTHALPY (J/GDA) · Zone Air (z1) | 52.677 | 51.990 | 52.775 | 52.511 | 52.746 | In range |
| AE204 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 52.677 | 51.990 | 52.775 | 52.511 | 52.746 | In range |
| AE204 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 53.012 | 52.290 | 53.109 | 52.819 | 53.081 | In range |
| AE204 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.1101 | 0.1095 | 0.1137 | 0.1119 | 0.1102 | In range |
| AE204 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3409 | 0.3284 | 0.3412 | 0.3387 | 0.3412 | In range |
| AE204 | MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco) | 0.3409 | 0.3284 | 0.3412 | 0.3387 | 0.3412 | In range |
| AE204 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3409 | 0.3284 | 0.3412 | 0.3387 | 0.3412 | In range |
| AE204 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3409 | 0.3284 | 0.3412 | 0.3387 | 0.3412 | In range |
| AE204 | MASS FLOW RATE (KGDA/S) · Zone Air (z1) | n/a* | |||||
| AE204 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.2308 | 0.2190 | 0.2310 | 0.2268 | 0.2310 | In range |
| AE204 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.2308 | 0.2190 | 0.2310 | 0.2268 | 0.2310 | In range |
| AE205 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 24.900 | 24.889 | 24.900 | 24.897 | 24.900 | In range |
| AE205 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 24.056 | 24.041 | 24.056 | 24.049 | 24.056 | Above range |
| AE205 | DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco) | 24.056 | 24.041 | 24.056 | 24.049 | 24.056 | Above range |
| AE205 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 18.502 | 18.444 | 18.524 | 18.498 | 18.506 | In range |
| AE205 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 19.087 | 19.053 | 19.109 | 19.091 | 19.090 | In range |
| AE205 | DRY BULB TEMPERATURE (°C) · Zone Air (z1) | 23.333 | 23.330 | 23.348 | 23.334 | 23.333 | In range |
| AE205 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.333 | 23.330 | 23.348 | 23.334 | 23.333 | In range |
| AE205 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 23.646 | 23.620 | 23.667 | 23.636 | 23.646 | In range |
| AE205 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE205 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.005875 | 0.005832 | 0.005916 | 0.005875 | 0.005884 | In range |
| AE205 | HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco) | 0.005875 | 0.005832 | 0.005916 | 0.005875 | 0.005884 | In range |
| AE205 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.005875 | 0.005832 | 0.005916 | 0.005875 | 0.005884 | In range |
| AE205 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.005875 | 0.005832 | 0.005916 | 0.005875 | 0.005884 | In range |
| AE205 | HUMIDITY RATIO (G/GDA) · Zone Air (z1) | 0.006554 | 0.006507 | 0.006620 | 0.006562 | 0.006562 | In range |
| AE205 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.006554 | 0.006507 | 0.006620 | 0.006562 | 0.006562 | In range |
| AE205 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.006554 | 0.006507 | 0.006620 | 0.006561 | 0.006562 | In range |
| AE205 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 851.19 | 830.35 | 850.44 | 839.47 | 850.43 | Above range |
| AE205 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 850.66 | 830.35 | 849.90 | 839.26 | 849.91 | Above range |
| AE205 | SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco) | 850.66 | 830.35 | 849.90 | 839.26 | 849.91 | Above range |
| AE205 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 834.78 | 830.35 | 834.06 | 832.92 | 834.04 | Above range |
| AE205 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 836.45 | 830.35 | 835.55 | 832.77 | 835.71 | Above range |
| AE205 | SPECIFIC VOLUME (L/KGDA) · Zone Air (z1) | 849.52 | 830.35 | 848.76 | 838.81 | 848.76 | Above range |
| AE205 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 849.52 | 830.35 | 848.76 | 838.81 | 848.76 | Above range |
| AE205 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 850.41 | 830.35 | 849.45 | 838.72 | 849.65 | Above range |
| AE205 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 36.435 | 36.435 | 36.500 | 36.474 | 36.491 | In range |
| AE205 | ENTHALPY (J/GDA) · Mixed Air (ma) | 39.128 | 39.008 | 39.183 | 39.105 | 39.180 | In range |
| AE205 | ENTHALPY (J/GDA) · Heat Coil Outlet (hco) | 39.128 | 39.008 | 39.183 | 39.105 | 39.180 | In range |
| AE205 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 33.487 | 33.399 | 33.549 | 33.469 | 33.536 | In range |
| AE205 | ENTHALPY (J/GDA) · Supply Air (sa) | 34.081 | 33.990 | 34.142 | 34.064 | 34.130 | In range |
| AE205 | ENTHALPY (J/GDA) · Zone Air (z1) | 40.122 | 39.999 | 40.230 | 40.113 | 40.172 | In range |
| AE205 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 40.122 | 39.999 | 40.230 | 40.113 | 40.172 | In range |
| AE205 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 40.440 | 40.295 | 40.530 | 40.416 | 40.490 | In range |
| AE205 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.1111 | 0.1111 | 0.1137 | 0.1124 | 0.1112 | In range |
| AE205 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3392 | 0.3333 | 0.3410 | 0.3390 | 0.3395 | In range |
| AE205 | MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco) | 0.3392 | 0.3333 | 0.3410 | 0.3390 | 0.3395 | In range |
| AE205 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3392 | 0.3333 | 0.3410 | 0.3390 | 0.3395 | In range |
| AE205 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3392 | 0.3333 | 0.3410 | 0.3390 | 0.3395 | In range |
| AE205 | MASS FLOW RATE (KGDA/S) · Zone Air (z1) | n/a* | |||||
| AE205 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.2281 | 0.2222 | 0.2284 | 0.2265 | 0.2283 | In range |
| AE205 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.2281 | 0.2222 | 0.2284 | 0.2265 | 0.2283 | In range |
| AE206 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 23.000 | 23 | 23.000 | 23 | 23.000 | In range |
| AE206 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 23.434 | 23.407 | 23.444 | 23.422 | 23.434 | In range |
| AE206 | DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco) | 23.434 | 23.407 | 23.444 | 23.422 | 23.434 | In range |
| AE206 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 18.510 | 18.444 | 18.589 | 18.517 | 18.514 | In range |
| AE206 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 19.094 | 19.045 | 19.165 | 19.112 | 19.097 | In range |
| AE206 | DRY BULB TEMPERATURE (°C) · Zone Air (z1) | 23.333 | 23.330 | 23.338 | 23.334 | 23.333 | In range |
| AE206 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.333 | 23.330 | 23.338 | 23.334 | 23.333 | In range |
| AE206 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 23.645 | 23.611 | 23.648 | 23.627 | 23.645 | In range |
| AE206 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.01557 | 0.01552 | 0.01563 | 0.01558 | 0.01556 | In range |
| AE206 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.01454 | 0.01448 | 0.01462 | 0.01454 | 0.01455 | In range |
| AE206 | HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco) | 0.01454 | 0.01448 | 0.01462 | 0.01454 | 0.01455 | In range |
| AE206 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.01335 | 0.01323 | 0.01342 | 0.01334 | 0.01337 | In range |
| AE206 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.01335 | 0.01323 | 0.01342 | 0.01334 | 0.01337 | In range |
| AE206 | HUMIDITY RATIO (G/GDA) · Zone Air (z1) | 0.01404 | 0.01392 | 0.01413 | 0.01403 | 0.01405 | In range |
| AE206 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.01404 | 0.01392 | 0.01413 | 0.01403 | 0.01405 | In range |
| AE206 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.01404 | 0.01392 | 0.01413 | 0.01403 | 0.01405 | In range |
| AE206 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 860.73 | 830.35 | 859.94 | 843.28 | 859.94 | Above range |
| AE206 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 860.60 | 830.35 | 859.84 | 843.24 | 859.83 | Above range |
| AE206 | SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco) | 860.60 | 830.35 | 859.84 | 843.24 | 859.83 | Above range |
| AE206 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 844.74 | 830.35 | 844.05 | 836.92 | 844.00 | Above range |
| AE206 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 846.43 | 830.35 | 845.57 | 836.77 | 845.69 | Above range |
| AE206 | SPECIFIC VOLUME (L/KGDA) · Zone Air (z1) | 859.63 | 830.35 | 858.91 | 842.87 | 858.88 | Above range |
| AE206 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 859.63 | 830.35 | 858.91 | 842.87 | 858.88 | Above range |
| AE206 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 860.54 | 830.35 | 859.62 | 842.78 | 859.78 | Above range |
| AE206 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 62.705 | 62.663 | 62.851 | 62.732 | 62.710 | In range |
| AE206 | ENTHALPY (J/GDA) · Mixed Air (ma) | 60.542 | 60.360 | 60.625 | 60.506 | 60.590 | In range |
| AE206 | ENTHALPY (J/GDA) · Heat Coil Outlet (hco) | 60.542 | 60.360 | 60.625 | 60.506 | 60.590 | In range |
| AE206 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 52.451 | 52.060 | 52.683 | 52.424 | 52.520 | In range |
| AE206 | ENTHALPY (J/GDA) · Supply Air (sa) | 53.052 | 52.670 | 53.290 | 53.026 | 53.121 | In range |
| AE206 | ENTHALPY (J/GDA) · Zone Air (z1) | 59.166 | 58.850 | 59.302 | 59.105 | 59.235 | In range |
| AE206 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 59.166 | 58.850 | 59.302 | 59.105 | 59.235 | In range |
| AE206 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 59.488 | 59.160 | 59.606 | 59.413 | 59.557 | In range |
| AE206 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.1098 | 0.1098 | 0.1137 | 0.1119 | 0.1099 | Below range |
| AE206 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3352 | 0.3295 | 0.3410 | 0.3373 | 0.3355 | In range |
| AE206 | MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco) | 0.3352 | 0.3295 | 0.3410 | 0.3373 | 0.3355 | In range |
| AE206 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3352 | 0.3295 | 0.3410 | 0.3373 | 0.3355 | In range |
| AE206 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3352 | 0.3295 | 0.3410 | 0.3373 | 0.3355 | In range |
| AE206 | MASS FLOW RATE (KGDA/S) · Zone Air (z1) | n/a* | |||||
| AE206 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.2254 | 0.2197 | 0.2273 | 0.2254 | 0.2256 | In range |
| AE206 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.2254 | 0.2197 | 0.2273 | 0.2254 | 0.2256 | In range |
| AE226 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 23.000 | 23 | 23.000 | 23 | 23.000 | In range |
| AE226 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 23.000 | 23 | 23.000 | 23 | 23.000 | In range |
| AE226 | DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco) | 23.000 | 23 | 23.000 | 23 | 23.000 | In range |
| AE226 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 18.510 | 18.444 | 18.590 | 18.515 | 18.514 | In range |
| AE226 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 19.094 | 19.034 | 19.165 | 19.110 | 19.097 | In range |
| AE226 | DRY BULB TEMPERATURE (°C) · Zone Air (z1) | 23.333 | 23.327 | 23.333 | 23.332 | 23.333 | In range |
| AE226 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.333 | 23.327 | 23.333 | 23.332 | 23.333 | In range |
| AE226 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 23.645 | 23.616 | 23.667 | 23.633 | 23.645 | In range |
| AE226 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.01557 | 0.01552 | 0.01563 | 0.01558 | 0.01556 | In range |
| AE226 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.01557 | 0.01552 | 0.01563 | 0.01558 | 0.01556 | In range |
| AE226 | HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco) | 0.01557 | 0.01552 | 0.01563 | 0.01558 | 0.01556 | In range |
| AE226 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.01335 | 0.01326 | 0.01342 | 0.01336 | 0.01337 | In range |
| AE226 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.01335 | 0.01326 | 0.01342 | 0.01336 | 0.01337 | In range |
| AE226 | HUMIDITY RATIO (G/GDA) · Zone Air (z1) | 0.01404 | 0.01395 | 0.01413 | 0.01407 | 0.01405 | In range |
| AE226 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.01404 | 0.01395 | 0.01413 | 0.01407 | 0.01405 | In range |
| AE226 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.01404 | 0.01395 | 0.01413 | 0.01407 | 0.01405 | In range |
| AE226 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 860.73 | 830.35 | 859.94 | 843.28 | 859.94 | Above range |
| AE226 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 860.73 | 830.35 | 859.94 | 843.28 | 859.94 | Above range |
| AE226 | SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco) | 860.73 | 830.35 | 859.94 | 843.28 | 859.94 | Above range |
| AE226 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 844.74 | 830.35 | 844.03 | 836.92 | 844.00 | Above range |
| AE226 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 846.43 | 830.35 | 845.57 | 836.77 | 845.69 | Above range |
| AE226 | SPECIFIC VOLUME (L/KGDA) · Zone Air (z1) | 859.63 | 830.35 | 858.89 | 842.87 | 858.88 | Above range |
| AE226 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 859.63 | 830.35 | 858.89 | 842.87 | 858.88 | Above range |
| AE226 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 860.54 | 830.35 | 859.62 | 842.78 | 859.78 | Above range |
| AE226 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 62.705 | 62.663 | 62.851 | 62.732 | 62.710 | In range |
| AE226 | ENTHALPY (J/GDA) · Mixed Air (ma) | 62.705 | 62.663 | 62.851 | 62.732 | 62.710 | In range |
| AE226 | ENTHALPY (J/GDA) · Heat Coil Outlet (hco) | 62.705 | 62.663 | 62.851 | 62.732 | 62.710 | In range |
| AE226 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 52.451 | 52.130 | 52.683 | 52.508 | 52.520 | In range |
| AE226 | ENTHALPY (J/GDA) · Supply Air (sa) | 53.052 | 52.740 | 53.290 | 53.110 | 53.121 | In range |
| AE226 | ENTHALPY (J/GDA) · Zone Air (z1) | 59.166 | 58.920 | 59.302 | 59.189 | 59.235 | In range |
| AE226 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 59.166 | 58.920 | 59.302 | 59.189 | 59.235 | In range |
| AE226 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 59.488 | 58.920 | 59.606 | 59.419 | 59.557 | In range |
| AE226 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.3352 | 0.3294 | 0.3410 | 0.3373 | 0.3355 | In range |
| AE226 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3352 | 0.3294 | 0.3410 | 0.3373 | 0.3355 | In range |
| AE226 | MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco) | 0.3352 | 0.3294 | 0.3410 | 0.3373 | 0.3355 | In range |
| AE226 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3352 | 0.3294 | 0.3410 | 0.3373 | 0.3355 | In range |
| AE226 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3352 | 0.3294 | 0.3410 | 0.3373 | 0.3355 | In range |
| AE226 | MASS FLOW RATE (KGDA/S) · Zone Air (z1) | n/a* | |||||
| AE226 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.2254 | 0.2196 | 0.2273 | 0.2254 | 0.2256 | In range |
| AE226 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.2254 | 0.2196 | 0.2273 | 0.2254 | 0.2256 | In range |
| AE245 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 24.900 | 24.889 | 24.900 | 24.897 | 24.900 | In range |
| AE245 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 24.900 | 24.889 | 24.900 | 24.897 | 24.900 | In range |
| AE245 | DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco) | 24.900 | 24.889 | 24.900 | 24.897 | 24.900 | In range |
| AE245 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 18.500 | 18.444 | 18.519 | 18.493 | 18.504 | In range |
| AE245 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 19.085 | 19.053 | 19.101 | 19.087 | 19.088 | In range |
| AE245 | DRY BULB TEMPERATURE (°C) · Zone Air (z1) | 23.333 | 23.323 | 23.348 | 23.333 | 23.333 | In range |
| AE245 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.333 | 23.323 | 23.348 | 23.333 | 23.333 | In range |
| AE245 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 23.646 | 23.621 | 23.667 | 23.635 | 23.646 | In range |
| AE245 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE245 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE245 | HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE245 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE245 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE245 | HUMIDITY RATIO (G/GDA) · Zone Air (z1) | 0.005159 | 0.005134 | 0.005212 | 0.005177 | 0.005168 | In range |
| AE245 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.005159 | 0.005134 | 0.005212 | 0.005177 | 0.005168 | In range |
| AE245 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.005159 | 0.005134 | 0.005212 | 0.005177 | 0.005168 | In range |
| AE245 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 851.19 | 830.35 | 850.44 | 839.47 | 850.43 | Above range |
| AE245 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 851.19 | 830.35 | 850.44 | 839.47 | 850.43 | Above range |
| AE245 | SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco) | 851.19 | 830.35 | 850.44 | 839.47 | 850.43 | Above range |
| AE245 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 832.92 | 830.35 | 833.33 | 832.18 | 832.18 | In range |
| AE245 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 834.59 | 829.76 | 833.70 | 832.03 | 833.85 | Above range |
| AE245 | SPECIFIC VOLUME (L/KGDA) · Zone Air (z1) | 847.63 | 830.35 | 846.85 | 838.05 | 846.88 | Above range |
| AE245 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 847.63 | 830.35 | 846.85 | 838.05 | 846.88 | Above range |
| AE245 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 848.52 | 830.35 | 847.57 | 837.96 | 847.77 | Above range |
| AE245 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 36.435 | 36.435 | 36.510 | 36.477 | 36.491 | In range |
| AE245 | ENTHALPY (J/GDA) · Mixed Air (ma) | 36.435 | 36.435 | 36.510 | 36.477 | 36.491 | In range |
| AE245 | ENTHALPY (J/GDA) · Heat Coil Outlet (hco) | 36.435 | 36.435 | 36.510 | 36.477 | 36.491 | In range |
| AE245 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 29.951 | 29.962 | 29.997 | 29.983 | 30.003 | Below range |
| AE245 | ENTHALPY (J/GDA) · Supply Air (sa) | 30.543 | 30.553 | 30.589 | 30.578 | 30.596 | Below range |
| AE245 | ENTHALPY (J/GDA) · Zone Air (z1) | 36.571 | 36.562 | 36.700 | 36.620 | 36.624 | In range |
| AE245 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 36.571 | 36.562 | 36.700 | 36.620 | 36.624 | In range |
| AE245 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 36.889 | 36.700 | 36.934 | 36.848 | 36.942 | In range |
| AE245 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.3400 | 0.3331 | 0.3410 | 0.3392 | 0.3403 | In range |
| AE245 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3400 | 0.3331 | 0.3410 | 0.3392 | 0.3403 | In range |
| AE245 | MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco) | 0.3400 | 0.3331 | 0.3410 | 0.3392 | 0.3403 | In range |
| AE245 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3400 | 0.3331 | 0.3410 | 0.3392 | 0.3403 | In range |
| AE245 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3400 | 0.3331 | 0.3410 | 0.3392 | 0.3403 | In range |
| AE245 | MASS FLOW RATE (KGDA/S) · Zone Air (z1) | n/a* | |||||
| AE245 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.2286 | 0.2221 | 0.2289 | 0.2267 | 0.2288 | In range |
| AE245 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.2286 | 0.2221 | 0.2289 | 0.2267 | 0.2288 | In range |
AE CV coil and zone loads91 rows · 2 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| AE301 | Sensible Heating Load (QZH1sensible) (kWh/h) | 2.931 | 2.930 | 2.931 | 2.931 | 2.931 | In range |
| AE301 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE301 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5861 | 0.5900 | 0.5868 | 0.5861 | In range |
| AE301 | Sensible Heating Load (QZH2sensible) (kWh/h) | 2.345 | 2.345 | 2.350 | 2.346 | 2.345 | In range |
| AE301 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE301 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8792 | 0.8800 | 0.8793 | 0.8792 | In range |
| AE301 | Coil Load (QHpreheat) (kWh/h) | 2.941 | 2.947 | 3.788 | 3.418 | 2.947 | Below range |
| AE301 | Loads Sensible (QCsensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE301 | Latent (QClatent) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE301 | Total (QCtotal) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE301 | Coil Outlet RH (RHcco) (%) | 24.748 | 23.891 | 24.733 | 24.374 | 24.733 | Above range |
| AE301 | Reheat Coil Load (QH1reheat) (kWh/h) | 7.699 | 7.472 | 7.709 | 7.607 | 7.713 | In range |
| AE301 | Reheat Coil Load (QH2reheat) (kWh/h) | 8.372 | 8.077 | 8.384 | 8.254 | 8.389 | In range |
| AE303 | Sensible Heating Load (QZH1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE303 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 1.465 | 1.465 | 1.467 | 1.465 | 1.465 | In range |
| AE303 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5860 | 0.5897 | 0.5867 | 0.5861 | In range |
| AE303 | Sensible Heating Load (QZH2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE303 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 2.345 | 2.345 | 2.346 | 2.345 | 2.345 | In range |
| AE303 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8790 | 0.8909 | 0.8811 | 0.8792 | In range |
| AE303 | Coil Load (QHpreheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE303 | Loads Sensible (QCsensible) (kWh/h) | 6.722 | 6.420 | 6.726 | 6.545 | 6.735 | In range |
| AE303 | Latent (QClatent) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE303 | Total (QCtotal) (kWh/h) | 6.722 | 6.420 | 6.726 | 6.545 | 6.735 | In range |
| AE303 | Coil Outlet RH (RHcco) (%) | 48.125 | 47.457 | 48.220 | 47.915 | 48.150 | In range |
| AE303 | Reheat Coil Load (QH1reheat) (kWh/h) | 2.252 | 2.136 | 2.255 | 2.194 | 2.258 | In range |
| AE303 | Reheat Coil Load (QH2reheat) (kWh/h) | 2.450 | 2.300 | 2.454 | 2.375 | 2.457 | In range |
| AE304 | Sensible Heating Load (QZH1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE304 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 2.931 | 2.931 | 2.934 | 2.931 | 2.931 | In range |
| AE304 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5861 | 0.5927 | 0.5872 | 0.5861 | In range |
| AE304 | Sensible Heating Load (QZH2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE304 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 3.517 | 3.516 | 3.517 | 3.517 | 3.517 | In range |
| AE304 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8792 | 0.8939 | 0.8816 | 0.8792 | In range |
| AE304 | Coil Load (QHpreheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE304 | Loads Sensible (QCsensible) (kWh/h) | 10.299 | 9.890 | 10.315 | 10.118 | 10.320 | In range |
| AE304 | Latent (QClatent) (kWh/h) | 6.258 | 6.214 | 7.011 | 6.505 | 6.258 | In range |
| AE304 | Total (QCtotal) (kWh/h) | 16.557 | 16.104 | 17.070 | 16.623 | 16.578 | In range |
| AE304 | Coil Outlet RH (RHcco) (%) | 99.886 | 95.490 | 100 | 99.102 | 100 | In range |
| AE304 | Reheat Coil Load (QH1reheat) (kWh/h) | 0.9882 | 0.7977 | 0.9915 | 0.9157 | 0.9933 | In range |
| AE304 | Reheat Coil Load (QH2reheat) (kWh/h) | 1.513 | 1.268 | 1.524 | 1.422 | 1.519 | In range |
| AE305 | Sensible Heating Load (QZH1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE305 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 1.465 | 1.465 | 1.466 | 1.465 | 1.465 | In range |
| AE305 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5861 | 0.5897 | 0.5867 | 0.5861 | In range |
| AE305 | Sensible Heating Load (QZH2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE305 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 2.345 | 2.344 | 2.345 | 2.345 | 2.345 | In range |
| AE305 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8791 | 0.8909 | 0.8811 | 0.8792 | In range |
| AE305 | Coil Load (QHpreheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE305 | Loads Sensible (QCsensible) (kWh/h) | 9.364 | 8.929 | 9.373 | 9.204 | 9.383 | In range |
| AE305 | Latent (QClatent) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE305 | Total (QCtotal) (kWh/h) | 9.364 | 8.929 | 9.373 | 9.204 | 9.383 | In range |
| AE305 | Coil Outlet RH (RHcco) (%) | 65.607 | 64.909 | 65.840 | 65.489 | 65.719 | In range |
| AE305 | Reheat Coil Load (QH1reheat) (kWh/h) | 2.254 | 2.072 | 2.257 | 2.184 | 2.260 | In range |
| AE305 | Reheat Coil Load (QH2reheat) (kWh/h) | 2.452 | 2.223 | 2.456 | 2.362 | 2.459 | In range |
| AE306 | Sensible Heating Load (QZH1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE306 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 1.465 | 1.465 | 1.466 | 1.465 | 1.465 | In range |
| AE306 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5861 | 0.5897 | 0.5867 | 0.5861 | In range |
| AE306 | Sensible Heating Load (QZH2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE306 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 2.345 | 2.345 | 2.345 | 2.345 | 2.345 | In range |
| AE306 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8792 | 0.8909 | 0.8811 | 0.8792 | In range |
| AE306 | Coil Load (QHpreheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE306 | Loads Sensible (QCsensible) (kWh/h) | 8.903 | 8.598 | 8.915 | 8.746 | 8.921 | In range |
| AE306 | Latent (QClatent) (kWh/h) | 5.452 | 5.434 | 6.103 | 5.654 | 5.443 | In range |
| AE306 | Total (QCtotal) (kWh/h) | 14.355 | 14.031 | 14.802 | 14.400 | 14.364 | In range |
| AE306 | Coil Outlet RH (RHcco) (%) | 99.886 | 96.210 | 100 | 99.243 | 100 | In range |
| AE306 | Reheat Coil Load (QH1reheat) (kWh/h) | 2.256 | 2.111 | 2.262 | 2.195 | 2.262 | In range |
| AE306 | Reheat Coil Load (QH2reheat) (kWh/h) | 2.455 | 2.270 | 2.462 | 2.376 | 2.462 | In range |
| AE326 | Sensible Heating Load (QZH1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE326 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 1.465 | 1.465 | 1.466 | 1.465 | 1.465 | In range |
| AE326 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5861 | 0.5897 | 0.5867 | 0.5861 | In range |
| AE326 | Sensible Heating Load (QZH2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE326 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 2.345 | 2.345 | 2.345 | 2.345 | 2.345 | In range |
| AE326 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8792 | 0.8909 | 0.8811 | 0.8792 | In range |
| AE326 | Coil Load (QHpreheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE326 | Loads Sensible (QCsensible) (kWh/h) | 8.444 | 8.096 | 8.470 | 8.252 | 8.461 | In range |
| AE326 | Latent (QClatent) (kWh/h) | 12.324 | 11.712 | 12.879 | 12.388 | 12.302 | In range |
| AE326 | Total (QCtotal) (kWh/h) | 20.768 | 19.944 | 20.993 | 20.640 | 20.763 | In range |
| AE326 | Coil Outlet RH (RHcco) (%) | 99.886 | 98.890 | 100 | 99.803 | 100 | In range |
| AE326 | Reheat Coil Load (QH1reheat) (kWh/h) | 2.256 | 2.126 | 2.267 | 2.198 | 2.262 | In range |
| AE326 | Reheat Coil Load (QH2reheat) (kWh/h) | 2.455 | 2.289 | 2.468 | 2.380 | 2.462 | In range |
| AE345 | Sensible Heating Load (QZH1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE345 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 1.465 | 1.465 | 1.466 | 1.465 | 1.465 | In range |
| AE345 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5861 | 0.5897 | 0.5867 | 0.5861 | In range |
| AE345 | Sensible Heating Load (QZH2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE345 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 2.345 | 2.344 | 2.345 | 2.345 | 2.345 | In range |
| AE345 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8791 | 0.8909 | 0.8811 | 0.8792 | In range |
| AE345 | Coil Load (QHpreheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE345 | Loads Sensible (QCsensible) (kWh/h) | 9.683 | 9.285 | 9.707 | 9.531 | 9.703 | In range |
| AE345 | Latent (QClatent) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE345 | Total (QCtotal) (kWh/h) | 9.683 | 9.285 | 9.707 | 9.531 | 9.703 | In range |
| AE345 | Coil Outlet RH (RHcco) (%) | 50.966 | 50.707 | 51.330 | 51.063 | 51.089 | In range |
| AE345 | Reheat Coil Load (QH1reheat) (kWh/h) | 2.253 | 2.089 | 2.261 | 2.186 | 2.259 | In range |
| AE345 | Reheat Coil Load (QH2reheat) (kWh/h) | 2.450 | 2.241 | 2.461 | 2.364 | 2.457 | In range |
AE CV node states385 rows · 80 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| AE301 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | −29.000 | −29 | −29 | −29 | −29 | In range |
| AE301 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 3.432 | 2.358 | 3.430 | 2.798 | 3.432 | Above range |
| AE301 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 7.222 | 7.220 | 7.222 | 7.221 | 7.222 | In range |
| AE301 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 7.222 | 7.220 | 7.222 | 7.221 | 7.222 | In range |
| AE301 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 7.785 | 7.778 | 7.810 | 7.794 | 7.784 | In range |
| AE301 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 29.287 | 29.270 | 29.670 | 29.491 | 29.279 | In range |
| AE301 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 27.827 | 27.810 | 28.089 | 27.968 | 27.823 | In range |
| AE301 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 21.111 | 21.110 | 21.130 | 21.114 | 21.111 | In range |
| AE301 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 22.222 | 22.217 | 22.248 | 22.225 | 22.222 | In range |
| AE301 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 21.671 | 21.666 | 21.709 | 21.681 | 21.671 | In range |
| AE301 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 22.019 | 21.944 | 22.016 | 21.978 | 22.019 | Above range |
| AE301 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 2.59e-4 | 2.59e-4 | 3.00e-4 | 2.66e-4 | 2.59e-4 | In range |
| AE301 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.001550 | 0.001496 | 0.001549 | 0.001528 | 0.001548 | Above range |
| AE301 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.001550 | 0.001496 | 0.001549 | 0.001528 | 0.001548 | Above range |
| AE301 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.001550 | 0.001496 | 0.001549 | 0.001528 | 0.001548 | Above range |
| AE301 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.001550 | 0.001496 | 0.001549 | 0.001528 | 0.001548 | Above range |
| AE301 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.001550 | 0.001496 | 0.001549 | 0.001528 | 0.001548 | Above range |
| AE301 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.001550 | 0.001496 | 0.001549 | 0.001528 | 0.001548 | Above range |
| AE301 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.002199 | 0.002172 | 0.002253 | 0.002207 | 0.002197 | In range |
| AE301 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.002384 | 0.002365 | 0.002454 | 0.002399 | 0.002382 | In range |
| AE301 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.002292 | 0.002200 | 0.002354 | 0.002287 | 0.002290 | In range |
| AE301 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.002292 | 0.002200 | 0.002354 | 0.002287 | 0.002290 | In range |
| AE301 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 692.65 | 691.84 | 833.33 | 761.86 | 691.93 | In range |
| AE301 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 786.22 | 785.27 | 833.33 | 808.60 | 785.47 | In range |
| AE301 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 796.98 | 796.13 | 833.33 | 814.01 | 796.23 | In range |
| AE301 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 796.98 | 796.13 | 833.33 | 814.01 | 796.23 | In range |
| AE301 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 798.58 | 793.92 | 833.33 | 813.83 | 797.83 | In range |
| AE301 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 859.67 | 830.35 | 858.84 | 845.33 | 858.87 | Above range |
| AE301 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 855.52 | 830.35 | 854.70 | 843.26 | 854.74 | Above range |
| AE301 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 837.31 | 830.35 | 836.54 | 834.16 | 836.55 | Above range |
| AE301 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 840.72 | 830.35 | 839.93 | 835.86 | 839.95 | Above range |
| AE301 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 839.03 | 830.35 | 838.25 | 835.02 | 838.26 | Above range |
| AE301 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 840.02 | 830.35 | 838.99 | 834.87 | 839.25 | Above range |
| AE301 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | −28.507 | −28.540 | −28.507 | −28.519 | −28.543 | In range |
| AE301 | ENTHALPY (J/GDA) · Mixed Air (ma) | 7.334 | 6.178 | 7.316 | 6.578 | 7.335 | Above range |
| AE301 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 11.154 | 11.016 | 11.140 | 11.089 | 11.159 | Above range |
| AE301 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 11.154 | 11.016 | 11.140 | 11.089 | 11.159 | Above range |
| AE301 | ENTHALPY (J/GDA) · Supply Air (sa) | 11.721 | 11.606 | 11.710 | 11.674 | 11.726 | Above range |
| AE301 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 33.389 | 33.386 | 33.740 | 33.580 | 33.414 | In range |
| AE301 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 31.918 | 31.913 | 32.140 | 32.032 | 31.945 | In range |
| AE301 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 26.799 | 26.750 | 26.866 | 26.803 | 26.821 | In range |
| AE301 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 28.390 | 28.368 | 28.485 | 28.411 | 28.413 | In range |
| AE301 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 27.601 | 27.559 | 27.740 | 27.630 | 27.622 | In range |
| AE301 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 27.953 | 27.855 | 28.040 | 27.946 | 27.974 | In range |
| AE301 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.2811 | 0.2814 | 0.2965 | 0.2850 | 0.2814 | Below range |
| AE301 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.7698 | 0.7362 | 0.7709 | 0.7539 | 0.7705 | In range |
| AE301 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.7698 | 0.7362 | 0.7709 | 0.7539 | 0.7705 | In range |
| AE301 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.7698 | 0.7362 | 0.7709 | 0.7539 | 0.7705 | In range |
| AE301 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.7698 | 0.7362 | 0.7709 | 0.7539 | 0.7705 | In range |
| AE301 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.3553 | 0.3398 | 0.3558 | 0.3480 | 0.3556 | In range |
| AE301 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.4145 | 0.3964 | 0.4151 | 0.4060 | 0.4149 | In range |
| AE301 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE301 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE301 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.4887 | 0.4531 | 0.4892 | 0.4689 | 0.4891 | In range |
| AE301 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.4887 | 0.4531 | 0.4892 | 0.4689 | 0.4891 | In range |
| AE303 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 15.500 | 15.500 | 15.500 | 15.500 | 15.500 | In range |
| AE303 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 21.019 | 20.833 | 21.015 | 20.901 | 21.018 | Above range |
| AE303 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 21.019 | 20.833 | 21.015 | 20.901 | 21.018 | Above range |
| AE303 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 12.205 | 12.167 | 12.215 | 12.198 | 12.207 | In range |
| AE303 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 12.778 | 12.778 | 12.795 | 12.783 | 12.778 | In range |
| AE303 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 19.176 | 19.050 | 19.180 | 19.122 | 19.180 | In range |
| AE303 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 18.743 | 18.570 | 18.750 | 18.668 | 18.748 | In range |
| AE303 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 23.333 | 23.328 | 23.339 | 23.333 | 23.333 | In range |
| AE303 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 24.444 | 24.439 | 24.452 | 24.444 | 24.444 | In range |
| AE303 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.892 | 23.887 | 23.946 | 23.902 | 23.892 | In range |
| AE303 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 24.232 | 24.178 | 24.241 | 24.207 | 24.232 | In range |
| AE303 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.002933 | 0.002895 | 0.002948 | 0.002927 | 0.002936 | In range |
| AE303 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.004230 | 0.004168 | 0.004236 | 0.004211 | 0.004231 | In range |
| AE303 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.004230 | 0.004168 | 0.004236 | 0.004211 | 0.004231 | In range |
| AE303 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.004230 | 0.004168 | 0.004236 | 0.004211 | 0.004231 | In range |
| AE303 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.004230 | 0.004168 | 0.004236 | 0.004211 | 0.004231 | In range |
| AE303 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.004230 | 0.004168 | 0.004236 | 0.004211 | 0.004231 | In range |
| AE303 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.004230 | 0.004168 | 0.004236 | 0.004211 | 0.004231 | In range |
| AE303 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.004892 | 0.004844 | 0.004938 | 0.004893 | 0.004893 | In range |
| AE303 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.005081 | 0.005036 | 0.005139 | 0.005088 | 0.005081 | In range |
| AE303 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.004987 | 0.004940 | 0.005040 | 0.004993 | 0.004988 | In range |
| AE303 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.004987 | 0.004940 | 0.005039 | 0.004985 | 0.004988 | In range |
| AE303 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 822.32 | 821.41 | 833.33 | 826.66 | 821.57 | In range |
| AE303 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 839.77 | 830.35 | 839.01 | 835.37 | 839.01 | Above range |
| AE303 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 839.77 | 830.35 | 839.01 | 835.37 | 839.01 | Above range |
| AE303 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 814.63 | 813.71 | 833.33 | 822.83 | 813.87 | In range |
| AE303 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 816.26 | 811.55 | 833.33 | 822.64 | 815.50 | In range |
| AE303 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 834.51 | 830.35 | 833.78 | 832.76 | 833.76 | Above range |
| AE303 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 833.28 | 830.35 | 833.33 | 832.15 | 832.53 | In range |
| AE303 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 847.27 | 830.35 | 846.51 | 839.13 | 846.50 | Above range |
| AE303 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 850.70 | 830.35 | 849.93 | 840.85 | 849.93 | Above range |
| AE303 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 848.99 | 830.35 | 848.23 | 839.99 | 848.23 | Above range |
| AE303 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 849.97 | 830.35 | 848.91 | 839.85 | 849.20 | Above range |
| AE303 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 22.996 | 22.996 | 23.032 | 23.016 | 23.022 | In range |
| AE303 | ENTHALPY (J/GDA) · Mixed Air (ma) | 31.863 | 31.540 | 31.900 | 31.723 | 31.893 | In range |
| AE303 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 31.863 | 31.540 | 31.900 | 31.723 | 31.893 | In range |
| AE303 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 22.938 | 22.775 | 22.978 | 22.901 | 22.958 | In range |
| AE303 | ENTHALPY (J/GDA) · Supply Air (sa) | 23.518 | 23.365 | 23.557 | 23.491 | 23.537 | In range |
| AE303 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 29.998 | 29.766 | 30.039 | 29.895 | 30.028 | In range |
| AE303 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 29.559 | 29.299 | 29.604 | 29.434 | 29.591 | In range |
| AE303 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 35.893 | 35.775 | 35.990 | 35.900 | 35.924 | In range |
| AE303 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 37.500 | 37.393 | 37.630 | 37.523 | 37.532 | In range |
| AE303 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 36.702 | 36.584 | 36.890 | 36.740 | 36.733 | In range |
| AE303 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 37.047 | 36.880 | 37.190 | 37.053 | 37.078 | In range |
| AE303 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.2778 | 0.2781 | 0.2842 | 0.2814 | 0.2781 | Below range |
| AE303 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.7531 | 0.7319 | 0.7540 | 0.7418 | 0.7538 | In range |
| AE303 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.7531 | 0.7319 | 0.7540 | 0.7418 | 0.7538 | In range |
| AE303 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.7531 | 0.7319 | 0.7540 | 0.7418 | 0.7538 | In range |
| AE303 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.7531 | 0.7319 | 0.7540 | 0.7418 | 0.7538 | In range |
| AE303 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.3476 | 0.3378 | 0.3480 | 0.3424 | 0.3479 | In range |
| AE303 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.4055 | 0.3941 | 0.4060 | 0.3995 | 0.4059 | In range |
| AE303 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE303 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE303 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.4753 | 0.4504 | 0.4758 | 0.4605 | 0.4758 | In range |
| AE303 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.4753 | 0.4504 | 0.4758 | 0.4605 | 0.4758 | In range |
| AE304 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 26.900 | 26.889 | 26.900 | 26.896 | 26.900 | In range |
| AE304 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 25.574 | 25.541 | 25.596 | 25.568 | 25.573 | In range |
| AE304 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 25.574 | 25.541 | 25.596 | 25.568 | 25.573 | In range |
| AE304 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 12.206 | 12.199 | 12.222 | 12.208 | 12.207 | In range |
| AE304 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 12.778 | 12.778 | 12.833 | 12.791 | 12.778 | Below range |
| AE304 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 15.582 | 15.310 | 15.590 | 15.478 | 15.590 | In range |
| AE304 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 16.459 | 16.185 | 16.480 | 16.355 | 16.464 | In range |
| AE304 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 23.889 | 23.881 | 23.891 | 23.888 | 23.889 | In range |
| AE304 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 25.000 | 25 | 25.005 | 25.001 | 25 | In range |
| AE304 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 24.448 | 24.445 | 24.502 | 24.458 | 24.448 | In range |
| AE304 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 24.791 | 24.722 | 24.797 | 24.754 | 24.790 | In range |
| AE304 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.01677 | 0.01677 | 0.01685 | 0.01680 | 0.01677 | In range |
| AE304 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.01224 | 0.01218 | 0.01244 | 0.01231 | 0.01225 | In range |
| AE304 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.01224 | 0.01218 | 0.01244 | 0.01231 | 0.01225 | In range |
| AE304 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.008844 | 0.008443 | 0.008900 | 0.008785 | 0.008852 | In range |
| AE304 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.008844 | 0.008443 | 0.008900 | 0.008785 | 0.008852 | In range |
| AE304 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.008844 | 0.008443 | 0.008900 | 0.008785 | 0.008852 | In range |
| AE304 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.008844 | 0.008443 | 0.008900 | 0.008785 | 0.008852 | In range |
| AE304 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.009511 | 0.009140 | 0.009595 | 0.009445 | 0.009518 | In range |
| AE304 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.009701 | 0.009340 | 0.009796 | 0.009640 | 0.009708 | In range |
| AE304 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.009607 | 0.009250 | 0.009700 | 0.009571 | 0.009614 | In range |
| AE304 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.009607 | 0.009250 | 0.009700 | 0.009571 | 0.009614 | In range |
| AE304 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 873.71 | 830.35 | 872.93 | 852.35 | 872.92 | Above range |
| AE304 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 863.68 | 830.35 | 862.92 | 847.33 | 862.91 | Above range |
| AE304 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 863.68 | 830.35 | 862.92 | 847.33 | 862.91 | Above range |
| AE304 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 820.63 | 819.77 | 833.33 | 825.84 | 819.88 | In range |
| AE304 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 822.27 | 817.53 | 833.33 | 825.66 | 821.52 | In range |
| AE304 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 830.33 | 829.47 | 833.33 | 830.69 | 829.60 | In range |
| AE304 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 832.85 | 830.35 | 833.33 | 831.96 | 832.11 | In range |
| AE304 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 855.11 | 830.35 | 854.34 | 843.06 | 854.35 | Above range |
| AE304 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 858.57 | 830.35 | 857.83 | 844.80 | 857.80 | Above range |
| AE304 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 856.85 | 830.35 | 856.09 | 843.94 | 856.09 | Above range |
| AE304 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 857.83 | 830.35 | 856.83 | 843.79 | 857.07 | Above range |
| AE304 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 69.814 | 69.814 | 69.994 | 69.886 | 69.854 | In range |
| AE304 | ENTHALPY (J/GDA) · Mixed Air (ma) | 56.903 | 56.750 | 57.106 | 56.938 | 56.949 | In range |
| AE304 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 56.903 | 56.750 | 57.106 | 56.938 | 56.949 | In range |
| AE304 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 34.583 | 33.560 | 34.630 | 34.196 | 34.621 | In range |
| AE304 | ENTHALPY (J/GDA) · Supply Air (sa) | 35.167 | 34.160 | 35.214 | 34.788 | 35.204 | In range |
| AE304 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 38.031 | 36.730 | 38.085 | 37.522 | 38.080 | In range |
| AE304 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 38.927 | 37.620 | 38.995 | 38.421 | 38.974 | In range |
| AE304 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 48.213 | 47.260 | 48.269 | 47.861 | 48.263 | In range |
| AE304 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 49.833 | 48.905 | 49.905 | 49.497 | 49.884 | In range |
| AE304 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 49.028 | 48.170 | 49.092 | 48.710 | 49.079 | In range |
| AE304 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 49.379 | 48.470 | 49.442 | 49.026 | 49.429 | In range |
| AE304 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.2753 | 0.2735 | 0.2842 | 0.2792 | 0.2755 | In range |
| AE304 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.7476 | 0.7111 | 0.7484 | 0.7365 | 0.7483 | In range |
| AE304 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.7476 | 0.7111 | 0.7484 | 0.7365 | 0.7483 | In range |
| AE304 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.7476 | 0.7111 | 0.7484 | 0.7365 | 0.7483 | In range |
| AE304 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.7476 | 0.7111 | 0.7484 | 0.7365 | 0.7483 | In range |
| AE304 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.3451 | 0.3282 | 0.3454 | 0.3399 | 0.3454 | In range |
| AE304 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.4026 | 0.3829 | 0.4030 | 0.3966 | 0.4029 | In range |
| AE304 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE304 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE304 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.4723 | 0.4376 | 0.4728 | 0.4573 | 0.4728 | In range |
| AE304 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.4723 | 0.4376 | 0.4728 | 0.4573 | 0.4728 | In range |
| AE305 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 24.900 | 24.889 | 24.900 | 24.896 | 24.900 | In range |
| AE305 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 24.478 | 24.444 | 24.485 | 24.461 | 24.478 | In range |
| AE305 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 24.478 | 24.444 | 24.485 | 24.461 | 24.478 | In range |
| AE305 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 12.206 | 12.199 | 12.278 | 12.217 | 12.207 | In range |
| AE305 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 12.778 | 12.778 | 12.889 | 12.801 | 12.778 | In range |
| AE305 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 19.178 | 19.051 | 19.180 | 19.125 | 19.181 | In range |
| AE305 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 18.745 | 18.572 | 18.750 | 18.672 | 18.750 | In range |
| AE305 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 23.333 | 23.327 | 23.339 | 23.333 | 23.333 | In range |
| AE305 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 24.444 | 24.437 | 24.452 | 24.444 | 24.444 | In range |
| AE305 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.892 | 23.885 | 23.946 | 23.901 | 23.892 | In range |
| AE305 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 24.232 | 24.167 | 24.241 | 24.198 | 24.232 | In range |
| AE305 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE305 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.005780 | 0.005716 | 0.005800 | 0.005776 | 0.005789 | In range |
| AE305 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.005780 | 0.005716 | 0.005800 | 0.005776 | 0.005789 | In range |
| AE305 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.005780 | 0.005716 | 0.005800 | 0.005776 | 0.005789 | In range |
| AE305 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.005780 | 0.005716 | 0.005800 | 0.005776 | 0.005789 | In range |
| AE305 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.005780 | 0.005716 | 0.005800 | 0.005776 | 0.005789 | In range |
| AE305 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.005780 | 0.005716 | 0.005800 | 0.005776 | 0.005789 | In range |
| AE305 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.006445 | 0.006391 | 0.006499 | 0.006452 | 0.006453 | In range |
| AE305 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.006634 | 0.006584 | 0.006700 | 0.006648 | 0.006642 | In range |
| AE305 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.006540 | 0.006487 | 0.006602 | 0.006560 | 0.006548 | In range |
| AE305 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.006540 | 0.006487 | 0.006602 | 0.006560 | 0.006548 | In range |
| AE305 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 851.19 | 830.35 | 850.44 | 841.09 | 850.43 | Above range |
| AE305 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 851.74 | 830.35 | 850.99 | 841.35 | 850.99 | Above range |
| AE305 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 851.74 | 830.35 | 850.99 | 841.35 | 850.99 | Above range |
| AE305 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 816.64 | 815.75 | 833.33 | 823.84 | 815.90 | In range |
| AE305 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 818.28 | 813.57 | 833.33 | 823.66 | 817.53 | In range |
| AE305 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 836.59 | 830.35 | 835.85 | 833.80 | 835.84 | Above range |
| AE305 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 835.35 | 830.35 | 834.62 | 833.18 | 834.61 | Above range |
| AE305 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 849.37 | 830.35 | 848.61 | 840.19 | 848.61 | Above range |
| AE305 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 852.80 | 830.35 | 852.04 | 841.90 | 852.05 | Above range |
| AE305 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 851.10 | 830.35 | 850.34 | 841.05 | 850.34 | Above range |
| AE305 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 852.07 | 830.35 | 851.03 | 840.91 | 851.31 | Above range |
| AE305 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 36.435 | 36.435 | 36.506 | 36.477 | 36.491 | In range |
| AE305 | ENTHALPY (J/GDA) · Mixed Air (ma) | 39.316 | 39.133 | 39.374 | 39.289 | 39.368 | In range |
| AE305 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 39.316 | 39.133 | 39.374 | 39.289 | 39.368 | In range |
| AE305 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 26.852 | 26.682 | 26.908 | 26.827 | 26.891 | In range |
| AE305 | ENTHALPY (J/GDA) · Supply Air (sa) | 27.433 | 27.273 | 27.490 | 27.417 | 27.471 | In range |
| AE305 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 33.933 | 33.703 | 33.992 | 33.845 | 33.982 | In range |
| AE305 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 33.494 | 33.240 | 33.555 | 33.385 | 33.544 | In range |
| AE305 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 39.843 | 39.713 | 39.960 | 39.858 | 39.893 | In range |
| AE305 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 41.455 | 41.334 | 41.610 | 41.487 | 41.506 | In range |
| AE305 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 40.654 | 40.523 | 40.860 | 40.700 | 40.704 | In range |
| AE305 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 41.000 | 40.819 | 41.160 | 41.013 | 41.050 | In range |
| AE305 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.2771 | 0.2774 | 0.2842 | 0.2805 | 0.2774 | Below range |
| AE305 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.7513 | 0.7213 | 0.7521 | 0.7394 | 0.7520 | In range |
| AE305 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.7513 | 0.7213 | 0.7521 | 0.7394 | 0.7520 | In range |
| AE305 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.7513 | 0.7213 | 0.7521 | 0.7394 | 0.7520 | In range |
| AE305 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.7513 | 0.7213 | 0.7521 | 0.7394 | 0.7520 | In range |
| AE305 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.3467 | 0.3329 | 0.3471 | 0.3413 | 0.3471 | In range |
| AE305 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.4045 | 0.3884 | 0.4050 | 0.3982 | 0.4049 | In range |
| AE305 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE305 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE305 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.4741 | 0.4439 | 0.4747 | 0.4590 | 0.4746 | In range |
| AE305 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.4741 | 0.4439 | 0.4747 | 0.4590 | 0.4746 | In range |
| AE306 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 23.000 | 23 | 23.000 | 23 | 23.000 | In range |
| AE306 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 23.774 | 23.722 | 23.774 | 23.742 | 23.774 | Above range |
| AE306 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 23.774 | 23.722 | 23.774 | 23.742 | 23.774 | Above range |
| AE306 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 12.206 | 12.176 | 12.222 | 12.203 | 12.207 | In range |
| AE306 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 12.778 | 12.766 | 12.784 | 12.778 | 12.778 | In range |
| AE306 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 19.181 | 19.025 | 19.190 | 19.127 | 19.184 | In range |
| AE306 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 18.749 | 18.540 | 18.760 | 18.675 | 18.754 | In range |
| AE306 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 23.333 | 23.331 | 23.339 | 23.334 | 23.333 | In range |
| AE306 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 24.444 | 24.442 | 24.452 | 24.445 | 24.444 | In range |
| AE306 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.892 | 23.887 | 23.917 | 23.897 | 23.892 | In range |
| AE306 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 24.232 | 24.167 | 24.231 | 24.193 | 24.232 | Above range |
| AE306 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.01557 | 0.01552 | 0.01563 | 0.01558 | 0.01556 | In range |
| AE306 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.01180 | 0.01175 | 0.01200 | 0.01187 | 0.01181 | In range |
| AE306 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.01180 | 0.01175 | 0.01200 | 0.01187 | 0.01181 | In range |
| AE306 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.008844 | 0.008492 | 0.008900 | 0.008795 | 0.008852 | In range |
| AE306 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.008844 | 0.008492 | 0.008900 | 0.008795 | 0.008852 | In range |
| AE306 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.008844 | 0.008492 | 0.008900 | 0.008795 | 0.008852 | In range |
| AE306 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.008844 | 0.008492 | 0.008900 | 0.008795 | 0.008852 | In range |
| AE306 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.009511 | 0.009190 | 0.009592 | 0.009457 | 0.009519 | In range |
| AE306 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.009701 | 0.009390 | 0.009793 | 0.009652 | 0.009709 | In range |
| AE306 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.009607 | 0.009296 | 0.009700 | 0.009580 | 0.009614 | In range |
| AE306 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.009607 | 0.009556 | 0.009700 | 0.009643 | 0.009614 | In range |
| AE306 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 860.73 | 830.35 | 859.94 | 845.85 | 859.94 | Above range |
| AE306 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 857.89 | 830.35 | 857.12 | 844.43 | 857.11 | Above range |
| AE306 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 857.89 | 830.35 | 857.12 | 844.43 | 857.11 | Above range |
| AE306 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 820.63 | 819.77 | 833.33 | 825.84 | 819.88 | In range |
| AE306 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 822.27 | 817.53 | 833.33 | 825.66 | 821.52 | In range |
| AE306 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 840.68 | 830.35 | 839.96 | 835.86 | 839.93 | Above range |
| AE306 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 839.44 | 830.35 | 839.81 | 835.55 | 838.69 | In range |
| AE306 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 853.51 | 830.35 | 852.77 | 842.27 | 852.75 | Above range |
| AE306 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 856.97 | 830.35 | 856.22 | 844.00 | 856.20 | Above range |
| AE306 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 855.25 | 830.35 | 854.50 | 843.14 | 854.49 | Above range |
| AE306 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 856.23 | 830.35 | 855.23 | 843.00 | 855.46 | Above range |
| AE306 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 62.705 | 62.705 | 62.851 | 62.755 | 62.710 | In range |
| AE306 | ENTHALPY (J/GDA) · Mixed Air (ma) | 53.935 | 53.770 | 54.042 | 53.930 | 53.968 | In range |
| AE306 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 53.935 | 53.770 | 54.042 | 53.930 | 53.968 | In range |
| AE306 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 34.583 | 33.660 | 34.636 | 34.241 | 34.621 | In range |
| AE306 | ENTHALPY (J/GDA) · Supply Air (sa) | 35.167 | 34.260 | 35.220 | 34.833 | 35.204 | In range |
| AE306 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 41.706 | 40.650 | 41.769 | 41.310 | 41.755 | In range |
| AE306 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 41.266 | 40.150 | 41.330 | 40.844 | 41.315 | In range |
| AE306 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 47.645 | 46.810 | 47.709 | 47.346 | 47.695 | In range |
| AE306 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 49.266 | 48.470 | 49.331 | 48.983 | 49.316 | In range |
| AE306 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 48.460 | 47.690 | 48.525 | 48.183 | 48.510 | In range |
| AE306 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 48.808 | 47.990 | 48.872 | 48.497 | 48.858 | In range |
| AE306 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.2758 | 0.2754 | 0.2842 | 0.2797 | 0.2761 | In range |
| AE306 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.7476 | 0.7160 | 0.7484 | 0.7373 | 0.7483 | In range |
| AE306 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.7476 | 0.7160 | 0.7484 | 0.7373 | 0.7483 | In range |
| AE306 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.7476 | 0.7160 | 0.7484 | 0.7373 | 0.7483 | In range |
| AE306 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.7476 | 0.7160 | 0.7484 | 0.7373 | 0.7483 | In range |
| AE306 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.3451 | 0.3305 | 0.3454 | 0.3403 | 0.3454 | In range |
| AE306 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.4026 | 0.3855 | 0.4030 | 0.3970 | 0.4029 | In range |
| AE306 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE306 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE306 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.4718 | 0.4406 | 0.4723 | 0.4577 | 0.4723 | In range |
| AE306 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.4718 | 0.4406 | 0.4723 | 0.4577 | 0.4723 | In range |
| AE326 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 23.000 | 23 | 23.000 | 23 | 23.000 | In range |
| AE326 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 23.000 | 23 | 23.000 | 23 | 23.000 | In range |
| AE326 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 23.000 | 23 | 23.000 | 23 | 23.000 | In range |
| AE326 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 12.206 | 12.199 | 12.222 | 12.206 | 12.207 | In range |
| AE326 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 12.778 | 12.770 | 12.794 | 12.780 | 12.778 | In range |
| AE326 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 19.181 | 19.052 | 19.190 | 19.132 | 19.184 | In range |
| AE326 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 18.749 | 18.568 | 18.760 | 18.680 | 18.754 | In range |
| AE326 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 23.333 | 23.331 | 23.339 | 23.334 | 23.333 | In range |
| AE326 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 24.444 | 24.442 | 24.452 | 24.445 | 24.444 | In range |
| AE326 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.892 | 23.887 | 23.945 | 23.902 | 23.892 | In range |
| AE326 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 24.232 | 24.167 | 24.240 | 24.198 | 24.232 | In range |
| AE326 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.01557 | 0.01552 | 0.01563 | 0.01558 | 0.01556 | In range |
| AE326 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.01557 | 0.01552 | 0.01563 | 0.01558 | 0.01556 | In range |
| AE326 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.01557 | 0.01552 | 0.01563 | 0.01558 | 0.01556 | In range |
| AE326 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.008844 | 0.008747 | 0.008909 | 0.008850 | 0.008852 | In range |
| AE326 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.008844 | 0.008747 | 0.008909 | 0.008850 | 0.008852 | In range |
| AE326 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.008844 | 0.008747 | 0.008909 | 0.008850 | 0.008852 | In range |
| AE326 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.008844 | 0.008747 | 0.008909 | 0.008850 | 0.008852 | In range |
| AE326 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.009511 | 0.009442 | 0.009613 | 0.009522 | 0.009519 | In range |
| AE326 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.009701 | 0.009650 | 0.009814 | 0.009719 | 0.009709 | In range |
| AE326 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.009607 | 0.009552 | 0.009713 | 0.009635 | 0.009614 | In range |
| AE326 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.009607 | 0.009552 | 0.009713 | 0.009635 | 0.009614 | In range |
| AE326 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 860.73 | 830.35 | 859.94 | 845.85 | 859.94 | Above range |
| AE326 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 860.73 | 830.35 | 859.94 | 845.85 | 859.94 | Above range |
| AE326 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 860.73 | 830.35 | 859.94 | 845.85 | 859.94 | Above range |
| AE326 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 820.63 | 819.77 | 833.33 | 825.83 | 819.88 | In range |
| AE326 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 822.27 | 817.48 | 833.33 | 825.65 | 821.52 | In range |
| AE326 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 840.68 | 830.35 | 839.95 | 835.86 | 839.93 | Above range |
| AE326 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 839.44 | 830.35 | 838.71 | 835.24 | 838.69 | Above range |
| AE326 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 853.51 | 830.35 | 852.76 | 842.27 | 852.75 | Above range |
| AE326 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 856.97 | 830.35 | 856.20 | 843.99 | 856.20 | Above range |
| AE326 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 855.25 | 830.35 | 854.49 | 843.14 | 854.49 | Above range |
| AE326 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 856.23 | 830.35 | 855.23 | 843.00 | 855.46 | Above range |
| AE326 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 62.705 | 62.705 | 62.851 | 62.755 | 62.710 | In range |
| AE326 | ENTHALPY (J/GDA) · Mixed Air (ma) | 62.705 | 62.705 | 62.851 | 62.755 | 62.710 | In range |
| AE326 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 62.705 | 62.705 | 62.851 | 62.755 | 62.710 | In range |
| AE326 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 34.583 | 34.330 | 34.602 | 34.504 | 34.621 | In range |
| AE326 | ENTHALPY (J/GDA) · Supply Air (sa) | 35.167 | 34.930 | 35.185 | 35.096 | 35.204 | In range |
| AE326 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 41.706 | 41.320 | 41.749 | 41.578 | 41.755 | In range |
| AE326 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 41.266 | 40.828 | 41.309 | 41.115 | 41.315 | In range |
| AE326 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 47.645 | 47.450 | 47.688 | 47.604 | 47.695 | In range |
| AE326 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 49.266 | 49.140 | 49.310 | 49.251 | 49.316 | In range |
| AE326 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 48.460 | 48.370 | 48.504 | 48.454 | 48.510 | In range |
| AE326 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 48.808 | 48.370 | 48.851 | 48.668 | 48.858 | In range |
| AE326 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.7476 | 0.7137 | 0.7484 | 0.7370 | 0.7483 | In range |
| AE326 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.7476 | 0.7137 | 0.7484 | 0.7370 | 0.7483 | In range |
| AE326 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.7476 | 0.7137 | 0.7484 | 0.7370 | 0.7483 | In range |
| AE326 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.7476 | 0.7137 | 0.7484 | 0.7370 | 0.7483 | In range |
| AE326 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.7476 | 0.7137 | 0.7484 | 0.7370 | 0.7483 | In range |
| AE326 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.3451 | 0.3294 | 0.3454 | 0.3401 | 0.3454 | In range |
| AE326 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.4026 | 0.3843 | 0.4030 | 0.3968 | 0.4029 | In range |
| AE326 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE326 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE326 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.4718 | 0.4392 | 0.4723 | 0.4574 | 0.4723 | In range |
| AE326 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.4718 | 0.4392 | 0.4723 | 0.4574 | 0.4723 | In range |
| AE345 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 24.900 | 24.889 | 24.900 | 24.896 | 24.900 | In range |
| AE345 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 24.900 | 24.889 | 24.900 | 24.896 | 24.900 | In range |
| AE345 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 24.900 | 24.889 | 24.900 | 24.896 | 24.900 | In range |
| AE345 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 12.206 | 12.197 | 12.222 | 12.205 | 12.207 | In range |
| AE345 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 12.778 | 12.771 | 12.795 | 12.780 | 12.778 | In range |
| AE345 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 19.177 | 19.052 | 19.180 | 19.122 | 19.180 | In range |
| AE345 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 18.743 | 18.572 | 18.750 | 18.669 | 18.748 | In range |
| AE345 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 23.333 | 23.328 | 23.339 | 23.333 | 23.333 | In range |
| AE345 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 24.444 | 24.438 | 24.452 | 24.444 | 24.444 | In range |
| AE345 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.892 | 23.887 | 23.946 | 23.901 | 23.892 | In range |
| AE345 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 24.232 | 24.167 | 24.241 | 24.198 | 24.232 | In range |
| AE345 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE345 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE345 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE345 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE345 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE345 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE345 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE345 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.005144 | 0.005119 | 0.005212 | 0.005169 | 0.005153 | In range |
| AE345 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.005333 | 0.005308 | 0.005413 | 0.005365 | 0.005342 | In range |
| AE345 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.005239 | 0.005214 | 0.005315 | 0.005274 | 0.005248 | In range |
| AE345 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.005239 | 0.005214 | 0.005315 | 0.005274 | 0.005248 | In range |
| AE345 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 851.19 | 830.35 | 850.44 | 841.09 | 850.43 | Above range |
| AE345 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 851.19 | 830.35 | 850.44 | 841.09 | 850.43 | Above range |
| AE345 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 851.19 | 830.35 | 850.44 | 841.09 | 850.43 | Above range |
| AE345 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 814.95 | 814.06 | 833.33 | 822.99 | 814.21 | In range |
| AE345 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 816.59 | 811.84 | 833.33 | 822.80 | 815.84 | In range |
| AE345 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 834.85 | 830.35 | 834.12 | 832.94 | 834.11 | Above range |
| AE345 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 833.61 | 830.35 | 833.33 | 832.32 | 832.88 | Above range |
| AE345 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 847.61 | 830.35 | 846.85 | 839.31 | 846.86 | Above range |
| AE345 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 851.04 | 830.35 | 850.28 | 841.02 | 850.28 | Above range |
| AE345 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 849.33 | 830.35 | 848.57 | 840.17 | 848.58 | Above range |
| AE345 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 850.31 | 830.35 | 849.27 | 840.03 | 849.55 | Above range |
| AE345 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 36.435 | 36.435 | 36.506 | 36.477 | 36.491 | In range |
| AE345 | ENTHALPY (J/GDA) · Mixed Air (ma) | 36.435 | 36.435 | 36.506 | 36.477 | 36.491 | In range |
| AE345 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 36.435 | 36.435 | 36.506 | 36.477 | 36.491 | In range |
| AE345 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 23.573 | 23.564 | 23.640 | 23.604 | 23.615 | In range |
| AE345 | ENTHALPY (J/GDA) · Supply Air (sa) | 24.153 | 24.155 | 24.240 | 24.194 | 24.194 | Below range |
| AE345 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 30.636 | 30.550 | 30.687 | 30.600 | 30.688 | In range |
| AE345 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 30.197 | 30.070 | 30.251 | 30.139 | 30.251 | In range |
| AE345 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 36.534 | 36.571 | 36.680 | 36.612 | 36.587 | Below range |
| AE345 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 38.141 | 38.190 | 38.330 | 38.239 | 38.196 | Below range |
| AE345 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 37.343 | 37.381 | 37.590 | 37.456 | 37.396 | Below range |
| AE345 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 37.688 | 37.590 | 37.741 | 37.669 | 37.741 | In range |
| AE345 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.7528 | 0.7217 | 0.7537 | 0.7400 | 0.7535 | In range |
| AE345 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.7528 | 0.7217 | 0.7537 | 0.7400 | 0.7535 | In range |
| AE345 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.7528 | 0.7217 | 0.7537 | 0.7400 | 0.7535 | In range |
| AE345 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.7528 | 0.7217 | 0.7537 | 0.7400 | 0.7535 | In range |
| AE345 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.7528 | 0.7217 | 0.7537 | 0.7400 | 0.7535 | In range |
| AE345 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.3475 | 0.3331 | 0.3478 | 0.3416 | 0.3478 | In range |
| AE345 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.4054 | 0.3886 | 0.4058 | 0.3985 | 0.4057 | In range |
| AE345 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE345 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE345 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.4751 | 0.4441 | 0.4757 | 0.4594 | 0.4756 | In range |
| AE345 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.4751 | 0.4441 | 0.4757 | 0.4594 | 0.4756 | In range |
AE VAV coil and zone loads91 rows · 4 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| AE401 | Sensible Heating Load (QZH1sensible) (kWh/h) | 2.931 | 2.930 | 2.931 | 2.931 | 2.931 | In range |
| AE401 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE401 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5861 | 0.5900 | 0.5868 | 0.5861 | In range |
| AE401 | Sensible Heating Load (QZH2sensible) (kWh/h) | 2.345 | 2.345 | 2.350 | 2.346 | 2.345 | In range |
| AE401 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE401 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8792 | 0.8800 | 0.8793 | 0.8792 | In range |
| AE401 | Coil Load (QHpreheat) (kWh/h) | 10.237 | 10.248 | 10.818 | 10.405 | 10.260 | Below range |
| AE401 | Loads Sensible (QCsensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE401 | Latent (QClatent) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE401 | Total (QCtotal) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE401 | Coil Outlet RH (RHcco) (%) | 4.143 | 4.146 | 4.802 | 4.283 | 4.145 | Below range |
| AE401 | Reheat Coil Load (QH1reheat) (kWh/h) | 4.485 | 4.489 | 4.584 | 4.516 | 4.499 | Below range |
| AE401 | Reheat Coil Load (QH2reheat) (kWh/h) | 4.863 | 4.869 | 5.015 | 4.913 | 4.877 | Below range |
| AE403 | Sensible Heating Load (QZH1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE403 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 1.465 | 1.465 | 1.467 | 1.465 | 1.465 | In range |
| AE403 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5860 | 0.5897 | 0.5867 | 0.5861 | In range |
| AE403 | Sensible Heating Load (QZH2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE403 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 2.345 | 2.345 | 2.346 | 2.345 | 2.345 | In range |
| AE403 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8790 | 0.8909 | 0.8811 | 0.8792 | In range |
| AE403 | Coil Load (QHpreheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE403 | Loads Sensible (QCsensible) (kWh/h) | 1.453 | 1.399 | 1.466 | 1.426 | 1.458 | In range |
| AE403 | Latent (QClatent) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE403 | Total (QCtotal) (kWh/h) | 1.453 | 1.399 | 1.466 | 1.426 | 1.458 | In range |
| AE403 | Coil Outlet RH (RHcco) (%) | 36.356 | 34.290 | 36.390 | 35.815 | 36.395 | In range |
| AE403 | Reheat Coil Load (QH1reheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE403 | Reheat Coil Load (QH2reheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE404 | Sensible Heating Load (QZH1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE404 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 2.931 | 2.931 | 2.934 | 2.931 | 2.931 | In range |
| AE404 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5861 | 0.5927 | 0.5872 | 0.5861 | In range |
| AE404 | Sensible Heating Load (QZH2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE404 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 3.517 | 3.516 | 3.517 | 3.517 | 3.517 | In range |
| AE404 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8792 | 0.8939 | 0.8816 | 0.8792 | In range |
| AE404 | Coil Load (QHpreheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE404 | Loads Sensible (QCsensible) (kWh/h) | 7.386 | 7.333 | 7.459 | 7.395 | 7.399 | In range |
| AE404 | Latent (QClatent) (kWh/h) | 5.924 | 5.917 | 6.581 | 6.171 | 5.924 | In range |
| AE404 | Total (QCtotal) (kWh/h) | 13.310 | 13.308 | 14.031 | 13.566 | 13.323 | In range |
| AE404 | Coil Outlet RH (RHcco) (%) | 99.886 | 97.240 | 100 | 99.324 | 100 | In range |
| AE404 | Reheat Coil Load (QH1reheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE404 | Reheat Coil Load (QH2reheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE405 | Sensible Heating Load (QZH1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE405 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 1.465 | 1.465 | 1.466 | 1.465 | 1.465 | In range |
| AE405 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5861 | 0.5897 | 0.5867 | 0.5861 | In range |
| AE405 | Sensible Heating Load (QZH2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE405 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 2.345 | 2.344 | 2.345 | 2.345 | 2.345 | In range |
| AE405 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8791 | 0.8909 | 0.8811 | 0.8792 | In range |
| AE405 | Coil Load (QHpreheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE405 | Loads Sensible (QCsensible) (kWh/h) | 4.092 | 4.091 | 4.143 | 4.110 | 4.102 | In range |
| AE405 | Latent (QClatent) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE405 | Total (QCtotal) (kWh/h) | 4.092 | 4.091 | 4.143 | 4.110 | 4.102 | In range |
| AE405 | Coil Outlet RH (RHcco) (%) | 53.338 | 51.855 | 53.520 | 52.968 | 53.463 | In range |
| AE405 | Reheat Coil Load (QH1reheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE405 | Reheat Coil Load (QH2reheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE406 | Sensible Heating Load (QZH1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE406 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 1.465 | 1.465 | 1.466 | 1.465 | 1.465 | In range |
| AE406 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5861 | 0.5897 | 0.5867 | 0.5861 | In range |
| AE406 | Sensible Heating Load (QZH2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE406 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 2.345 | 2.345 | 2.345 | 2.345 | 2.345 | In range |
| AE406 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8792 | 0.8909 | 0.8811 | 0.8792 | In range |
| AE406 | Coil Load (QHpreheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE406 | Loads Sensible (QCsensible) (kWh/h) | 3.626 | 3.567 | 3.680 | 3.616 | 3.635 | In range |
| AE406 | Latent (QClatent) (kWh/h) | 4.596 | 4.495 | 4.969 | 4.728 | 4.588 | In range |
| AE406 | Total (QCtotal) (kWh/h) | 8.222 | 8.175 | 8.596 | 8.344 | 8.223 | In range |
| AE406 | Coil Outlet RH (RHcco) (%) | 99.885 | 99.380 | 100 | 99.857 | 100 | In range |
| AE406 | Reheat Coil Load (QH1reheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE406 | Reheat Coil Load (QH2reheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE426 | Sensible Heating Load (QZH1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE426 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 1.465 | 1.465 | 1.466 | 1.465 | 1.465 | In range |
| AE426 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5861 | 0.5897 | 0.5867 | 0.5861 | In range |
| AE426 | Sensible Heating Load (QZH2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE426 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 2.345 | 2.345 | 2.345 | 2.345 | 2.345 | In range |
| AE426 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8792 | 0.8909 | 0.8811 | 0.8792 | In range |
| AE426 | Coil Load (QHpreheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE426 | Loads Sensible (QCsensible) (kWh/h) | 3.585 | 3.516 | 3.642 | 3.570 | 3.594 | In range |
| AE426 | Latent (QClatent) (kWh/h) | 5.244 | 5.189 | 5.633 | 5.359 | 5.237 | In range |
| AE426 | Total (QCtotal) (kWh/h) | 8.829 | 8.805 | 9.207 | 8.928 | 8.830 | In range |
| AE426 | Coil Outlet RH (RHcco) (%) | 99.885 | 99.580 | 100 | 99.922 | 100 | In range |
| AE426 | Reheat Coil Load (QH1reheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE426 | Reheat Coil Load (QH2reheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE445 | Sensible Heating Load (QZH1sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE445 | Sensible Cooling Load (QZC1sensible) (kWh/h) | 1.465 | 1.465 | 1.466 | 1.465 | 1.465 | In range |
| AE445 | Latent Load (QZ1latent) (kWh/h) | 0.5861 | 0.5861 | 0.5897 | 0.5867 | 0.5861 | In range |
| AE445 | Sensible Heating Load (QZH2sensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE445 | Sensible Cooling Load (QZC2sensible) (kWh/h) | 2.345 | 2.344 | 2.345 | 2.345 | 2.345 | In range |
| AE445 | Latent Load (QZ2latent) (kWh/h) | 0.8792 | 0.8791 | 0.8909 | 0.8811 | 0.8792 | In range |
| AE445 | Coil Load (QHpreheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE445 | Loads Sensible (QCsensible) (kWh/h) | 4.146 | 4.145 | 4.191 | 4.162 | 4.157 | In range |
| AE445 | Latent (QClatent) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE445 | Total (QCtotal) (kWh/h) | 4.146 | 4.145 | 4.191 | 4.162 | 4.157 | In range |
| AE445 | Coil Outlet RH (RHcco) (%) | 49.452 | 49.242 | 49.780 | 49.548 | 49.575 | In range |
| AE445 | Reheat Coil Load (QH1reheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE445 | Reheat Coil Load (QH2reheat) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
AE VAV node states385 rows · 67 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| AE401 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | −29.000 | −29 | −29 | −29 | −29 | In range |
| AE401 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | −29.000 | −29 | −28.996 | −28.999 | −29 | In range |
| AE401 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 7.222 | 7.203 | 7.222 | 7.218 | 7.222 | In range |
| AE401 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 7.222 | 7.203 | 7.222 | 7.218 | 7.222 | In range |
| AE401 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 7.297 | 7.278 | 7.310 | 7.298 | 7.297 | In range |
| AE401 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 46.880 | 46.505 | 46.948 | 46.767 | 46.920 | In range |
| AE401 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 36.019 | 35.766 | 36.055 | 35.930 | 36.039 | In range |
| AE401 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 21.111 | 21.110 | 21.145 | 21.117 | 21.111 | In range |
| AE401 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 22.222 | 22.221 | 22.259 | 22.228 | 22.222 | In range |
| AE401 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | n/a | |||||
| AE401 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | n/a | |||||
| AE401 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 2.59e-4 | 2.59e-4 | 3.00e-4 | 2.66e-4 | 2.59e-4 | In range |
| AE401 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 2.59e-4 | 2.59e-4 | 3.00e-4 | 2.67e-4 | 2.59e-4 | Below range |
| AE401 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 2.59e-4 | 2.59e-4 | 3.00e-4 | 2.67e-4 | 2.59e-4 | Below range |
| AE401 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 2.59e-4 | 2.59e-4 | 3.00e-4 | 2.67e-4 | 2.59e-4 | Below range |
| AE401 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 2.59e-4 | 2.59e-4 | 3.00e-4 | 2.66e-4 | 2.59e-4 | In range |
| AE401 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 2.59e-4 | 2.59e-4 | 3.00e-4 | 2.67e-4 | 2.59e-4 | In range |
| AE401 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 2.59e-4 | 2.59e-4 | 3.00e-4 | 2.66e-4 | 2.59e-4 | In range |
| AE401 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.002306 | 0.002269 | 0.002374 | 0.002314 | 0.002304 | In range |
| AE401 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.002312 | 0.002287 | 0.002374 | 0.002318 | 0.002310 | In range |
| AE401 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | n/a | |||||
| AE401 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | n/a | |||||
| AE401 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 692.65 | 691.84 | 833.33 | 761.86 | 691.93 | In range |
| AE401 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 692.65 | 691.85 | 833.33 | 761.87 | 691.93 | In range |
| AE401 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 795.33 | 794.48 | 833.33 | 813.19 | 794.59 | In range |
| AE401 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 795.33 | 794.48 | 833.33 | 813.19 | 794.59 | In range |
| AE401 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 795.55 | 794.28 | 833.33 | 813.17 | 794.80 | In range |
| AE401 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 907.76 | 830.35 | 907.05 | 869.40 | 907.09 | Above range |
| AE401 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 876.97 | 830.35 | 876.18 | 854.00 | 876.25 | Above range |
| AE401 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 837.45 | 833.33 | 836.66 | 835.52 | 836.69 | Above range |
| AE401 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 840.62 | 833.33 | 839.83 | 837.64 | 839.86 | Above range |
| AE401 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | n/a | |||||
| AE401 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | n/a | |||||
| AE401 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | −28.507 | −28.540 | −28.507 | −28.519 | −28.543 | In range |
| AE401 | ENTHALPY (J/GDA) · Mixed Air (ma) | −28.507 | −28.538 | −28.507 | −28.519 | −28.543 | In range |
| AE401 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 7.908 | 7.889 | 7.914 | 7.905 | 7.917 | In range |
| AE401 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 7.908 | 7.889 | 7.914 | 7.905 | 7.917 | In range |
| AE401 | ENTHALPY (J/GDA) · Supply Air (sa) | 7.983 | 7.977 | 8 | 7.989 | 7.992 | In range |
| AE401 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 47.777 | 47.593 | 47.791 | 47.715 | 47.876 | In range |
| AE401 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 36.858 | 36.727 | 36.869 | 36.799 | 36.923 | In range |
| AE401 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 27.071 | 27.006 | 27.138 | 27.069 | 27.093 | In range |
| AE401 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 28.208 | 28.174 | 28.252 | 28.203 | 28.231 | In range |
| AE401 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | n/a | |||||
| AE401 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | n/a | |||||
| AE401 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.2811 | 0.2814 | 0.2971 | 0.2851 | 0.2814 | Below range |
| AE401 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.2811 | 0.2814 | 0.2971 | 0.2851 | 0.2814 | Below range |
| AE401 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.2811 | 0.2814 | 0.2971 | 0.2851 | 0.2814 | Below range |
| AE401 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.2811 | 0.2814 | 0.2971 | 0.2851 | 0.2814 | Below range |
| AE401 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.2811 | 0.2814 | 0.2971 | 0.2851 | 0.2814 | Below range |
| AE401 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.1127 | 0.1128 | 0.1188 | 0.1141 | 0.1128 | Below range |
| AE401 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.1684 | 0.1686 | 0.1782 | 0.1710 | 0.1686 | Below range |
| AE401 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE401 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE401 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0 | 0 | 0 | 0 | 0 | In range |
| AE401 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0 | 0 | 0 | 0 | 0 | In range |
| AE403 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 15.500 | 15.500 | 15.500 | 15.500 | 15.500 | In range |
| AE403 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 16.952 | 16.776 | 16.962 | 16.856 | 16.955 | In range |
| AE403 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 16.952 | 16.776 | 16.962 | 16.856 | 16.955 | In range |
| AE403 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 12.664 | 12.647 | 12.670 | 12.662 | 12.664 | In range |
| AE403 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 12.778 | 12.778 | 12.795 | 12.782 | 12.778 | In range |
| AE403 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 12.783 | 12.778 | 12.795 | 12.783 | 12.778 | In range |
| AE403 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 12.783 | 12.778 | 12.795 | 12.783 | 12.778 | In range |
| AE403 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 23.333 | 23.330 | 23.344 | 23.334 | 23.333 | In range |
| AE403 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 24.444 | 24.439 | 24.461 | 24.446 | 24.444 | In range |
| AE403 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.950 | 23.936 | 24.005 | 23.958 | 23.950 | In range |
| AE403 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 23.954 | 23.944 | 24.009 | 23.965 | 23.955 | In range |
| AE403 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.002933 | 0.002895 | 0.002948 | 0.002927 | 0.002936 | In range |
| AE403 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.003288 | 0.003100 | 0.003291 | 0.003240 | 0.003291 | In range |
| AE403 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.003288 | 0.003100 | 0.003291 | 0.003240 | 0.003291 | In range |
| AE403 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.003288 | 0.003100 | 0.003290 | 0.003239 | 0.003291 | In range |
| AE403 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.003288 | 0.003100 | 0.003289 | 0.003239 | 0.003291 | In range |
| AE403 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.003290 | 0.003100 | 0.003289 | 0.003239 | 0.003291 | Above range |
| AE403 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.003290 | 0.003100 | 0.003289 | 0.003239 | 0.003291 | Above range |
| AE403 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.004972 | 0.004925 | 0.005021 | 0.004972 | 0.004970 | In range |
| AE403 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.005031 | 0.004985 | 0.005084 | 0.005035 | 0.005029 | In range |
| AE403 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.005005 | 0.004100 | 0.005040 | 0.004853 | 0.005003 | In range |
| AE403 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.005005 | 0.004100 | 0.005055 | 0.004856 | 0.005003 | In range |
| AE403 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 822.32 | 821.41 | 833.33 | 826.66 | 821.57 | In range |
| AE403 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 826.92 | 826.04 | 833.33 | 828.97 | 826.18 | In range |
| AE403 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 826.92 | 826.04 | 833.33 | 828.97 | 826.18 | In range |
| AE403 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 814.71 | 813.75 | 833.33 | 822.85 | 813.96 | In range |
| AE403 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 815.03 | 813.51 | 833.33 | 822.83 | 814.28 | In range |
| AE403 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 815.05 | 814.12 | 833.33 | 823.03 | 814.28 | In range |
| AE403 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 815.05 | 814.12 | 833.33 | 823.03 | 814.28 | In range |
| AE403 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 847.38 | 830.35 | 846.63 | 839.19 | 846.61 | Above range |
| AE403 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 850.63 | 830.35 | 849.88 | 840.81 | 849.86 | Above range |
| AE403 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 849.18 | 830.35 | 848.43 | 840.09 | 848.41 | Above range |
| AE403 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 849.20 | 830.35 | 848.41 | 840.11 | 848.43 | Above range |
| AE403 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 22.996 | 22.996 | 23.032 | 23.016 | 23.022 | In range |
| AE403 | ENTHALPY (J/GDA) · Mixed Air (ma) | 25.361 | 25.077 | 25.377 | 25.251 | 25.392 | In range |
| AE403 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 25.361 | 25.077 | 25.377 | 25.251 | 25.392 | In range |
| AE403 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 21.026 | 20.903 | 21.052 | 20.995 | 21.049 | In range |
| AE403 | ENTHALPY (J/GDA) · Supply Air (sa) | 21.141 | 21.024 | 21.163 | 21.116 | 21.164 | In range |
| AE403 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 21.151 | 21.024 | 21.163 | 21.116 | 21.164 | In range |
| AE403 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 21.151 | 21.024 | 21.163 | 21.116 | 21.164 | In range |
| AE403 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 36.096 | 35.989 | 36.162 | 36.100 | 36.121 | In range |
| AE403 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 37.373 | 37.273 | 37.470 | 37.395 | 37.401 | In range |
| AE403 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 36.805 | 36.687 | 36.950 | 36.836 | 36.831 | In range |
| AE403 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 36.810 | 36.691 | 36.950 | 36.839 | 36.836 | In range |
| AE403 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.2778 | 0.2781 | 0.2860 | 0.2821 | 0.2781 | Below range |
| AE403 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3352 | 0.3335 | 0.3385 | 0.3358 | 0.3357 | In range |
| AE403 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.3352 | 0.3335 | 0.3385 | 0.3358 | 0.3357 | In range |
| AE403 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3352 | 0.3335 | 0.3385 | 0.3358 | 0.3357 | In range |
| AE403 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3352 | 0.3335 | 0.3385 | 0.3358 | 0.3357 | In range |
| AE403 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.1369 | 0.1362 | 0.1383 | 0.1372 | 0.1371 | In range |
| AE403 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.1983 | 0.1973 | 0.2002 | 0.1986 | 0.1985 | In range |
| AE403 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE403 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE403 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.05739 | 0.05055 | 0.05797 | 0.05370 | 0.05760 | In range |
| AE403 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.05739 | 0.05037 | 0.05797 | 0.05373 | 0.05760 | In range |
| AE404 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 26.900 | 26.889 | 26.900 | 26.896 | 26.900 | In range |
| AE404 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 25.726 | 25.721 | 25.910 | 25.768 | 25.726 | In range |
| AE404 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 25.726 | 25.721 | 25.910 | 25.768 | 25.726 | In range |
| AE404 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 12.480 | 12.444 | 12.491 | 12.467 | 12.481 | In range |
| AE404 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 12.778 | 12.778 | 12.792 | 12.782 | 12.778 | In range |
| AE404 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 12.778 | 12.778 | 12.792 | 12.784 | 12.778 | In range |
| AE404 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 12.778 | 12.778 | 12.792 | 12.784 | 12.778 | In range |
| AE404 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 23.889 | 23.883 | 23.900 | 23.891 | 23.889 | In range |
| AE404 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 25.000 | 24.999 | 25.017 | 25.003 | 25 | In range |
| AE404 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 24.379 | 24.368 | 24.480 | 24.398 | 24.379 | In range |
| AE404 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 24.486 | 24.474 | 24.582 | 24.500 | 24.486 | In range |
| AE404 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.01677 | 0.01677 | 0.01685 | 0.01680 | 0.01677 | In range |
| AE404 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.01348 | 0.01345 | 0.01364 | 0.01352 | 0.01349 | In range |
| AE404 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.01348 | 0.01345 | 0.01364 | 0.01352 | 0.01349 | In range |
| AE404 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.009007 | 0.008749 | 0.009056 | 0.008954 | 0.009015 | In range |
| AE404 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.009007 | 0.008749 | 0.009056 | 0.008953 | 0.009015 | In range |
| AE404 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.009007 | 0.008749 | 0.009056 | 0.008954 | 0.009015 | In range |
| AE404 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.009007 | 0.008749 | 0.009056 | 0.008954 | 0.009015 | In range |
| AE404 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.009900 | 0.009651 | 0.009980 | 0.009847 | 0.009908 | In range |
| AE404 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.01023 | 0.009998 | 0.01033 | 0.01019 | 0.01024 | In range |
| AE404 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.01005 | 0.009832 | 0.01013 | 0.01002 | 0.01005 | In range |
| AE404 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.01005 | 0.009832 | 0.01013 | 0.01002 | 0.01005 | In range |
| AE404 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 873.71 | 830.35 | 872.93 | 852.35 | 872.92 | Above range |
| AE404 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 865.80 | 830.35 | 865.04 | 848.41 | 865.03 | Above range |
| AE404 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 865.80 | 830.35 | 865.04 | 848.41 | 865.03 | Above range |
| AE404 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 821.63 | 820.70 | 833.33 | 826.33 | 820.88 | In range |
| AE404 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 822.49 | 819.66 | 833.33 | 826.24 | 821.73 | In range |
| AE404 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 822.49 | 821.61 | 833.33 | 826.77 | 821.73 | In range |
| AE404 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 822.49 | 821.61 | 833.33 | 826.77 | 821.73 | In range |
| AE404 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 855.64 | 830.35 | 854.88 | 843.33 | 854.87 | Above range |
| AE404 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 859.29 | 830.35 | 858.56 | 845.16 | 858.53 | Above range |
| AE404 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 857.25 | 830.35 | 856.48 | 844.13 | 856.49 | Above range |
| AE404 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 857.56 | 830.35 | 856.69 | 844.10 | 856.79 | Above range |
| AE404 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 69.814 | 69.814 | 69.994 | 69.886 | 69.854 | In range |
| AE404 | ENTHALPY (J/GDA) · Mixed Air (ma) | 60.207 | 60.150 | 60.405 | 60.274 | 60.255 | In range |
| AE404 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 60.207 | 60.150 | 60.405 | 60.274 | 60.255 | In range |
| AE404 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 35.274 | 34.600 | 35.337 | 34.973 | 35.312 | In range |
| AE404 | ENTHALPY (J/GDA) · Supply Air (sa) | 35.578 | 34.930 | 35.624 | 35.284 | 35.616 | In range |
| AE404 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 35.579 | 34.930 | 35.640 | 35.290 | 35.616 | In range |
| AE404 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 35.579 | 34.930 | 35.640 | 35.290 | 35.616 | In range |
| AE404 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 49.203 | 48.560 | 49.280 | 48.923 | 49.253 | In range |
| AE404 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 51.193 | 50.580 | 51.288 | 50.932 | 51.242 | In range |
| AE404 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 50.080 | 49.630 | 50.147 | 49.858 | 50.131 | In range |
| AE404 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 50.189 | 49.730 | 50.256 | 49.958 | 50.240 | In range |
| AE404 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.2751 | 0.2729 | 0.2842 | 0.2790 | 0.2753 | In range |
| AE404 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.5389 | 0.5354 | 0.5492 | 0.5405 | 0.5392 | In range |
| AE404 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.5389 | 0.5354 | 0.5492 | 0.5405 | 0.5392 | In range |
| AE404 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.5389 | 0.5354 | 0.5492 | 0.5405 | 0.5392 | In range |
| AE404 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.5389 | 0.5354 | 0.5492 | 0.5405 | 0.5392 | In range |
| AE404 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.2578 | 0.2554 | 0.2628 | 0.2585 | 0.2579 | In range |
| AE404 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.2811 | 0.2800 | 0.2864 | 0.2820 | 0.2813 | In range |
| AE404 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE404 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE404 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.2638 | 0.2543 | 0.2661 | 0.2615 | 0.2639 | In range |
| AE404 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.2638 | 0.2543 | 0.2661 | 0.2615 | 0.2639 | In range |
| AE405 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 24.900 | 24.889 | 24.900 | 24.896 | 24.900 | In range |
| AE405 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 24.738 | 24.722 | 24.758 | 24.743 | 24.738 | In range |
| AE405 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 24.738 | 24.722 | 24.758 | 24.743 | 24.738 | In range |
| AE405 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 12.664 | 12.647 | 12.670 | 12.662 | 12.664 | In range |
| AE405 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 12.778 | 12.778 | 12.795 | 12.782 | 12.778 | Below range |
| AE405 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 12.783 | 12.778 | 12.795 | 12.783 | 12.778 | In range |
| AE405 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 12.783 | 12.778 | 12.795 | 12.783 | 12.778 | In range |
| AE405 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 23.333 | 23.332 | 23.344 | 23.335 | 23.333 | In range |
| AE405 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 24.444 | 24.440 | 24.461 | 24.446 | 24.444 | In range |
| AE405 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.949 | 23.936 | 23.996 | 23.956 | 23.949 | In range |
| AE405 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 23.954 | 23.944 | 24.000 | 23.959 | 23.954 | In range |
| AE405 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE405 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.004836 | 0.004700 | 0.004851 | 0.004802 | 0.004846 | In range |
| AE405 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.004836 | 0.004700 | 0.004851 | 0.004802 | 0.004846 | In range |
| AE405 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.004836 | 0.004700 | 0.004851 | 0.004801 | 0.004846 | In range |
| AE405 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.004836 | 0.004700 | 0.004851 | 0.004802 | 0.004846 | In range |
| AE405 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.004838 | 0.004700 | 0.004851 | 0.004802 | 0.004846 | In range |
| AE405 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.004838 | 0.004700 | 0.004851 | 0.004802 | 0.004846 | In range |
| AE405 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.006525 | 0.006473 | 0.006582 | 0.006529 | 0.006530 | In range |
| AE405 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.006584 | 0.006533 | 0.006645 | 0.006593 | 0.006590 | In range |
| AE405 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.006557 | 0.005900 | 0.006616 | 0.006453 | 0.006563 | In range |
| AE405 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.006557 | 0.005900 | 0.006616 | 0.006453 | 0.006563 | In range |
| AE405 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 851.19 | 830.35 | 850.44 | 841.09 | 850.43 | Above range |
| AE405 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 851.20 | 830.35 | 850.45 | 841.10 | 850.45 | Above range |
| AE405 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 851.20 | 830.35 | 850.45 | 841.10 | 850.45 | Above range |
| AE405 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 816.73 | 815.78 | 833.33 | 823.86 | 815.98 | In range |
| AE405 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 817.05 | 815.52 | 833.33 | 823.84 | 816.31 | In range |
| AE405 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 817.07 | 816.16 | 833.33 | 824.04 | 816.31 | In range |
| AE405 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 817.07 | 816.16 | 833.33 | 824.04 | 816.31 | In range |
| AE405 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 849.48 | 830.35 | 848.73 | 840.24 | 848.72 | Above range |
| AE405 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 852.74 | 830.35 | 851.98 | 841.87 | 851.98 | Above range |
| AE405 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 851.28 | 830.35 | 850.53 | 841.15 | 850.52 | Above range |
| AE405 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 851.30 | 830.35 | 850.51 | 841.15 | 850.54 | Above range |
| AE405 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 36.435 | 36.435 | 36.506 | 36.477 | 36.491 | In range |
| AE405 | ENTHALPY (J/GDA) · Mixed Air (ma) | 37.174 | 37.062 | 37.216 | 37.160 | 37.230 | In range |
| AE405 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 37.174 | 37.062 | 37.216 | 37.160 | 37.230 | In range |
| AE405 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 24.934 | 24.799 | 24.970 | 24.907 | 24.975 | In range |
| AE405 | ENTHALPY (J/GDA) · Supply Air (sa) | 25.049 | 24.919 | 25.100 | 25.029 | 25.090 | In range |
| AE405 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 25.058 | 24.919 | 25.100 | 25.029 | 25.090 | In range |
| AE405 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 25.058 | 24.919 | 25.100 | 25.029 | 25.090 | In range |
| AE405 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 40.047 | 39.926 | 40.116 | 40.049 | 40.091 | In range |
| AE405 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 41.327 | 41.214 | 41.450 | 41.351 | 41.374 | In range |
| AE405 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 40.757 | 40.625 | 40.920 | 40.787 | 40.802 | In range |
| AE405 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 40.762 | 40.628 | 40.920 | 40.790 | 40.807 | In range |
| AE405 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.2771 | 0.2774 | 0.2842 | 0.2805 | 0.2774 | Below range |
| AE405 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3343 | 0.3335 | 0.3383 | 0.3352 | 0.3347 | In range |
| AE405 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.3343 | 0.3335 | 0.3383 | 0.3352 | 0.3347 | In range |
| AE405 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3343 | 0.3335 | 0.3383 | 0.3352 | 0.3347 | In range |
| AE405 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3343 | 0.3335 | 0.3383 | 0.3352 | 0.3347 | In range |
| AE405 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.1365 | 0.1362 | 0.1383 | 0.1369 | 0.1368 | In range |
| AE405 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.1977 | 0.1973 | 0.2000 | 0.1982 | 0.1980 | In range |
| AE405 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE405 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE405 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.05712 | 0.04961 | 0.05830 | 0.05461 | 0.05733 | In range |
| AE405 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.05712 | 0.04997 | 0.05830 | 0.05467 | 0.05733 | In range |
| AE406 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 23.000 | 23 | 23.000 | 23 | 23.000 | In range |
| AE406 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 23.161 | 23.134 | 23.167 | 23.155 | 23.161 | In range |
| AE406 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 23.161 | 23.134 | 23.167 | 23.155 | 23.161 | In range |
| AE406 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 12.665 | 12.647 | 12.669 | 12.661 | 12.665 | In range |
| AE406 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 12.778 | 12.771 | 12.794 | 12.780 | 12.778 | In range |
| AE406 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 12.783 | 12.771 | 12.794 | 12.782 | 12.778 | In range |
| AE406 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 12.783 | 12.771 | 12.794 | 12.782 | 12.778 | In range |
| AE406 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 23.333 | 23.318 | 23.344 | 23.332 | 23.333 | In range |
| AE406 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 24.444 | 24.431 | 24.461 | 24.445 | 24.444 | In range |
| AE406 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.949 | 23.935 | 24.004 | 23.954 | 23.949 | In range |
| AE406 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 23.954 | 23.939 | 24.008 | 23.958 | 23.954 | In range |
| AE406 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.01557 | 0.01552 | 0.01563 | 0.01558 | 0.01556 | In range |
| AE406 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.01476 | 0.01470 | 0.01491 | 0.01481 | 0.01475 | In range |
| AE406 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.01476 | 0.01470 | 0.01491 | 0.01481 | 0.01475 | In range |
| AE406 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.009118 | 0.009068 | 0.009200 | 0.009131 | 0.009126 | In range |
| AE406 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.009118 | 0.009068 | 0.009200 | 0.009131 | 0.009126 | In range |
| AE406 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.009118 | 0.009068 | 0.009200 | 0.009131 | 0.009126 | In range |
| AE406 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.009118 | 0.009068 | 0.009200 | 0.009131 | 0.009126 | In range |
| AE406 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.01082 | 0.01078 | 0.01093 | 0.01083 | 0.01082 | In range |
| AE406 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.01088 | 0.01085 | 0.01099 | 0.01090 | 0.01088 | In range |
| AE406 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.01085 | 0.01030 | 0.01097 | 0.01077 | 0.01086 | In range |
| AE406 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.01085 | 0.01030 | 0.01097 | 0.01077 | 0.01086 | In range |
| AE406 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 860.73 | 830.35 | 859.94 | 845.85 | 859.94 | Above range |
| AE406 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 860.11 | 830.35 | 859.33 | 845.55 | 859.32 | Above range |
| AE406 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 860.11 | 830.35 | 859.39 | 845.56 | 859.32 | Above range |
| AE406 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 822.31 | 821.38 | 833.33 | 826.65 | 821.55 | In range |
| AE406 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 822.63 | 821.07 | 833.33 | 826.63 | 821.88 | In range |
| AE406 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 822.65 | 821.76 | 833.33 | 826.83 | 821.88 | In range |
| AE406 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 822.65 | 821.76 | 833.33 | 826.83 | 821.88 | In range |
| AE406 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 855.28 | 830.35 | 854.50 | 843.14 | 854.51 | Above range |
| AE406 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 858.56 | 830.35 | 857.79 | 844.78 | 857.80 | Above range |
| AE406 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 857.10 | 830.35 | 856.32 | 844.05 | 856.33 | Above range |
| AE406 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 857.11 | 830.35 | 856.30 | 844.05 | 856.35 | Above range |
| AE406 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 62.705 | 62.705 | 62.851 | 62.755 | 62.710 | In range |
| AE406 | ENTHALPY (J/GDA) · Mixed Air (ma) | 60.832 | 60.862 | 61.128 | 61.007 | 60.839 | Below range |
| AE406 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 60.832 | 60.956 | 61.128 | 61.038 | 60.839 | Below range |
| AE406 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 35.744 | 35.620 | 35.764 | 35.699 | 35.781 | In range |
| AE406 | ENTHALPY (J/GDA) · Supply Air (sa) | 35.860 | 35.740 | 35.879 | 35.817 | 35.897 | In range |
| AE406 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 35.866 | 35.740 | 35.879 | 35.817 | 35.897 | In range |
| AE406 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 35.866 | 35.740 | 35.879 | 35.817 | 35.897 | In range |
| AE406 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 50.971 | 50.850 | 51.035 | 50.942 | 51.015 | In range |
| AE406 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 52.262 | 52.180 | 52.335 | 52.252 | 52.308 | In range |
| AE406 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 51.687 | 51.644 | 51.755 | 51.683 | 51.731 | In range |
| AE406 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 51.692 | 51.647 | 51.760 | 51.686 | 51.736 | In range |
| AE406 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.2753 | 0.2747 | 0.2842 | 0.2794 | 0.2755 | In range |
| AE406 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3317 | 0.3297 | 0.3384 | 0.3328 | 0.3321 | In range |
| AE406 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.3317 | 0.3297 | 0.3384 | 0.3328 | 0.3321 | In range |
| AE406 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3317 | 0.3297 | 0.3384 | 0.3328 | 0.3321 | In range |
| AE406 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3317 | 0.3297 | 0.3384 | 0.3328 | 0.3321 | In range |
| AE406 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.1355 | 0.1346 | 0.1382 | 0.1360 | 0.1357 | In range |
| AE406 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.1962 | 0.1951 | 0.2001 | 0.1969 | 0.1964 | In range |
| AE406 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE406 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE406 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.05641 | 0.04727 | 0.05697 | 0.05344 | 0.05661 | In range |
| AE406 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.05641 | 0.04727 | 0.05697 | 0.05344 | 0.05661 | In range |
| AE426 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 23.000 | 23 | 23.000 | 23 | 23.000 | In range |
| AE426 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 23.000 | 23 | 23.000 | 23 | 23.000 | In range |
| AE426 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 23.000 | 23 | 23.000 | 23 | 23.000 | In range |
| AE426 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 12.665 | 12.647 | 12.670 | 12.661 | 12.665 | In range |
| AE426 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 12.778 | 12.778 | 12.782 | 12.780 | 12.778 | Below range |
| AE426 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 12.783 | 12.778 | 12.790 | 12.782 | 12.778 | In range |
| AE426 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 12.783 | 12.778 | 12.790 | 12.782 | 12.778 | In range |
| AE426 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 23.333 | 23.329 | 23.344 | 23.334 | 23.333 | In range |
| AE426 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 24.444 | 24.442 | 24.461 | 24.446 | 24.444 | In range |
| AE426 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.949 | 23.936 | 23.992 | 23.954 | 23.949 | In range |
| AE426 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 23.954 | 23.944 | 23.997 | 23.958 | 23.954 | In range |
| AE426 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.01557 | 0.01552 | 0.01563 | 0.01558 | 0.01556 | In range |
| AE426 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.01557 | 0.01552 | 0.01563 | 0.01558 | 0.01556 | In range |
| AE426 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.01557 | 0.01552 | 0.01563 | 0.01558 | 0.01556 | In range |
| AE426 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.009118 | 0.009080 | 0.009200 | 0.009139 | 0.009126 | In range |
| AE426 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.009118 | 0.009080 | 0.009200 | 0.009139 | 0.009126 | In range |
| AE426 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.009118 | 0.009080 | 0.009200 | 0.009139 | 0.009126 | In range |
| AE426 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.009118 | 0.009080 | 0.009200 | 0.009139 | 0.009126 | In range |
| AE426 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.01082 | 0.01079 | 0.01094 | 0.01084 | 0.01082 | In range |
| AE426 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.01088 | 0.01086 | 0.01100 | 0.01091 | 0.01088 | In range |
| AE426 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.01085 | 0.01040 | 0.01097 | 0.01080 | 0.01086 | In range |
| AE426 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.01085 | 0.01040 | 0.01097 | 0.01080 | 0.01086 | In range |
| AE426 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 860.73 | 830.35 | 859.94 | 845.85 | 859.94 | Above range |
| AE426 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 860.73 | 830.35 | 859.94 | 845.85 | 859.94 | Above range |
| AE426 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 860.73 | 830.35 | 859.94 | 845.85 | 859.94 | Above range |
| AE426 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 822.31 | 821.38 | 833.33 | 826.66 | 821.55 | In range |
| AE426 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 822.63 | 821.11 | 833.33 | 826.64 | 821.88 | In range |
| AE426 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 822.65 | 821.76 | 833.33 | 826.84 | 821.88 | In range |
| AE426 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 822.65 | 821.76 | 833.33 | 826.84 | 821.88 | In range |
| AE426 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 855.28 | 830.35 | 854.53 | 843.15 | 854.51 | Above range |
| AE426 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 858.56 | 830.35 | 857.83 | 844.79 | 857.80 | Above range |
| AE426 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 857.10 | 830.35 | 856.36 | 844.06 | 856.33 | Above range |
| AE426 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 857.11 | 830.35 | 856.34 | 844.06 | 856.35 | Above range |
| AE426 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 62.705 | 62.705 | 62.851 | 62.755 | 62.710 | In range |
| AE426 | ENTHALPY (J/GDA) · Mixed Air (ma) | 62.705 | 62.705 | 62.851 | 62.755 | 62.710 | In range |
| AE426 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 62.705 | 62.705 | 62.851 | 62.755 | 62.710 | In range |
| AE426 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 35.744 | 35.630 | 35.793 | 35.727 | 35.781 | In range |
| AE426 | ENTHALPY (J/GDA) · Supply Air (sa) | 35.860 | 35.760 | 35.908 | 35.848 | 35.897 | In range |
| AE426 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 35.866 | 35.760 | 35.908 | 35.852 | 35.897 | In range |
| AE426 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 35.866 | 35.760 | 35.908 | 35.852 | 35.897 | In range |
| AE426 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 50.971 | 50.880 | 51.061 | 50.980 | 51.015 | In range |
| AE426 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 52.262 | 52.208 | 52.361 | 52.289 | 52.308 | In range |
| AE426 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 51.687 | 51.670 | 51.781 | 51.717 | 51.731 | In range |
| AE426 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 51.692 | 51.670 | 51.786 | 51.720 | 51.736 | In range |
| AE426 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.3317 | 0.3294 | 0.3384 | 0.3328 | 0.3321 | In range |
| AE426 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3317 | 0.3294 | 0.3384 | 0.3328 | 0.3321 | In range |
| AE426 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.3317 | 0.3294 | 0.3384 | 0.3328 | 0.3321 | In range |
| AE426 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3317 | 0.3294 | 0.3384 | 0.3328 | 0.3321 | In range |
| AE426 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3317 | 0.3294 | 0.3384 | 0.3328 | 0.3321 | In range |
| AE426 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.1355 | 0.1345 | 0.1382 | 0.1359 | 0.1357 | In range |
| AE426 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.1962 | 0.1949 | 0.2001 | 0.1968 | 0.1964 | In range |
| AE426 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE426 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE426 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.05641 | 0.04726 | 0.05697 | 0.05342 | 0.05661 | In range |
| AE426 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.05641 | 0.04726 | 0.05697 | 0.05342 | 0.05661 | In range |
| AE445 | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 24.900 | 24.889 | 24.900 | 24.896 | 24.900 | In range |
| AE445 | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 24.900 | 24.889 | 24.900 | 24.896 | 24.900 | In range |
| AE445 | DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco) | 24.900 | 24.889 | 24.900 | 24.896 | 24.900 | In range |
| AE445 | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 12.664 | 12.652 | 12.670 | 12.663 | 12.664 | In range |
| AE445 | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 12.778 | 12.778 | 12.795 | 12.782 | 12.778 | Below range |
| AE445 | DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s) | 12.783 | 12.778 | 12.795 | 12.783 | 12.778 | In range |
| AE445 | DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s) | 12.783 | 12.778 | 12.795 | 12.783 | 12.778 | In range |
| AE445 | DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1) | 23.333 | 23.332 | 23.344 | 23.335 | 23.333 | In range |
| AE445 | DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2) | 24.444 | 24.442 | 24.461 | 24.446 | 24.444 | In range |
| AE445 | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.949 | 23.936 | 24.005 | 23.958 | 23.949 | In range |
| AE445 | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 23.954 | 23.944 | 24.009 | 23.961 | 23.954 | In range |
| AE445 | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE445 | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE445 | HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE445 | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE445 | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE445 | HUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s) | 0.004519 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | Above range |
| AE445 | HUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s) | 0.004519 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | Above range |
| AE445 | HUMIDITY RATIO (G/GDA) · Zone 1 Air (z1) | 0.006205 | 0.006139 | 0.006264 | 0.006196 | 0.006174 | In range |
| AE445 | HUMIDITY RATIO (G/GDA) · Zone 2 Air (z2) | 0.006264 | 0.006197 | 0.006327 | 0.006260 | 0.006234 | In range |
| AE445 | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.006238 | 0.005700 | 0.006298 | 0.006143 | 0.006207 | In range |
| AE445 | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.006238 | 0.005700 | 0.006298 | 0.006143 | 0.006207 | In range |
| AE445 | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 851.19 | 830.35 | 850.44 | 841.09 | 850.43 | Above range |
| AE445 | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 851.19 | 830.35 | 850.44 | 841.09 | 850.43 | Above range |
| AE445 | SPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco) | 851.19 | 830.35 | 850.44 | 841.09 | 850.43 | Above range |
| AE445 | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 816.26 | 815.32 | 833.33 | 823.64 | 815.52 | In range |
| AE445 | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 816.59 | 815.07 | 833.33 | 823.61 | 815.84 | In range |
| AE445 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s) | 816.65 | 815.69 | 833.33 | 823.81 | 815.84 | In range |
| AE445 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s) | 816.65 | 815.69 | 833.33 | 823.81 | 815.84 | In range |
| AE445 | SPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1) | 849.04 | 830.35 | 848.26 | 840.00 | 848.23 | Above range |
| AE445 | SPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2) | 852.30 | 830.35 | 851.52 | 841.63 | 851.49 | Above range |
| AE445 | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 850.85 | 830.35 | 850.07 | 840.91 | 850.04 | Above range |
| AE445 | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 850.87 | 830.35 | 850.05 | 840.91 | 850.06 | Above range |
| AE445 | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 36.435 | 36.435 | 36.506 | 36.477 | 36.491 | In range |
| AE445 | ENTHALPY (J/GDA) · Mixed Air (ma) | 36.435 | 36.435 | 36.506 | 36.477 | 36.491 | In range |
| AE445 | ENTHALPY (J/GDA) · Preheat Coil Outlet (pco) | 36.435 | 36.435 | 36.506 | 36.477 | 36.491 | In range |
| AE445 | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 24.038 | 24.034 | 24.110 | 24.076 | 24.079 | In range |
| AE445 | ENTHALPY (J/GDA) · Supply Air (sa) | 24.153 | 24.155 | 24.240 | 24.198 | 24.194 | Below range |
| AE445 | ENTHALPY (J/GDA) · Zone 1 Supply Air (z1s) | 24.254 | 24.155 | 24.240 | 24.198 | 24.194 | Above range |
| AE445 | ENTHALPY (J/GDA) · Zone 2 Supply Air (z2s) | 24.254 | 24.155 | 24.240 | 24.198 | 24.194 | Above range |
| AE445 | ENTHALPY (J/GDA) · Zone 1 Air (z1) | 39.234 | 39.153 | 39.260 | 39.214 | 39.185 | In range |
| AE445 | ENTHALPY (J/GDA) · Zone 2 Air (z2) | 40.514 | 40.441 | 40.580 | 40.511 | 40.467 | In range |
| AE445 | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 39.944 | 39.852 | 40.050 | 39.947 | 39.896 | In range |
| AE445 | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 39.949 | 39.856 | 40.060 | 39.953 | 39.901 | In range |
| AE445 | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.3345 | 0.3335 | 0.3383 | 0.3352 | 0.3350 | In range |
| AE445 | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3345 | 0.3335 | 0.3383 | 0.3352 | 0.3350 | In range |
| AE445 | MASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco) | 0.3345 | 0.3335 | 0.3383 | 0.3352 | 0.3350 | In range |
| AE445 | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3345 | 0.3335 | 0.3383 | 0.3352 | 0.3350 | In range |
| AE445 | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3345 | 0.3335 | 0.3383 | 0.3352 | 0.3350 | In range |
| AE445 | MASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s) | 0.1366 | 0.1362 | 0.1382 | 0.1369 | 0.1368 | In range |
| AE445 | MASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s) | 0.1978 | 0.1973 | 0.2001 | 0.1983 | 0.1981 | In range |
| AE445 | MASS FLOW RATE (KGDA/S) · Zone 1 Air (z1) | n/a* | |||||
| AE445 | MASS FLOW RATE (KGDA/S) · Zone 2 Air (z2) | n/a* | |||||
| AE445 | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.05718 | 0.04979 | 0.05829 | 0.05466 | 0.05740 | In range |
| AE445 | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.05718 | 0.05009 | 0.05829 | 0.05471 | 0.05740 | In range |
Nothing in this suite fits the current filters.
Min, Max and Mean describe the example programs published with the standard. Analytical is the closed-form or quasi-analytical solution where the standard gives one.
Air-side Equipment
54 of 54 range cases inside; 48 required. Tables A3-8, A3-9, A3-10, A3-11, A3-12, A3-13.
ASoftware information
1. SOFTWARE VENDOR:
Jared Bell, Roots Ontological Technologies, LLC
2. SOFTWARE NAME:
SIMsara
3. SOFTWARE VERSION (unique software version identifier):
SIMsara 0.1.0
4. OPERATING SYSTEM REQUIREMENTS:
macOS 13 or later on Apple silicon (arm64). This is the build that was
tested; other targets are listed only when they have been built and run
for these tests.
5. APPROX HARD DISK SPACE REQUIRED FOR INSTALLATION:
About 6.6 MB: the release binary s140_run, which needs no other runtime
files beyond the TOML input and the EPW weather file.
6. MINIMUM RAM REQUIRED FOR SOFTWARE OPERATION:
16 MB: the largest peak resident memory of any submitted test case,
measured with /usr/bin/time -l on the tested build.
7. MINIMUM DISPLAY MONITOR REQUIREMENTS:
None. SIMsara is a command-line program with no graphical display.
8. OTHER HARDWARE OR SOFTWARE-RELATED REQUIREMENTS:
Input is TOML (docs/TOML-INPUT.md in the source distribution) with EPW
weather. Building from source needs Rust 1.98.1. The Standard 140 harness
scripts that generate the test inputs and fill the output templates need
Python 3.11 or later, standard library only.BAlternative modeling methods
NOTE 1 - Cooling-Coil Model and Bypass Factor (Section 11.2.1.1.3 d,
11.2.2.1.3, 11.2.3.1.3 f and 11.2.4.1.4 (140-2014a 5.5.1.1.3 d))
---------------------------------------------------------
1.1 Describe the Effect Being Simulated:
Cooling-coil leaving-air humidity, and with it the coil latent load, the
zone humidity and the mixed-air state.
1.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
1.2.1 Coil:Cooling:Water, SimpleAnalysis
Physical Meaning: one wet or dry regime per call; the air-side UA is
derived from a user design point, and the leaving air lies exp(-UA/(m
cp)) of the way from the effective coil-surface state back to the
entering state (an effective bypass factor).
1.2.2 Coil:Cooling:Water, DetailedAnalysis
Physical Meaning: a fin-and-tube geometry model with a part-wet,
part-dry regime; the UA follows from the geometry.
1.3 Setting or Capability Used:
SimpleAnalysis in every case. The design point (26 C and 0.0135 entering,
14 C and 0.0099 leaving, 12 C entering water at 0.00023 m3/s) forces a
large air-side UA, so the leaving air is practically saturated whenever the
coil is wet (at least 99.87 percent RH in AE104, AE204, AE206, AE226,
AE304, AE306, AE326, AE404, AE406 and AE426). It is the tightest design
point at which the program's design UA calculation still converges. In the
constant-volume cases the coil's design air flow is the system supply, and
its design water flow and the controller's maximum water flow are 2.1666
times the single-zone values (the ratio of the system supply volumes), so
the derived air-side UA scales with the flows and the coil's air-side NTU,
and with it the effective bypass factor, is the single-zone coil's. The
variable-air-volume cases use the same coil, its design air flow the loop
design flow (the constant-volume supply, 11.2.4.1.2 informative note); at
their smaller flows its NTU is larger still. SIMsara has no bypass-factor
input; this is the lowest effective bypass factor the model allows, as
11.2.1.1.3 d and 11.2.3.1.3 f ask.
NOTE 2 - Coil Control and Convergence Tolerance (Section 11.2.1.1.3 a,
11.2.2.1.3, 11.2.3.1.3 a and 11.2.4.1.3 a (140-2014a 5.5.1.1.3 a))
---------------------------------------------------------
2.1 Describe the Effect Being Simulated:
How exactly each coil holds its leaving-air or zone setpoint.
2.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
2.2.1 Controller:WaterCoil convergence tolerance
Physical Meaning: any positive temperature tolerance, in kelvin, on the
sensed coil leaving-air temperature; the controller modulates the coil
water flow until the sensed temperature is within it.
2.2.2 Coil:Heating:Electric with a temperature setpoint node
Physical Meaning: the coil delivers exactly the heat that brings its
leaving air to the setpoint, up to its capacity; no controller.
2.3 Setting or Capability Used:
1e-06 K for the cooling-coil controller (no throttling range; the smallest
practical value). The electric heating coil, and the electric preheat coil
of the constant-volume and variable-air-volume cases, hold their
leaving-air setpoints exactly; each zone's electric reheat coil delivers
exactly the heat that holds its zone at the heating setpoint (11.2.3.1.3 e
and 11.2.4.1.3 e). Each variable-air-volume terminal holds its zone at the
cooling setpoint by its damper, which the program sets each iteration to
the flow that meets the zone's load (11.2.4.1.3 a and f). Every capacity is
well above the loads.
NOTE 3 - Economizer Control (Section 11.2.2.3.1.1.1, 11.2.2.3.2.1.1,
11.2.3.3.1.1.1, 11.2.3.3.2.1.1, 11.2.4.3.1.1 and 11.2.4.3.2.1)
---------------------------------------------------------
3.1 Describe the Effect Being Simulated:
Outdoor-air fraction, mixed-air state and cooling-coil loads of AE226,
AE245, AE326, AE345, AE426 and AE445.
3.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
3.2.1 DifferentialDryBulb
Physical Meaning: the economizer runs while the outdoor dry bulb is
below the return-air dry bulb.
3.2.2 DifferentialEnthalpy
Physical Meaning: the economizer runs while the outdoor enthalpy is
below the return-air enthalpy.
3.2.3 Minimum limit dry bulb
Physical Meaning: the economizer is off when the outdoor dry bulb is
below this limit.
3.2.4 ModulateFlow
Physical Meaning: while it runs, the outdoor-air flow is raised from
the minimum toward the full supply flow to reach the mixed-air
setpoint.
3.3 Setting or Capability Used:
DifferentialDryBulb for AE226, AE326 and AE426 and DifferentialEnthalpy for
AE245, AE345 and AE445, each comparing the outdoor air with the return air
at the return fan outlet (the return-air node of the outdoor-air
controller), with ModulateFlow and the minimum limit dry bulb set to
ODBecono,min (Block C notes 9, 14 and 19). No economizer in the other
cases. In the last hour of AE226, AE245, AE326, AE345, AE426 and AE445 the
economizer runs at 100 percent outdoor air and the cooling coil meets the
rest of the load; in AE426 and AE445 the supply fan keeps the flow the
terminals set (11.2.4.3.1.1 informative note).
NOTE 4 - Time Step and Run Length (Section 11.3.1, 11.3.2, 11.3.3 and 11.3.4
(140-2014a 6.5.1))
---------------------------------------------------------
4.1 Describe the Effect Being Simulated:
Convergence to the steady state that the last-hour outputs report.
4.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
4.2.1 Zone time steps per hour
Physical Meaning: 1 to 60; the HVAC system may sub-step within a zone
step.
4.3 Setting or Capability Used:
6 zone time steps per hour. Each case runs 7 days (January 1-7, a modeling
choice; the specification sets no run length) on its constant weather file;
the last hour is reported only after every output agrees with the previous
hour to 1e-6 relative (or 1e-6 absolute). The reported values are hourly
means; in every case no reported quantity varies between the time steps of
the last hour.
NOTE 5 - Outputs That Are Not Direct Program Outputs (Section 11.3, 11.3.1,
11.3.2, 11.3.3 and 11.3.4 (140-2014a 6.5 and 6.5.1))
---------------------------------------------------------
5.1 Describe the Effect Being Simulated:
Reported values computed from program outputs by the SIMsara
post-processor.
5.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
5.2.1 Direct program outputs
Physical Meaning: zone air system sensible heating and cooling rates,
zone total internal latent gain rate, heating-coil heating rate,
cooling-coil total and sensible cooling rates, fan electricity rate,
zone exhaust fan mass flow rate, and the temperature, humidity ratio
and mass flow rate of every system node.
5.2.2 Post-processed outputs
Physical Meaning: quantities computed from the direct outputs with the
program's own psychrometric fits (after the ASHRAE Fundamentals
psychrometrics chapter), for example h = 1.00484 t + W (2500.94 +
1.85895 t) kJ/kg dry air.
5.3 Setting or Capability Used:
Post-processed (scripts/s140/suites/ae_sz.py, ae_cv.py, ae_vav.py and
psy.py): node specific volume and enthalpy, and RHcco, from each node's
temperature, humidity ratio and the outdoor barometric pressure; each
zone's sensible and latent loads from that zone's system sensible heating
and cooling rates and its total internal latent gain rate; the cooling-coil
total load as the program's total cooling rate (the air-side enthalpy drop)
minus the enthalpy the condensate carries away, taken to leave at the coil
leaving-air temperature (52 W in AE104); the cooling-coil sensible load as
the program's sensible cooling rate plus a condensate term. The program's
sensible rate is the air mass flow times the moist-air specific heat at the
entering humidity times the dry-bulb drop, so it cools the vapour that
condenses, as vapour, all the way to the leaving temperature. Section 3.1
cools that vapour only to the condensation temperature, here the
entering-air dew point, and the condensate from there to the leaving
temperature (items b and c of the definition; the condensate temperatures
of 11.2.1.1.3 d and 11.2.3.1.3 f informative note 1). The term is therefore
the condensate mass flow times the liquid-water less the vapour specific
heat (4.18 and 1.85895 kJ/(kg K), the program's) times the entering dew
point less the leaving temperature: 6.2 W in AE104, at most 1.21 percent of
the sensible load (AE326), and 0 on a dry coil. The cooling-coil latent
load is the total less that sensible load, so the total, sensible and
latent loads all follow the Section 3.1 definitions. The psychrometric
relations are the ones the program uses internally for its node states. In
AE401 both variable-air-volume terminals sit at their minimum flow, so the
return fan carries no air (11.2.4.1.2.4 informative note 1); the return fan
inlet and outlet states are then reported as n/a, as the quasi-analytical
solution has them, and their mass flow is the program's. Units: loads in
kWh/h are the rates in kW; humidity ratio in g/g dry air.CEquivalent modeling methods
NOTE 1 - Four-Pipe Fan Coil as a One-Zone Air Loop (Section 11.2.1.1, Figure
11-1 (140-2014a 5.5.1.1, Figure 5-25))
-------------------------------------------------------------------------------
1.1 Describe the Effect Being Simulated:
System configuration; none on the specified loads.
1.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.1.1, 11.2.1.1.1.1 and Figure 11-1.
1.3 Equivalent Input(s) Used:
One air loop serving one zone: outdoor-air mixer, electric heating coil,
chilled-water cooling coil, draw-through constant-volume supply fan (total
efficiency 0.7, motor and drive losses outside the airstream, so all
0.28317 m3/s x 498 Pa / 0.7 = 201.46 W of fan power enters the air), a
constant-volume terminal without reheat, the zone exhaust fan of note 3,
and single-zone heating and cooling supply-air setpoint managers carried to
the coil outlets (lowered by the fan's temperature rise).
1.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The same components in the same order as Figure 11-1; the program has no
dedicated fan-coil unit with an outdoor-air mixer and a draw-through fan.
The heating coil is electric, the same coil type as in the single-zone
series (5.1.1.4); it holds its setpoint exactly, as 11.2.1.1.3 a asks, and
the coil type is free (Figure 11-1 informative note).
NOTE 2 - Single-Zone System as a One-Zone Air Loop with a Return Fan (Section
11.2.2.1, Figure 11-3)
-------------------------------------------------------------------------------
2.1 Describe the Effect Being Simulated:
System configuration; none on the specified loads.
2.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.2.1, 11.2.2.1.1 and Figure 11-3.
2.3 Equivalent Input(s) Used:
The air loop of note 1 with a return fan as the first component of the loop
branch, between the zone return and the outdoor-air mixer (note 4). The
mixer's return stream and the economizer's return-air sensor are the return
fan outlet.
2.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The same components in the same order as Figure 11-3; the program treats a
fan ahead of the outdoor-air system on the branch as the system's return
fan.
NOTE 3 - Zone Exhaust Fan (Section 11.2.1.1.1.2, 11.2.1.1.2.3, 11.2.2.1.1.3,
11.2.2.1.2.3-11.2.2.1.2.4, 11.2.3.1.1.3, 11.2.3.1.2.3-11.2.3.1.2.5,
11.2.4.1.1.3 and 11.2.4.1.2.3-11.2.4.1.2.5 (140-2014a 5.5.1.1.1.2,
5.5.1.1.2.3))
-------------------------------------------------------------------------------
3.1 Describe the Effect Being Simulated:
None on the zone or mixed-air energy balance.
3.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.1.1.1.2, 11.2.1.1.2.2-11.2.1.1.2.3, 11.2.2.1.1.3,
11.2.2.1.2.2-11.2.2.1.2.4, 11.2.3.1.1.3, 11.2.3.1.2.3-11.2.3.1.2.5,
11.2.4.1.1.3 and 11.2.4.1.2.3-11.2.4.1.2.5.
3.3 Equivalent Input(s) Used:
A zone exhaust fan draws the specified exhaust from the zone at the zone
air state (one per zone in the two-zone cases). The outdoor-air
controller's minimum flow equals the exhaust mass flow (the sum of both
zones' in the two-zone cases), so the return air is the supply less the
exhaust mass and no air is relieved at the mixer; while an economizer
raises the outdoor air above the minimum, the surplus return air is
relieved there. In the variable-air-volume cases each zone's exhaust flow
is also its terminal's minimum flow (note 16). The exhaust fan's power goes
to the exhausted air.
3.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The specification leaves the exhaust fan undefined because it does not
affect the results (informative notes of 11.2.1.1.1.2, 11.2.2.1.1.3,
11.2.3.1.1.3 and 11.2.4.1.1.3); its heat leaves the building with the
exhaust. (The first fan-coil submission relieved the exhaust mass at the
mixer instead, which gives the same coil and zone loads.)
NOTE 4 - Return Fan Pressure Rise as a Cubic Power Curve (Section 11.2.2.1.1.2,
11.2.3.1.1.2 and 11.2.4.1.1.2)
-------------------------------------------------------------------------------
4.1 Describe the Effect Being Simulated:
Return fan heat, and with it the return-air state, the mixed-air state and
the coil loads.
4.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.2.1.1.2 b, c, g, h, 11.2.2.1.1.4, 11.2.3.1.1.2 b, c, g, h,
11.2.3.1.1.4, 11.2.4.1.1.2 b, c, g, h and 11.2.4.1.1.4.
4.3 Equivalent Input(s) Used:
A variable-volume fan whose power is its maximum-flow power times the cube
of the flow fraction (power coefficients 0, 0, 0, 1, 0, no minimum flow),
so its pressure rise varies with the square of the flow; efficiency 0.7
with motor and drive losses outside the airstream. Its maximum flow is the
loop design flow, and its pressure input is the specified rise (249 Pa at
0.18878 m3/s, or at 0.37756 m3/s in the two-zone cases, varying with the
square of the volume at the return fan inlet) evaluated at that maximum, in
the units of note 7. At the steady return flow the fan then draws exactly
V_ret x P(V_ret) / 0.7 (59.6 to 172.0 W across the single-zone and
constant-volume cases, 0.28 to 28.9 W in the variable-air-volume cases, 0
in AE401, which returns no air), all of it to the air. The
variable-air-volume supply fan is the same kind of fan (note 15).
4.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
11.2.2.1.1.2 c gives the pressure rise as the square of the actual return
volume over the design return volume; at constant efficiency the fan power
is then cubic in the flow. The maximum at the loop design flow keeps the
program's flow limit above the return flow. The same fan-heat convention as
the supply fan (note 1).
NOTE 5 - Adiabatic Zone and Ideal Plant (Section 11.2.1.1.3 b, 11.2.1.1.4,
11.2.2.1.4, 11.2.3.1.4 and 11.2.4.1.5 (140-2014a 5.5.1.1.3 b,
5.5.1.1.4))
-------------------------------------------------------------------------------
5.1 Describe the Effect Being Simulated:
None on the reported loads.
5.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.1.1.3 b, 11.2.1.1.4, 11.2.2.1.4, 11.2.3.1.3 b, 11.2.3.1.4, 11.2.4.1.3
b, 11.2.4.1.4 and 11.2.4.1.5.
5.3 Equivalent Input(s) Used:
Each zone has only adiabatic surfaces; the sensible load is a constant
internal gain (negative for AE101, AE201, AE301 and AE401) and the latent
load a constant latent gain of 586.1 W (586.1 W and 879.2 W in the two
zones of the two-zone cases), both fully convective. The cooling coil is
served by an oversized chilled-water loop held at 6.67 C, with a pump of 1
W (its chiller sized as note 13 says in the two-zone cases); the heating,
preheat and reheat coils are electric.
5.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
11.2.1.1.4 prefers an adiabatic zone with negative internal gains; the
plant only supplies the cooling coil, whose capacity exceeds the loads
(11.2.1.1.3 b).
NOTE 6 - Constant Weather Files Converted to EPW (Section 11.2.1.1.7,
11.2.2.1.7, Annex A1 (140-2014a 5.5.1.1.7, Annex A1))
-------------------------------------------------------------------------------
6.1 Describe the Effect Being Simulated:
None; the converted fields are identical hour by hour.
6.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.1.1.7, 11.2.1.2.1.1 b, 11.2.1.2.2.1 b, 11.2.2.2.1.1 b to 11.2.2.2.4.1
b, 11.2.3.1.7, 11.2.3.2.1.1 b to 11.2.3.2.4.1 b, 11.2.4.1.8, 11.2.4.2.1.1 b
to 11.2.4.2.4.1 b and Annex A1.
6.3 Equivalent Input(s) Used:
AE101.TM2, AE103.TM2, AE104.TM2, AE105.TM2 and AE106.TM2 converted to EPW
by the SIMsara converter (dry bulb, dew point, relative humidity, 101300 Pa
station pressure, wind; no solar), with the specified site in the location
record and the checksums archived. Each case runs on the file its case
table names (AE201, AE301 and AE401 on AE101.TM2, AE226, AE326 and AE426 on
AE106.TM2, AE245, AE345 and AE445 on AE105.TM2) for 7 days until the last
hour repeats.
6.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The program reads EPW weather. The TM2 pressure of 1013 mbar is used as
given (11.2.1.1.7, Table 11-4 note b: the effect is below 0.05 percent).
NOTE 7 - Volumetric Flows Converted to Mass Flow at the Specified States
(Section 11.2.1.1.1.1, 11.2.1.1.2, 11.2.2.1.1.1 and 11.2.2.1.2
(140-2014a 5.5.1.1.1.1, 5.5.1.1.2))
-------------------------------------------------------------------------------
7.1 Describe the Effect Being Simulated:
Supply, exhaust, outdoor-air and return mass flows, and the fan heat.
7.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.1.1.1.1 b and g, 11.2.1.1.2.1-11.2.1.1.2.3, 11.2.2.1.1.1-11.2.2.1.1.2
and 11.2.2.1.2.1-11.2.2.1.2.4.
7.3 Equivalent Input(s) Used:
The program takes volume flows at standard density (1.2043 kg/m3). For each
case the supply mass flow is 0.28317 m3/s divided by the specific volume at
the supply-fan inlet (the cooling-coil outlet), the exhaust mass flow
0.09439 m3/s divided by the specific volume of the zone air; both are
entered as mass flow / 1.2043 (the supply flow also as the terminal, coil
and return-fan maximum), and the outdoor-air minimum equals the exhaust, so
the return air carries the supply less the exhaust mass. The supply fan
pressure input is 498 Pa x 1.2043 x the fan-inlet specific volume, so the
fan power is 0.28317 x 498 / 0.7 W; the return fan pressure input is its
specified rise at the loop design flow in the same units (note 4). The
states come from the case's own converged run; the conversion is repeated
until every input changes by less than 1e-7 relative (4 to 5 runs). The
arithmetic of each step is archived with the results.
7.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
11.2.1.1.2 and 11.2.2.1.2 define the flows at the supply fan inlet, the
exhaust fan inlet (the zone air) and the return fan inlet, and set the
outdoor-air mass flow equal to the exhaust mass flow. The two-zone
conversions are notes 12 (constant volume) and 17 (variable air volume).
NOTE 8 - Thermostat Setpoint Adjustment (Section 11.2.1.1.6.3, 11.2.2.1.6,
11.2.3.1.6 and 11.2.4.1.7 (140-2014a 5.5.1.1.6.3))
-------------------------------------------------------------------------------
8.1 Describe the Effect Being Simulated:
Removes a zone temperature offset of up to 0.0418 K.
8.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.1.1.6, 11.2.1.1.6.3, 11.2.2.1.6, 11.2.3.1.6 and 11.2.4.1.7.
8.3 Equivalent Input(s) Used:
The active setpoint, the specified zone temperature of each case (of each
zone in the two-zone cases: in the constant-volume cases the heating
setpoint the reheat coil holds, in the variable-air-volume cases the
heating setpoint of a heated zone and the cooling setpoint of a cooled
zone, the side of the zone's load), is shifted by the offset between the
specified and the modeled zone temperature of the previous run, in the same
iteration as the flow conversion, until the zone is within 1e-5 K of the
specified temperature. The unused setpoint is 5 K beyond the active one.
The specified zone temperature is the case table's SI value, which the
tables give to three decimals beside the I-P value; the preheat and
supply-air setpoints, which 11.2.3.1.3 c and d give in I-P with a
two-decimal SI value, are the exact conversion of the I-P value. Each input
takes the more precise of its two given forms; the two conventions differ
by less than 4.5e-4 K.
8.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
11.2.1.1.6.3 permits adjusting the modeled thermostat setpoint, case by
case, so that the modeled zone temperature agrees with the specification.
NOTE 9 - Economizer Minimum Limit at ODBecono,min (Section 11.2.2.3.1.1.1 and
11.2.2.3.2.1.1)
-------------------------------------------------------------------------------
9.1 Describe the Effect Being Simulated:
None in the reported hour; the limit decides only at outdoor states far
from the cases'.
9.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.2.3.1.1.1 and 11.2.2.3.2.1.1.
9.3 Equivalent Input(s) Used:
The economizer's minimum limit dry bulb is ODBecono,min: the outdoor dry
bulb at which the minimum outdoor air (the exhaust mass) gives the zone
setpoint with both coils off, computed from the case's loads, flows and fan
heat with the program's own psychrometric relations (the latent gain as
moisture at the zone temperature, both fans' heat to the air, the mixer
conserving dry air, moisture and enthalpy): 7.91 C for AE226 and 7.90 C for
AE245, with the arithmetic archived with the results. The outdoor humidity
ratio is the case's (its specified dew point at the weather file's station
pressure), limited to saturation at that dry bulb: AE245's dew point lies
below its limit, so its outdoor air keeps the case's humidity ratio;
AE226's dew point lies far above its limit, so its outdoor air is saturated
there. No state of either calculation is supersaturated. The program keeps
the economizer off below the limit.
9.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The specification sets the economizer off at or below ODBecono,min and
defines it by the dry bulb alone; at a dry bulb below the case's dew point
the case's own humidity ratio is not a physical outdoor state, so the
saturation limit is used. The program's limit is a dry-bulb input, and both
cases run far above it.
NOTE 10 - Constant-Volume Terminal Reheat System as a Two-Zone Air Loop
(Section 11.2.3.1, 11.2.3.1.1, 11.2.3.1.3 and Figure 11-4)
-------------------------------------------------------------------------------
10.1 Describe the Effect Being Simulated:
System configuration; none on the specified loads.
10.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.3.1, 11.2.3.1.1.1-11.2.3.1.1.3, 11.2.3.1.3 c-e and Figure 11-4.
10.3 Equivalent Input(s) Used:
One air loop serving two zones: the return fan first on the branch (note
4), the outdoor-air mixer, an electric preheat coil holding its leaving air
at the preheat setpoint whenever the mixed air is colder, the chilled-water
cooling coil holding the supply fan's leaving air at the supply-air
setpoint (its own setpoint lowered by the fan's temperature rise), a
draw-through constant-volume supply fan (total efficiency 0.7, motor and
drive losses outside the airstream, so all 0.61353 m3/s x 498 Pa / 0.7 =
436.48 W of fan power enters the air), a splitter to one terminal per zone
with an electric reheat coil (note 11), the zone exhaust fans of note 3,
and a mixer of the two zone returns ahead of the return fan. The mixer's
return stream and the economizer's return-air sensor are the return fan
outlet.
10.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The same components in the same order as Figure 11-4. The preheat and
reheat coils are electric, the coil type of the other series (5.1.1.4).
NOTE 11 - Constant-Volume Reheat Terminal as a Variable-Air-Volume Terminal at
a Constant Flow Fraction of 1 (Section 11.2.3.1.2.2 and 11.2.3.1.3 e)
-------------------------------------------------------------------------------
11.1 Describe the Effect Being Simulated:
None; each terminal delivers its specified constant flow in every regime.
11.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.3.1.2.1, 11.2.3.1.2.2 and 11.2.3.1.3 e.
11.3 Equivalent Input(s) Used:
Each zone's terminal is the program's variable-air-volume terminal with
reheat (AirTerminal:SingleDuct:VAV:Reheat) with a constant minimum flow
fraction of 1, so its flow is its maximum in every regime; the maximum is
the zone's supply mass flow of note 12 over the standard density. Its
electric reheat coil modulates to hold the zone at its heating setpoint,
delivering the supply air at the temperature above the system supply air
that the zone needs; every zone of the series is held by its reheat coil,
since the supply air at the supply-air setpoint is colder than each zone
needs, in the cooling cases too.
11.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
SIMsara has no dedicated constant-volume reheat terminal; at a minimum flow
fraction of 1 the variable-air-volume terminal is a constant-volume
terminal with reheat, as 11.2.3.1.3 e describes.
NOTE 12 - Two-Zone Flows from the Table 11-18 Zone Fractions (Section
11.2.3.1.2)
-------------------------------------------------------------------------------
12.1 Describe the Effect Being Simulated:
System, zone supply, exhaust, outdoor-air and return mass flows, and the
fan heat.
12.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.3.1.1.1-11.2.3.1.1.2 and 11.2.3.1.2.1-11.2.3.1.2.5, Table 11-18 and
its notes.
12.3 Equivalent Input(s) Used:
The system supply mass flow is 0.61353 m3/s divided by the specific volume
at the supply-fan inlet (the cooling-coil outlet). Each zone's supply mass
flow is its Table 11-18 fraction of it (0.4615 and 0.5385, the nominal zone
volumes over the system volume, notes d and e), entered as its terminal's
maximum over the standard density; the loop, supply fan, return fan and
cooling-coil design flows are their sum. Each zone's exhaust is its
specified volume (0.09439 and 0.14158 m3/s) divided by the specific volume
of that zone's air, and the outdoor-air minimum is the sum of the two
exhaust mass flows, so the return fan carries the supply less both
exhausts. The fan pressure inputs follow notes 4 and 7. The conversion is
repeated with each zone's thermostat adjustment (note 8) until every input
changes by less than 1e-7 relative and both zones are within 1e-5 K of
their specified temperatures (4 runs); the arithmetic of each step is
archived with the results.
12.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
11.2.3.1.2.2 defines each zone's supply mass flow by its nominal volume at
the supply-fan inlet state, and Table 11-18 gives it as a fraction of the
system supply mass flow; 11.2.3.1.2.3-11.2.3.1.2.5 define the exhaust at
the zone air, the return at the return fan inlet, and the outdoor air as
the sum of the zone exhaust mass flows.
NOTE 13 - Chilled-Water Plant and Cooling-Coil Water Flow of the Two-Zone Cases
(Section 11.2.3.1.3 b and f, and 11.2.4.1.4)
-------------------------------------------------------------------------------
13.1 Describe the Effect Being Simulated:
None on the loads; the cooling coil holds its setpoint in every case.
13.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.3.1.3 b, d and f, and 11.2.4.1.4.
13.3 Equivalent Input(s) Used:
The air-cooled chiller of the chilled-water loop has a reference capacity
of 40 kW, above every cooling-coil load of the series (at most 20.77 kW, in
AE326; at most 13.31 kW in the variable-air-volume cases), and the cooling
coil holds the supply-air setpoint in every case. The coil's design water
flow and its controller's maximum water flow are the single-zone values
scaled with the supply volume (Block B note 1); the variable-air-volume
cases use the same plant and coil.
13.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
11.2.3.1.3 b asks for coil capacities at least equal to the coil loads.
With a smaller chiller the chilled water would leave warm at the largest
load and the coil could fall short of the supply-air setpoint.
NOTE 14 - Economizer Minimum Limit at ODBecono,min, Constant-Volume Cases
(Section 11.2.3.3.1.1.1 and 11.2.3.3.2.1.1)
-------------------------------------------------------------------------------
14.1 Describe the Effect Being Simulated:
None in the reported hour; the limit decides only at outdoor states far
from the cases'.
14.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.3.3.1.1.1 and 11.2.3.3.2.1.1.
14.3 Equivalent Input(s) Used:
The economizer's minimum limit dry bulb is ODBecono,min: the outdoor dry
bulb at which the minimum outdoor air (the sum of the two exhaust mass
flows) gives a mixed-air temperature equal to the supply-air setpoint less
the supply fan's temperature rise, with the coils off and each zone at its
setpoint. It is computed from the case's loads, flows and fan heat with the
program's own psychrometric relations: the supply fan's whole power to the
air, each zone's supply its Table 11-18 fraction, each zone's latent gain
as moisture at its temperature, the zone returns mixed by mass, the return
fan's power to the return air, and the mixer conserving dry air, moisture
and enthalpy. The result is -8.45 C for AE326 and -8.45 C for AE345, with
the arithmetic archived with the results. As in note 9 the outdoor humidity
ratio is the case's, limited to saturation at that dry bulb; both cases'
dew points lie above the limit, so their outdoor air is saturated there. No
state of either calculation is supersaturated. The program keeps the
economizer off below the limit.
14.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The specification sets the economizer off at or below ODBecono,min and
defines it by the mixed-air temperature at minimum outdoor air; at a dry
bulb below the case's dew point the case's own humidity ratio is not a
physical outdoor state, so the saturation limit is used. The program's
limit is a dry-bulb input, and both cases run far above it.
NOTE 15 - Variable-Air-Volume Terminal Reheat System as a Two-Zone Air Loop
(Section 11.2.4.1, 11.2.4.1.1 and Figure 11-5)
-------------------------------------------------------------------------------
15.1 Describe the Effect Being Simulated:
System configuration; none on the specified loads.
15.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.4.1, 11.2.4.1.1.1-11.2.4.1.1.3, 11.2.4.1.4 and Figure 11-5.
15.3 Equivalent Input(s) Used:
The air loop of note 10 with a variable-volume supply fan: like the return
fan of note 4, its power is its maximum-flow power times the cube of the
flow fraction, so its pressure rise varies with the square of the flow
(11.2.4.1.1.1 c); its maximum is the loop design flow, the terminals'
maxima summed (note 16), which is the design system supply (0.61353 m3/s,
at the supply-fan inlet state as each nominal zone supply is, Table 11-31
note c), and its pressure input is the specified rise (498 Pa at 0.61353
m3/s, 11.2.4.1.1.1 b and Table 11-31 note a) at that maximum in the units
of note 7, so at the steady supply it draws exactly V_sup x P(V_sup) / 0.7
(21.1 to 164.0 W across the cases), all of it to the air. The return fan,
preheat coil, cooling coil and setpoints are those of the constant-volume
cases (notes 4 and 10), each zone's terminal the variable-air-volume
terminal of note 16.
15.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The same components in the same order as Figure 11-5; the supply and return
fans modulate with the flow the terminals set (11.2.4.1.1.1 d and
11.2.4.1.1.2 d).
NOTE 16 - Variable-Air-Volume Terminals with the Zone Exhaust as Their Minimum
Flow (Section 11.2.4.1.2.2 and 11.2.4.1.3)
-------------------------------------------------------------------------------
16.1 Describe the Effect Being Simulated:
None; each terminal delivers the specified flow.
16.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.4.1.2.2 and 11.2.4.1.3 a-f, Table 11-31 notes c and d.
16.3 Equivalent Input(s) Used:
Each zone's terminal is the program's variable-air-volume terminal with an
electric reheat coil, a fixed minimum flow and normal damper action. Its
minimum flow input is the zone exhaust fan's flow input, the zone's exhaust
mass flow over the standard density (note 17), so the terminal's minimum
mass flow is the exhaust mass flow; the flow conversion keeps both at the
zone's exhaust as the zone state changes. Its maximum is the zone's nominal
supply volume at the supply-fan inlet state. Above the minimum the damper
opens until the supply air at the supply-air setpoint meets the zone's
sensible load (AE403 to AE445, both zones); at the minimum the reheat coil
heats the supply air to the temperature the zone needs (AE401, both zones),
with no limit on the reheat coil's leaving-air temperature (AE401's zone 1
needs 46.9 C).
16.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
11.2.4.1.3 c and d set each terminal's minimum to its zone's exhaust mass
flow, which varies with the zone state; the program takes a volume at the
standard density, so the volume is converted with the run's own zone state,
as for the exhaust itself. Table 11-31 note c permits any maximum that
meets the zone loads, and 11.2.4.1.3 b asks for a reheat capacity at least
the load.
NOTE 17 - Two-Zone Variable-Air-Volume Flows (Section 11.2.4.1.2)
-------------------------------------------------------------------------------
17.1 Describe the Effect Being Simulated:
Terminal, exhaust, outdoor-air and return mass flows, and the fan heat.
17.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.4.1.1.1-11.2.4.1.1.2, 11.2.4.1.2.1-11.2.4.1.2.5 and Table 11-31 with
its notes.
17.3 Equivalent Input(s) Used:
Each zone's terminal maximum is its nominal supply volume divided by the
specific volume at the supply-fan inlet (the cooling-coil outlet), over the
standard density. Each zone's exhaust is its specified volume (0.09439 and
0.14158 m3/s) divided by the specific volume of that zone's air, entered
over the standard density as the exhaust fan's flow and the terminal's
minimum (note 16), and the outdoor-air minimum is the sum of the two
exhaust mass flows. The supply is what the terminals deliver, and the
return fan carries it less both exhausts, nothing when both terminals sit
at their minimum (AE401). The fan pressure inputs follow notes 4 and 15,
the air loop's design supply note 18. The conversion is repeated with each
zone's thermostat adjustment (note 8) until every input changes by less
than 1e-7 relative and both zones are within 1e-5 K of their specified
temperatures (4 to 5 runs); the arithmetic of each step is archived with
the results.
17.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
11.2.4.1.2 and 11.2.4.1.3 define the zone supply by the terminals, the
exhaust at the zone air, the return at the return fan inlet and the outdoor
air as the sum of the zone exhaust mass flows; Table 11-31 note c defines
the nominal zone supply at the supply-fan inlet state.
NOTE 18 - Air-Loop Design Supply Flow at the Steady Supply Flow (Section
11.2.4.1.1.1 b and c, 11.2.4.1.2.1 and Table 11-31)
-------------------------------------------------------------------------------
18.1 Describe the Effect Being Simulated:
The supply-air state the zones receive in AE403, AE405 and AE445, and with
it their zone air and return humidity ratios: the program's zone supply air
in these cases depends on this input, which the specification does not set.
As used, the zone supply air is 0.039 g/kg moister than the supply-fan
outlet in AE445 and 0.0018 g/kg in AE403 and AE405, and at most 0.0055 K
warmer in any case. With the input at the design system supply flow, AE403
and AE405 would be about 0.07 g/kg off (their zone air and return humidity
ratios up to about 0.085 g/kg above the quasi-analytical solution) and
AE445 not at all; 5 percent above the steady flow, AE403 and AE405 would be
about 0.043 g/kg off and AE445 not at all.
18.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.4.1.1.1 b and c, 11.2.4.1.2.1 and Table 11-31 notes a and c.
18.3 Equivalent Input(s) Used:
The air system's design supply flow, a program input distinct from the
specified design system supply, is set 0.1 percent above the steady supply
of the case's previous conversion run, and the outdoor-air maximum to the
same flow. The specified design system supply is applied where the
specification uses it, as both fans' maximum and the flow at which their
pressure rises are entered (note 15). The program starts each time step's
HVAC iteration at its design supply flow input, which also caps the supply
flow, and it re-simulates the zone equipment only while the supply-air
state it hands to the zones changes by more than its loop convergence
tolerances (0.01 kg/s, 0.0001 kg/kg, 0.01 K, 260 J/kg and 10 W), so the
zones can keep the supply air of an earlier iteration, and the starting
flow decides in which cases they do. No starting flow gives every case the
supply-fan outlet air: at the design system supply (up to about 2.7 times a
case's steady flow) AE403 and AE405 are 0.07 g/kg off, 5 percent above the
steady flow 0.043 g/kg, 1 percent above it 0.017 g/kg with AE445 at 0.023
g/kg, and at the steady flow itself AE445 stays 0.040 g/kg off while the
supply reaches the design supply input in AE403 and AE405. Every one of
these differences is within the program's 0.0001 kg/kg tolerance.
18.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The specification defines the system supply by the terminals' flows
(11.2.4.1.2.1) and the design system supply as the basis of the supply
fan's pressure rise (Table 11-31 note a, 11.2.4.1.1.1 b and c), and both
are used that way; the program's iteration starting flow has no specified
value. Starting at the steady flow makes the first iteration's outdoor-air
fraction and fan heat the steady ones, and the margin keeps the design
supply input above the flow the terminals ask for. The remaining
differences come from the program's loop convergence tolerances, not from a
case input; the six example-range flags they cause (the AE403 and AE445
zone supply air) are reported in Block G.
NOTE 19 - Economizer Minimum Limit at ODBecono,min, Variable-Air-Volume Cases
(Section 11.2.4.3.1.1 and 11.2.4.3.2.1 (11.2.3.3.1.1.1 and
11.2.3.3.2.1.1))
-------------------------------------------------------------------------------
19.1 Describe the Effect Being Simulated:
None in the reported hour; the limit decides only at outdoor states far
from the cases'.
19.2 Section(s) of the Standard where Relevant Inputs are Specified:
11.2.3.3.1.1.1, 11.2.3.3.2.1.1, 11.2.4.3.1.1 and 11.2.4.3.2.1.
19.3 Equivalent Input(s) Used:
As note 14 on Figure 11-5: the outdoor dry bulb at which the minimum
outdoor air gives a mixed-air temperature equal to the supply-air setpoint
less the supply fan's temperature rise, with the coils off and each zone at
its setpoint, now with each terminal at the flow its zone needs (at least
its exhaust mass flow) and the supply fan's power at that supply's volume.
The result is 10.35 C for AE426 and 10.34 C for AE445, with the arithmetic
archived with the results. The outdoor humidity ratio is the case's,
limited to saturation at that dry bulb (AE426's dew point lies above the
limit, AE445's below it). No state of either calculation is supersaturated.
19.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The specification applies the constant-volume economizer controls to the
variable-air-volume system (11.2.4.3.1.1 and 11.2.4.3.2.1), whose supply
fan keeps modulating with the zone loads; the program's limit is a dry-bulb
input, and both cases run far above it.DUse of non-specified inputs
* Alternative constant exterior surface coefficients in Sections 7.2.1.9.3, 7.2.3.1.4.3, 7.2.3.3.2, and 9.2.1.8 * Alternative constant interior surface coefficients in Sections 7.2.1.10.3, 7.2.3.1.4.4, 7.2.3.2.2, and 9.2.1.9 * Alternative constant interior solar distribution fractions in Sections 7.2.1.12, 7.2.2.1.2.2, 7.2.2.1.6.2, 7.2.2.1.7.2, 7.2.2.2.7.4, 7.2.3.9.3, 7.2.3.10.2, and 7.2.3.12.2 * Air density given at specific altitudes for the space-cooling and space- heating equipment cases in Sections 9.2.1.4.3, 9.2.3.4.3, and 10.2.1.4.3. NONE
EOmitted test cases and resultsNone
NONE
FChanges to source code
NOTE 1 - Other Equipment Internal Gains (Section 11.2.1.1.4, 11.2.2.1.4,
11.2.3.1.4 and 11.2.4.1.5 (140-2014a 5.5.1.1.4))
-------------------------------------------------------------------------------
1.1 List the Change(s) to the Source Code:
The OtherEquipment internal-gain input is read and applied as a zone heat
gain (sensible convective, radiant and latent fractions), including a
negative design level, without adding it to the electric equipment output
or meter.
1.2 List the Test Case(s) Relevant to the Change(s) in the Source Code:
Every case of this report (the zone sensible and latent loads).
1.3 Explanation of Why the Change is Not Included in the Publicly Released
Version of the Software:
The tested build carries this change but no tagged public release
includes it yet. Remove this note when the release tag used for the
submission run (user action U4) contains it.
NOTE 2 - Zone Exhaust Fan and Return Fan (Section 11.2.1.1.1.2, 11.2.2.1.1.2,
11.2.2.1.1.3, 11.2.3.1.1.2, 11.2.3.1.1.3, 11.2.4.1.1.2 and
11.2.4.1.1.3)
-------------------------------------------------------------------------------
2.1 List the Change(s) to the Source Code:
A zone exhaust fan (Fan:ZoneExhaust) on a zone's equipment list, with the
zone air mass balance that returns the supply less the exhaust, was added;
and the program now identifies the supply and return fans of an air loop, a
fan ahead of the outdoor-air system being the return fan.
2.2 List the Test Case(s) Relevant to the Change(s) in the Source Code:
Every case of this report (the exhaust fan); AE201 to AE245, AE301 to AE345
and AE401 to AE445 (the return fan).
2.3 Explanation of Why the Change is Not Included in the Publicly Released
Version of the Software:
The tested build carries these changes but no tagged public
release includes them yet. Remove this note when the release tag used for
the submission run (user action U4) contains them.GAnomalous results
NOTE 1 - Node Specific Volume, Enthalpy and Mass Flow Just Outside the Example
Range (Section 11.3.1.3 and 11.3.2.3 (140-2014a 6.5.1.3))
-------------------------------------------------------------------------------
1.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
Detailed outputs (11.3.1.3 and 11.3.2.3) of AE101, AE103, AE104 and AE201
to AE245: the specific volume of several nodes is up to 0.12 percent above
the largest example result, the AE101 and AE201 heating-coil outlet,
cooling-coil outlet and supply enthalpies up to 0.021 percent above the
largest, and some outdoor-air, supply and return dry-air mass flows of
AE101, AE103, AE201, AE203 and AE206 up to 0.10 percent below the smallest.
Every other coil and zone load, RHcco, node dry bulb and humidity ratio is
inside the example range, or explained in note 2 or 3.
1.2 Explanation of Reason for the Anomalous Results:
The specific volume is the program's psychrometric relation v = 159.473 (1
+ 1.6078 W)(1.8 T + 492) / P (ideal gas, with the 1.8 T + 492
absolute-temperature form) at the station pressure of the weather files,
101300 Pa (1013 mbar in the TM2 files, 11.2.1.1.7 Table 11-4 note b), where
the specification's reference values use 101325 Pa and a real-gas model.
Together these make v about 0.09 percent larger. Because the supply and
exhaust mass flows are the specified volumetric flows divided by this v
(11.2.1.1.2, 11.2.2.1.2), they are about 0.09 percent smaller. The
heating-coil outlet, cooling-coil outlet and supply enthalpies of AE101 and
AE201 are within 0.08 percent of the quasi-analytical solution, which lies
0.088 to 0.097 percent above the largest example result, so SIMsara sits
between the example programs and the quasi-analytical solution. The
differences are the consistent use of the program's own psychrometrics, not
a modeling error. Every coil load is within 2 percent of the
quasi-analytical solution.
NOTE 2 - Mixed-Air and Return-Fan-Outlet Temperatures and AE203 Coil Loads at
the Edge of the Example Range (Section 11.3.2.1, 11.3.2.2 and
11.3.2.3)
-------------------------------------------------------------------------------
2.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
AE201 mixed-air and return-fan-outlet dry bulbs, AE203 and AE205 mixed-air
and heating-coil outlet dry bulbs (at most 0.003 K outside the range of the
example results), and the AE203 cooling-coil sensible and total loads (up
to 0.33 percent above the largest example result).
2.2 Explanation of Reason for the Anomalous Results:
Each of these values agrees with the quasi-analytical solution, to within
0.001 K for the temperatures and 0.04 percent for the loads, and the
quasi-analytical solution lies outside the example range by about the same
margin; the example results cluster closely in these quantities. AE203's
loads include the return fan's heat, all of it delivered to the return air
(Block C note 4). Every value is within the tolerances of the
quasi-analytical solution applied to these results (2 percent on coil
loads, 0.1 K on node temperatures).
NOTE 3 - AE245 Cooling-Coil Outlet and Supply Enthalpy Just Below the Example
Range (Section 11.3.2.3)
-------------------------------------------------------------------------------
3.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
AE245 detailed outputs: the cooling-coil outlet and supply-air enthalpies
are 0.04 and 0.03 percent below the smallest example result; their dry
bulbs and humidity ratios, and every AE245 coil load, are inside the
example range.
3.2 Explanation of Reason for the Anomalous Results:
At 100 percent outdoor air these nodes carry the outdoor humidity ratio,
which the program computes from the weather file's dry bulb, relative
humidity and station pressure. The weather file holds the relative humidity
as an integer percent (Table 11-14 note b), which puts the humidity ratio
0.2 percent below the quasi-analytical solution's, and the program's
ideal-gas enthalpy relation adds a smaller difference of the same sign. The
humidity ratio and dry bulb of both nodes are within 0.05 g/kg and 0.1 K of
the quasi-analytical solution.
NOTE 4 - Constant-Volume Cases: Node Specific Volume and Outdoor-Air Mass Flow
Just Outside the Example Range (Section 11.3.3.3)
-------------------------------------------------------------------------------
4.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
Detailed outputs (11.3.3.3) of AE301 to AE345: the specific volume of
several nodes is up to 0.13 percent above the largest example result, and
the outdoor-air dry-air mass flows of AE301, AE303 and AE305 up to 0.10
percent below the smallest.
4.2 Explanation of Reason for the Anomalous Results:
The same cause as note 1: the program's ideal-gas specific volume at the
weather files' station pressure, 101300 Pa, is about 0.09 percent larger
than the specification's reference values, and the dry-air mass flows, the
specified volumes divided by it (11.2.3.1.2), are about 0.09 percent
smaller. Each of these specific volumes is within 0.10 percent, and each of
these mass flows within 0.10 percent, of the quasi-analytical solution.
NOTE 5 - AE301 Supply-Path Humidity, Enthalpy, RHcco and Preheat-Coil Load at
the Edge of the Example Range (Section 11.3.3.2 and 11.3.3.3)
-------------------------------------------------------------------------------
5.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
AE301: the humidity ratios of the mixed air and of every node from the
preheat-coil outlet to the zone supply air (0.046 percent above the largest
example result), the mixed-air, preheat-coil outlet, cooling-coil outlet
and supply-air enthalpies (up to 0.24 percent above the largest), RHcco
(0.015 points above the largest) and the preheat-coil load (0.21 percent
below the smallest).
5.2 Explanation of Reason for the Anomalous Results:
AE301's outdoor air is nearly dry, so the humidity of the mixed and supply
air comes from the two zones' latent gains returned with the return air.
With the dry-air mass flows about 0.09 percent smaller (note 4), each
kilogram of supply air picks up about 0.09 percent more moisture: these
humidity ratios are 0.090 percent above the quasi-analytical solution, and
RHcco, at the same dry bulb, 0.015 points above it. The enthalpies are
within 0.06 percent of the quasi-analytical solution, which lies 0.14 to
0.25 percent above the largest example result, so SIMsara sits between the
example programs and the quasi-analytical solution. The preheat-coil load
is the supply mass flow times the enthalpy rise from the mixed air to the
preheat setpoint: the mass flow is about 0.09 percent smaller, and the
program's enthalpy fit (Block B note 5) uses a dry-air specific heat of
1.00484 kJ/(kg K), about 0.12 percent below the 1.006 kJ/(kg K) of the
current Handbook equation, so the load is 0.22 percent below the
quasi-analytical solution, well within the 2 percent applied to these
results.
NOTE 6 - Constant-Volume Cases: Mixed-Air, Preheat-Coil Outlet, Return-Fan
Outlet and Supply Dry Bulbs at the Edge of the Example Range (Section
11.3.3.3)
-------------------------------------------------------------------------------
6.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
The mixed-air dry bulbs of AE301, AE303 and AE306, the preheat-coil outlet
dry bulbs of AE303 and AE306 and the return-fan outlet dry bulbs of AE301
and AE306 (at most 0.0036 K outside the range of the example results), and
the AE304 supply-air dry bulb.
6.2 Explanation of Reason for the Anomalous Results:
Each of the first seven agrees with the quasi-analytical solution to within
0.0005 K, and the quasi-analytical solution lies outside the example range
by about the same margin; the example results cluster closely in these
quantities (as in note 2). The AE304 supply-air dry bulb lies 5.4e-07 K
below the supply-air setpoint (11.2.3.1.3 d), within the cooling-coil
controller tolerance of Block B note 2, which puts it just outside the
example range.
NOTE 7 - AE345 Supply, Zone and Return Enthalpies Just Below the Example Range
(Section 11.3.3.3)
-------------------------------------------------------------------------------
7.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
AE345 detailed outputs: the supply-air, zone 1, zone 2 and return-fan inlet
enthalpies are up to 0.13 percent below the smallest example result; their
dry bulbs and humidity ratios, and every AE345 coil load, are inside the
example range.
7.2 Explanation of Reason for the Anomalous Results:
As in note 3: at 100 percent outdoor air the supply air carries the outdoor
humidity ratio, which the program computes from the weather file's dry
bulb, relative humidity and station pressure. The weather file holds the
relative humidity as an integer percent (Table 11-27 note b), which puts
the outdoor humidity ratio 0.22 percent below the quasi-analytical
solution's; each zone adds its latent moisture to it, so these enthalpies
are 0.14 to 0.17 percent below the quasi-analytical solution; the program's
enthalpy fit, with its dry-air specific heat about 0.12 percent below the
current Handbook equation's (note 5), adds a difference of the same sign.
The humidity ratio and dry bulb of every AE345 node are within 0.05 g/kg
and 0.1 K of the quasi-analytical solution.
NOTE 8 - Variable-Air-Volume Cases: Node Specific Volume and Dry-Air Mass Flow
Just Outside the Example Range (Section 11.3.4.3)
-------------------------------------------------------------------------------
8.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
Detailed outputs (11.3.4.3) of AE401 to AE445: the specific volume of
several nodes is up to 0.11 percent above the largest example result, and
the dry-air mass flows of AE401's supply path and the outdoor-air mass
flows of AE403 and AE405 up to 0.10 percent below the smallest.
8.2 Explanation of Reason for the Anomalous Results:
The same cause as notes 1 and 4: the program's ideal-gas specific volume at
the weather files' station pressure, 101300 Pa, is about 0.09 percent
larger than the specification's reference values, and the dry-air mass
flows, the specified volumes divided by it (11.2.4.1.2), are about 0.09
percent smaller. Each of these specific volumes is within 0.10 percent, and
each of these mass flows within 0.10 percent, of the quasi-analytical
solution.
NOTE 9 - AE401 Preheat and Reheat Loads, RHcco and Supply-Path Humidity Just
Below the Example Range (Section 11.3.4.2 and 11.3.4.3)
-------------------------------------------------------------------------------
9.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
AE401: the preheat-coil load and both reheat-coil loads (up to 0.12 percent
below the smallest example result), RHcco (0.004 points below the smallest)
and the humidity ratios of the mixed air, the preheat-coil outlet and the
cooling-coil outlet (0.045 percent below the smallest).
9.2 Explanation of Reason for the Anomalous Results:
Both terminals sit at their minimum flow, so the system supplies only the
outdoor air that replaces the two exhausts, about 0.09 percent less dry air
than the quasi-analytical solution's (note 8). The preheat-coil load is
that mass flow times the enthalpy rise, and the program's enthalpy fit
(Block B note 5) has a dry-air specific heat about 0.12 percent below the
current Handbook equation's: the load is 0.22 percent below the
quasi-analytical solution. Each reheat coil heats the supply air at the
specific heat of the supply humidity, while the program holds the zone with
its system sensible rate, the mass flow times the specific heat at the zone
humidity times the supply-to-zone temperature difference (the zone's
reported load). A reheat load is therefore the zone load scaled by the
ratio of the two specific heats plus the supply's rise to the zone
temperature: the ratio takes 8.9 to 11.1 W off the two reheat loads, 63 to
78 percent of their gaps to the quasi-analytical solution; the rest of each
gap, at most 0.21 percent of the rise, comes from the same mass flow and
specific heat differences as the preheat load's. The reheat loads are 0.29
to 0.31 percent below the quasi-analytical solution, well within the 2
percent applied to these results. The outdoor-air node itself, at 100.00
percent relative humidity from the weather file's dry bulb, relative
humidity and station pressure, is inside the example range, 0.031 percent
above the quasi-analytical solution. With no return air the mixer finds
that air at or above saturation by the program's saturation-temperature fit
at its enthalpy and pressure, and moves it to that saturation temperature
at constant enthalpy, 0.00032 K warmer and 0.050 percent drier. The
mixed-air, preheat-coil outlet and cooling-coil outlet humidity ratios are
therefore 0.020 percent below the quasi-analytical solution, which lies
below the example range too, and RHcco, at the same dry bulb, 0.003 points
below it.
NOTE 10 - Variable-Air-Volume Cases: Supply-Air Dry Bulbs and Mixed-Air and
Supply Enthalpies at the Edge of the Example Range (Section 11.3.4.3)
-------------------------------------------------------------------------------
10.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
The supply-air dry bulbs of AE405, AE426 and AE445, the AE406 mixed-air and
preheat-coil outlet enthalpies, and the AE445 supply-air enthalpy.
10.2 Explanation of Reason for the Anomalous Results:
The three supply-air dry bulbs lie at most 4.6e-07 K below the supply-air
setpoint (11.2.3.1.3 d, which 11.2.4.1.4 applies), within the cooling-coil
controller tolerance of Block B note 2, which puts them just outside the
example range. The AE406 enthalpies are within 0.013 percent of the
quasi-analytical solution, which lies outside the example range too. As in
note 7: at 100 percent outdoor air the AE445 supply air carries the outdoor
humidity ratio from the weather file's integer relative humidity (Table
11-36 note b), 0.22 percent below the quasi-analytical solution's, and its
enthalpy is 0.17 percent below the quasi-analytical solution.
NOTE 11 - AE403 and AE445 Zone Supply-Air Humidity and Enthalpy Just Above the
Example Range (Section 11.3.4.3)
-------------------------------------------------------------------------------
11.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
The zone 1 and zone 2 supply-air humidity ratios of AE403 (0.027 percent
above the largest example result) and AE445 (0.21 percent above), and the
AE445 zone supply-air enthalpies (0.059 percent above).
11.2 Explanation of Reason for the Anomalous Results:
All six come from the zone supply air lagging the supply-fan outlet within
the program's loop convergence tolerances (Block C note 18): the zones
receive the supply air of an earlier HVAC iteration of the time step, and
which cases do depends on the air system's design supply flow input, which
the specification does not set. The supply-fan outlet air's humidity ratio
lies inside the example range of each of these humidity cells, and at that
humidity the AE445 zone supply enthalpies would lie inside theirs. In AE403
the zone supply air is 0.0018 g/kg moister than the supply-fan outlet, just
enough to lift both zone supply humidity ratios above the range; they
remain 0.026 percent below the quasi-analytical solution, which lies above
the example range. In AE445 the zone supply air is 0.039 g/kg moister and
0.0054 K warmer than the supply-fan outlet, and the moisture alone lifts
its enthalpy above the range; with the design supply input 1 percent or
more above the steady flow these four cells fall inside the example range,
while AE403 and AE405 then carry a larger lag (Block C note 18). The zone
supply humidity ratio and dry bulb are within 0.05 g/kg and 0.1 K of the
quasi-analytical solution in every case, and every AE445 coil load is
inside the example range.Rendered from S140outNotes-SIMsara-AE.txt, the modeler report in the form Standard 140 prescribes. The template's own instructions are left out here.