Section 11 · Air-side equipment

Case AE201

Values compared
47
Outside example range
18
Run time
0.05 s
Input file
AE201.toml, 31.4 kB

Against the example programs

Each reported quantity next to the spread of the simulation programs published with the standard.

Position in the example range
Example rangeSIMsara
Sensible Heating Load (QZHsensible) (kWh/h)AE SZ coil and zone loads
2.9302.931
In range
Sensible Heating Load (QZHsensible) (kWh/h), AE SZ coil and zone loads: SIMsara 2.931 · range 2.930 to 2.931
Latent Load (QZlatent) (kWh/h)AE SZ coil and zone loads
0.58610.5900
In range
Latent Load (QZlatent) (kWh/h), AE SZ coil and zone loads: SIMsara 0.5861 · range 0.5861 to 0.5900
Coil Load (QH) (kWh/h)AE SZ coil and zone loads
8.3028.709
In range
Coil Load (QH) (kWh/h), AE SZ coil and zone loads: SIMsara 8.344 · range 8.302 to 8.709
Loads Sensible (QCsensible) (kWh/h)AE SZ coil and zone loads
08.05e-8
In range
Loads Sensible (QCsensible) (kWh/h), AE SZ coil and zone loads: SIMsara 0 · range 0 to 8.05e-8
Latent (QClatent) (kWh/h)AE SZ coil and zone loads
01.84e-5
In range
Latent (QClatent) (kWh/h), AE SZ coil and zone loads: SIMsara 0 · range 0 to 1.84e-5
Total (QCtotal) (kWh/h)AE SZ coil and zone loads
01.85e-5
In range
Total (QCtotal) (kWh/h), AE SZ coil and zone loads: SIMsara 0 · range 0 to 1.85e-5
Outlet RH (RHcco) (%)AE SZ coil and zone loads
6.3536.871
In range
Outlet RH (RHcco) (%), AE SZ coil and zone loads: SIMsara 6.386 · range 6.353 to 6.871
DRY BULB TEMPERATURE (°C) · Mixed Air (ma)AE SZ node states
4.1854.648
Below range
DRY BULB TEMPERATURE (°C) · Mixed Air (ma), AE SZ node states: SIMsara 4.183 · range 4.185 to 4.648
DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)AE SZ node states
28.66729.326
In range
DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco), AE SZ node states: SIMsara 29.324 · range 28.667 to 29.326
DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)AE SZ node states
28.66729.326
In range
DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco), AE SZ node states: SIMsara 29.324 · range 28.667 to 29.326
DRY BULB TEMPERATURE (°C) · Supply Air (sa)AE SZ node states
29.57629.933
In range
DRY BULB TEMPERATURE (°C) · Supply Air (sa), AE SZ node states: SIMsara 29.930 · range 29.576 to 29.933
DRY BULB TEMPERATURE (°C) · Zone Air (z1)AE SZ node states
21.09921.119
In range
DRY BULB TEMPERATURE (°C) · Zone Air (z1), AE SZ node states: SIMsara 21.111 · range 21.099 to 21.119
DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)AE SZ node states
21.09921.119
In range
DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi), AE SZ node states: SIMsara 21.111 · range 21.099 to 21.119
DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)AE SZ node states
21.38621.408
Below range
DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo), AE SZ node states: SIMsara 21.384 · range 21.386 to 21.408
HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)AE SZ node states
2.59e-43.44e-4
In range
HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa), AE SZ node states: SIMsara 2.59e-4 · range 2.59e-4 to 3.44e-4
HUMIDITY RATIO (G/GDA) · Mixed Air (ma)AE SZ node states
0.0015950.001698
In range
HUMIDITY RATIO (G/GDA) · Mixed Air (ma), AE SZ node states: SIMsara 0.001606 · range 0.001595 to 0.001698
HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)AE SZ node states
0.0015950.001698
In range
HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco), AE SZ node states: SIMsara 0.001606 · range 0.001595 to 0.001698
HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)AE SZ node states
0.0015950.001698
In range
HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco), AE SZ node states: SIMsara 0.001606 · range 0.001595 to 0.001698
HUMIDITY RATIO (G/GDA) · Supply Air (sa)AE SZ node states
0.0015950.001698
In range
HUMIDITY RATIO (G/GDA) · Supply Air (sa), AE SZ node states: SIMsara 0.001606 · range 0.001595 to 0.001698
HUMIDITY RATIO (G/GDA) · Zone Air (z1)AE SZ node states
0.0022000.002374
In range
HUMIDITY RATIO (G/GDA) · Zone Air (z1), AE SZ node states: SIMsara 0.002306 · range 0.002200 to 0.002374
HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)AE SZ node states
0.0022000.002374
In range
HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi), AE SZ node states: SIMsara 0.002306 · range 0.002200 to 0.002374
HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)AE SZ node states
0.0022000.002374
In range
HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo), AE SZ node states: SIMsara 0.002306 · range 0.002200 to 0.002374
SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)AE SZ node states
691.84833.33
In range
SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa), AE SZ node states: SIMsara 692.65 · range 691.84 to 833.33
SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)AE SZ node states
787.61833.33
In range
SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma), AE SZ node states: SIMsara 788.42 · range 787.61 to 833.33
TableQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE SZ coil and zone loadsSensible Heating Load (QZHsensible) (kWh/h)2.9312.9302.9312.9312.931In range
AE SZ coil and zone loadsSensible Cooling Load (QZClatent) (kWh/h)00000In range
AE SZ coil and zone loadsLatent Load (QZlatent) (kWh/h)0.58610.58610.59000.58670.5861In range
AE SZ coil and zone loadsCoil Load (QH) (kWh/h)8.3448.3028.7098.4198.360In range
AE SZ coil and zone loadsLoads Sensible (QCsensible) (kWh/h)008.05e-81.15e-80In range
AE SZ coil and zone loadsLatent (QClatent) (kWh/h)001.84e-52.63e-60In range
AE SZ coil and zone loadsTotal (QCtotal) (kWh/h)001.85e-52.64e-60In range
AE SZ coil and zone loadsOutlet RH (RHcco) (%)6.3866.3536.8716.5816.385In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)−29.000−29−29−29−29In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Mixed Air (ma)4.1834.1854.6484.4934.183Below range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)29.32428.66729.32629.06729.316In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)29.32428.66729.32629.06729.316In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Supply Air (sa)29.93029.57629.93329.72729.922In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Zone Air (z1)21.11121.09921.11921.11121.111In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)21.11121.09921.11921.11121.111In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)21.38421.38621.40821.39921.383Below range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)2.59e-42.59e-43.44e-42.78e-42.59e-4In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0016060.0015950.0016980.0016320.001604In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.0016060.0015950.0016980.0016320.001604In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0016060.0015950.0016980.0016320.001604In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0016060.0015950.0016980.0016320.001604In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Zone Air (z1)0.0023060.0022000.0023740.0023090.002304In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0023060.0022000.0023740.0023090.002304In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0023060.0022000.0023740.0023090.002304In range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)692.65691.84833.33776.09691.93In range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)788.42787.61833.33814.39787.67In range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)859.85830.35859.03842.94859.06Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)859.85830.35859.03842.94859.06Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Supply Air (sa)861.57830.35860.69842.78860.78Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Zone Air (z1)837.45830.35836.69833.99836.69Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)837.45830.35836.69833.99836.69Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)838.23830.35837.42833.93837.46Above range
AE SZ node statesENTHALPY (J/GDA) · Location Outdoor Air (oa)−28.507−28.540−28.330−28.472−28.543In range
AE SZ node statesENTHALPY (J/GDA) · Mixed Air (ma)8.2318.2128.8928.6428.232In range
AE SZ node statesENTHALPY (J/GDA) · Heat Coil Outlet (hco)33.56833.30933.56233.46233.594Above range
AE SZ node statesENTHALPY (J/GDA) · Cool Coil Outlet (cco)33.56833.30933.56233.46233.594Above range
AE SZ node statesENTHALPY (J/GDA) · Supply Air (sa)34.18033.90034.17334.05834.206Above range
AE SZ node statesENTHALPY (J/GDA) · Zone Air (z1)27.07127.03527.26627.12327.093In range
AE SZ node statesENTHALPY (J/GDA) · Return Fan Inlet (rfi)27.07127.03527.26627.12327.093In range
AE SZ node statesENTHALPY (J/GDA) · Return Fan Outlet (rfo)27.34627.32727.56427.41127.367In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.11270.11280.11970.11410.1128Below range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.32930.32960.35910.33980.3296Below range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.32930.32960.35910.33980.3296Below range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.32930.32960.35910.33980.3296Below range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Supply Air (sa)0.32930.32960.35910.33980.3296Below range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE SZ node statesMASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.21660.21680.23940.22570.2168Below range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.21660.21680.23940.22570.2168Below range

Reported outputs

The values the engine wrote for this case, before they are placed in the output template.

OutputValue
Loads (kWh/h) · qZHsensible2.931
Loads (kWh/h) · qZCsensible0
Loads (kWh/h) · qZlatent0.5861
Loads (kWh/h) · qH8.344
Loads (kWh/h) · qCsensible0
Loads (kWh/h) · qClatent0
Loads (kWh/h) · qCtotal0
Loads (kWh/h) · rHcco6.386
Nodes · oa · tdb (°C)−29.000
Nodes · oa · w (g/g)2.59e-4
Nodes · oa · v (L/kg)692.65
Nodes · oa · h (J/g)−28.507
Nodes · oa · m (kg/s)0.1127
Nodes · oa · rh (%)100
Nodes · ma · tdb (°C)4.183
Nodes · ma · w (g/g)0.001606
Nodes · ma · v (L/kg)788.42
Nodes · ma · h (J/g)8.231
Nodes · ma · m (kg/s)0.3293
Nodes · ma · rh (%)31.652
Nodes · hco · tdb (°C)29.324
Nodes · hco · w (g/g)0.001606
Nodes · hco · v (L/kg)859.85
Nodes · hco · h (J/g)33.568
Nodes · hco · m (kg/s)0.3293
Nodes · hco · rh (%)6.386
Nodes · cco · tdb (°C)29.324
Nodes · cco · w (g/g)0.001606
Nodes · cco · v (L/kg)859.85
Nodes · cco · h (J/g)33.568
Nodes · cco · m (kg/s)0.3293
Nodes · cco · rh (%)6.386
Nodes · sa · tdb (°C)29.930
Nodes · sa · w (g/g)0.001606
Nodes · sa · v (L/kg)861.57
Nodes · sa · h (J/g)34.180
Nodes · sa · m (kg/s)0.3293
Nodes · sa · rh (%)6.167
Nodes · z1 · tdb (°C)21.111
Nodes · z1 · w (g/g)0.002306
Nodes · z1 · v (L/kg)837.45
Nodes · z1 · h (J/g)27.071
Nodes · z1 · rh (%)14.940
Nodes · rfi · tdb (°C)21.111
Nodes · rfi · w (g/g)0.002306
Nodes · rfi · v (L/kg)837.45
Nodes · rfi · h (J/g)27.071
Nodes · rfi · m (kg/s)0.2166
Nodes · rfi · rh (%)14.940
Nodes · rfo · tdb (°C)21.384
Nodes · rfo · w (g/g)0.002306
Nodes · rfo · v (L/kg)838.23
Nodes · rfo · h (J/g)27.346
Nodes · rfo · m (kg/s)0.2166
Nodes · rfo · rh (%)14.692
Pressure pa101,300
Fans · supply (W)201.46
Fans · return (W)59.586
Fans · exhaust (kg/s)0.1127
Fan power (W)201.46
Zone tdb (°C)21.111
Economizer status0
Oa fraction0.3422
Program outputs · cooling coil total (W)0
Program outputs · cooling coil sensible (W)0
Program outputs · heating coil (W)8,344.3
Program outputs · condensate · kg (s)0
Program outputs · condensate · temp (°C)29.324
Program outputs · condensate · h j kg122,572
Program outputs · condensate · w0
Program outputs · condensate · entering dew point (°C)−9.961
Program outputs · condensate · sensible (W)0
Balance · residual (W) · return fan−8.10e-13
Balance · residual (W) · mixer−1.36e-12
Balance · residual (W) · heating coil0
Balance · residual (W) · cooling coil0
Balance · residual (W) · supply fan1.05e-12
Balance · residual (W) · zone−3.783
Balance · residual (W) · system−3.783
Balance · relative · return fan9.71e-17
Balance · relative · mixer1.63e-16
Balance · relative · heating coil0
Balance · relative · cooling coil0
Balance · relative · supply fan1.26e-16
Balance · relative · zone4.53e-4
Balance · relative · system4.53e-4
Balance · max relative4.53e-4
Balance · reference (W)8,344.3
Cycling · steps6
Flows · supply std (m³/s)0.2735
Flows · exhaust std (m³/s)0.09359
Flows · oa std (m³/s)0.09359
Flows · supply fan dp pa515.69
Flows · return fan max std (m³/s)0.2735
Flows · return fan dp pa536.00
Flows · setpoint offset k−0.008285
Flow iterations5
Flow record · convergedtrue
Flow record · iterations5
Flow record · relative change2.88e-8
Flow record · zone tdb error k−4.47e-9

Input file

sha256 87cf2ca55b3f8fd68a6c4bcc2d62bb946206e8172952b6500aabe250a171535d

AE201.tomlDownload
[version]
version_identifier = "26.1"

[simulation-control]
do_zone_sizing_calculation = "No"
do_system_sizing_calculation = "No"
do_plant_sizing_calculation = "No"
run_simulation_for_sizing_periods = "No"
run_simulation_for_weather_file_run_periods = "Yes"
do_hvac_sizing_simulation_for_sizing_periods = "No"
maximum_number_of_hvac_sizing_simulation_passes = 1

[building."ASHRAE 140 AE201"]
north_axis = 0.0
terrain = "Suburbs"
loads_convergence_tolerance_value = 0.04
temperature_convergence_tolerance_value = 0.4
solar_distribution = "FullExterior"
maximum_number_of_warmup_days = 25
minimum_number_of_warmup_days = 6

[building.surface.detailed."South Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."East Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."North Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."West Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."Floor"]
surface_type = "Floor"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
]

[building.surface.detailed."Roof"]
surface_type = "Roof"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[timestep]
number_of_timesteps_per_hour = 6

[heat-balance-algorithm]
algorithm = "ConductionTransferFunction"
surface_temperature_upper_limit = 200.0

[surface.convection.algorithm.inside]
algorithm = "TARP"

[surface.convection.algorithm.outside]
algorithm = "DOE-2"

[global-geometry-rules]
starting_vertex_position = "UpperLeftCorner"
vertex_entry_direction = "Counterclockwise"
coordinate_system = "Relative"

[site.location."AE artificial site"]
latitude = 25.8
longitude = -80.3
time_zone = -5.0
elevation = 0.0

[schedule-type-limits."Any Number"]

[schedule-type-limits."Fraction"]
lower_limit_value = 0.0
upper_limit_value = 1.0
numeric_type = "Continuous"

[schedule-type-limits."Temperature"]
lower_limit_value = -60.0
upper_limit_value = 200.0
numeric_type = "Continuous"
unit_type = "Temperature"

[schedule-type-limits."Control Type"]
lower_limit_value = 0.0
upper_limit_value = 4.0
numeric_type = "Discrete"

[schedule.compact."Always On"]
schedule_type_limits_name = "Fraction"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 1.0 },
]

[schedule.compact."Heating Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 21.10271510316629 },
]

[schedule.compact."Cooling Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 26.10271510316629 },
]

[schedule.compact."Dual Setpoint Control"]
schedule_type_limits_name = "Control Type"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 4 },
]

[schedule.compact."CHW Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 6.67 },
]

[material."Gypsum Board 13mm"]
roughness = "Smooth"
thickness = 0.0127
conductivity = 0.16
density = 800.0
specific_heat = 1090.0
thermal_absorptance = 0.9
solar_absorptance = 0.5
visible_absorptance = 0.5

[construction."Adiabatic Panel"]
outside_layer = "Gypsum Board 13mm"

[zone."Zone One"]
direction_of_relative_north = 0.0
x_origin = 0.0
y_origin = 0.0
z_origin = 0.0
type = 1
multiplier = 1
ceiling_height = "Autocalculate"
volume = "Autocalculate"
floor_area = "Autocalculate"
zone_inside_convection_algorithm = "TARP"
zone_outside_convection_algorithm = "DOE-2"
part_of_total_floor_area = "Yes"

[zone.control.thermostat."Zone One Thermostat"]
zone_or_zonelist_name = "Zone One"
control_type_schedule_name = "Dual Setpoint Control"
control_1_object_type = "ThermostatSetpoint:DualSetpoint"
control_1_name = "Zone One Dual Setpoint"

[zone.hvac.air-distribution-unit."Zone One ADU"]
air_distribution_unit_outlet_node_name = "Zone One Supply Inlet"
air_terminal_object_type = "AirTerminal:SingleDuct:ConstantVolume:NoReheat"
air_terminal_name = "Zone One Terminal"
nominal_upstream_leakage_fraction = 0.0
constant_downstream_leakage_fraction = 0.0

[zone.hvac.equipment-list."Zone One Equipment List"]
load_distribution_scheme = "SequentialLoad"
equipment = [
  { zone_equipment_object_type = "ZoneHVAC:AirDistributionUnit", zone_equipment_name = "Zone One ADU", zone_equipment_cooling_sequence = 1, zone_equipment_heating_or_no_load_sequence = 1 },
  { zone_equipment_object_type = "Fan:ZoneExhaust", zone_equipment_name = "Zone Exhaust Fan", zone_equipment_cooling_sequence = 2, zone_equipment_heating_or_no_load_sequence = 2 },
]

[[zone.hvac.equipment-connections]]
zone_name = "Zone One"
zone_conditioning_equipment_list_name = "Zone One Equipment List"
zone_air_inlet_node_or_nodelist_name = "Zone One Supply Inlet"
zone_air_node_name = "Zone One Air Node"
zone_return_air_node_or_nodelist_name = "Zone One Return Outlet"
zone_air_exhaust_node_or_nodelist_name = "Zone One Exhaust Node"

[other-equipment."Zone Sensible Heating Load"]
fuel_type = "None"
zone_or_zonelist_or_space_or_spacelist_name = "Zone One"
schedule_name = "Always On"
design_level_calculation_method = "EquipmentLevel"
design_level = -2931.0
fraction_latent = 0.0
fraction_radiant = 0.0
fraction_lost = 0.0

[other-equipment."Zone Latent Load"]
fuel_type = "None"
zone_or_zonelist_or_space_or_spacelist_name = "Zone One"
schedule_name = "Always On"
design_level_calculation_method = "EquipmentLevel"
design_level = 586.1
fraction_latent = 1.0
fraction_radiant = 0.0
fraction_lost = 0.0

[thermostat.setpoint.dual-setpoint."Zone One Dual Setpoint"]
heating_setpoint_temperature_schedule_name = "Heating Setpoint"
cooling_setpoint_temperature_schedule_name = "Cooling Setpoint"

[air-loop-hvac."SZ Air Loop"]
controller_list_name = "SZ Controllers"
availability_manager_list_name = "SZ Availability"
design_supply_air_flow_rate = 0.2734570149252094
branch_list_name = "SZ Branches"
supply_side_inlet_node_name = "Air Loop Inlet Node"
demand_side_outlet_node_name = "Zone Equipment Outlet Node"
demand_side_inlet_node_names = "Zone Equipment Inlet Node"
supply_side_outlet_node_names = "Supply Outlet Node"
design_return_air_flow_fraction_of_supply_air_flow = 1.0

[branch-list."SZ Branches"]
branches = [
  { branch_name = "SZ Branch" },
]

[branch-list."CHW Supply Branches"]
branches = [
  { branch_name = "CHW Supply Inlet Branch" },
  { branch_name = "CHW Chiller Branch" },
  { branch_name = "CHW Supply Bypass Branch" },
  { branch_name = "CHW Supply Outlet Branch" },
]

[branch-list."CHW Demand Branches"]
branches = [
  { branch_name = "CHW Demand Inlet Branch" },
  { branch_name = "CHW Cooling Coil Branch" },
  { branch_name = "CHW Demand Bypass Branch" },
  { branch_name = "CHW Demand Outlet Branch" },
]

[branch."SZ Branch"]
components = [
  { component_object_type = "Fan:VariableVolume", component_name = "SZ Return Fan", component_inlet_node_name = "Air Loop Inlet Node", component_outlet_node_name = "Return Fan Outlet Node" },
  { component_object_type = "AirLoopHVAC:OutdoorAirSystem", component_name = "SZ OA System", component_inlet_node_name = "Return Fan Outlet Node", component_outlet_node_name = "Mixed Air Node" },
  { component_object_type = "Coil:Heating:Electric", component_name = "SZ Heating Coil", component_inlet_node_name = "Mixed Air Node", component_outlet_node_name = "Heating Coil Outlet Node" },
  { component_object_type = "Coil:Cooling:Water", component_name = "SZ Cooling Coil", component_inlet_node_name = "Heating Coil Outlet Node", component_outlet_node_name = "Cooling Coil Outlet Node" },
  { component_object_type = "Fan:ConstantVolume", component_name = "SZ Supply Fan", component_inlet_node_name = "Cooling Coil Outlet Node", component_outlet_node_name = "Supply Outlet Node" },
]

[branch."CHW Supply Inlet Branch"]
components = [
  { component_object_type = "Pump:VariableSpeed", component_name = "CHW Pump", component_inlet_node_name = "CHW Supply Inlet Node", component_outlet_node_name = "CHW Pump Outlet Node" },
]

[branch."CHW Chiller Branch"]
components = [
  { component_object_type = "Chiller:Electric:EIR", component_name = "CHW Chiller", component_inlet_node_name = "CHW Chiller Inlet Node", component_outlet_node_name = "CHW Chiller Outlet Node" },
]

[branch."CHW Supply Bypass Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Supply Bypass Pipe", component_inlet_node_name = "CHW Supply Bypass Inlet Node", component_outlet_node_name = "CHW Supply Bypass Outlet Node" },
]

[branch."CHW Supply Outlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Supply Outlet Pipe", component_inlet_node_name = "CHW Supply Outlet Pipe Inlet Node", component_outlet_node_name = "CHW Supply Outlet Node" },
]

[branch."CHW Demand Inlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Inlet Pipe", component_inlet_node_name = "CHW Demand Inlet Node", component_outlet_node_name = "CHW Demand Inlet Pipe Outlet Node" },
]

[branch."CHW Cooling Coil Branch"]
components = [
  { component_object_type = "Coil:Cooling:Water", component_name = "SZ Cooling Coil", component_inlet_node_name = "Cooling Coil Water Inlet Node", component_outlet_node_name = "Cooling Coil Water Outlet Node" },
]

[branch."CHW Demand Bypass Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Bypass Pipe", component_inlet_node_name = "CHW Demand Bypass Inlet Node", component_outlet_node_name = "CHW Demand Bypass Outlet Node" },
]

[branch."CHW Demand Outlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Outlet Pipe", component_inlet_node_name = "CHW Demand Outlet Pipe Inlet Node", component_outlet_node_name = "CHW Demand Outlet Node" },
]

[air.loop.hvac.controller-list."SZ Controllers"]
controller_1_object_type = "Controller:WaterCoil"
controller_1_name = "Cooling Coil Controller"

[air.loop.hvac.controller-list."SZ OA Controllers"]
controller_1_object_type = "Controller:OutdoorAir"
controller_1_name = "SZ OA Controller"

[air.loop.hvac.outdoor-air-system."SZ OA System"]
controller_list_name = "SZ OA Controllers"
outdoor_air_equipment_list_name = "SZ OA Equipment"

[air.loop.hvac.outdoor.air.system.equipment-list."SZ OA Equipment"]
component_1_object_type = "OutdoorAir:Mixer"
component_1_name = "SZ OA Mixer"

[air.loop.hvac.supply-path."SZ Supply Path"]
supply_air_path_inlet_node_name = "Zone Equipment Inlet Node"
components = [
  { component_object_type = "AirLoopHVAC:ZoneSplitter", component_name = "Zone Supply Air Splitter" },
]

[air.loop.hvac.zone-splitter."Zone Supply Air Splitter"]
inlet_node_name = "Zone Equipment Inlet Node"
nodes = [
  { outlet_node_name = "Zone One Terminal Inlet" },
]

[air.loop.hvac.return-path."SZ Return Path"]
return_air_path_outlet_node_name = "Zone Equipment Outlet Node"
components = [
  { component_object_type = "AirLoopHVAC:ZoneMixer", component_name = "Zone Return Air Mixer" },
]

[air.loop.hvac.zone-mixer."Zone Return Air Mixer"]
outlet_node_name = "Zone Equipment Outlet Node"
nodes = [
  { inlet_node_name = "Zone One Return Outlet" },
]

[air.terminal.single.duct.constant.volume.no-reheat."Zone One Terminal"]
availability_schedule_name = "Always On"
air_inlet_node_name = "Zone One Terminal Inlet"
air_outlet_node_name = "Zone One Supply Inlet"
maximum_air_flow_rate = 0.2734570149252094

[availability-manager-assignment-list."SZ Availability"]
managers = [
  { availability_manager_object_type = "AvailabilityManager:Scheduled", availability_manager_name = "SZ Avail" },
]

[availability.manager.scheduled."SZ Avail"]
schedule_name = "Always On"

[fan.variable-volume."SZ Return Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.7
pressure_rise = 535.9955233963692
maximum_flow_rate = 0.2734570149252094
fan_power_minimum_flow_rate_input_method = "Fraction"
fan_power_minimum_flow_fraction = 0.0
motor_efficiency = 1.0
motor_in_airstream_fraction = 0.0
fan_power_coefficient_1 = 0.0
fan_power_coefficient_2 = 0.0
fan_power_coefficient_3 = 0.0
fan_power_coefficient_4 = 1.0
fan_power_coefficient_5 = 0.0
air_inlet_node_name = "Air Loop Inlet Node"
air_outlet_node_name = "Return Fan Outlet Node"
end_use_subcategory = "Return Fans"

[fan.constant-volume."SZ Supply Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.7
pressure_rise = 515.6885810318987
maximum_flow_rate = 0.2734570149252094
motor_efficiency = 1.0
motor_in_airstream_fraction = 0.0
air_inlet_node_name = "Cooling Coil Outlet Node"
air_outlet_node_name = "Supply Outlet Node"
end_use_subcategory = "General"

[fan.zone-exhaust."Zone Exhaust Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.5
pressure_rise = 160.0
maximum_flow_rate = 0.0935895672021557
air_inlet_node_name = "Zone One Exhaust Node"
air_outlet_node_name = "Zone Exhaust Fan Outlet"
end_use_subcategory = "General Exhaust"
system_availability_manager_coupling_mode = "Coupled"

[outdoor.air.mixer."SZ OA Mixer"]
mixed_air_node_name = "Mixed Air Node"
outdoor_air_stream_node_name = "Outdoor Air Inlet Node"
relief_air_stream_node_name = "Relief Air Outlet Node"
return_air_stream_node_name = "Return Fan Outlet Node"

[[outdoor.air.node-list]]
nodes = [
  { node_or_nodelist_name = "Outdoor Air Inlet Node" },
  { node_or_nodelist_name = "CHW Chiller Condenser Inlet Node" },
]

[controller.outdoor-air."SZ OA Controller"]
relief_air_outlet_node_name = "Relief Air Outlet Node"
return_air_node_name = "Return Fan Outlet Node"
mixed_air_node_name = "Mixed Air Node"
actuator_node_name = "Outdoor Air Inlet Node"
minimum_outdoor_air_flow_rate = 0.0935895672021557
maximum_outdoor_air_flow_rate = 0.2734570149252094
economizer_control_type = "NoEconomizer"
economizer_control_action_type = "ModulateFlow"
lockout_type = "NoLockout"
minimum_limit_type = "FixedMinimum"

[controller.water-coil."Cooling Coil Controller"]
control_variable = "Temperature"
action = "Reverse"
actuator_variable = "Flow"
sensor_node_name = "Cooling Coil Outlet Node"
actuator_node_name = "Cooling Coil Water Inlet Node"
controller_convergence_tolerance = 1e-06
maximum_actuated_flow = 0.00023
minimum_actuated_flow = 0.0

[coil.heating.electric."SZ Heating Coil"]
availability_schedule_name = "Always On"
efficiency = 1.0
nominal_capacity = 20000.0
air_inlet_node_name = "Mixed Air Node"
air_outlet_node_name = "Heating Coil Outlet Node"
temperature_setpoint_node_name = "Heating Coil Outlet Node"

[coil.cooling.water."SZ Cooling Coil"]
availability_schedule_name = "Always On"
design_water_flow_rate = 0.00023
design_air_flow_rate = 0.2734570149252094
design_inlet_water_temperature = 12.0
design_inlet_air_temperature = 26.0
design_outlet_air_temperature = 14.0
design_inlet_air_humidity_ratio = 0.0135
design_outlet_air_humidity_ratio = 0.0099
water_inlet_node_name = "Cooling Coil Water Inlet Node"
water_outlet_node_name = "Cooling Coil Water Outlet Node"
air_inlet_node_name = "Heating Coil Outlet Node"
air_outlet_node_name = "Cooling Coil Outlet Node"
type_of_analysis = "SimpleAnalysis"
heat_exchanger_configuration = "CrossFlow"

[setpoint.manager.single.zone.heating."Heating Supply Air Temp Manager"]
control_variable = "Temperature"
minimum_supply_air_temperature = -99.0
maximum_supply_air_temperature = 99.0
control_zone_name = "Zone One"
zone_node_name = "Zone One Air Node"
zone_inlet_node_name = "Zone One Supply Inlet"
setpoint_node_or_nodelist_name = "Zone Equipment Inlet Node"

[setpoint.manager.single.zone.cooling."Cooling Supply Air Temp Manager"]
control_variable = "Temperature"
minimum_supply_air_temperature = -99.0
maximum_supply_air_temperature = 99.0
control_zone_name = "Zone One"
zone_node_name = "Zone One Air Node"
zone_inlet_node_name = "Zone One Supply Inlet"
setpoint_node_or_nodelist_name = "Supply Outlet Node"

[setpoint.manager.mixed-air."Heating Coil Air Temp Manager"]
control_variable = "Temperature"
reference_setpoint_node_name = "Zone Equipment Inlet Node"
fan_inlet_node_name = "Cooling Coil Outlet Node"
fan_outlet_node_name = "Supply Outlet Node"
setpoint_node_or_nodelist_name = "Heating Coil Outlet Node"

[setpoint.manager.mixed-air."Cooling Coil Air Temp Manager"]
control_variable = "Temperature"
reference_setpoint_node_name = "Supply Outlet Node"
fan_inlet_node_name = "Cooling Coil Outlet Node"
fan_outlet_node_name = "Supply Outlet Node"
setpoint_node_or_nodelist_name = "Cooling Setpoint Nodes"

[setpoint.manager.scheduled."CHW Loop Setpoint Manager"]
control_variable = "Temperature"
schedule_name = "CHW Setpoint"
setpoint_node_or_nodelist_name = "CHW Supply Outlet Node"

[node-list."Cooling Setpoint Nodes"]
nodes = [
  { node_name = "Cooling Coil Outlet Node" },
  { node_name = "Mixed Air Node" },
]

[plant-loop."Chilled Water Loop"]
fluid_type = "Water"
plant_equipment_operation_scheme_name = "CHW Loop Operation"
loop_temperature_setpoint_node_name = "CHW Supply Outlet Node"
maximum_loop_temperature = 98.0
minimum_loop_temperature = 1.0
maximum_loop_flow_rate = 0.0006
minimum_loop_flow_rate = 0.0
plant_loop_volume = 0.5
plant_side_inlet_node_name = "CHW Supply Inlet Node"
plant_side_outlet_node_name = "CHW Supply Outlet Node"
plant_side_branch_list_name = "CHW Supply Branches"
plant_side_connector_list_name = "CHW Supply Connectors"
demand_side_inlet_node_name = "CHW Demand Inlet Node"
demand_side_outlet_node_name = "CHW Demand Outlet Node"
demand_side_branch_list_name = "CHW Demand Branches"
demand_side_connector_list_name = "CHW Demand Connectors"
load_distribution_scheme = "SequentialLoad"

[plant-equipment-operation-schemes."CHW Loop Operation"]
control_scheme_1_object_type = "PlantEquipmentOperation:CoolingLoad"
control_scheme_1_name = "CHW Cooling Scheme"
control_scheme_1_schedule_name = "Always On"

[plant.equipment.operation.cooling-load."CHW Cooling Scheme"]
load_range_1_lower_limit = 0.0
load_range_1_upper_limit = 1000000000.0
range_1_equipment_list_name = "CHW Chillers"

[plant-equipment-list."CHW Chillers"]
equipment = [
  { equipment_object_type = "Chiller:Electric:EIR", equipment_name = "CHW Chiller" },
]

[connector-list."CHW Supply Connectors"]
connector_1_object_type = "Connector:Splitter"
connector_1_name = "CHW Supply Splitter"
connector_2_object_type = "Connector:Mixer"
connector_2_name = "CHW Supply Mixer"

[connector-list."CHW Demand Connectors"]
connector_1_object_type = "Connector:Splitter"
connector_1_name = "CHW Demand Splitter"
connector_2_object_type = "Connector:Mixer"
connector_2_name = "CHW Demand Mixer"

[connector.splitter."CHW Supply Splitter"]
inlet_branch_name = "CHW Supply Inlet Branch"
branches = [
  { outlet_branch_name = "CHW Chiller Branch" },
  { outlet_branch_name = "CHW Supply Bypass Branch" },
]

[connector.splitter."CHW Demand Splitter"]
inlet_branch_name = "CHW Demand Inlet Branch"
branches = [
  { outlet_branch_name = "CHW Cooling Coil Branch" },
  { outlet_branch_name = "CHW Demand Bypass Branch" },
]

[connector.mixer."CHW Supply Mixer"]
outlet_branch_name = "CHW Supply Outlet Branch"
branches = [
  { inlet_branch_name = "CHW Chiller Branch" },
  { inlet_branch_name = "CHW Supply Bypass Branch" },
]

[connector.mixer."CHW Demand Mixer"]
outlet_branch_name = "CHW Demand Outlet Branch"
branches = [
  { inlet_branch_name = "CHW Cooling Coil Branch" },
  { inlet_branch_name = "CHW Demand Bypass Branch" },
]

[pump.variable-speed."CHW Pump"]
inlet_node_name = "CHW Supply Inlet Node"
outlet_node_name = "CHW Pump Outlet Node"
design_maximum_flow_rate = 0.0006
design_pump_head = 1000.0
design_power_consumption = 1.0
motor_efficiency = 0.9
fraction_of_motor_inefficiencies_to_fluid_stream = 0.0
coefficient_1_of_the_part_load_performance_curve = 0.0
coefficient_2_of_the_part_load_performance_curve = 1.0
coefficient_3_of_the_part_load_performance_curve = 0.0
coefficient_4_of_the_part_load_performance_curve = 0.0
design_minimum_flow_rate = 0.0
pump_control_type = "Intermittent"

[chiller.electric.eir."CHW Chiller"]
reference_capacity = 20000.0
reference_cop = 3.0
reference_leaving_chilled_water_temperature = 6.67
reference_entering_condenser_fluid_temperature = 35.0
reference_chilled_water_flow_rate = 0.0006
cooling_capacity_function_of_temperature_curve_name = "CHW Chiller Cap FT"
electric_input_to_cooling_output_ratio_function_of_temperature_curve_name = "CHW Chiller EIR FT"
electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name = "CHW Chiller EIR FPLR"
minimum_part_load_ratio = 0.1
maximum_part_load_ratio = 1.0
optimum_part_load_ratio = 1.0
minimum_unloading_ratio = 0.2
chilled_water_inlet_node_name = "CHW Chiller Inlet Node"
chilled_water_outlet_node_name = "CHW Chiller Outlet Node"
condenser_inlet_node_name = "CHW Chiller Condenser Inlet Node"
condenser_outlet_node_name = "CHW Chiller Condenser Outlet Node"
condenser_type = "AirCooled"
condenser_fan_power_ratio = 0.0
fraction_of_compressor_electric_consumption_rejected_by_condenser = 1.0
leaving_chilled_water_lower_temperature_limit = 2.0
chiller_flow_mode = "ConstantFlow"

[curve.biquadratic."CHW Chiller Cap FT"]
coefficient1_constant = 0.507883
coefficient2_x = 0.145228
coefficient3_x_2 = -0.00625644
coefficient4_y = -0.0011178
coefficient5_y_2 = -0.0001296
coefficient6_x_y = -0.00028188
minimum_value_of_x = 5.0
maximum_value_of_x = 10.0
minimum_value_of_y = 24.0
maximum_value_of_y = 35.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.biquadratic."CHW Chiller EIR FT"]
coefficient1_constant = 1.03076
coefficient2_x = -0.103536
coefficient3_x_2 = 0.00710208
coefficient4_y = 0.0093186
coefficient5_y_2 = 0.00031752
coefficient6_x_y = -0.00104328
minimum_value_of_x = 5.0
maximum_value_of_x = 10.0
minimum_value_of_y = 24.0
maximum_value_of_y = 35.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.quadratic."CHW Chiller EIR FPLR"]
coefficient1_constant = 0.088065
coefficient2_x = 1.137742
coefficient3_x_2 = -0.225806
minimum_value_of_x = 0.0
maximum_value_of_x = 1.0

[pipe.adiabatic."CHW Supply Bypass Pipe"]
inlet_node_name = "CHW Supply Bypass Inlet Node"
outlet_node_name = "CHW Supply Bypass Outlet Node"

[pipe.adiabatic."CHW Supply Outlet Pipe"]
inlet_node_name = "CHW Supply Outlet Pipe Inlet Node"
outlet_node_name = "CHW Supply Outlet Node"

[pipe.adiabatic."CHW Demand Inlet Pipe"]
inlet_node_name = "CHW Demand Inlet Node"
outlet_node_name = "CHW Demand Inlet Pipe Outlet Node"

[pipe.adiabatic."CHW Demand Bypass Pipe"]
inlet_node_name = "CHW Demand Bypass Inlet Node"
outlet_node_name = "CHW Demand Bypass Outlet Node"

[pipe.adiabatic."CHW Demand Outlet Pipe"]
inlet_node_name = "CHW Demand Outlet Pipe Inlet Node"
outlet_node_name = "CHW Demand Outlet Node"

[[output.variable-dictionary]]
key_field = "IDF"

[[output.variable]]
key_value = "*"
variable_name = "Zone Air System Sensible Heating Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Air System Sensible Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Total Internal Latent Gain Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Mean Air Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Heating Coil Heating Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Cooling Coil Total Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Cooling Coil Sensible Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Site Outdoor Air Barometric Pressure"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Supply Fan"
variable_name = "Fan Electricity Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Return Fan"
variable_name = "Fan Electricity Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone Exhaust Fan"
variable_name = "Fan Air Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Air Loop"
variable_name = "Air System Outdoor Air Economizer Status"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Air Loop"
variable_name = "Air System Outdoor Air Flow Fraction"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Heating Coil Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Heating Coil Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Heating Coil Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Return Fan Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Return Fan Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Return Fan Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[run-period."AE201 Run"]
begin_month = 1
begin_day_of_month = 1
end_month = 1
end_day_of_month = 7
use_weather_file_holidays_and_special_days = "No"
use_weather_file_daylight_saving_period = "No"
apply_weekend_holiday_rule = "No"
use_weather_file_rain_indicators = "Yes"
use_weather_file_snow_indicators = "Yes"