Section 11 · Air-side equipment

Case AE204

Values compared
47
Outside example range
6
Run time
0.08 s
Input file
AE204.toml, 31.4 kB

Against the example programs

Each reported quantity next to the spread of the simulation programs published with the standard.

Position in the example range
Example rangeSIMsara
Sensible Cooling Load (QZClatent) (kWh/h)AE SZ coil and zone loads
2.9302.931
In range
Sensible Cooling Load (QZClatent) (kWh/h), AE SZ coil and zone loads: SIMsara 2.931 · range 2.930 to 2.931
Latent Load (QZlatent) (kWh/h)AE SZ coil and zone loads
0.58580.5861
In range
Latent Load (QZlatent) (kWh/h), AE SZ coil and zone loads: SIMsara 0.5861 · range 0.5858 to 0.5861
Loads Sensible (QCsensible) (kWh/h)AE SZ coil and zone loads
3.4563.608
In range
Loads Sensible (QCsensible) (kWh/h), AE SZ coil and zone loads: SIMsara 3.570 · range 3.456 to 3.608
Latent (QClatent) (kWh/h)AE SZ coil and zone loads
2.0542.289
In range
Latent (QClatent) (kWh/h), AE SZ coil and zone loads: SIMsara 2.057 · range 2.054 to 2.289
Total (QCtotal) (kWh/h)AE SZ coil and zone loads
5.6235.897
In range
Total (QCtotal) (kWh/h), AE SZ coil and zone loads: SIMsara 5.626 · range 5.623 to 5.897
Outlet RH (RHcco) (%)AE SZ coil and zone loads
98.620100
In range
Outlet RH (RHcco) (%), AE SZ coil and zone loads: SIMsara 99.884 · range 98.620 to 100
DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)AE SZ node states
26.88926.900
In range
DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa), AE SZ node states: SIMsara 26.900 · range 26.889 to 26.900
DRY BULB TEMPERATURE (°C) · Mixed Air (ma)AE SZ node states
25.06525.111
In range
DRY BULB TEMPERATURE (°C) · Mixed Air (ma), AE SZ node states: SIMsara 25.088 · range 25.065 to 25.111
DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)AE SZ node states
25.06525.111
In range
DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco), AE SZ node states: SIMsara 25.088 · range 25.065 to 25.111
DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)AE SZ node states
14.61114.949
In range
DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco), AE SZ node states: SIMsara 14.929 · range 14.611 to 14.949
DRY BULB TEMPERATURE (°C) · Supply Air (sa)AE SZ node states
15.31215.525
In range
DRY BULB TEMPERATURE (°C) · Supply Air (sa), AE SZ node states: SIMsara 15.506 · range 15.312 to 15.525
DRY BULB TEMPERATURE (°C) · Zone Air (z1)AE SZ node states
23.88223.897
In range
DRY BULB TEMPERATURE (°C) · Zone Air (z1), AE SZ node states: SIMsara 23.889 · range 23.882 to 23.897
DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)AE SZ node states
23.88223.897
In range
DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi), AE SZ node states: SIMsara 23.889 · range 23.882 to 23.897
DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)AE SZ node states
24.16724.217
In range
DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo), AE SZ node states: SIMsara 24.216 · range 24.167 to 24.217
HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)AE SZ node states
0.016760.01685
In range
HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa), AE SZ node states: SIMsara 0.01677 · range 0.01676 to 0.01685
HUMIDITY RATIO (G/GDA) · Mixed Air (ma)AE SZ node states
0.012950.01314
In range
HUMIDITY RATIO (G/GDA) · Mixed Air (ma), AE SZ node states: SIMsara 0.01304 · range 0.01295 to 0.01314
HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)AE SZ node states
0.012950.01314
In range
HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco), AE SZ node states: SIMsara 0.01304 · range 0.01295 to 0.01314
HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)AE SZ node states
0.010310.01061
In range
HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco), AE SZ node states: SIMsara 0.01059 · range 0.01031 to 0.01061
HUMIDITY RATIO (G/GDA) · Supply Air (sa)AE SZ node states
0.010310.01061
In range
HUMIDITY RATIO (G/GDA) · Supply Air (sa), AE SZ node states: SIMsara 0.01059 · range 0.01031 to 0.01061
HUMIDITY RATIO (G/GDA) · Zone Air (z1)AE SZ node states
0.011000.01129
In range
HUMIDITY RATIO (G/GDA) · Zone Air (z1), AE SZ node states: SIMsara 0.01126 · range 0.01100 to 0.01129
HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)AE SZ node states
0.011000.01129
In range
HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi), AE SZ node states: SIMsara 0.01126 · range 0.01100 to 0.01129
HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)AE SZ node states
0.011100.01132
In range
HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo), AE SZ node states: SIMsara 0.01126 · range 0.01110 to 0.01132
SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)AE SZ node states
830.35872.93
Above range
SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa), AE SZ node states: SIMsara 873.71 · range 830.35 to 872.93
SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)AE SZ node states
830.35862.62
Above range
SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma), AE SZ node states: SIMsara 863.36 · range 830.35 to 862.62
TableQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE SZ coil and zone loadsSensible Heating Load (QZHsensible) (kWh/h)00000In range
AE SZ coil and zone loadsSensible Cooling Load (QZClatent) (kWh/h)2.9312.9302.9312.9312.931In range
AE SZ coil and zone loadsLatent Load (QZlatent) (kWh/h)0.58610.58580.58610.58610.5861In range
AE SZ coil and zone loadsCoil Load (QH) (kWh/h)00000In range
AE SZ coil and zone loadsLoads Sensible (QCsensible) (kWh/h)3.5703.4563.6083.5573.574In range
AE SZ coil and zone loadsLatent (QClatent) (kWh/h)2.0572.0542.2892.1552.054In range
AE SZ coil and zone loadsTotal (QCtotal) (kWh/h)5.6265.6235.8975.7125.628In range
AE SZ coil and zone loadsOutlet RH (RHcco) (%)99.88498.62010099.751100In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)26.90026.88926.90026.89726.900In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Mixed Air (ma)25.08825.06525.11125.08925.088In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)25.08825.06525.11125.08925.088In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)14.92914.61114.94914.84314.939In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Supply Air (sa)15.50615.31215.52515.46315.514In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Zone Air (z1)23.88923.88223.89723.88923.889In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.88923.88223.89723.88923.889In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)24.21624.16724.21724.18524.215In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.016770.016760.016850.016800.01677In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.013040.012950.013140.013050.01305In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.013040.012950.013140.013050.01305In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.010590.010310.010610.010520.01060In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Supply Air (sa)0.010590.010310.010610.010520.01060In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Zone Air (z1)0.011260.011000.011290.011210.01128In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.011260.011000.011290.011210.01128In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.011260.011100.011320.011250.01128In range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)873.71830.35872.93848.48872.92Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)863.36830.35862.62844.34862.60Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)863.36830.35862.62844.34862.60Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)830.75829.89833.33831.33830.03In range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Supply Air (sa)832.41827.67833.33831.18831.69In range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Zone Air (z1)857.49830.35856.76842.01856.73Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)857.49830.35856.76842.01856.73Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)858.43830.35857.47841.91857.67Above range
AE SZ node statesENTHALPY (J/GDA) · Location Outdoor Air (oa)69.81469.79569.99469.86369.854In range
AE SZ node statesENTHALPY (J/GDA) · Mixed Air (ma)58.43858.20058.58158.45858.497In range
AE SZ node statesENTHALPY (J/GDA) · Heat Coil Outlet (hco)58.43858.20058.58158.45858.497In range
AE SZ node statesENTHALPY (J/GDA) · Cool Coil Outlet (cco)41.77840.84041.87441.54641.846In range
AE SZ node statesENTHALPY (J/GDA) · Supply Air (sa)42.36941.44042.46542.14342.437In range
AE SZ node statesENTHALPY (J/GDA) · Zone Air (z1)52.67751.99052.77552.51152.746In range
AE SZ node statesENTHALPY (J/GDA) · Return Fan Inlet (rfi)52.67751.99052.77552.51152.746In range
AE SZ node statesENTHALPY (J/GDA) · Return Fan Outlet (rfo)53.01252.29053.10952.81953.081In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.11010.10950.11370.11190.1102In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.34090.32840.34120.33870.3412In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.34090.32840.34120.33870.3412In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.34090.32840.34120.33870.3412In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Supply Air (sa)0.34090.32840.34120.33870.3412In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE SZ node statesMASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.23080.21900.23100.22680.2310In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.23080.21900.23100.22680.2310In range

Reported outputs

The values the engine wrote for this case, before they are placed in the output template.

OutputValue
Loads (kWh/h) · qZHsensible0
Loads (kWh/h) · qZCsensible2.931
Loads (kWh/h) · qZlatent0.5861
Loads (kWh/h) · qH0
Loads (kWh/h) · qCsensible3.570
Loads (kWh/h) · qClatent2.057
Loads (kWh/h) · qCtotal5.626
Loads (kWh/h) · rHcco99.884
Nodes · oa · tdb (°C)26.900
Nodes · oa · w (g/g)0.01677
Nodes · oa · v (L/kg)873.71
Nodes · oa · h (J/g)69.814
Nodes · oa · m (kg/s)0.1101
Nodes · oa · rh (%)75.000
Nodes · ma · tdb (°C)25.088
Nodes · ma · w (g/g)0.01304
Nodes · ma · v (L/kg)863.36
Nodes · ma · h (J/g)58.438
Nodes · ma · m (kg/s)0.3409
Nodes · ma · rh (%)65.307
Nodes · hco · tdb (°C)25.088
Nodes · hco · w (g/g)0.01304
Nodes · hco · v (L/kg)863.36
Nodes · hco · h (J/g)58.438
Nodes · hco · m (kg/s)0.3409
Nodes · hco · rh (%)65.307
Nodes · cco · tdb (°C)14.929
Nodes · cco · w (g/g)0.01059
Nodes · cco · v (L/kg)830.75
Nodes · cco · h (J/g)41.778
Nodes · cco · m (kg/s)0.3409
Nodes · cco · rh (%)99.884
Nodes · sa · tdb (°C)15.506
Nodes · sa · w (g/g)0.01059
Nodes · sa · v (L/kg)832.41
Nodes · sa · h (J/g)42.369
Nodes · sa · m (kg/s)0.3409
Nodes · sa · rh (%)96.247
Nodes · z1 · tdb (°C)23.889
Nodes · z1 · w (g/g)0.01126
Nodes · z1 · v (L/kg)857.49
Nodes · z1 · h (J/g)52.677
Nodes · z1 · rh (%)60.770
Nodes · rfi · tdb (°C)23.889
Nodes · rfi · w (g/g)0.01126
Nodes · rfi · v (L/kg)857.49
Nodes · rfi · h (J/g)52.677
Nodes · rfi · m (kg/s)0.2308
Nodes · rfi · rh (%)60.770
Nodes · rfo · tdb (°C)24.216
Nodes · rfo · w (g/g)0.01126
Nodes · rfo · v (L/kg)858.43
Nodes · rfo · h (J/g)53.012
Nodes · rfo · m (kg/s)0.2308
Nodes · rfo · rh (%)59.589
Pressure pa101,300
Fans · supply (W)201.46
Fans · return (W)77.354
Fans · exhaust (kg/s)0.1101
Fan power (W)201.46
Zone tdb (°C)23.889
Economizer status0
Oa fraction0.3229
Program outputs · cooling coil total (W)5,678.7
Program outputs · cooling coil sensible (W)3,563.5
Program outputs · heating coil (W)0
Program outputs · condensate · kg (s)8.36e-4
Program outputs · condensate · temp (°C)14.929
Program outputs · condensate · h j kg62,405.0
Program outputs · condensate · w52.199
Program outputs · condensate · entering dew point (°C)18.126
Program outputs · condensate · sensible (W)6.205
Balance · residual (W) · return fan−7.67e-13
Balance · residual (W) · mixer0
Balance · residual (W) · heating coil0
Balance · residual (W) · cooling coil−9.09e-13
Balance · residual (W) · supply fan−3.07e-12
Balance · residual (W) · zone3.588
Balance · residual (W) · system3.588
Balance · relative · return fan1.35e-16
Balance · relative · mixer0
Balance · relative · heating coil0
Balance · relative · cooling coil1.60e-16
Balance · relative · supply fan5.41e-16
Balance · relative · zone6.32e-4
Balance · relative · system6.32e-4
Balance · max relative6.32e-4
Balance · reference (W)5,678.7
Cycling · steps6
Flows · supply std (m³/s)0.2830
Flows · exhaust std (m³/s)0.09140
Flows · oa std (m³/s)0.09140
Flows · supply fan dp pa498.24
Flows · return fan max std (m³/s)0.2830
Flows · return fan dp pa616.40
Flows · setpoint offset k0.007914
Flow iterations4
Flow record · convergedtrue
Flow record · iterations4
Flow record · relative change3.71e-8
Flow record · zone tdb error k−4.37e-7

Input file

sha256 981d8530ff83eac3e272e4bd647c66fe9fa35e5a354a37e7348670512b651056

AE204.tomlDownload
[version]
version_identifier = "26.1"

[simulation-control]
do_zone_sizing_calculation = "No"
do_system_sizing_calculation = "No"
do_plant_sizing_calculation = "No"
run_simulation_for_sizing_periods = "No"
run_simulation_for_weather_file_run_periods = "Yes"
do_hvac_sizing_simulation_for_sizing_periods = "No"
maximum_number_of_hvac_sizing_simulation_passes = 1

[building."ASHRAE 140 AE204"]
north_axis = 0.0
terrain = "Suburbs"
loads_convergence_tolerance_value = 0.04
temperature_convergence_tolerance_value = 0.4
solar_distribution = "FullExterior"
maximum_number_of_warmup_days = 25
minimum_number_of_warmup_days = 6

[building.surface.detailed."South Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."East Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."North Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."West Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."Floor"]
surface_type = "Floor"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
]

[building.surface.detailed."Roof"]
surface_type = "Roof"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[timestep]
number_of_timesteps_per_hour = 6

[heat-balance-algorithm]
algorithm = "ConductionTransferFunction"
surface_temperature_upper_limit = 200.0

[surface.convection.algorithm.inside]
algorithm = "TARP"

[surface.convection.algorithm.outside]
algorithm = "DOE-2"

[global-geometry-rules]
starting_vertex_position = "UpperLeftCorner"
vertex_entry_direction = "Counterclockwise"
coordinate_system = "Relative"

[site.location."AE artificial site"]
latitude = 25.8
longitude = -80.3
time_zone = -5.0
elevation = 0.0

[schedule-type-limits."Any Number"]

[schedule-type-limits."Fraction"]
lower_limit_value = 0.0
upper_limit_value = 1.0
numeric_type = "Continuous"

[schedule-type-limits."Temperature"]
lower_limit_value = -60.0
upper_limit_value = 200.0
numeric_type = "Continuous"
unit_type = "Temperature"

[schedule-type-limits."Control Type"]
lower_limit_value = 0.0
upper_limit_value = 4.0
numeric_type = "Discrete"

[schedule.compact."Always On"]
schedule_type_limits_name = "Fraction"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 1.0 },
]

[schedule.compact."Heating Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 18.896913576203595 },
]

[schedule.compact."Cooling Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 23.896913576203595 },
]

[schedule.compact."Dual Setpoint Control"]
schedule_type_limits_name = "Control Type"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 4 },
]

[schedule.compact."CHW Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 6.67 },
]

[material."Gypsum Board 13mm"]
roughness = "Smooth"
thickness = 0.0127
conductivity = 0.16
density = 800.0
specific_heat = 1090.0
thermal_absorptance = 0.9
solar_absorptance = 0.5
visible_absorptance = 0.5

[construction."Adiabatic Panel"]
outside_layer = "Gypsum Board 13mm"

[zone."Zone One"]
direction_of_relative_north = 0.0
x_origin = 0.0
y_origin = 0.0
z_origin = 0.0
type = 1
multiplier = 1
ceiling_height = "Autocalculate"
volume = "Autocalculate"
floor_area = "Autocalculate"
zone_inside_convection_algorithm = "TARP"
zone_outside_convection_algorithm = "DOE-2"
part_of_total_floor_area = "Yes"

[zone.control.thermostat."Zone One Thermostat"]
zone_or_zonelist_name = "Zone One"
control_type_schedule_name = "Dual Setpoint Control"
control_1_object_type = "ThermostatSetpoint:DualSetpoint"
control_1_name = "Zone One Dual Setpoint"

[zone.hvac.air-distribution-unit."Zone One ADU"]
air_distribution_unit_outlet_node_name = "Zone One Supply Inlet"
air_terminal_object_type = "AirTerminal:SingleDuct:ConstantVolume:NoReheat"
air_terminal_name = "Zone One Terminal"
nominal_upstream_leakage_fraction = 0.0
constant_downstream_leakage_fraction = 0.0

[zone.hvac.equipment-list."Zone One Equipment List"]
load_distribution_scheme = "SequentialLoad"
equipment = [
  { zone_equipment_object_type = "ZoneHVAC:AirDistributionUnit", zone_equipment_name = "Zone One ADU", zone_equipment_cooling_sequence = 1, zone_equipment_heating_or_no_load_sequence = 1 },
  { zone_equipment_object_type = "Fan:ZoneExhaust", zone_equipment_name = "Zone Exhaust Fan", zone_equipment_cooling_sequence = 2, zone_equipment_heating_or_no_load_sequence = 2 },
]

[[zone.hvac.equipment-connections]]
zone_name = "Zone One"
zone_conditioning_equipment_list_name = "Zone One Equipment List"
zone_air_inlet_node_or_nodelist_name = "Zone One Supply Inlet"
zone_air_node_name = "Zone One Air Node"
zone_return_air_node_or_nodelist_name = "Zone One Return Outlet"
zone_air_exhaust_node_or_nodelist_name = "Zone One Exhaust Node"

[other-equipment."Zone Sensible Cooling Load"]
fuel_type = "None"
zone_or_zonelist_or_space_or_spacelist_name = "Zone One"
schedule_name = "Always On"
design_level_calculation_method = "EquipmentLevel"
design_level = 2931.0
fraction_latent = 0.0
fraction_radiant = 0.0
fraction_lost = 0.0

[other-equipment."Zone Latent Load"]
fuel_type = "None"
zone_or_zonelist_or_space_or_spacelist_name = "Zone One"
schedule_name = "Always On"
design_level_calculation_method = "EquipmentLevel"
design_level = 586.1
fraction_latent = 1.0
fraction_radiant = 0.0
fraction_lost = 0.0

[thermostat.setpoint.dual-setpoint."Zone One Dual Setpoint"]
heating_setpoint_temperature_schedule_name = "Heating Setpoint"
cooling_setpoint_temperature_schedule_name = "Cooling Setpoint"

[air-loop-hvac."SZ Air Loop"]
controller_list_name = "SZ Controllers"
availability_manager_list_name = "SZ Availability"
design_supply_air_flow_rate = 0.28303424361025065
branch_list_name = "SZ Branches"
supply_side_inlet_node_name = "Air Loop Inlet Node"
demand_side_outlet_node_name = "Zone Equipment Outlet Node"
demand_side_inlet_node_names = "Zone Equipment Inlet Node"
supply_side_outlet_node_names = "Supply Outlet Node"
design_return_air_flow_fraction_of_supply_air_flow = 1.0

[branch-list."SZ Branches"]
branches = [
  { branch_name = "SZ Branch" },
]

[branch-list."CHW Supply Branches"]
branches = [
  { branch_name = "CHW Supply Inlet Branch" },
  { branch_name = "CHW Chiller Branch" },
  { branch_name = "CHW Supply Bypass Branch" },
  { branch_name = "CHW Supply Outlet Branch" },
]

[branch-list."CHW Demand Branches"]
branches = [
  { branch_name = "CHW Demand Inlet Branch" },
  { branch_name = "CHW Cooling Coil Branch" },
  { branch_name = "CHW Demand Bypass Branch" },
  { branch_name = "CHW Demand Outlet Branch" },
]

[branch."SZ Branch"]
components = [
  { component_object_type = "Fan:VariableVolume", component_name = "SZ Return Fan", component_inlet_node_name = "Air Loop Inlet Node", component_outlet_node_name = "Return Fan Outlet Node" },
  { component_object_type = "AirLoopHVAC:OutdoorAirSystem", component_name = "SZ OA System", component_inlet_node_name = "Return Fan Outlet Node", component_outlet_node_name = "Mixed Air Node" },
  { component_object_type = "Coil:Heating:Electric", component_name = "SZ Heating Coil", component_inlet_node_name = "Mixed Air Node", component_outlet_node_name = "Heating Coil Outlet Node" },
  { component_object_type = "Coil:Cooling:Water", component_name = "SZ Cooling Coil", component_inlet_node_name = "Heating Coil Outlet Node", component_outlet_node_name = "Cooling Coil Outlet Node" },
  { component_object_type = "Fan:ConstantVolume", component_name = "SZ Supply Fan", component_inlet_node_name = "Cooling Coil Outlet Node", component_outlet_node_name = "Supply Outlet Node" },
]

[branch."CHW Supply Inlet Branch"]
components = [
  { component_object_type = "Pump:VariableSpeed", component_name = "CHW Pump", component_inlet_node_name = "CHW Supply Inlet Node", component_outlet_node_name = "CHW Pump Outlet Node" },
]

[branch."CHW Chiller Branch"]
components = [
  { component_object_type = "Chiller:Electric:EIR", component_name = "CHW Chiller", component_inlet_node_name = "CHW Chiller Inlet Node", component_outlet_node_name = "CHW Chiller Outlet Node" },
]

[branch."CHW Supply Bypass Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Supply Bypass Pipe", component_inlet_node_name = "CHW Supply Bypass Inlet Node", component_outlet_node_name = "CHW Supply Bypass Outlet Node" },
]

[branch."CHW Supply Outlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Supply Outlet Pipe", component_inlet_node_name = "CHW Supply Outlet Pipe Inlet Node", component_outlet_node_name = "CHW Supply Outlet Node" },
]

[branch."CHW Demand Inlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Inlet Pipe", component_inlet_node_name = "CHW Demand Inlet Node", component_outlet_node_name = "CHW Demand Inlet Pipe Outlet Node" },
]

[branch."CHW Cooling Coil Branch"]
components = [
  { component_object_type = "Coil:Cooling:Water", component_name = "SZ Cooling Coil", component_inlet_node_name = "Cooling Coil Water Inlet Node", component_outlet_node_name = "Cooling Coil Water Outlet Node" },
]

[branch."CHW Demand Bypass Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Bypass Pipe", component_inlet_node_name = "CHW Demand Bypass Inlet Node", component_outlet_node_name = "CHW Demand Bypass Outlet Node" },
]

[branch."CHW Demand Outlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Outlet Pipe", component_inlet_node_name = "CHW Demand Outlet Pipe Inlet Node", component_outlet_node_name = "CHW Demand Outlet Node" },
]

[air.loop.hvac.controller-list."SZ Controllers"]
controller_1_object_type = "Controller:WaterCoil"
controller_1_name = "Cooling Coil Controller"

[air.loop.hvac.controller-list."SZ OA Controllers"]
controller_1_object_type = "Controller:OutdoorAir"
controller_1_name = "SZ OA Controller"

[air.loop.hvac.outdoor-air-system."SZ OA System"]
controller_list_name = "SZ OA Controllers"
outdoor_air_equipment_list_name = "SZ OA Equipment"

[air.loop.hvac.outdoor.air.system.equipment-list."SZ OA Equipment"]
component_1_object_type = "OutdoorAir:Mixer"
component_1_name = "SZ OA Mixer"

[air.loop.hvac.supply-path."SZ Supply Path"]
supply_air_path_inlet_node_name = "Zone Equipment Inlet Node"
components = [
  { component_object_type = "AirLoopHVAC:ZoneSplitter", component_name = "Zone Supply Air Splitter" },
]

[air.loop.hvac.zone-splitter."Zone Supply Air Splitter"]
inlet_node_name = "Zone Equipment Inlet Node"
nodes = [
  { outlet_node_name = "Zone One Terminal Inlet" },
]

[air.loop.hvac.return-path."SZ Return Path"]
return_air_path_outlet_node_name = "Zone Equipment Outlet Node"
components = [
  { component_object_type = "AirLoopHVAC:ZoneMixer", component_name = "Zone Return Air Mixer" },
]

[air.loop.hvac.zone-mixer."Zone Return Air Mixer"]
outlet_node_name = "Zone Equipment Outlet Node"
nodes = [
  { inlet_node_name = "Zone One Return Outlet" },
]

[air.terminal.single.duct.constant.volume.no-reheat."Zone One Terminal"]
availability_schedule_name = "Always On"
air_inlet_node_name = "Zone One Terminal Inlet"
air_outlet_node_name = "Zone One Supply Inlet"
maximum_air_flow_rate = 0.28303424361025065

[availability-manager-assignment-list."SZ Availability"]
managers = [
  { availability_manager_object_type = "AvailabilityManager:Scheduled", availability_manager_name = "SZ Avail" },
]

[availability.manager.scheduled."SZ Avail"]
schedule_name = "Always On"

[fan.variable-volume."SZ Return Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.7
pressure_rise = 616.3956077864873
maximum_flow_rate = 0.28303424361025065
fan_power_minimum_flow_rate_input_method = "Fraction"
fan_power_minimum_flow_fraction = 0.0
motor_efficiency = 1.0
motor_in_airstream_fraction = 0.0
fan_power_coefficient_1 = 0.0
fan_power_coefficient_2 = 0.0
fan_power_coefficient_3 = 0.0
fan_power_coefficient_4 = 1.0
fan_power_coefficient_5 = 0.0
air_inlet_node_name = "Air Loop Inlet Node"
air_outlet_node_name = "Return Fan Outlet Node"
end_use_subcategory = "Return Fans"

[fan.constant-volume."SZ Supply Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.7
pressure_rise = 498.23886396653927
maximum_flow_rate = 0.28303424361025065
motor_efficiency = 1.0
motor_in_airstream_fraction = 0.0
air_inlet_node_name = "Cooling Coil Outlet Node"
air_outlet_node_name = "Supply Outlet Node"
end_use_subcategory = "General"

[fan.zone-exhaust."Zone Exhaust Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.5
pressure_rise = 160.0
maximum_flow_rate = 0.09140316988096642
air_inlet_node_name = "Zone One Exhaust Node"
air_outlet_node_name = "Zone Exhaust Fan Outlet"
end_use_subcategory = "General Exhaust"
system_availability_manager_coupling_mode = "Coupled"

[outdoor.air.mixer."SZ OA Mixer"]
mixed_air_node_name = "Mixed Air Node"
outdoor_air_stream_node_name = "Outdoor Air Inlet Node"
relief_air_stream_node_name = "Relief Air Outlet Node"
return_air_stream_node_name = "Return Fan Outlet Node"

[[outdoor.air.node-list]]
nodes = [
  { node_or_nodelist_name = "Outdoor Air Inlet Node" },
  { node_or_nodelist_name = "CHW Chiller Condenser Inlet Node" },
]

[controller.outdoor-air."SZ OA Controller"]
relief_air_outlet_node_name = "Relief Air Outlet Node"
return_air_node_name = "Return Fan Outlet Node"
mixed_air_node_name = "Mixed Air Node"
actuator_node_name = "Outdoor Air Inlet Node"
minimum_outdoor_air_flow_rate = 0.09140316988096642
maximum_outdoor_air_flow_rate = 0.28303424361025065
economizer_control_type = "NoEconomizer"
economizer_control_action_type = "ModulateFlow"
lockout_type = "NoLockout"
minimum_limit_type = "FixedMinimum"

[controller.water-coil."Cooling Coil Controller"]
control_variable = "Temperature"
action = "Reverse"
actuator_variable = "Flow"
sensor_node_name = "Cooling Coil Outlet Node"
actuator_node_name = "Cooling Coil Water Inlet Node"
controller_convergence_tolerance = 1e-06
maximum_actuated_flow = 0.00023
minimum_actuated_flow = 0.0

[coil.heating.electric."SZ Heating Coil"]
availability_schedule_name = "Always On"
efficiency = 1.0
nominal_capacity = 20000.0
air_inlet_node_name = "Mixed Air Node"
air_outlet_node_name = "Heating Coil Outlet Node"
temperature_setpoint_node_name = "Heating Coil Outlet Node"

[coil.cooling.water."SZ Cooling Coil"]
availability_schedule_name = "Always On"
design_water_flow_rate = 0.00023
design_air_flow_rate = 0.28303424361025065
design_inlet_water_temperature = 12.0
design_inlet_air_temperature = 26.0
design_outlet_air_temperature = 14.0
design_inlet_air_humidity_ratio = 0.0135
design_outlet_air_humidity_ratio = 0.0099
water_inlet_node_name = "Cooling Coil Water Inlet Node"
water_outlet_node_name = "Cooling Coil Water Outlet Node"
air_inlet_node_name = "Heating Coil Outlet Node"
air_outlet_node_name = "Cooling Coil Outlet Node"
type_of_analysis = "SimpleAnalysis"
heat_exchanger_configuration = "CrossFlow"

[setpoint.manager.single.zone.heating."Heating Supply Air Temp Manager"]
control_variable = "Temperature"
minimum_supply_air_temperature = -99.0
maximum_supply_air_temperature = 99.0
control_zone_name = "Zone One"
zone_node_name = "Zone One Air Node"
zone_inlet_node_name = "Zone One Supply Inlet"
setpoint_node_or_nodelist_name = "Zone Equipment Inlet Node"

[setpoint.manager.single.zone.cooling."Cooling Supply Air Temp Manager"]
control_variable = "Temperature"
minimum_supply_air_temperature = -99.0
maximum_supply_air_temperature = 99.0
control_zone_name = "Zone One"
zone_node_name = "Zone One Air Node"
zone_inlet_node_name = "Zone One Supply Inlet"
setpoint_node_or_nodelist_name = "Supply Outlet Node"

[setpoint.manager.mixed-air."Heating Coil Air Temp Manager"]
control_variable = "Temperature"
reference_setpoint_node_name = "Zone Equipment Inlet Node"
fan_inlet_node_name = "Cooling Coil Outlet Node"
fan_outlet_node_name = "Supply Outlet Node"
setpoint_node_or_nodelist_name = "Heating Coil Outlet Node"

[setpoint.manager.mixed-air."Cooling Coil Air Temp Manager"]
control_variable = "Temperature"
reference_setpoint_node_name = "Supply Outlet Node"
fan_inlet_node_name = "Cooling Coil Outlet Node"
fan_outlet_node_name = "Supply Outlet Node"
setpoint_node_or_nodelist_name = "Cooling Setpoint Nodes"

[setpoint.manager.scheduled."CHW Loop Setpoint Manager"]
control_variable = "Temperature"
schedule_name = "CHW Setpoint"
setpoint_node_or_nodelist_name = "CHW Supply Outlet Node"

[node-list."Cooling Setpoint Nodes"]
nodes = [
  { node_name = "Cooling Coil Outlet Node" },
  { node_name = "Mixed Air Node" },
]

[plant-loop."Chilled Water Loop"]
fluid_type = "Water"
plant_equipment_operation_scheme_name = "CHW Loop Operation"
loop_temperature_setpoint_node_name = "CHW Supply Outlet Node"
maximum_loop_temperature = 98.0
minimum_loop_temperature = 1.0
maximum_loop_flow_rate = 0.0006
minimum_loop_flow_rate = 0.0
plant_loop_volume = 0.5
plant_side_inlet_node_name = "CHW Supply Inlet Node"
plant_side_outlet_node_name = "CHW Supply Outlet Node"
plant_side_branch_list_name = "CHW Supply Branches"
plant_side_connector_list_name = "CHW Supply Connectors"
demand_side_inlet_node_name = "CHW Demand Inlet Node"
demand_side_outlet_node_name = "CHW Demand Outlet Node"
demand_side_branch_list_name = "CHW Demand Branches"
demand_side_connector_list_name = "CHW Demand Connectors"
load_distribution_scheme = "SequentialLoad"

[plant-equipment-operation-schemes."CHW Loop Operation"]
control_scheme_1_object_type = "PlantEquipmentOperation:CoolingLoad"
control_scheme_1_name = "CHW Cooling Scheme"
control_scheme_1_schedule_name = "Always On"

[plant.equipment.operation.cooling-load."CHW Cooling Scheme"]
load_range_1_lower_limit = 0.0
load_range_1_upper_limit = 1000000000.0
range_1_equipment_list_name = "CHW Chillers"

[plant-equipment-list."CHW Chillers"]
equipment = [
  { equipment_object_type = "Chiller:Electric:EIR", equipment_name = "CHW Chiller" },
]

[connector-list."CHW Supply Connectors"]
connector_1_object_type = "Connector:Splitter"
connector_1_name = "CHW Supply Splitter"
connector_2_object_type = "Connector:Mixer"
connector_2_name = "CHW Supply Mixer"

[connector-list."CHW Demand Connectors"]
connector_1_object_type = "Connector:Splitter"
connector_1_name = "CHW Demand Splitter"
connector_2_object_type = "Connector:Mixer"
connector_2_name = "CHW Demand Mixer"

[connector.splitter."CHW Supply Splitter"]
inlet_branch_name = "CHW Supply Inlet Branch"
branches = [
  { outlet_branch_name = "CHW Chiller Branch" },
  { outlet_branch_name = "CHW Supply Bypass Branch" },
]

[connector.splitter."CHW Demand Splitter"]
inlet_branch_name = "CHW Demand Inlet Branch"
branches = [
  { outlet_branch_name = "CHW Cooling Coil Branch" },
  { outlet_branch_name = "CHW Demand Bypass Branch" },
]

[connector.mixer."CHW Supply Mixer"]
outlet_branch_name = "CHW Supply Outlet Branch"
branches = [
  { inlet_branch_name = "CHW Chiller Branch" },
  { inlet_branch_name = "CHW Supply Bypass Branch" },
]

[connector.mixer."CHW Demand Mixer"]
outlet_branch_name = "CHW Demand Outlet Branch"
branches = [
  { inlet_branch_name = "CHW Cooling Coil Branch" },
  { inlet_branch_name = "CHW Demand Bypass Branch" },
]

[pump.variable-speed."CHW Pump"]
inlet_node_name = "CHW Supply Inlet Node"
outlet_node_name = "CHW Pump Outlet Node"
design_maximum_flow_rate = 0.0006
design_pump_head = 1000.0
design_power_consumption = 1.0
motor_efficiency = 0.9
fraction_of_motor_inefficiencies_to_fluid_stream = 0.0
coefficient_1_of_the_part_load_performance_curve = 0.0
coefficient_2_of_the_part_load_performance_curve = 1.0
coefficient_3_of_the_part_load_performance_curve = 0.0
coefficient_4_of_the_part_load_performance_curve = 0.0
design_minimum_flow_rate = 0.0
pump_control_type = "Intermittent"

[chiller.electric.eir."CHW Chiller"]
reference_capacity = 20000.0
reference_cop = 3.0
reference_leaving_chilled_water_temperature = 6.67
reference_entering_condenser_fluid_temperature = 35.0
reference_chilled_water_flow_rate = 0.0006
cooling_capacity_function_of_temperature_curve_name = "CHW Chiller Cap FT"
electric_input_to_cooling_output_ratio_function_of_temperature_curve_name = "CHW Chiller EIR FT"
electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name = "CHW Chiller EIR FPLR"
minimum_part_load_ratio = 0.1
maximum_part_load_ratio = 1.0
optimum_part_load_ratio = 1.0
minimum_unloading_ratio = 0.2
chilled_water_inlet_node_name = "CHW Chiller Inlet Node"
chilled_water_outlet_node_name = "CHW Chiller Outlet Node"
condenser_inlet_node_name = "CHW Chiller Condenser Inlet Node"
condenser_outlet_node_name = "CHW Chiller Condenser Outlet Node"
condenser_type = "AirCooled"
condenser_fan_power_ratio = 0.0
fraction_of_compressor_electric_consumption_rejected_by_condenser = 1.0
leaving_chilled_water_lower_temperature_limit = 2.0
chiller_flow_mode = "ConstantFlow"

[curve.biquadratic."CHW Chiller Cap FT"]
coefficient1_constant = 0.507883
coefficient2_x = 0.145228
coefficient3_x_2 = -0.00625644
coefficient4_y = -0.0011178
coefficient5_y_2 = -0.0001296
coefficient6_x_y = -0.00028188
minimum_value_of_x = 5.0
maximum_value_of_x = 10.0
minimum_value_of_y = 24.0
maximum_value_of_y = 35.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.biquadratic."CHW Chiller EIR FT"]
coefficient1_constant = 1.03076
coefficient2_x = -0.103536
coefficient3_x_2 = 0.00710208
coefficient4_y = 0.0093186
coefficient5_y_2 = 0.00031752
coefficient6_x_y = -0.00104328
minimum_value_of_x = 5.0
maximum_value_of_x = 10.0
minimum_value_of_y = 24.0
maximum_value_of_y = 35.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.quadratic."CHW Chiller EIR FPLR"]
coefficient1_constant = 0.088065
coefficient2_x = 1.137742
coefficient3_x_2 = -0.225806
minimum_value_of_x = 0.0
maximum_value_of_x = 1.0

[pipe.adiabatic."CHW Supply Bypass Pipe"]
inlet_node_name = "CHW Supply Bypass Inlet Node"
outlet_node_name = "CHW Supply Bypass Outlet Node"

[pipe.adiabatic."CHW Supply Outlet Pipe"]
inlet_node_name = "CHW Supply Outlet Pipe Inlet Node"
outlet_node_name = "CHW Supply Outlet Node"

[pipe.adiabatic."CHW Demand Inlet Pipe"]
inlet_node_name = "CHW Demand Inlet Node"
outlet_node_name = "CHW Demand Inlet Pipe Outlet Node"

[pipe.adiabatic."CHW Demand Bypass Pipe"]
inlet_node_name = "CHW Demand Bypass Inlet Node"
outlet_node_name = "CHW Demand Bypass Outlet Node"

[pipe.adiabatic."CHW Demand Outlet Pipe"]
inlet_node_name = "CHW Demand Outlet Pipe Inlet Node"
outlet_node_name = "CHW Demand Outlet Node"

[[output.variable-dictionary]]
key_field = "IDF"

[[output.variable]]
key_value = "*"
variable_name = "Zone Air System Sensible Heating Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Air System Sensible Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Total Internal Latent Gain Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Mean Air Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Heating Coil Heating Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Cooling Coil Total Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Cooling Coil Sensible Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Site Outdoor Air Barometric Pressure"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Supply Fan"
variable_name = "Fan Electricity Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Return Fan"
variable_name = "Fan Electricity Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone Exhaust Fan"
variable_name = "Fan Air Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Air Loop"
variable_name = "Air System Outdoor Air Economizer Status"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Air Loop"
variable_name = "Air System Outdoor Air Flow Fraction"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Heating Coil Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Heating Coil Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Heating Coil Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Return Fan Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Return Fan Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Return Fan Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[run-period."AE204 Run"]
begin_month = 1
begin_day_of_month = 1
end_month = 1
end_day_of_month = 7
use_weather_file_holidays_and_special_days = "No"
use_weather_file_daylight_saving_period = "No"
apply_weekend_holiday_rule = "No"
use_weather_file_rain_indicators = "Yes"
use_weather_file_snow_indicators = "Yes"