Section 10 · HE
Space heating
A fuel-fired furnace from steady state to cycling operation with circulating and draft fans, compared with analytical solutions.
- Cases run
- 11
- Values compared
- 48
- Outside example range
- 12
- Run date
- 2026-10-02
Cases
Each case page shows its results, where they sit in the reference range, and the input file.
HE furnace load11 rows · 4 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| HE100 | GJ | 77.739 | 77.750 | 77.940 | 77.815 | 77.740 | Below range |
| HE110 | GJ | 77.739 | 77.750 | 77.940 | 77.815 | 77.740 | Below range |
| HE120 | GJ | 31.097 | 31.100 | 31.250 | 31.160 | 31.100 | Below range |
| HE130 | GJ | 0 | 0 | 0.1550 | 0.05167 | 0 | In range |
| HE140 | GJ | 31.096 | 31.100 | 31.260 | 31.161 | 31.100 | Below range |
| HE150 | GJ | 29.602 | 29.565 | 29.880 | 29.678 | 29.650 | In range |
| HE160 | GJ | 30.485 | 30.460 | 31.260 | 30.737 | 31.100 | In range |
| HE170 | GJ | 29.602 | 29.565 | 29.880 | 29.678 | 29.650 | In range |
| HE210 | GJ | 42.037 | 41.360 | 42.057 | 41.819 | In range | |
| HE220 | GJ | 39.818 | 39.410 | 39.870 | 39.679 | In range | |
| HE230 | GJ | 34.526 | 34.320 | 34.590 | 34.427 | In range |
HE furnace input11 rows · 2 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| HE100 | GJ | 77.737 | 77.713 | 78.417 | 77.957 | 77.713 | In range |
| HE110 | GJ | 97.172 | 96.920 | 98.020 | 97.385 | 97.216 | In range |
| HE120 | GJ | 38.271 | 38.266 | 38.556 | 38.412 | 38.266 | In range |
| HE130 | GJ | 0 | 0 | 0.1420 | 0.04733 | 0 | In range |
| HE140 | GJ | 38.829 | 38.764 | 39.004 | 38.924 | 39.004 | In range |
| HE150 | GJ | 36.944 | 36.820 | 37.231 | 36.996 | 37.025 | In range |
| HE160 | GJ | 38.046 | 37.962 | 38.118 | 38.066 | 38.088 | In range |
| HE170 | GJ | 36.944 | 36.820 | 37.231 | 36.996 | 37.025 | In range |
| HE210 | GJ | 52.369 | 50.528 | 52.371 | 51.635 | In range | |
| HE220 | GJ | 49.532 | 47.869 | 49.466 | 48.894 | Above range | |
| HE230 | GJ | 43.254 | 41.368 | 43.219 | 42.379 | Above range |
HE fuel consumption11 rows · 3 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| HE100 | m3/s | 2.63e-4 | 2.63e-4 | 2.65e-4 | 2.64e-4 | 2.63e-4 | In range |
| HE110 | m3/s | 3.29e-4 | 3.28e-4 | 3.32e-4 | 3.30e-4 | 3.29e-4 | In range |
| HE120 | m3/s | 1.30e-4 | 1.30e-4 | 1.31e-4 | 1.30e-4 | 1.30e-4 | In range |
| HE130 | m3/s | 0 | 0 | 0 | 0 | 0 | In range |
| HE140 | m3/s | 1.31e-4 | 1.31e-4 | 1.32e-4 | 1.32e-4 | 1.32e-4 | In range |
| HE150 | m3/s | 1.25e-4 | 1.25e-4 | 1.26e-4 | 1.25e-4 | 1.25e-4 | In range |
| HE160 | m3/s | 1.29e-4 | 1.29e-4 | 1.29e-4 | 1.29e-4 | 1.29e-4 | In range |
| HE170 | m3/s | 1.25e-4 | 1.25e-4 | 1.26e-4 | 1.25e-4 | 1.25e-4 | In range |
| HE210 | m3/s | 1.77e-4 | 1.71e-4 | 1.77e-4 | 1.75e-4 | Above range | |
| HE220 | m3/s | 1.68e-4 | 1.62e-4 | 1.67e-4 | 1.65e-4 | Above range | |
| HE230 | m3/s | 1.46e-4 | 1.40e-4 | 1.46e-4 | 1.43e-4 | Above range |
HE fan energy6 rows · 3 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| HE150 | kWh | 432.00 | 432 | 433.30 | 432.46 | 432 | In range |
| HE160 | kWh | 169.98 | 170.20 | 172.38 | 171.59 | 172.76 | Below range |
| HE170 | kWh | 473.05 | 473.10 | 473.40 | 473.21 | 473.18 | Below range |
| HE210 | kWh | 292.24 | 281.60 | 298.92 | 290.64 | In range | |
| HE220 | kWh | 276.65 | 268.30 | 281.16 | 275.19 | In range | |
| HE230 | kWh | 480.70 | 431.40 | 478.41 | 456.04 | Above range |
HE mean zone temperature3 rows
HE maximum zone temperature3 rows
HE minimum zone temperature3 rows
Nothing in this suite fits the current filters.
Min, Max and Mean describe the example programs published with the standard. Analytical is the closed-form or quasi-analytical solution where the standard gives one.
Heating Equipment
6 of 6 range cases inside; 5 required. Tables A3-6, A3-7.
ASoftware information
1. SOFTWARE VENDOR:
Jared Bell, Roots Ontological Technologies, LLC
2. SOFTWARE NAME:
SIMsara
3. SOFTWARE VERSION (unique software version identifier):
SIMsara 0.1.0
4. OPERATING SYSTEM REQUIREMENTS:
macOS 13 or later on Apple silicon (arm64). This is the build that was
tested; other targets are listed only when they have been built and run
for these tests.
5. APPROX HARD DISK SPACE REQUIRED FOR INSTALLATION:
About 6.4 MB: the release binary s140_run, which needs no other runtime
files beyond the TOML input and the EPW weather file.
6. MINIMUM RAM REQUIRED FOR SOFTWARE OPERATION:
16 MB: the largest peak resident memory of any submitted test case,
measured with /usr/bin/time -l on the tested build.
7. MINIMUM DISPLAY MONITOR REQUIREMENTS:
None. SIMsara is a command-line program with no graphical display.
8. OTHER HARDWARE OR SOFTWARE-RELATED REQUIREMENTS:
Input is TOML (docs/TOML-INPUT.md in the source distribution) with EPW
weather. Building from source needs Rust 1.98.1. The Standard 140 harness
scripts that generate the test inputs and fill the output templates need
Python 3.11 or later, standard library only.BAlternative modeling methods
NOTE 1 - Interior Surface Convection (Section 10.2.1.7)
---------------------------------------------------------
1.1 Describe the Effect Being Simulated:
Heat transfer between the zone air and the inside faces, and so the
building heat loss the furnace meets.
1.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
1.2.1 User Value (SurfaceProperty:ConvectionCoefficients)
Physical Meaning: A constant coefficient entered per surface, or per
surface class through the MultipleSurface form; the
HeatBalanceAlgorithm minimum surface convection coefficient bounds it
from below.
1.2.2 Simple
Physical Meaning: Constant coefficients by orientation and heat-flow
direction (4.040 W/m2K for upward flow at a ceiling, 3.076 vertical,
0.948 downward).
1.2.3 TARP
Physical Meaning: Natural-convection correlations of temperature
difference and tilt.
1.2.4 CeilingDiffuser, AdaptiveConvectionAlgorithm, ASTMC1340
Physical Meaning: Room-air-flow and adaptive correlations.
1.3 Setting or Capability Used:
User Value on every inside face: 20 W/m2K on the roof, 1e-6 W/m2K on the
walls and floor (Block C note 1). The zone default (Simple) applies to no
surface.
NOTE 2 - Exterior Surface Convection (Section 10.2.1.7)
---------------------------------------------------------
2.1 Describe the Effect Being Simulated:
Heat transfer between the outside faces and the outdoor air.
2.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
2.2.1 User Value (SurfaceProperty:ConvectionCoefficients)
Physical Meaning: A constant convection coefficient entered per surface
or surface class; long-wave exchange stays explicit.
2.2.2 SimpleCombined
Physical Meaning: A combined convection and radiation coefficient D + E
V + F V^2 by roughness (8.23 W/m2K for a very smooth surface at zero
wind); a face with a user value keeps it, and such faces are reported
in a mixed-algorithms Severe message.
2.2.3 TARP, DOE-2, MoWiTT
Physical Meaning: Separate convection correlations with explicit
long-wave exchange.
2.3 Setting or Capability Used:
User Value on every outside face: 20 W/m2K on the roof, 1e-6 W/m2K on the
walls and floor (Block C note 1), with DOE-2 as the zone default, which
applies to no surface; every surface NoWind.
NOTE 3 - Time Step (Section 10.2.1.10.4)
---------------------------------------------------------
3.1 Describe the Effect Being Simulated:
Resolution of the thermostat, burner cycling and part-load calculation.
3.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
3.2.1 Zone time steps per hour
Physical Meaning: 1 to 60 steps per hour; the HVAC system may sub-step.
3.3 Setting or Capability Used:
6 steps per hour (10 minutes). The furnace cycles within a step through its
part-load ratio (no on-off simulation within the step).
NOTE 4 - Circulating Fan Heat (Section 10.2.2.5)
---------------------------------------------------------
4.1 Describe the Effect Being Simulated:
Where the circulating fan's electric power ends up.
4.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
4.2.1 Motor in the airstream fraction
Physical Meaning: Fraction 0 to 1 of the motor losses added to the air;
the shaft power always heats the air.
4.3 Setting or Capability Used:
Fraction 1: all 200 W of fan power is added to the supply air, upstream of
the burner (blow-through), as 10.2.2.5 and 10.2.1.10.1 g specify.CEquivalent modeling methods
NOTE 1 - Roof Heat Loss with Fixed Surface Coefficients (Section 10.2.1.3,
10.2.1.4, 10.2.1.7, 10.2.1.8 and Table 10-1)
-------------------------------------------------------------------------------
1.1 Describe the Effect Being Simulated:
The building heat loss that drives every furnace load.
1.2 Section(s) of the Standard where Relevant Inputs are Specified:
Inside and outside convection coefficients of 20 W/m2K on the roof and
approaching 0 on the walls and floor (combined coefficients where radiation
and convection are modeled together), emissivity and solar absorptivity
approaching 0, walls and floor of R 100 and a 48 m2 roof of R 0.14006: a
building UA of 199.953 W/K, all of it through the roof.
1.3 Equivalent Input(s) Used:
The surface coefficients are entered as fixed convection coefficients
(SurfaceProperty:ConvectionCoefficients, type Value). The roof, the Figure
10-1 roof over the floor, carries an Inside and an Outside Value of 20
W/m2K. Every wall and the floor carry 1e-6 W/m2K inside and outside (two
SurfaceProperty:ConvectionCoefficients:MultipleSurface objects,
AllExteriorWalls and AllExteriorFloors) for the specified 0, which cannot
be entered: the HeatBalanceAlgorithm minimum surface convection
coefficient, also set to 1e-6 W/m2K, must be above 0 and bounds every user
value from below. Any value above 0 is admitted, so 1e-6 W/m2K is a chosen
effective 0, not a program limit. These are convection coefficients, not
the combined coefficients of 10.2.1.7.2: radiation stays explicit; every
surface is NoSun and NoWind, with thermal absorptance 1e-7 (for the
specified 0) and solar absorptance 0. The outside default algorithm is
DOE-2 and the inside default Simple; neither applies to any surface. Layers
are Material:NoMass with R = thickness / k (10.2.1.4.2: no thermal or
moisture capacitance). Site:HeightVariation sets the outdoor air
temperature gradient to 0, so every face sees the weather file dry-bulb, as
the analytical solution does (by default the outdoor air would cool with
height above the weather station). The zone volume (129.6 m3), floor area
(48 m2) and ceiling height (2.7 m) are entered explicitly. The infiltration
method of 10.2.1.9 is not used: it is for programs without direct input of
constant convection coefficients.
1.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The building is the specified one but for the 0 coefficients. At 1e-6 W/m2K
on both faces the walls and floor are nearly decoupled from the zone air
and float near their initial temperature; as a steady conduction path they
would add at most 6.2e-5 W/K to the roof's 199.953 W/K (0.31 parts per
million), convection and conduction only (their long-wave exchange, at the
1e-7 emissivity, is of the same order). Re-running every case with 1e-9
W/m2K in place of 1e-6 W/m2K moves every furnace load, input, fuel and fan
result by at most 9.3e-8 relative and the hourly zone temperatures by at
most 1.2e-5 K, so the chosen value acts as 0. The design loss at the HE100
temperature difference is 9997.7 W. The HE100 furnace load is 77.7387 GJ,
0.002 percent from the analytical value, and the HE120 and HE140 loads are
0.011 and 0.012 percent from theirs.
NOTE 2 - Furnace Modeled as a Heat-Only Unitary System (Section 10.2.1.10,
10.2.2.5-10.2.2.7, 10.2.3)
-------------------------------------------------------------------------------
2.1 Describe the Effect Being Simulated:
Burner, part-load, circulating fan and draft fan performance.
2.2 Section(s) of the Standard where Relevant Inputs are Specified:
A sealed-combustion fuel-fired furnace of 10 kW (HE230: 5 kW), a capacity
that does not include fan heat, 80 percent full-load efficiency (HE100: 100
percent), the part-load curve PLF = PLR / HIR(PLR) with the cubic HIR of
10.2.1.10.4, a 200 W circulating fan (0.355 m3/s, motor in the airstream)
continuous or cycling with the burner, and a 50 W draft fan cycling with
the burner whose heat goes up the flue. The base case simulates both fans
at 0 W.
2.3 Equivalent Input(s) Used:
A single-zone AirLoopHVAC without an outdoor-air system whose branch holds
one AirLoopHVAC:UnitarySystem under Load control of the zone thermostat,
with Coil:Heating:Fuel (NaturalGas) at the full 10,000 W (5,000 W) in every
case, a blow-through Fan:OnOff in HE150-HE230 (operating-mode schedule 1
for continuous, 0 for cycling) and no fan object in HE100-HE140, whose 0 W
fans carry neither power nor heat. The draft fan is the coil's on-cycle
parasitic electric load, which never heats the air. The fan is 200 W at
0.355 m3/s (pressure rise 563.38 Pa, total and motor efficiency 1). The
part-load curve enters as the coil's part-load fraction PLF, with fuel =
full-load fuel x PLR / PLF, so PLF = PLR / HIR; that rational function has
no supported curve form, and every case uses the Curve:Cubic that equals
PLR / HIR exactly at PLR 0.1, 0.4, 0.7 and 1.0 (within 1.3 percent between
0.1 and 1).
2.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
Same components and control as the specified furnace. The cubic is exact at
the HE120 part-load ratio and at full load; for HE140 it gives a furnace
input 0.45 percent below the quasi-analytical value. At 100 percent
full-load efficiency the HE100 furnace input (77.7372 GJ) is 0.002 percent
below its load (77.7387 GJ): the furnace runs at a part-load ratio of about
0.9997, where the specified HIR gives PLR / HIR = 1.00003 (HIR(1) =
0.99995) and the cubic gives 1.00002, so the input falls just below the
load with the specified curve itself.
NOTE 3 - Weather Data Converted from WYEC2 (Section 10.2.1.1, Annex A1 A1.2.3
and A1.7)
-------------------------------------------------------------------------------
3.1 Describe the Effect Being Simulated:
Outdoor dry-bulb temperature of every case.
3.2 Section(s) of the Standard where Relevant Inputs are Specified:
The WYEC2 files HE100W, HE120W, HE130W, HE140W and HE210W (Table A1-8), in
the format of Table A1-18, at the site of Table A1-9 (45.32 N, 75.67 W, 115
m, time zone 5).
3.3 Equivalent Input(s) Used:
SIMsara reads EPW. SIMsara's converter (scripts/s140/wx/wy2.py) writes each
WYEC2 file as an EPW with 8760 records, reading the data positions of Table
A1-18; the LOCATION line carries the Table A1-9 site. The processed files
are archived with their sha256. With every surface NoSun and NoWind only
the dry-bulb temperature and the station pressure affect the results.
3.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The dry-bulb temperatures are carried over unchanged; the converter is
checked field by field (plan WP1).
NOTE 4 - Furnace Load Integrated from the Heating-Coil Rate (Section 10.3.1 and
10.3.2)
-------------------------------------------------------------------------------
4.1 Describe the Effect Being Simulated:
The reported total furnace load.
4.2 Section(s) of the Standard where Relevant Inputs are Specified:
Total furnace load (the load at the furnace coil), total furnace input,
fuel consumption at 38 MJ/m3 over 7.776e6 s, and the energy of both fans,
January through March.
4.3 Equivalent Input(s) Used:
The decks request the fuel coil's heating rate (W) at each time step, and
the load is the rate times the step length summed over the 90 days
(SIMsara's Heating Coil Heating Energy, available on request, is the same
product): the burner heat at the coil, without the circulating fan's heat.
The furnace input is the summed NaturalGas energy; the fuel volume is input
/ (38 MJ/m3 x 7.776e6 s); fan energy is the circulating fan plus the coil's
parasitic (draft fan) electricity.
4.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
Exact for a quantity held constant within each step.DUse of non-specified inputs
* Alternative constant exterior surface coefficients in Sections 7.2.1.9.3, 7.2.3.1.4.3, 7.2.3.3.2, and 9.2.1.8 * Alternative constant interior surface coefficients in Sections 7.2.1.10.3, 7.2.3.1.4.4, 7.2.3.2.2, and 9.2.1.9 * Alternative constant interior solar distribution fractions in Sections 7.2.1.12, 7.2.2.1.2.2, 7.2.2.1.6.2, 7.2.2.1.7.2, 7.2.2.2.7.4, 7.2.3.9.3, 7.2.3.10.2, and 7.2.3.12.2 * Air density given at specific altitudes for the space-cooling and space- heating equipment cases in Sections 9.2.1.4.3, 9.2.3.4.3, and 10.2.1.4.3. NONE
EOmitted test cases and resultsNone
NONE
FChanges to source codeNone
NONE
GAnomalous results
NOTE 1 - Furnace Input, Fuel and Fan Energy above the Example Range
(HE210-HE230) (Section 10.3.1.2, 10.3.1.3 and 10.3.2.1)
-------------------------------------------------------------------------------
1.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
HE220 and HE230 furnace input 49.532 and 43.254 GJ (0.133 and 0.081 percent
above the largest example result) and HE210, HE220 and HE230 fuel 1.772e-4,
1.676e-4 and 1.464e-4 m3/s (0.016, 0.135 and 0.124 percent above it); HE230
fan energy 480.70 kWh (0.479 percent above it).
1.2 Explanation of Reason for the Anomalous Results:
The input and fuel follow from the part-load curve, entered as a cubic
through PLR / HIR (Block C note 2), which each program represents in its
own way. The undersized HE230 burner of 5 kW, which excludes the fan heat,
runs at full load for long periods, and the fan runs with it. The furnace
input and fan energy of HE210, HE220 - HE210 and HE230 - HE220 are inside
the Annex A3 Tables A3-6 and A3-7 ranges (6 of 6).
NOTE 2 - Results at the Edge of the Example Range (Section 10.3.1.1 and
10.3.2.1)
-------------------------------------------------------------------------------
2.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
HE100 and HE110 furnace load 77.739 GJ (0.002 percent from the analytical
value, 0.015 percent below the example range); HE120 and HE140 furnace load
31.097 and 31.096 GJ (0.011 and 0.012 percent from the analytical values,
0.011 and 0.012 percent below the example range); HE160 fan energy 169.98
kWh (0.129 percent below the example range); HE170 fan energy 473.05 kWh
(0.028 percent from the quasi-analytical value, 0.011 percent below the
example range).
2.2 Explanation of Reason for the Anomalous Results:
HE100 and HE110 match the analytical load to 0.002 percent, HE120 and HE140
theirs to 0.011 and 0.012 percent, and HE170 the quasi-analytical fan
energy to 0.028 percent. In HE160 the 10 kW capacity excludes the fan heat
(10.2.1.10.3), so burner and cycling fan deliver 10.2 kW together and run
for the load over 10.2 kW; the informative quasi-analytical solution runs
the fan for the load over 10 kW and counts its heat in the furnace load, so
its fan energy and load are 10.2 / 10 of SIMsara's reading (SIMsara's HE160
load and fan are within 0.02 and 0.36 percent of the scaled values).Rendered from S140outNotes-SIMsara-HE.txt, the modeler report in the form Standard 140 prescribes. The template's own instructions are left out here.
The filled output template and the results workbook are the official record. They hold ASHRAE's licensed template content and are not published here.