Sections 9.2.3 to 9.2.4 · CE b
Space cooling B
The same class of cooling system over a full year of hourly weather, with part load, outdoor air and economizer controls.
- Cases run
- 20
- Values compared
- 783
- Outside example range
- 178
- Harness checks passed
- 34 of 34
- Run date
- 2026-10-02
Cases
Each case page shows its results, where they sit in the reference range, and the input file.
CE b annual results231 rows · 49 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Status |
|---|---|---|---|---|---|---|
| CE300 | Cooling Energy Consumption Total (kWh) | 35,097.9 | 34,745.6 | 35,633.8 | 34,988.5 | In range |
| CE300 | Compressor (kWh) | 21,886.3 | 21,569 | 23,883.5 | 22,170.8 | In range |
| CE300 | Cond Fan (kWh) | 2,331.6 | 2,301 | 2,400.3 | 2,330.6 | In range |
| CE300 | Indoor Fan (kWh) | 10,879.9 | 10,862.1 | 10,880 | 10,877.0 | In range |
| CE300 | Evaporator Coil Load Total (kWh) | 78,492.2 | 77,283.4 | 80,426.9 | 78,053.6 | In range |
| CE300 | Sensible (kWh) | 55,217.3 | 55,191 | 56,661.7 | 55,652.6 | In range |
| CE300 | Latent (kWh) | 23,274.9 | 21,486.6 | 23,765.1 | 22,401.2 | In range |
| CE300 | COP2 | 3.241 | 3.226 | 3.249 | 3.236 | In range |
| CE300 | IDB (°C) | 24.083 | 23.624 | 24.091 | 23.983 | In range |
| CE300 | Zone Humidity Ratio (kg/kg) | 0.009150 | 0.009069 | 0.009286 | 0.009188 | In range |
| CE300 | Zone Relative Humidity (%) | 47.877 | 47.826 | 48.615 | 48.250 | In range |
| CE310 | Cooling Energy Consumption Total (kWh) | 39,497.8 | 39,290.4 | 39,973.4 | 39,525.7 | In range |
| CE310 | Compressor (kWh) | 25,917.9 | 25,813 | 28,428.3 | 26,398.0 | In range |
| CE310 | Cond Fan (kWh) | 2,699.9 | 2,686 | 2,753.8 | 2,704.1 | In range |
| CE310 | Indoor Fan (kWh) | 10,879.9 | 10,862.1 | 10,880 | 10,877.0 | In range |
| CE310 | Evaporator Coil Load Total (kWh) | 97,477.0 | 96,447.6 | 99,342.1 | 97,525.6 | In range |
| CE310 | Sensible (kWh) | 55,091.9 | 55,083 | 56,312.7 | 55,727.2 | In range |
| CE310 | Latent (kWh) | 42,385.0 | 41,093.8 | 43,085.8 | 41,798.4 | In range |
| CE310 | COP2 | 3.406 | 3.380 | 3.417 | 3.403 | In range |
| CE310 | IDB (°C) | 24.092 | 23.756 | 24.111 | 24.019 | In range |
| CE310 | Zone Humidity Ratio (kg/kg) | 0.01114 | 0.01107 | 0.01130 | 0.01120 | In range |
| CE310 | Zone Relative Humidity (%) | 57.863 | 57.800 | 58.551 | 58.260 | In range |
| CE320 | Cooling Energy Consumption Total (kWh) | 39,410.7 | 38,745 | 40,059.7 | 39,255.6 | In range |
| CE320 | Compressor (kWh) | 25,858.3 | 25,250 | 28,217.0 | 26,158.7 | In range |
| CE320 | Cond Fan (kWh) | 2,672.5 | 2,615 | 2,746.6 | 2,667.1 | In range |
| CE320 | Indoor Fan (kWh) | 10,879.9 | 10,862.1 | 10,880 | 10,877.0 | In range |
| CE320 | Evaporator Coil Load Total (kWh) | 97,469.8 | 96,083.6 | 99,791.7 | 97,137.2 | In range |
| CE320 | Sensible (kWh) | 61,723.1 | 62,008.8 | 62,859.2 | 62,514.9 | Below range |
| CE320 | Latent (kWh) | 35,746.6 | 33,659.3 | 36,932.5 | 34,622.5 | In range |
| CE320 | COP2 | 3.416 | 3.390 | 3.458 | 3.423 | In range |
| CE320 | IDB (°C) | 24.231 | 23.900 | 24.530 | 24.298 | In range |
| CE320 | Zone Humidity Ratio (kg/kg) | 0.01002 | 0.009900 | 0.01011 | 0.01004 | In range |
| CE320 | Zone Relative Humidity (%) | 51.351 | 49.940 | 52.005 | 51.225 | In range |
| CE330 | Cooling Energy Consumption Total (kWh) | 40,522.7 | 39,438 | 40,963.3 | 40,186.3 | In range |
| CE330 | Compressor (kWh) | 26,915.0 | 25,925 | 29,281.3 | 27,063.5 | In range |
| CE330 | Cond Fan (kWh) | 2,727.7 | 2,633 | 2,783.6 | 2,698.6 | In range |
| CE330 | Indoor Fan (kWh) | 10,879.9 | 10,862.1 | 10,880 | 10,877.0 | In range |
| CE330 | Evaporator Coil Load Total (kWh) | 103,896 | 100,730 | 105,013 | 102,445 | In range |
| CE330 | Sensible (kWh) | 63,042.9 | 61,822 | 63,778.7 | 62,995.4 | In range |
| CE330 | Latent (kWh) | 40,853.0 | 37,418.9 | 41,929.5 | 39,449.4 | In range |
| CE330 | COP2 | 3.505 | 3.460 | 3.536 | 3.495 | In range |
| CE330 | IDB (°C) | 24.294 | 23.880 | 24.295 | 24.197 | In range |
| CE330 | Zone Humidity Ratio (kg/kg) | 0.009858 | 0.009741 | 0.009968 | 0.009870 | In range |
| CE330 | Zone Relative Humidity (%) | 50.488 | 50.085 | 51.176 | 50.673 | In range |
| CE340 | Cooling Energy Consumption Total (kWh) | 40,114.0 | 39,265 | 40,619.3 | 39,839.6 | In range |
| CE340 | Compressor (kWh) | 26,518.9 | 25,745 | 28,920.9 | 26,721.8 | In range |
| CE340 | Cond Fan (kWh) | 2,715.2 | 2,640 | 2,776.4 | 2,692.4 | In range |
| CE340 | Indoor Fan (kWh) | 10,879.9 | 10,862.1 | 10,880 | 10,877.0 | In range |
| CE340 | Evaporator Coil Load Total (kWh) | 101,179 | 99,027.6 | 102,728 | 100,186 | In range |
| CE340 | Sensible (kWh) | 62,359.8 | 61,406 | 63,110.6 | 62,644.8 | In range |
| CE340 | Latent (kWh) | 38,819.4 | 35,974.2 | 39,695.4 | 37,541.1 | In range |
| CE340 | COP2 | 3.461 | 3.420 | 3.496 | 3.457 | In range |
| CE340 | IDB (°C) | 24.310 | 23.876 | 24.309 | 24.208 | Above range |
| CE340 | Zone Humidity Ratio (kg/kg) | 0.009882 | 0.009791 | 0.009984 | 0.009891 | In range |
| CE340 | Zone Relative Humidity (%) | 50.537 | 50.297 | 51.148 | 50.788 | In range |
| CE350 | Cooling Energy Consumption Total (kWh) | 31,421.5 | 30,547 | 32,237.0 | 31,300.9 | In range |
| CE350 | Compressor (kWh) | 18,592.1 | 17,801 | 20,283.0 | 18,805.3 | In range |
| CE350 | Cond Fan (kWh) | 1,949.5 | 1,865 | 2,040.2 | 1,942.2 | In range |
| CE350 | Indoor Fan (kWh) | 10,879.9 | 10,862.1 | 10,880 | 10,877.0 | In range |
| CE350 | Evaporator Coil Load Total (kWh) | 66,625.6 | 63,634.6 | 69,388.0 | 66,133.1 | In range |
| CE350 | Sensible (kWh) | 48,338.0 | 47,676.5 | 50,370.8 | 48,605.6 | In range |
| CE350 | Latent (kWh) | 18,287.6 | 15,958.1 | 19,017.2 | 17,527.5 | In range |
| CE350 | COP2 | 3.243 | 3.229 | 3.249 | 3.238 | In range |
| CE350 | IDB (°C) | 26.236 | 25.659 | 26.269 | 26.109 | In range |
| CE350 | Zone Humidity Ratio (kg/kg) | 0.009787 | 0.009706 | 0.01000 | 0.009860 | In range |
| CE350 | Zone Relative Humidity (%) | 44.532 | 44.316 | 45.550 | 45.089 | In range |
| CE360 | Cooling Energy Consumption Total (kWh) | 54,948.1 | 54,016 | 55,298.8 | 54,665.8 | In range |
| CE360 | Compressor (kWh) | 39,797.8 | 38,955 | 43,842.6 | 40,256.8 | In range |
| CE360 | Cond Fan (kWh) | 4,270.4 | 4,181 | 4,313.0 | 4,243.4 | In range |
| CE360 | Indoor Fan (kWh) | 10,879.9 | 10,862.1 | 10,880 | 10,877.0 | In range |
| CE360 | Evaporator Coil Load Total (kWh) | 162,138 | 159,807 | 162,974 | 161,209 | In range |
| CE360 | Sensible (kWh) | 134,610 | 134,206 | 135,287 | 134,838 | In range |
| CE360 | Latent (kWh) | 27,527.9 | 24,887.4 | 27,997.2 | 26,370.7 | In range |
| CE360 | COP2 | 3.679 | 3.660 | 3.706 | 3.680 | In range |
| CE360 | IDB (°C) | 25.470 | 25.323 | 25.611 | 25.451 | In range |
| CE360 | Zone Humidity Ratio (kg/kg) | 0.008597 | 0.008499 | 0.008766 | 0.008633 | In range |
| CE360 | Zone Relative Humidity (%) | 41.219 | 40.871 | 42.369 | 41.411 | In range |
| CE400 | Cooling Energy Consumption Total (kWh) | 31,327.9 | 30,846 | 32,045.2 | 31,238.6 | In range |
| CE400 | Compressor (kWh) | 18,544.0 | 18,106 | 20,150.6 | 18,839.1 | In range |
| CE400 | Cond Fan (kWh) | 1,904.0 | 1,860 | 1,986.3 | 1,903.3 | In range |
| CE400 | Indoor Fan (kWh) | 10,879.9 | 10,862.1 | 10,880 | 10,876.4 | In range |
| CE400 | Evaporator Coil Load Total (kWh) | 66,649.9 | 64,917.5 | 68,792.8 | 66,209.5 | In range |
| CE400 | Sensible (kWh) | 40,611.5 | 40,687.7 | 41,952.4 | 41,335.5 | Below range |
| CE400 | Latent (kWh) | 26,038.4 | 23,498.4 | 26,840.5 | 24,874.0 | In range |
| CE400 | COP2 | 3.259 | 3.246 | 3.260 | 3.252 | In range |
| CE400 | IDB (°C) | 24.085 | 23.990 | 24.126 | 24.064 | In range |
| CE400 | Zone Humidity Ratio (kg/kg) | 0.01003 | 0.009801 | 0.01009 | 0.009978 | In range |
| CE400 | Zone Relative Humidity (%) | 52.240 | 50.771 | 52.549 | 51.958 | In range |
| CE410 | Cooling Energy Consumption Total (kWh) | 32,218.3 | 31,503 | 32,078.4 | 31,737.1 | Above range |
| CE410 | Compressor (kWh) | 19,321.2 | 18,685 | 19,204.5 | 18,890.6 | Above range |
| CE410 | Cond Fan (kWh) | 2,017.2 | 1,936 | 1,994.0 | 1,966.0 | Above range |
| CE410 | Indoor Fan (kWh) | 10,879.9 | 10,879.9 | 10,880 | 10,880.0 | In range |
| CE410 | Evaporator Coil Load Total (kWh) | 68,710.1 | 66,175 | 68,672.9 | 67,117.7 | Above range |
| CE410 | Sensible (kWh) | 47,435.0 | 45,585 | 47,659.8 | 46,645.0 | In range |
| CE410 | Latent (kWh) | 21,275.1 | 19,121.0 | 22,996.2 | 20,472.7 | In range |
| CE410 | COP2 | 3.220 | 3.210 | 3.240 | 3.218 | In range |
| CE410 | IDB (°C) | 24.083 | 23.990 | 24.122 | 24.056 | In range |
| CE410 | Zone Humidity Ratio (kg/kg) | 0.009445 | 0.009500 | 0.009740 | 0.009560 | Below range |
| CE410 | Zone Relative Humidity (%) | 49.342 | 49.630 | 50.497 | 49.882 | Below range |
| CE420 | Cooling Energy Consumption Total (kWh) | 33,039.7 | 32,530 | 33,387.0 | 32,954.1 | In range |
| CE420 | Compressor (kWh) | 20,056.5 | 19,596 | 21,873.4 | 20,395.2 | In range |
| CE420 | Cond Fan (kWh) | 2,103.2 | 2,054 | 2,148.5 | 2,103.4 | In range |
| CE420 | Indoor Fan (kWh) | 10,879.9 | 10,862.1 | 10,880 | 10,876.4 | In range |
| CE420 | Evaporator Coil Load Total (kWh) | 71,360.3 | 69,611.0 | 72,609.3 | 71,051.0 | In range |
| CE420 | Sensible (kWh) | 49,500.1 | 49,523.9 | 50,612.2 | 50,035.2 | Below range |
| CE420 | Latent (kWh) | 21,860.2 | 19,944.9 | 22,219.5 | 21,023.0 | In range |
| CE420 | COP2 | 3.220 | 3.210 | 3.226 | 3.217 | In range |
| CE420 | IDB (°C) | 24.083 | 23.926 | 24.091 | 24.024 | In range |
| CE420 | Zone Humidity Ratio (kg/kg) | 0.009330 | 0.009264 | 0.009449 | 0.009362 | In range |
| CE420 | Zone Relative Humidity (%) | 48.773 | 48.760 | 49.398 | 49.009 | In range |
| CE430 | Cooling Energy Consumption Total (kWh) | 32,137.1 | 31,772.4 | 32,538.0 | 31,974.3 | In range |
| CE430 | Compressor (kWh) | 19,247.4 | 18,951 | 20,910.3 | 19,497.0 | In range |
| CE430 | Cond Fan (kWh) | 2,009.7 | 1,970 | 2,059.5 | 2,000.6 | In range |
| CE430 | Indoor Fan (kWh) | 10,879.9 | 10,862.1 | 10,880 | 10,876.4 | In range |
| CE430 | Evaporator Coil Load Total (kWh) | 68,370.8 | 67,141.4 | 69,756.3 | 67,791.5 | In range |
| CE430 | Sensible (kWh) | 46,933.5 | 46,143 | 47,863.3 | 47,186.1 | In range |
| CE430 | Latent (kWh) | 21,437.2 | 19,765.2 | 21,893.0 | 20,605.5 | In range |
| CE430 | COP2 | 3.216 | 3.210 | 3.221 | 3.213 | In range |
| CE430 | IDB (°C) | 24.083 | 23.990 | 24.091 | 24.037 | In range |
| CE430 | Zone Humidity Ratio (kg/kg) | 0.009373 | 0.009310 | 0.009490 | 0.009400 | In range |
| CE430 | Zone Relative Humidity (%) | 48.986 | 48.822 | 49.600 | 49.212 | In range |
| CE440 | Cooling Energy Consumption Total (kWh) | 33,340.2 | 32,973 | 33,691.3 | 33,195.2 | In range |
| CE440 | Compressor (kWh) | 20,323.4 | 19,989 | 22,169.6 | 20,615.7 | In range |
| CE440 | Cond Fan (kWh) | 2,136.9 | 2,104 | 2,182.3 | 2,129.1 | In range |
| CE440 | Indoor Fan (kWh) | 10,879.9 | 10,862.1 | 10,880 | 10,876.4 | In range |
| CE440 | Evaporator Coil Load Total (kWh) | 72,459.9 | 71,181.1 | 73,711.4 | 71,943.8 | In range |
| CE440 | Sensible (kWh) | 50,018.7 | 49,785 | 50,876.1 | 50,361.2 | In range |
| CE440 | Latent (kWh) | 22,441.2 | 20,689.0 | 22,835.3 | 21,582.6 | In range |
| CE440 | COP2 | 3.226 | 3.220 | 3.231 | 3.223 | In range |
| CE440 | IDB (°C) | 24.083 | 23.912 | 24.091 | 24.021 | In range |
| CE440 | Zone Humidity Ratio (kg/kg) | 0.009217 | 0.009158 | 0.009334 | 0.009258 | In range |
| CE440 | Zone Relative Humidity (%) | 48.213 | 48.230 | 48.829 | 48.484 | Below range |
| CE500 | Cooling Energy Consumption Total (kWh) | 23,103.4 | 22,323.0 | 23,138 | 22,745.4 | In range |
| CE500 | Compressor (kWh) | 18,482.8 | 17,854.3 | 20,406.3 | 18,598.6 | In range |
| CE500 | Cond Fan (kWh) | 1,978.5 | 1,911.9 | 1,976 | 1,951.5 | Above range |
| CE500 | Indoor Fan (kWh) | 2,642.2 | 2,369 | 2,639 | 2,520.4 | Above range |
| CE500 | Evaporator Coil Load Total (kWh) | 65,617.4 | 63,105.4 | 65,995.9 | 64,939.3 | In range |
| CE500 | Sensible (kWh) | 47,386.3 | 44,874.2 | 47,649.9 | 46,705.9 | In range |
| CE500 | Latent (kWh) | 18,231.1 | 18,079.9 | 18,346.3 | 18,233.4 | In range |
| CE500 | COP2 | 3.207 | 3.192 | 3.227 | 3.211 | In range |
| CE500 | IDB (°C) | 21.005 | 20.234 | 22.860 | 20.966 | In range |
| CE500 | Zone Humidity Ratio (kg/kg) | 0.009230 | 0.009373 | 0.01070 | 0.01002 | Below range |
| CE500 | Zone Relative Humidity (%) | 56.467 | 59.198 | 66.526 | 63.849 | Below range |
| CE500 | CE500 MAY-SEP · Cooling Energy Consumption Total (kWh) | 18,051.7 | 17,390.9 | 18,051 | 17,769.1 | Above range |
| CE500 | CE500 MAY-SEP · Compressor (kWh) | 14,484.2 | 13,942.1 | 15,967.1 | 14,567.1 | In range |
| CE500 | CE500 MAY-SEP · Cond Fan (kWh) | 1,527.5 | 1,475.5 | 1,527 | 1,506.0 | Above range |
| CE500 | CE500 MAY-SEP · Indoor Fan (kWh) | 2,040.0 | 1,837 | 2,035 | 1,946.8 | Above range |
| CE500 | CE500 MAY-SEP · Evaporator Coil Load Total (kWh) | 50,374.9 | 48,439.6 | 50,692.8 | 49,829.6 | In range |
| CE500 | CE500 MAY-SEP · Sensible (kWh) | 36,384.7 | 34,443.2 | 36,595.6 | 35,839.3 | In range |
| CE500 | CE500 MAY-SEP · Latent (kWh) | 13,990.2 | 13,877 | 14,097.2 | 13,990.3 | In range |
| CE500 | CE500 MAY-SEP · COP2 | 3.146 | 3.132 | 3.162 | 3.148 | In range |
| CE500 | CE500 MAY-SEP · IDB (°C) | 25.000 | 24.572 | 25 | 24.926 | Above range |
| CE500 | CE500 MAY-SEP · Zone Humidity Ratio (kg/kg) | 0.01097 | 0.01090 | 0.01140 | 0.01123 | In range |
| CE500 | CE500 MAY-SEP · Zone Relative Humidity (%) | 55.462 | 55.130 | 57.470 | 56.919 | In range |
| CE510 | CE510 MAY-SEP · Cooling Energy Consumption Total (kWh) | 35,811.2 | 34,608.8 | 35,971 | 35,496.0 | In range |
| CE510 | CE510 MAY-SEP · Compressor (kWh) | 28,674.7 | 27,747.9 | 31,669.2 | 28,943.5 | In range |
| CE510 | CE510 MAY-SEP · Cond Fan (kWh) | 3,055.7 | 2,937.7 | 3,061 | 3,016.8 | In range |
| CE510 | CE510 MAY-SEP · Indoor Fan (kWh) | 4,080.8 | 3,923.2 | 4,099 | 4,038.3 | In range |
| CE510 | CE510 MAY-SEP · Evaporator Coil Load Total (kWh) | 112,822 | 108,974 | 114,018 | 111,927 | In range |
| CE510 | CE510 MAY-SEP · Sensible (kWh) | 81,341.9 | 77,489.4 | 82,305.7 | 80,454.4 | In range |
| CE510 | CE510 MAY-SEP · Latent (kWh) | 31,479.6 | 31,217 | 31,712.2 | 31,472.1 | In range |
| CE510 | CE510 MAY-SEP · COP2 | 3.556 | 3.530 | 3.577 | 3.558 | In range |
| CE510 | CE510 MAY-SEP · IDB (°C) | 25.000 | 24.960 | 25.817 | 25.166 | In range |
| CE510 | CE510 MAY-SEP · Zone Humidity Ratio (kg/kg) | 0.01099 | 0.01090 | 0.01140 | 0.01129 | In range |
| CE510 | CE510 MAY-SEP · Zone Relative Humidity (%) | 55.566 | 54.700 | 57.436 | 56.526 | In range |
| CE520 | Cooling Energy Consumption Total (kWh) | 25,837.5 | 24,986.6 | 25,781 | 25,282.5 | Above range |
| CE520 | Compressor (kWh) | 20,317.5 | 19,521.3 | 21,998.5 | 20,267.8 | In range |
| CE520 | Cond Fan (kWh) | 2,363.5 | 2,340.1 | 2,396 | 2,373.6 | In range |
| CE520 | Indoor Fan (kWh) | 3,156.5 | 2,871 | 3,200 | 3,036.7 | In range |
| CE520 | Evaporator Coil Load Total (kWh) | 66,247.3 | 63,212.1 | 66,571.2 | 65,334.0 | In range |
| CE520 | Sensible (kWh) | 48,018.7 | 44,976.7 | 48,101.5 | 47,054.8 | In range |
| CE520 | Latent (kWh) | 18,228.6 | 18,087 | 18,469.7 | 18,279.1 | In range |
| CE520 | COP2 | 2.921 | 2.873 | 3.004 | 2.935 | In range |
| CE520 | IDB (°C) | 14.082 | 13.517 | 14.890 | 13.938 | In range |
| CE520 | Zone Humidity Ratio (kg/kg) | 0.005896 | 0.006045 | 0.007630 | 0.006848 | Below range |
| CE520 | Zone Relative Humidity (%) | 58.152 | 61.405 | 72.170 | 68.419 | Below range |
| CE522 | Cooling Energy Consumption Total (kWh) | 24,412.0 | 23,544.2 | 24,360 | 24,033.6 | Above range |
| CE522 | Compressor (kWh) | 19,352.8 | 18,620.3 | 21,235.2 | 19,441.9 | In range |
| CE522 | Cond Fan (kWh) | 2,166.2 | 2,108.3 | 2,182 | 2,151.4 | In range |
| CE522 | Indoor Fan (kWh) | 2,893.0 | 2,704 | 2,904 | 2,798.7 | In range |
| CE522 | Evaporator Coil Load Total (kWh) | 65,925.6 | 63,157.0 | 66,373.1 | 65,173.7 | In range |
| CE522 | Sensible (kWh) | 47,695.3 | 44,924.1 | 47,962.3 | 46,912.8 | In range |
| CE522 | Latent (kWh) | 18,230.3 | 18,093.0 | 18,410.8 | 18,260.8 | In range |
| CE522 | COP2 | 3.064 | 3.036 | 3.101 | 3.069 | In range |
| CE522 | IDB (°C) | 17.623 | 16.946 | 18.700 | 17.479 | In range |
| CE522 | Zone Humidity Ratio (kg/kg) | 0.007501 | 0.007607 | 0.009010 | 0.008347 | Below range |
| CE522 | Zone Relative Humidity (%) | 57.744 | 60.752 | 68.677 | 66.443 | Below range |
| CE525 | Cooling Energy Consumption Total (kWh) | 20,810.8 | 20,241.7 | 21,323 | 20,569.4 | In range |
| CE525 | Compressor (kWh) | 16,965.0 | 16,506.8 | 18,521.7 | 17,133.7 | In range |
| CE525 | Cond Fan (kWh) | 1,646.7 | 1,599.2 | 1,663 | 1,631.7 | In range |
| CE525 | Indoor Fan (kWh) | 2,199.1 | 1,885 | 2,221 | 2,076.6 | In range |
| CE525 | Evaporator Coil Load Total (kWh) | 65,050.0 | 63,001.6 | 65,399.1 | 64,536.2 | In range |
| CE525 | Sensible (kWh) | 46,819.4 | 44,775.1 | 47,217.5 | 46,370.8 | In range |
| CE525 | Latent (kWh) | 18,230.6 | 18,043.6 | 18,313.9 | 18,165.4 | In range |
| CE525 | COP2 | 3.495 | 3.410 | 3.531 | 3.490 | In range |
| CE525 | IDB (°C) | 27.712 | 26.844 | 30.690 | 27.846 | In range |
| CE525 | Zone Humidity Ratio (kg/kg) | 0.01350 | 0.01371 | 0.01510 | 0.01415 | Below range |
| CE525 | Zone Relative Humidity (%) | 52.767 | 54.994 | 61.467 | 58.493 | Below range |
| CE530 | Cooling Energy Consumption Total (kWh) | 18,478.1 | 17,281.3 | 17,875 | 17,569.6 | Above range |
| CE530 | Compressor (kWh) | 14,599.8 | 13,657.0 | 15,651.7 | 14,264.6 | In range |
| CE530 | Cond Fan (kWh) | 1,660.6 | 1,535.7 | 1,585 | 1,566.5 | Above range |
| CE530 | Indoor Fan (kWh) | 2,217.7 | 1,833 | 2,117 | 1,999.4 | Above range |
| CE530 | Evaporator Coil Load Total (kWh) | 47,100.9 | 44,875.4 | 47,002 | 46,188.8 | Above range |
| CE530 | Sensible (kWh) | 47,100.9 | 44,874.2 | 47,002 | 46,168.3 | Above range |
| CE530 | Latent (kWh) | 1.41e-13 | 0 | 60.672 | 20.422 | In range |
| CE530 | COP2 | 2.897 | 2.916 | 2.999 | 2.966 | Below range |
| CE530 | IDB (°C) | 21.005 | 20.025 | 22.860 | 20.956 | In range |
| CE530 | Zone Humidity Ratio (kg/kg) | 0.002841 | 0.005798 | 0.006712 | 0.006352 | Below range |
| CE530 | Zone Relative Humidity (%) | 20.262 | 39.600 | 48.973 | 44.189 | Below range |
| CE540 | Cooling Energy Consumption Total (kWh) | 20,277.7 | 19,061.1 | 20,164 | 19,657.3 | Above range |
| CE540 | Compressor (kWh) | 15,856.3 | 15,020.7 | 16,751.9 | 15,659.6 | In range |
| CE540 | Cond Fan (kWh) | 1,893.1 | 1,872.3 | 1,940 | 1,913.1 | In range |
| CE540 | Indoor Fan (kWh) | 2,528.2 | 2,258 | 2,573 | 2,403.4 | In range |
| CE540 | Evaporator Coil Load Total (kWh) | 47,507.7 | 44,979.8 | 47,462 | 46,517.9 | Above range |
| CE540 | Sensible (kWh) | 47,507.7 | 44,976.7 | 47,460 | 46,479.8 | Above range |
| CE540 | Latent (kWh) | −2.94e-14 | 0.9798 | 106.98 | 38.098 | Below range |
| CE540 | COP2 | 2.677 | 2.640 | 2.823 | 2.695 | In range |
| CE540 | IDB (°C) | 14.080 | 13.289 | 14.980 | 13.951 | In range |
| CE540 | Zone Humidity Ratio (kg/kg) | 0.002841 | 0.003855 | 0.004630 | 0.004323 | Below range |
| CE540 | Zone Relative Humidity (%) | 29.054 | 40.051 | 48.521 | 44.675 | Below range |
| CE545 | Cooling Energy Consumption Total (kWh) | 17,052.5 | 15,687.1 | 16,635.7 | 16,007.6 | Above range |
| CE545 | Compressor (kWh) | 13,637.1 | 12,621.9 | 14,764.8 | 13,212.7 | In range |
| CE545 | Cond Fan (kWh) | 1,462.4 | 1,301.8 | 1,337 | 1,323.6 | Above range |
| CE545 | Indoor Fan (kWh) | 1,953.0 | 1,501 | 1,870.9 | 1,691.7 | Above range |
| CE545 | Evaporator Coil Load Total (kWh) | 46,740.0 | 44,775.1 | 46,668 | 45,918.7 | Above range |
| CE545 | Sensible (kWh) | 46,740.0 | 44,775.1 | 46,668 | 45,910.2 | Above range |
| CE545 | Latent (kWh) | 8.19e-14 | 0 | 25.500 | 8.501 | In range |
| CE545 | COP2 | 3.095 | 3.157 | 3.236 | 3.207 | Below range |
| CE545 | IDB (°C) | 27.711 | 26.605 | 30.690 | 27.823 | In range |
| CE545 | Zone Humidity Ratio (kg/kg) | 0.002841 | 0.006227 | 0.007220 | 0.006732 | Below range |
| CE545 | Zone Relative Humidity (%) | 15.891 | 29.200 | 38.631 | 35.333 | Below range |
CE b CE300 outdoor means2 rows
CE b annual hourly maxima240 rows · 26 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Status |
|---|---|---|---|---|---|---|
| CE300 | Energy Consumption Compr + Both Fans Wh | 11,956.9 | 11,548 | 11,932 | 11,695.3 | Above range |
| CE300 | Date | Jul 20 | ||||
| CE300 | Hour | 15 | ||||
| CE300 | Wh | 23,456.4 | 22,908 | 23,530.8 | 23,263.5 | In range |
| CE300 | Sensible Date | Jul 20 | ||||
| CE300 | EvaporatorCoilLoads Hour | 15 | ||||
| CE300 | Wh | 10,393.1 | 9,304 | 10,392 | 9,889.3 | Above range |
| CE300 | Latent Date | Jul 10 | ||||
| CE300 | Hour | 13 | ||||
| CE300 | Sensible + Latent Wh | 32,899.0 | 31,401 | 32,733.3 | 32,056.2 | Above range |
| CE300 | Date | Jul 20 | ||||
| CE300 | Hour | 15 | ||||
| CE310 | Energy Consumption Compr + Both Fans Wh | 12,561.3 | 12,162 | 12,653 | 12,521.4 | In range |
| CE310 | Date | Jul 20 | ||||
| CE310 | Hour | 15 | ||||
| CE310 | Wh | 23,100.2 | 22,649 | 23,276.5 | 23,049.5 | In range |
| CE310 | Sensible Date | Jul 11 | ||||
| CE310 | EvaporatorCoilLoads Hour | 16 | ||||
| CE310 | Wh | 16,369.1 | 15,139 | 16,274.8 | 15,796.6 | Above range |
| CE310 | Latent Date | Aug 4 | ||||
| CE310 | Hour | 15 | ||||
| CE310 | Sensible + Latent Wh | 37,216.5 | 36,750 | 37,328 | 37,081.6 | In range |
| CE310 | Date | Sep 17 | ||||
| CE310 | Hour | 15 | ||||
| CE320 | Energy Consumption Compr + Both Fans Wh | 12,992.0 | 12,875 | 13,104 | 12,976.4 | In range |
| CE320 | Date | Jul 20 | ||||
| CE320 | Hour | 15 | ||||
| CE320 | Wh | 31,425.3 | 30,967 | 31,972.1 | 31,263.3 | In range |
| CE320 | Sensible Date | Apr 24 | ||||
| CE320 | EvaporatorCoilLoads Hour | 15 | ||||
| CE320 | Wh | 22,721.9 | 21,697 | 31,503 | 25,328.1 | In range |
| CE320 | Latent Date | Oct 2 | ||||
| CE320 | Hour | 10 | ||||
| CE320 | Sensible + Latent Wh | 40,034.3 | 39,765.2 | 53,823 | 44,590.5 | In range |
| CE320 | Date | Oct 2 | ||||
| CE320 | Hour | 10 | ||||
| CE330 | Energy Consumption Compr + Both Fans Wh | 13,362.2 | 13,212 | 13,467 | 13,347.0 | In range |
| CE330 | Date | Jul 20 | ||||
| CE330 | Hour | 15 | ||||
| CE330 | Wh | 34,580.8 | 33,226.1 | 34,764.8 | 33,884.8 | In range |
| CE330 | Sensible Date | Jun 14 | ||||
| CE330 | EvaporatorCoilLoads Hour | 14 | ||||
| CE330 | Wh | 27,599.4 | 26,941 | 40,809 | 29,730.3 | In range |
| CE330 | Latent Date | Sep 18 | ||||
| CE330 | Hour | 16 | ||||
| CE330 | Sensible + Latent Wh | 43,568.1 | 42,415 | 64,572 | 46,921.7 | In range |
| CE330 | Date | Oct 2 | ||||
| CE330 | Hour | 9 | ||||
| CE340 | Energy Consumption Compr + Both Fans Wh | 13,179.6 | 13,101 | 13,277 | 13,173.5 | In range |
| CE340 | Date | Jul 20 | ||||
| CE340 | Hour | 15 | ||||
| CE340 | Wh | 32,679.6 | 32,086 | 32,940 | 32,501.4 | In range |
| CE340 | Sensible Date | May 16 | ||||
| CE340 | EvaporatorCoilLoads Hour | 16 | ||||
| CE340 | Wh | 24,464.7 | 23,794 | 36,011 | 27,206.8 | In range |
| CE340 | Latent Date | Oct 2 | ||||
| CE340 | Hour | 10 | ||||
| CE340 | Sensible + Latent Wh | 41,604.8 | 41,132 | 59,549 | 45,974.3 | In range |
| CE340 | Date | Oct 2 | ||||
| CE340 | Hour | 10 | ||||
| CE350 | Energy Consumption Compr + Both Fans Wh | 11,956.9 | 11,546 | 11,932 | 11,710.1 | Above range |
| CE350 | Date | Jul 20 | ||||
| CE350 | Hour | 15 | ||||
| CE350 | Wh | 23,456.4 | 22,876 | 23,530.8 | 23,258.2 | In range |
| CE350 | Sensible Date | Jul 20 | ||||
| CE350 | EvaporatorCoilLoads Hour | 15 | ||||
| CE350 | Wh | 10,393.1 | 9,303 | 11,603 | 10,173.4 | In range |
| CE350 | Latent Date | Jul 10 | ||||
| CE350 | Hour | 13 | ||||
| CE350 | Sensible + Latent Wh | 32,899.0 | 31,401 | 32,733.3 | 32,043.2 | Above range |
| CE350 | Date | Jul 20 | ||||
| CE350 | Hour | 15 | ||||
| CE360 | Energy Consumption Compr + Both Fans Wh | 12,776.7 | 12,726 | 12,863 | 12,766.8 | In range |
| CE360 | Date | Jul 20 | ||||
| CE360 | Hour | 15 | ||||
| CE360 | Wh | 32,323.3 | 31,981 | 32,620.9 | 32,169.6 | In range |
| CE360 | Sensible Date | Apr 24 | ||||
| CE360 | EvaporatorCoilLoads Hour | 16 | ||||
| CE360 | Wh | 8,948.9 | 8,520.3 | 10,336 | 9,325.1 | In range |
| CE360 | Latent Date | Oct 2 | ||||
| CE360 | Hour | 10 | ||||
| CE360 | Sensible + Latent Wh | 38,634.2 | 38,322 | 41,019 | 39,287.0 | In range |
| CE360 | Date | Oct 2 | ||||
| CE360 | Hour | 11 | ||||
| CE400 | Energy Consumption Compr + Both Fans Wh | 11,956.9 | 11,519 | 11,899.9 | 11,657.5 | Above range |
| CE400 | Date | Jul 20 | ||||
| CE400 | Hour | 15 | ||||
| CE400 | Wh | 23,456.4 | 22,877 | 23,530.8 | 23,218.7 | In range |
| CE400 | Sensible Date | Jul 20 | ||||
| CE400 | EvaporatorCoilLoads Hour | 15 | ||||
| CE400 | Wh | 26,790.5 | 25,578 | 32,396 | 27,602.3 | In range |
| CE400 | Latent Date | Sep 16 | ||||
| CE400 | Hour | 15 | ||||
| CE400 | Sensible + Latent Wh | 41,067.2 | 40,543 | 49,838 | 42,612.3 | In range |
| CE400 | Date | Sep 16 | ||||
| CE400 | Hour | 15 | ||||
| CE410 | Energy Consumption Compr + Both Fans Wh | 11,956.9 | 11,549 | 11,627.9 | 11,585.7 | Above range |
| CE410 | Date | Jul 20 | ||||
| CE410 | Hour | 15 | ||||
| CE410 | Wh | 23,456.4 | 22,893 | 23,265.7 | 23,141.7 | Above range |
| CE410 | Sensible Date | Jul 20 | ||||
| CE410 | EvaporatorCoilLoads Hour | 15 | ||||
| CE410 | Wh | 10,393.1 | 9,304 | 11,138.9 | 10,052.7 | In range |
| CE410 | Latent Date | Jul 10 | ||||
| CE410 | Hour | 13 | ||||
| CE410 | Sensible + Latent Wh | 32,899.0 | 31,401 | 32,091.7 | 31,755.2 | Above range |
| CE410 | Date | Jul 20 | ||||
| CE410 | Hour | 15 | ||||
| CE420 | Energy Consumption Compr + Both Fans Wh | 11,956.9 | 11,548 | 11,899.9 | 11,648.0 | Above range |
| CE420 | Date | Jul 20 | ||||
| CE420 | Hour | 15 | ||||
| CE420 | Wh | 23,456.4 | 22,893 | 23,530.8 | 23,221.8 | In range |
| CE420 | Sensible Date | Jul 20 | ||||
| CE420 | EvaporatorCoilLoads Hour | 15 | ||||
| CE420 | Wh | 10,393.1 | 9,304 | 10,394 | 9,815.6 | In range |
| CE420 | Latent Date | Jul 10 | ||||
| CE420 | Hour | 13 | ||||
| CE420 | Sensible + Latent Wh | 32,899.0 | 31,401 | 32,733.3 | 31,967.1 | Above range |
| CE420 | Date | Jul 20 | ||||
| CE420 | Hour | 15 | ||||
| CE430 | Energy Consumption Compr + Both Fans Wh | 11,956.9 | 11,548 | 11,899.9 | 11,648.0 | Above range |
| CE430 | Date | Jul 20 | ||||
| CE430 | Hour | 15 | ||||
| CE430 | Wh | 23,456.4 | 22,893 | 23,530.8 | 23,221.8 | In range |
| CE430 | Sensible Date | Jul 20 | ||||
| CE430 | EvaporatorCoilLoads Hour | 15 | ||||
| CE430 | Wh | 10,436.6 | 9,635.7 | 11,105 | 10,661.9 | In range |
| CE430 | Latent Date | Oct 24 | ||||
| CE430 | Hour | 13 | ||||
| CE430 | Sensible + Latent Wh | 32,899.0 | 31,401 | 32,733.3 | 31,967.1 | Above range |
| CE430 | Date | Jul 20 | ||||
| CE430 | Hour | 15 | ||||
| CE440 | Energy Consumption Compr + Both Fans Wh | 11,956.9 | 11,461 | 11,899.9 | 11,630.6 | Above range |
| CE440 | Date | Jul 20 | ||||
| CE440 | Hour | 15 | ||||
| CE440 | Wh | 23,456.4 | 22,875 | 23,530.8 | 23,218.2 | In range |
| CE440 | Sensible Date | Jul 20 | ||||
| CE440 | EvaporatorCoilLoads Hour | 15 | ||||
| CE440 | Wh | 10,393.1 | 9,304 | 10,234.8 | 9,740.9 | Above range |
| CE440 | Latent Date | Jul 10 | ||||
| CE440 | Hour | 13 | ||||
| CE440 | Sensible + Latent Wh | 32,899.0 | 31,401 | 32,733.3 | 31,908.1 | Above range |
| CE440 | Date | Jul 20 | ||||
| CE440 | Hour | 15 | ||||
| CE500 | Energy Consumption Compr + Both Fans Wh | 10,439.2 | 10,166.5 | 10,431 | 10,312.0 | Above range |
| CE500 | Date | Jul 20 | ||||
| CE500 | Hour | 15 | ||||
| CE500 | Wh | 19,795.8 | 18,776 | 20,009 | 19,668.2 | In range |
| CE500 | Sensible Date | Jul 20 | ||||
| CE500 | EvaporatorCoilLoads Hour | 15 | ||||
| CE500 | Wh | 7,857.2 | 7,733 | 7,965.5 | 7,806.2 | In range |
| CE500 | Latent Date | Jun 29 | ||||
| CE500 | Hour | 16 | ||||
| CE500 | Sensible + Latent Wh | 27,609.0 | 26,567 | 27,707 | 27,444.5 | In range |
| CE500 | Date | Jun 29 | ||||
| CE500 | Hour | 16 | ||||
| CE510 | Energy Consumption Compr + Both Fans Wh | 11,454.8 | 11,186 | 11,590 | 11,387.0 | In range |
| CE510 | Date | Jul 20 | ||||
| CE510 | Hour | 15 | ||||
| CE510 | Wh | 22,237.7 | 21,121 | 22,513 | 22,072.6 | In range |
| CE510 | Sensible Date | Jul 20 | ||||
| CE510 | EvaporatorCoilLoads Hour | 15 | ||||
| CE510 | Wh | 8,955.6 | 8,723 | 8,954.8 | 8,836.2 | Above range |
| CE510 | Latent Date | Jun 17 | ||||
| CE510 | Hour | 14 | ||||
| CE510 | Sensible + Latent Wh | 31,111.4 | 29,948 | 31,188 | 30,865.3 | In range |
| CE510 | Date | Jun 17 | ||||
| CE510 | Hour | 14 | ||||
| CE520 | Energy Consumption Compr + Both Fans Wh | 11,212.9 | 10,684 | 11,100.5 | 10,977.8 | Above range |
| CE520 | Date | Jul 20 | ||||
| CE520 | Hour | 15 | ||||
| CE520 | Wh | 20,073.1 | 18,969 | 20,378 | 19,845.9 | In range |
| CE520 | Sensible Date | Jul 30 | ||||
| CE520 | EvaporatorCoilLoads Hour | 16 | ||||
| CE520 | Wh | 7,758.6 | 7,698.5 | 7,964 | 7,812.0 | In range |
| CE520 | Latent Date | Jun 29 | ||||
| CE520 | Hour | 16 | ||||
| CE520 | Sensible + Latent Wh | 27,786.0 | 26,675 | 28,343 | 27,626.0 | In range |
| CE520 | Date | Sep 6 | ||||
| CE520 | Hour | 16 | ||||
| CE522 | Energy Consumption Compr + Both Fans Wh | 10,900.5 | 10,430.8 | 10,972 | 10,752.9 | In range |
| CE522 | Date | Jul 20 | ||||
| CE522 | Hour | 15 | ||||
| CE522 | Wh | 19,903.6 | 18,785 | 20,137 | 19,733.2 | In range |
| CE522 | Sensible Date | Jul 20 | ||||
| CE522 | EvaporatorCoilLoads Hour | 15 | ||||
| CE522 | Wh | 7,807.6 | 7,743 | 7,906.7 | 7,780.7 | In range |
| CE522 | Latent Date | Jun 29 | ||||
| CE522 | Hour | 16 | ||||
| CE522 | Sensible + Latent Wh | 27,661.7 | 26,514 | 27,868 | 27,487.7 | In range |
| CE522 | Date | Jun 29 | ||||
| CE522 | Hour | 16 | ||||
| CE525 | Energy Consumption Compr + Both Fans Wh | 9,593.4 | 9,366.7 | 9,585 | 9,501.6 | Above range |
| CE525 | Date | Jul 20 | ||||
| CE525 | Hour | 15 | ||||
| CE525 | Wh | 19,594.7 | 18,759 | 19,850 | 19,581.1 | In range |
| CE525 | Sensible Date | Jul 20 | ||||
| CE525 | EvaporatorCoilLoads Hour | 15 | ||||
| CE525 | Wh | 7,941.5 | 7,663 | 8,037.1 | 7,844.7 | In range |
| CE525 | Latent Date | Jun 29 | ||||
| CE525 | Hour | 16 | ||||
| CE525 | Sensible + Latent Wh | 27,503.0 | 26,683 | 27,739.8 | 27,398.9 | In range |
| CE525 | Date | Jun 29 | ||||
| CE525 | Hour | 16 | ||||
| CE530 | Energy Consumption Compr + Both Fans Wh | 8,469.1 | 7,992 | 8,171.0 | 8,065.7 | Above range |
| CE530 | Date | Jul 20 | ||||
| CE530 | Hour | 15 | ||||
| CE530 | Wh | 19,697.0 | 18,776 | 19,834.1 | 19,504.3 | In range |
| CE530 | Sensible Date | Jul 20 | ||||
| CE530 | EvaporatorCoilLoads Hour | 15 | ||||
| CE530 | Wh | 4.24e-12 | 0 | 179 | 35.993 | In range |
| CE530 | Latent Date | May 11 | ||||
| CE530 | Hour | 15 | ||||
| CE530 | Sensible + Latent Wh | 19,697.0 | 18,776 | 19,834.1 | 19,504.3 | In range |
| CE530 | Date | Jul 20 | ||||
| CE530 | Hour | 15 | ||||
| CE540 | Energy Consumption Compr + Both Fans Wh | 9,127.7 | 8,677.4 | 8,985 | 8,848.2 | Above range |
| CE540 | Date | Jul 20 | ||||
| CE540 | Hour | 15 | ||||
| CE540 | Wh | 19,830.4 | 18,794 | 19,799 | 19,571.1 | Above range |
| CE540 | Sensible Date | Jul 20 | ||||
| CE540 | EvaporatorCoilLoads Hour | 15 | ||||
| CE540 | Wh | 4.24e-12 | 0 | 1,655.0 | 718.02 | In range |
| CE540 | Latent Date | Aug 12 | ||||
| CE540 | Hour | 16 | ||||
| CE540 | Sensible + Latent Wh | 19,830.4 | 18,794 | 19,799 | 19,571.1 | Above range |
| CE540 | Date | Jul 20 | ||||
| CE540 | Hour | 15 | ||||
| CE545 | Energy Consumption Compr + Both Fans Wh | 7,935.6 | 7,204.8 | 7,762.8 | 7,414.3 | Above range |
| CE545 | Date | Jul 20 | ||||
| CE545 | Hour | 15 | ||||
| CE545 | Wh | 19,576.1 | 18,759 | 20,075.2 | 19,470.0 | In range |
| CE545 | Sensible Date | Jul 20 | ||||
| CE545 | EvaporatorCoilLoads Hour | 15 | ||||
| CE545 | Wh | 4.85e-12 | 0 | 4 | 0.6667 | In range |
| CE545 | Latent Date | Jul 15 | ||||
| CE545 | Hour | 15 | ||||
| CE545 | Sensible + Latent Wh | 19,576.1 | 18,764 | 20,075.2 | 19,470.8 | In range |
| CE545 | Date | Jul 20 | ||||
| CE545 | Hour | 15 |
CE b CE300 weather maxima6 rows · 1 outside
CE b CE300 June 28 hourly264 rows · 48 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Status |
|---|---|---|---|---|---|---|
| CE300 | 1 · Energy Consumption Compressor (Wh) | 1,924.8 | 1,886 | 2,118.7 | 1,965.7 | In range |
| CE300 | 1 · Cond Fan (Wh) | 238.63 | 237 | 256.53 | 241.69 | In range |
| CE300 | 1 · Evaporator Coil Load Total (Wh) | 7,630.9 | 7,471.7 | 8,131.7 | 7,640.0 | In range |
| CE300 | 1 · Sensible (Wh) | 5,823.2 | 5,788 | 6,189.3 | 5,905.7 | In range |
| CE300 | 1 · Latent (Wh) | 1,807.7 | 1,658.1 | 1,942.4 | 1,734.3 | In range |
| CE300 | 1 · Zone Hum. Rat. (kg/kg) | 0.009225 | 0.009078 | 0.009405 | 0.009302 | In range |
| CE300 | 1 · COP2 | 3.527 | 3.511 | 3.541 | 3.526 | In range |
| CE300 | 1 · ODB (°C) | 18.008 | 17.778 | 18.050 | 17.866 | In range |
| CE300 | 1 · EDB (°C) | 23.948 | 23.407 | 23.945 | 23.813 | Above range |
| CE300 | 1 · EWB (°C) | 17.256 | 16.964 | 17.340 | 17.221 | In range |
| CE300 | 1 · Outdoor Hum. Rat. (kg/kg) | 0.01122 | 0.01107 | 0.01140 | 0.01124 | In range |
| CE300 | 2 · Energy Consumption Compressor (Wh) | 1,931.2 | 1,941 | 2,131.3 | 1,996.9 | Below range |
| CE300 | 2 · Cond Fan (Wh) | 239.16 | 240 | 256.53 | 244.53 | Below range |
| CE300 | 2 · Evaporator Coil Load Total (Wh) | 7,638.1 | 7,494.4 | 8,115.8 | 7,708.2 | In range |
| CE300 | 2 · Sensible (Wh) | 5,851.0 | 5,853.1 | 6,201.6 | 6,004.1 | Below range |
| CE300 | 2 · Latent (Wh) | 1,787.1 | 1,559.9 | 1,914.2 | 1,704.3 | In range |
| CE300 | 2 · Zone Hum. Rat. (kg/kg) | 0.009186 | 0.009014 | 0.009366 | 0.009257 | In range |
| CE300 | 2 · COP2 | 3.519 | 3.490 | 3.516 | 3.503 | Above range |
| CE300 | 2 · ODB (°C) | 18.092 | 18.050 | 18.333 | 18.238 | In range |
| CE300 | 2 · EDB (°C) | 23.960 | 23.375 | 24 | 23.861 | In range |
| CE300 | 2 · EWB (°C) | 17.228 | 16.905 | 17.310 | 17.207 | In range |
| CE300 | 2 · Outdoor Hum. Rat. (kg/kg) | 0.01128 | 0.01120 | 0.01146 | 0.01131 | In range |
| CE300 | 3 · Energy Consumption Compressor (Wh) | 1,921.2 | 1,881 | 2,112.6 | 1,956.9 | In range |
| CE300 | 3 · Cond Fan (Wh) | 238.23 | 236 | 256.54 | 240.68 | In range |
| CE300 | 3 · Evaporator Coil Load Total (Wh) | 7,614.0 | 7,445 | 8,127.9 | 7,607.3 | In range |
| CE300 | 3 · Sensible (Wh) | 5,821.4 | 5,782.9 | 6,194.4 | 5,889.0 | In range |
| CE300 | 3 · Latent (Wh) | 1,792.6 | 1,637.2 | 1,933.5 | 1,718.3 | In range |
| CE300 | 3 · Zone Hum. Rat. (kg/kg) | 0.009205 | 0.009064 | 0.009400 | 0.009280 | In range |
| CE300 | 3 · COP2 | 3.526 | 3.517 | 3.541 | 3.526 | In range |
| CE300 | 3 · ODB (°C) | 18.008 | 17.778 | 18.050 | 17.866 | In range |
| CE300 | 3 · EDB (°C) | 23.948 | 23.383 | 23.945 | 23.802 | Above range |
| CE300 | 3 · EWB (°C) | 17.240 | 16.942 | 17.370 | 17.202 | In range |
| CE300 | 3 · Outdoor Hum. Rat. (kg/kg) | 0.01121 | 0.01107 | 0.01140 | 0.01124 | In range |
| CE300 | 4 · Energy Consumption Compressor (Wh) | 1,882.3 | 1,830.1 | 2,074.7 | 1,901.5 | In range |
| CE300 | 4 · Cond Fan (Wh) | 234.45 | 229.59 | 237 | 233.94 | In range |
| CE300 | 4 · Evaporator Coil Load Total (Wh) | 7,484.2 | 7,224.2 | 7,533.8 | 7,394.6 | In range |
| CE300 | 4 · Sensible (Wh) | 5,748.7 | 5,548.6 | 5,878.1 | 5,752.5 | In range |
| CE300 | 4 · Latent (Wh) | 1,735.5 | 1,588.4 | 1,675.6 | 1,642.1 | Above range |
| CE300 | 4 · Zone Hum. Rat. (kg/kg) | 0.009140 | 0.008986 | 0.009400 | 0.009234 | In range |
| CE300 | 4 · COP2 | 3.536 | 3.507 | 3.541 | 3.527 | In range |
| CE300 | 4 · ODB (°C) | 17.800 | 17.778 | 17.800 | 17.793 | In range |
| CE300 | 4 · EDB (°C) | 23.917 | 23.374 | 23.920 | 23.786 | In range |
| CE300 | 4 · EWB (°C) | 17.172 | 16.862 | 17.370 | 17.150 | In range |
| CE300 | 4 · Outdoor Hum. Rat. (kg/kg) | 0.01106 | 0.01105 | 0.01140 | 0.01118 | In range |
| CE300 | 5 · Energy Consumption Compressor (Wh) | 1,813.6 | 1,694 | 2,029.3 | 1,848.0 | In range |
| CE300 | 5 · Cond Fan (Wh) | 227.66 | 215 | 256.39 | 229.82 | In range |
| CE300 | 5 · Evaporator Coil Load Total (Wh) | 7,244.7 | 6,753.0 | 8,104.8 | 7,210.2 | In range |
| CE300 | 5 · Sensible (Wh) | 5,627.9 | 5,580 | 6,318.9 | 5,802.5 | In range |
| CE300 | 5 · Latent (Wh) | 1,616.8 | 1,081.2 | 1,786.0 | 1,407.7 | In range |
| CE300 | 5 · Zone Hum. Rat. (kg/kg) | 0.009014 | 0.008841 | 0.009192 | 0.008976 | In range |
| CE300 | 5 · COP2 | 3.549 | 3.490 | 3.555 | 3.536 | In range |
| CE300 | 5 · ODB (°C) | 17.450 | 17.200 | 17.500 | 17.295 | In range |
| CE300 | 5 · EDB (°C) | 23.865 | 23.350 | 23.976 | 23.762 | In range |
| CE300 | 5 · EWB (°C) | 17.016 | 16.697 | 17.008 | 16.856 | Above range |
| CE300 | 5 · Outdoor Hum. Rat. (kg/kg) | 0.01052 | 0.01016 | 0.01061 | 0.01034 | In range |
| CE300 | 6 · Energy Consumption Compressor (Wh) | 1,932.6 | 1,839.4 | 2,506.6 | 2,136.9 | In range |
| CE300 | 6 · Cond Fan (Wh) | 238.40 | 229.56 | 292.59 | 258.63 | In range |
| CE300 | 6 · Evaporator Coil Load Total (Wh) | 7,531.2 | 7,130.9 | 9,222.9 | 8,002.5 | In range |
| CE300 | 6 · Sensible (Wh) | 5,989.0 | 5,686.2 | 7,311.8 | 6,371.9 | In range |
| CE300 | 6 · Latent (Wh) | 1,542.1 | 1,410.0 | 1,911.2 | 1,630.7 | In range |
| CE300 | 6 · Zone Hum. Rat. (kg/kg) | 0.008846 | 0.008658 | 0.009200 | 0.009046 | In range |
| CE300 | 6 · COP2 | 3.469 | 3.295 | 3.467 | 3.407 | Above range |
| CE300 | 6 · ODB (°C) | 18.483 | 18.300 | 19.444 | 19.094 | In range |
| CE300 | 6 · EDB (°C) | 24.020 | 23.417 | 24.576 | 24.068 | In range |
| CE300 | 6 · EWB (°C) | 16.943 | 16.573 | 17.541 | 17.149 | In range |
| CE300 | 6 · Outdoor Hum. Rat. (kg/kg) | 0.01061 | 0.01057 | 0.01130 | 0.01096 | In range |
| CE300 | 7 · Energy Consumption Compressor (Wh) | 2,604.4 | 2,667.2 | 3,223 | 3,027.3 | Below range |
| CE300 | 7 · Cond Fan (Wh) | 296.93 | 308.54 | 353 | 338.10 | Below range |
| CE300 | 7 · Evaporator Coil Load Total (Wh) | 9,350.6 | 9,216.0 | 11,232.8 | 10,409.3 | In range |
| CE300 | 7 · Sensible (Wh) | 7,454.5 | 7,532.5 | 8,646.9 | 8,123.9 | Below range |
| CE300 | 7 · Latent (Wh) | 1,896.1 | 1,683.5 | 2,885.0 | 2,285.4 | In range |
| CE300 | 7 · Zone Hum. Rat. (kg/kg) | 0.009152 | 0.009153 | 0.01000 | 0.009541 | Below range |
| CE300 | 7 · COP2 | 3.223 | 3.065 | 3.263 | 3.150 | In range |
| CE300 | 7 · ODB (°C) | 22.667 | 22.200 | 25 | 24.183 | In range |
| CE300 | 7 · EDB (°C) | 24.648 | 24.040 | 25.164 | 24.796 | In range |
| CE300 | 7 · EWB (°C) | 17.512 | 17.319 | 18.390 | 17.969 | In range |
| CE300 | 7 · Outdoor Hum. Rat. (kg/kg) | 0.01220 | 0.01207 | 0.01330 | 0.01286 | In range |
| CE300 | 8 · Energy Consumption Compressor (Wh) | 3,235.3 | 3,135 | 3,552.7 | 3,344.7 | In range |
| CE300 | 8 · Cond Fan (Wh) | 347.11 | 332 | 384.05 | 352.73 | In range |
| CE300 | 8 · Evaporator Coil Load Total (Wh) | 10,883.6 | 10,271.7 | 12,121.3 | 10,882.1 | In range |
| CE300 | 8 · Sensible (Wh) | 8,724.8 | 8,756.7 | 9,558.2 | 9,131.8 | Below range |
| CE300 | 8 · Latent (Wh) | 2,158.8 | 1,202.6 | 2,563.1 | 1,750.3 | In range |
| CE300 | 8 · Zone Hum. Rat. (kg/kg) | 0.009520 | 0.009314 | 0.009642 | 0.009443 | In range |
| CE300 | 8 · COP2 | 3.038 | 2.948 | 3.079 | 2.990 | In range |
| CE300 | 8 · ODB (°C) | 26.283 | 26.100 | 27.222 | 26.887 | In range |
| CE300 | 8 · EDB (°C) | 25.193 | 24.572 | 25.453 | 25.186 | In range |
| CE300 | 8 · EWB (°C) | 17.984 | 17.646 | 17.959 | 17.792 | Above range |
| CE300 | 8 · Outdoor Hum. Rat. (kg/kg) | 0.01194 | 0.01090 | 0.01217 | 0.01131 | In range |
| CE300 | 9 · Energy Consumption Compressor (Wh) | 4,331.2 | 4,364.8 | 4,681.8 | 4,512.1 | Below range |
| CE300 | 9 · Cond Fan (Wh) | 450.97 | 458.10 | 469 | 463.58 | Below range |
| CE300 | 9 · Evaporator Coil Load Total (Wh) | 14,341.7 | 14,032.3 | 14,844.0 | 14,598.9 | In range |
| CE300 | 9 · Sensible (Wh) | 11,739.6 | 11,757.9 | 11,971 | 11,861.2 | Below range |
| CE300 | 9 · Latent (Wh) | 2,602.1 | 2,265.2 | 2,968.8 | 2,737.7 | In range |
| CE300 | 9 · Zone Hum. Rat. (kg/kg) | 0.009629 | 0.009673 | 0.009900 | 0.009785 | Below range |
| CE300 | 9 · COP2 | 2.999 | 2.958 | 3.018 | 2.981 | In range |
| CE300 | 9 · ODB (°C) | 28.192 | 28.050 | 28.900 | 28.648 | In range |
| CE300 | 9 · EDB (°C) | 25.480 | 25.094 | 25.590 | 25.477 | In range |
| CE300 | 9 · EWB (°C) | 18.070 | 17.973 | 18.360 | 18.211 | In range |
| CE300 | 9 · Outdoor Hum. Rat. (kg/kg) | 0.01154 | 0.01154 | 0.01200 | 0.01174 | In range |
| CE300 | 10 · Energy Consumption Compressor (Wh) | 4,587.1 | 4,441.1 | 4,947.6 | 4,690.3 | In range |
| CE300 | 10 · Cond Fan (Wh) | 470.35 | 457.99 | 489.45 | 475.29 | In range |
| CE300 | 10 · Evaporator Coil Load Total (Wh) | 15,104.6 | 14,639.4 | 15,882.1 | 15,188.5 | In range |
| CE300 | 10 · Sensible (Wh) | 11,992.3 | 11,506.4 | 12,287.1 | 11,973.5 | In range |
| CE300 | 10 · Latent (Wh) | 3,112.3 | 2,781.4 | 3,595.0 | 3,215.0 | In range |
| CE300 | 10 · Zone Hum. Rat. (kg/kg) | 0.009995 | 0.01004 | 0.01030 | 0.01017 | Below range |
| CE300 | 10 · COP2 | 2.987 | 2.973 | 2.999 | 2.986 | In range |
| CE300 | 10 · ODB (°C) | 28.900 | 28.889 | 28.900 | 28.896 | In range |
| CE300 | 10 · EDB (°C) | 25.587 | 25.282 | 25.739 | 25.551 | In range |
| CE300 | 10 · EWB (°C) | 18.459 | 18.397 | 18.854 | 18.595 | In range |
| CE300 | 10 · Outdoor Hum. Rat. (kg/kg) | 0.01237 | 0.01239 | 0.01276 | 0.01254 | Below range |
| CE300 | 11 · Energy Consumption Compressor (Wh) | 4,998.3 | 4,999.6 | 5,456 | 5,283.1 | Below range |
| CE300 | 11 · Cond Fan (Wh) | 499.60 | 506.30 | 537 | 520.70 | Below range |
| CE300 | 11 · Evaporator Coil Load Total (Wh) | 16,208.4 | 15,905.4 | 17,605.1 | 16,779.4 | In range |
| CE300 | 11 · Sensible (Wh) | 12,448.9 | 12,342.2 | 12,817.6 | 12,625.4 | In range |
| CE300 | 11 · Latent (Wh) | 3,759.5 | 3,417.3 | 4,787.5 | 4,154.0 | In range |
| CE300 | 11 · Zone Hum. Rat. (kg/kg) | 0.01041 | 0.01041 | 0.01090 | 0.01064 | Below range |
| CE300 | 11 · COP2 | 2.948 | 2.906 | 2.974 | 2.935 | In range |
| CE300 | 11 · ODB (°C) | 30.183 | 30 | 31.111 | 30.783 | In range |
| CE300 | 11 · EDB (°C) | 25.782 | 25.359 | 25.910 | 25.784 | In range |
| CE300 | 11 · EWB (°C) | 18.946 | 18.825 | 19.480 | 19.193 | In range |
| CE300 | 11 · Outdoor Hum. Rat. (kg/kg) | 0.01386 | 0.01378 | 0.01481 | 0.01448 | In range |
| CE300 | 12 · Energy Consumption Compressor (Wh) | 5,230.1 | 5,005.0 | 5,632.4 | 5,175.7 | In range |
| CE300 | 12 · Cond Fan (Wh) | 516.20 | 496.50 | 529.36 | 505.17 | In range |
| CE300 | 12 · Evaporator Coil Load Total (Wh) | 16,866.9 | 16,029.6 | 17,248.4 | 16,410.1 | In range |
| CE300 | 12 · Sensible (Wh) | 12,667.3 | 12,559 | 12,810 | 12,637.4 | In range |
| CE300 | 12 · Latent (Wh) | 4,199.6 | 3,468.2 | 4,438.4 | 3,772.7 | In range |
| CE300 | 12 · Zone Hum. Rat. (kg/kg) | 0.01072 | 0.01043 | 0.01094 | 0.01071 | In range |
| CE300 | 12 · COP2 | 2.935 | 2.914 | 2.950 | 2.932 | In range |
| CE300 | 12 · ODB (°C) | 30.808 | 30.556 | 30.850 | 30.658 | In range |
| CE300 | 12 · EDB (°C) | 25.875 | 25.588 | 25.871 | 25.805 | Above range |
| CE300 | 12 · EWB (°C) | 19.240 | 18.867 | 19.230 | 19.076 | Above range |
| CE300 | 12 · Outdoor Hum. Rat. (kg/kg) | 0.01383 | 0.01321 | 0.01404 | 0.01351 | In range |
| CE300 | 13 · Energy Consumption Compressor (Wh) | 6,556.2 | 6,036 | 7,132.8 | 6,382.3 | In range |
| CE300 | 13 · Cond Fan (Wh) | 651.06 | 597 | 642 | 618.98 | Above range |
| CE300 | 13 · Evaporator Coil Load Total (Wh) | 21,775.8 | 19,621.0 | 21,588.4 | 20,616.7 | Above range |
| CE300 | 13 · Sensible (Wh) | 17,369.2 | 16,816.1 | 17,430.7 | 17,224.1 | In range |
| CE300 | 13 · Latent (Wh) | 4,406.5 | 2,485.8 | 4,187.1 | 3,392.8 | Above range |
| CE300 | 13 · Zone Hum. Rat. (kg/kg) | 0.01007 | 0.009971 | 0.01039 | 0.01012 | In range |
| CE300 | 13 · COP2 | 3.021 | 2.957 | 3.027 | 2.988 | In range |
| CE300 | 13 · ODB (°C) | 30.892 | 30.850 | 31.111 | 31.031 | In range |
| CE300 | 13 · EDB (°C) | 25.888 | 25.884 | 26.530 | 26.026 | In range |
| CE300 | 13 · EWB (°C) | 18.705 | 18.326 | 18.838 | 18.576 | In range |
| CE300 | 13 · Outdoor Hum. Rat. (kg/kg) | 0.01208 | 0.01129 | 0.01231 | 0.01165 | In range |
| CE300 | 14 · Energy Consumption Compressor (Wh) | 6,424.6 | 6,210.9 | 6,983.3 | 6,511.6 | In range |
| CE300 | 14 · Cond Fan (Wh) | 636.72 | 616.12 | 645 | 633.82 | In range |
| CE300 | 14 · Evaporator Coil Load Total (Wh) | 20,843.8 | 20,234.1 | 21,067 | 20,777.0 | In range |
| CE300 | 14 · Sensible (Wh) | 17,571.2 | 17,283.5 | 17,639.1 | 17,565.0 | In range |
| CE300 | 14 · Latent (Wh) | 3,272.6 | 2,950.6 | 3,446.8 | 3,211.9 | In range |
| CE300 | 14 · Zone Hum. Rat. (kg/kg) | 0.009622 | 0.009744 | 0.01000 | 0.009881 | Below range |
| CE300 | 14 · COP2 | 2.952 | 2.939 | 2.964 | 2.951 | In range |
| CE300 | 14 · ODB (°C) | 31.450 | 31.400 | 31.700 | 31.601 | In range |
| CE300 | 14 · EDB (°C) | 25.974 | 25.968 | 26.562 | 26.111 | In range |
| CE300 | 14 · EWB (°C) | 18.273 | 18.269 | 18.600 | 18.493 | In range |
| CE300 | 14 · Outdoor Hum. Rat. (kg/kg) | 0.01151 | 0.01152 | 0.01210 | 0.01178 | Below range |
| CE300 | 15 · Energy Consumption Compressor (Wh) | 7,895.1 | 7,671 | 8,572.0 | 7,981.5 | In range |
| CE300 | 15 · Cond Fan (Wh) | 776.78 | 751 | 785 | 771.18 | In range |
| CE300 | 15 · Evaporator Coil Load Total (Wh) | 26,369.3 | 25,387.1 | 27,069.8 | 26,217.7 | In range |
| CE300 | 15 · Sensible (Wh) | 22,451.0 | 22,196.5 | 22,882.4 | 22,432.9 | In range |
| CE300 | 15 · Latent (Wh) | 3,918.3 | 3,190.7 | 4,719.5 | 3,784.7 | In range |
| CE300 | 15 · Zone Hum. Rat. (kg/kg) | 0.009468 | 0.009579 | 0.009810 | 0.009725 | Below range |
| CE300 | 15 · COP2 | 3.041 | 3.010 | 3.067 | 3.040 | In range |
| CE300 | 15 · ODB (°C) | 31.992 | 31.950 | 32.222 | 32.134 | In range |
| CE300 | 15 · EDB (°C) | 26.056 | 26.051 | 26.781 | 26.211 | In range |
| CE300 | 15 · EWB (°C) | 18.257 | 18.239 | 18.647 | 18.471 | In range |
| CE300 | 15 · Outdoor Hum. Rat. (kg/kg) | 0.01206 | 0.01190 | 0.01238 | 0.01211 | In range |
| CE300 | 16 · Energy Consumption Compressor (Wh) | 8,060.2 | 7,964.8 | 8,732.7 | 8,235.4 | In range |
| CE300 | 16 · Cond Fan (Wh) | 788.55 | 781.01 | 803 | 795.32 | In range |
| CE300 | 16 · Evaporator Coil Load Total (Wh) | 26,966.6 | 26,664.6 | 27,721.1 | 27,288.1 | In range |
| CE300 | 16 · Sensible (Wh) | 22,532.5 | 22,284.7 | 22,557.3 | 22,447.7 | In range |
| CE300 | 16 · Latent (Wh) | 4,434.2 | 4,107.3 | 5,331.3 | 4,840.4 | In range |
| CE300 | 16 · Zone Hum. Rat. (kg/kg) | 0.009592 | 0.009666 | 0.01000 | 0.009824 | Below range |
| CE300 | 16 · COP2 | 3.048 | 3.053 | 3.094 | 3.067 | Below range |
| CE300 | 16 · ODB (°C) | 32.200 | 32.200 | 32.222 | 32.207 | In range |
| CE300 | 16 · EDB (°C) | 26.089 | 26.032 | 26.563 | 26.182 | In range |
| CE300 | 16 · EWB (°C) | 18.462 | 18.557 | 18.840 | 18.725 | Below range |
| CE300 | 16 · Outdoor Hum. Rat. (kg/kg) | 0.01341 | 0.01332 | 0.01440 | 0.01400 | In range |
| CE300 | 17 · Energy Consumption Compressor (Wh) | 5,331.5 | 5,211.8 | 5,718.3 | 5,511.3 | In range |
| CE300 | 17 · Cond Fan (Wh) | 519.61 | 509.58 | 561 | 535.02 | In range |
| CE300 | 17 · Evaporator Coil Load Total (Wh) | 16,730.1 | 16,344.6 | 18,244.6 | 17,213.0 | In range |
| CE300 | 17 · Sensible (Wh) | 13,065.8 | 12,739.1 | 13,600.1 | 13,164.5 | In range |
| CE300 | 17 · Latent (Wh) | 3,664.3 | 3,283.1 | 4,644.5 | 4,048.5 | In range |
| CE300 | 17 · Zone Hum. Rat. (kg/kg) | 0.01041 | 0.01026 | 0.01077 | 0.01058 | In range |
| CE300 | 17 · COP2 | 2.859 | 2.858 | 2.918 | 2.889 | In range |
| CE300 | 17 · ODB (°C) | 31.908 | 31.667 | 31.950 | 31.762 | In range |
| CE300 | 17 · EDB (°C) | 26.044 | 25.943 | 26.198 | 26.048 | In range |
| CE300 | 17 · EWB (°C) | 19.033 | 19.063 | 19.403 | 19.255 | Below range |
| CE300 | 17 · Outdoor Hum. Rat. (kg/kg) | 0.01448 | 0.01449 | 0.01473 | 0.01460 | Below range |
| CE300 | 18 · Energy Consumption Compressor (Wh) | 5,470.7 | 5,122.3 | 5,880.6 | 5,476.8 | In range |
| CE300 | 18 · Cond Fan (Wh) | 533.69 | 506.96 | 544 | 529.87 | In range |
| CE300 | 18 · Evaporator Coil Load Total (Wh) | 17,579.9 | 16,829.6 | 17,977.9 | 17,458.7 | In range |
| CE300 | 18 · Sensible (Wh) | 12,866.4 | 12,180.9 | 12,869.6 | 12,693.6 | In range |
| CE300 | 18 · Latent (Wh) | 4,713.5 | 4,323.8 | 5,146.2 | 4,764.9 | In range |
| CE300 | 18 · Zone Hum. Rat. (kg/kg) | 0.01097 | 0.01086 | 0.01120 | 0.01109 | In range |
| CE300 | 18 · COP2 | 2.928 | 2.924 | 2.990 | 2.950 | In range |
| CE300 | 18 · ODB (°C) | 31.350 | 31.100 | 31.400 | 31.191 | In range |
| CE300 | 18 · EDB (°C) | 25.959 | 25.695 | 26.226 | 25.946 | In range |
| CE300 | 18 · EWB (°C) | 19.527 | 19.394 | 19.772 | 19.611 | In range |
| CE300 | 18 · Outdoor Hum. Rat. (kg/kg) | 0.01525 | 0.01523 | 0.01570 | 0.01554 | In range |
| CE300 | 19 · Energy Consumption Compressor (Wh) | 5,152.1 | 4,689 | 5,555.1 | 4,973.0 | In range |
| CE300 | 19 · Cond Fan (Wh) | 516.25 | 479 | 529.23 | 494.84 | In range |
| CE300 | 19 · Evaporator Coil Load Total (Wh) | 17,212.1 | 15,914.5 | 17,661.7 | 16,555.5 | In range |
| CE300 | 19 · Sensible (Wh) | 12,198.8 | 11,540.7 | 12,490.8 | 11,951.5 | In range |
| CE300 | 19 · Latent (Wh) | 5,013.3 | 4,043.3 | 5,170.9 | 4,603.8 | In range |
| CE300 | 19 · Zone Hum. Rat. (kg/kg) | 0.01109 | 0.01091 | 0.01131 | 0.01108 | In range |
| CE300 | 19 · COP2 | 3.037 | 3.038 | 3.124 | 3.075 | Below range |
| CE300 | 19 · ODB (°C) | 29.467 | 28.300 | 29.700 | 28.719 | In range |
| CE300 | 19 · EDB (°C) | 25.674 | 25.409 | 25.700 | 25.544 | In range |
| CE300 | 19 · EWB (°C) | 19.533 | 19.199 | 19.575 | 19.405 | In range |
| CE300 | 19 · Outdoor Hum. Rat. (kg/kg) | 0.01498 | 0.01430 | 0.01513 | 0.01461 | In range |
| CE300 | 20 · Energy Consumption Compressor (Wh) | 4,837.1 | 4,809 | 5,259.2 | 4,922.9 | In range |
| CE300 | 20 · Cond Fan (Wh) | 498.18 | 498 | 506.22 | 502.49 | In range |
| CE300 | 20 · Evaporator Coil Load Total (Wh) | 16,786.8 | 16,536.5 | 17,131.1 | 16,954.5 | In range |
| CE300 | 20 · Sensible (Wh) | 11,562.5 | 11,359.2 | 11,655.3 | 11,502.9 | In range |
| CE300 | 20 · Latent (Wh) | 5,224.2 | 4,980.9 | 5,771.9 | 5,451.6 | In range |
| CE300 | 20 · Zone Hum. Rat. (kg/kg) | 0.01110 | 0.01099 | 0.01140 | 0.01128 | In range |
| CE300 | 20 · COP2 | 3.146 | 3.144 | 3.195 | 3.174 | In range |
| CE300 | 20 · ODB (°C) | 27.658 | 27.200 | 27.750 | 27.368 | In range |
| CE300 | 20 · EDB (°C) | 25.402 | 25.167 | 25.392 | 25.314 | Above range |
| CE300 | 20 · EWB (°C) | 19.524 | 19.372 | 19.760 | 19.657 | In range |
| CE300 | 20 · Outdoor Hum. Rat. (kg/kg) | 0.01587 | 0.01575 | 0.01688 | 0.01636 | In range |
| CE300 | 21 · Energy Consumption Compressor (Wh) | 3,977.7 | 3,913 | 4,325.7 | 3,995.0 | In range |
| CE300 | 21 · Cond Fan (Wh) | 411.05 | 405 | 409.08 | 406.73 | Above range |
| CE300 | 21 · Evaporator Coil Load Total (Wh) | 13,675.2 | 13,435.4 | 13,539.9 | 13,479.1 | Above range |
| CE300 | 21 · Sensible (Wh) | 9,058.9 | 8,882.2 | 9,302.7 | 9,086.2 | In range |
| CE300 | 21 · Latent (Wh) | 4,616.3 | 4,133.0 | 4,657.8 | 4,392.7 | In range |
| CE300 | 21 · Zone Hum. Rat. (kg/kg) | 0.01135 | 0.01114 | 0.01156 | 0.01134 | In range |
| CE300 | 21 · COP2 | 3.116 | 3.102 | 3.115 | 3.110 | Above range |
| CE300 | 21 · ODB (°C) | 27.200 | 27.200 | 27.222 | 27.207 | In range |
| CE300 | 21 · EDB (°C) | 25.333 | 24.654 | 25.333 | 25.212 | In range |
| CE300 | 21 · EWB (°C) | 19.792 | 19.438 | 19.760 | 19.682 | Above range |
| CE300 | 21 · Outdoor Hum. Rat. (kg/kg) | 0.01681 | 0.01640 | 0.01689 | 0.01670 | In range |
| CE300 | 22 · Energy Consumption Compressor (Wh) | 3,934.0 | 3,823 | 4,278.9 | 3,924.5 | In range |
| CE300 | 22 · Cond Fan (Wh) | 408.23 | 398.94 | 409.53 | 401.69 | In range |
| CE300 | 22 · Evaporator Coil Load Total (Wh) | 13,613.8 | 13,280.4 | 13,564.5 | 13,365.7 | Above range |
| CE300 | 22 · Sensible (Wh) | 8,954.3 | 8,747.2 | 8,973.8 | 8,898.6 | In range |
| CE300 | 22 · Latent (Wh) | 4,659.4 | 4,306.8 | 4,684.3 | 4,467.3 | In range |
| CE300 | 22 · Zone Hum. Rat. (kg/kg) | 0.01139 | 0.01118 | 0.01160 | 0.01139 | In range |
| CE300 | 22 · COP2 | 3.135 | 3.129 | 3.148 | 3.138 | In range |
| CE300 | 22 · ODB (°C) | 26.908 | 26.667 | 26.950 | 26.762 | In range |
| CE300 | 22 · EDB (°C) | 25.289 | 24.744 | 25.285 | 25.156 | Above range |
| CE300 | 22 · EWB (°C) | 19.816 | 19.485 | 19.800 | 19.714 | Above range |
| CE300 | 22 · Outdoor Hum. Rat. (kg/kg) | 0.01677 | 0.01670 | 0.01686 | 0.01677 | In range |
| CE300 | 23 · Energy Consumption Compressor (Wh) | 3,830.9 | 3,748 | 4,172.6 | 3,892.1 | In range |
| CE300 | 23 · Cond Fan (Wh) | 401.07 | 394 | 433.86 | 403.03 | In range |
| CE300 | 23 · Evaporator Coil Load Total (Wh) | 13,407.0 | 13,139 | 14,531.3 | 13,431.4 | In range |
| CE300 | 23 · Sensible (Wh) | 8,756.4 | 8,646.8 | 9,449.4 | 8,846.7 | In range |
| CE300 | 23 · Latent (Wh) | 4,650.7 | 4,404.4 | 5,082.0 | 4,584.5 | In range |
| CE300 | 23 · Zone Hum. Rat. (kg/kg) | 0.01140 | 0.01118 | 0.01161 | 0.01144 | In range |
| CE300 | 23 · COP2 | 3.168 | 3.161 | 3.189 | 3.177 | In range |
| CE300 | 23 · ODB (°C) | 26.350 | 26.100 | 26.400 | 26.191 | In range |
| CE300 | 23 · EDB (°C) | 25.204 | 24.671 | 25.200 | 25.070 | Above range |
| CE300 | 23 · EWB (°C) | 19.800 | 19.469 | 19.840 | 19.736 | In range |
| CE300 | 23 · Outdoor Hum. Rat. (kg/kg) | 0.01678 | 0.01676 | 0.01690 | 0.01686 | In range |
| CE300 | 24 · Energy Consumption Compressor (Wh) | 3,805.7 | 3,664.2 | 4,152.0 | 3,874.6 | In range |
| CE300 | 24 · Cond Fan (Wh) | 399.74 | 385.64 | 409.58 | 401.64 | In range |
| CE300 | 24 · Evaporator Coil Load Total (Wh) | 13,403.7 | 12,972.7 | 13,754.3 | 13,443.7 | In range |
| CE300 | 24 · Sensible (Wh) | 8,667.7 | 8,359.6 | 8,806.5 | 8,682.5 | In range |
| CE300 | 24 · Latent (Wh) | 4,735.9 | 4,522.2 | 4,954.6 | 4,761.1 | In range |
| CE300 | 24 · Zone Hum. Rat. (kg/kg) | 0.01146 | 0.01127 | 0.01170 | 0.01155 | In range |
| CE300 | 24 · COP2 | 3.187 | 3.177 | 3.208 | 3.194 | In range |
| CE300 | 24 · ODB (°C) | 26.100 | 26.100 | 26.111 | 26.104 | In range |
| CE300 | 24 · EDB (°C) | 25.166 | 24.726 | 25.166 | 25.052 | In range |
| CE300 | 24 · EWB (°C) | 19.847 | 19.573 | 20.140 | 19.869 | In range |
| CE300 | 24 · Outdoor Hum. Rat. (kg/kg) | 0.01706 | 0.01706 | 0.01780 | 0.01740 | Below range |
CE b COP2, IDB, humidity and RH extremes480 rows · 35 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Status |
|---|---|---|---|---|---|---|
| CE300 | COP2 | 3.919 | 3.857 | 4.168 | 3.928 | In range |
| CE300 | Maximum Date | Apr 30 | ||||
| CE300 | C O P 2 Hour | 15 | ||||
| CE300 | COP2 | 2.776 | 2.782 | 2.810 | 2.795 | Below range |
| CE300 | Minimum Date | Jun 13 | ||||
| CE300 | Hour | 17 | ||||
| CE300 | °C | 25.007 | 25.002 | 26.200 | 25.444 | In range |
| CE300 | Indoor Drybulb Temperature Maximum Date | Oct 11 | ||||
| CE300 | Hour | 16 | ||||
| CE300 | °C | 8.458 | 6.990 | 8.890 | 8.226 | In range |
| CE300 | Minimum* Date | Jan 6 | ||||
| CE300 | Hour | 6 | ||||
| CE300 | kg/kg | 0.01354 | 0.01328 | 0.01380 | 0.01354 | In range |
| CE300 | Humidity Ratio Maximum Date | Nov 16 | ||||
| CE300 | Hour | 17 | ||||
| CE300 | kg/kg | 0.001902 | 0.001700 | 0.001970 | 0.001857 | In range |
| CE300 | Minimum* Date | Jan 11 | ||||
| CE300 | Hour | 3 | ||||
| CE300 | % | 67.864 | 67.440 | 69.350 | 68.466 | In range |
| CE300 | Relative Humidity Maximum* Date | Nov 16 | ||||
| CE300 | Hour | 17 | ||||
| CE300 | % | 13.852 | 11.970 | 15 | 13.602 | In range |
| CE300 | Minimum* Date | Nov 6 | ||||
| CE300 | Hour | 6 | ||||
| CE310 | COP2 | 4.186 | 4.120 | 4.173 | 4.139 | Above range |
| CE310 | Maximum Date | Apr 30 | ||||
| CE310 | C O P 2 Hour | 15 | ||||
| CE310 | COP2 | 2.863 | 2.850 | 2.893 | 2.867 | In range |
| CE310 | Minimum Date | Dec 1 | ||||
| CE310 | Hour | 15 | ||||
| CE310 | °C | 26.704 | 26.475 | 27.190 | 26.829 | In range |
| CE310 | Indoor Drybulb Temperature Maximum Date | Jul 20 | ||||
| CE310 | Hour | 16 | ||||
| CE310 | °C | 8.458 | 6.990 | 8.890 | 8.226 | In range |
| CE310 | Minimum* Date | Jan 6 | ||||
| CE310 | Hour | 6 | ||||
| CE310 | kg/kg | 0.01550 | 0.01543 | 0.01890 | 0.01670 | In range |
| CE310 | Humidity Ratio Maximum Date | Oct 1 | ||||
| CE310 | Hour | 8 | ||||
| CE310 | kg/kg | 0.001923 | 0.001700 | 0.002019 | 0.001867 | In range |
| CE310 | Minimum* Date | Jan 11 | ||||
| CE310 | Hour | 3 | ||||
| CE310 | % | 77.848 | 77 | 100.70 | 85.403 | In range |
| CE310 | Relative Humidity Maximum* Date | Oct 2 | ||||
| CE310 | Hour | 8 | ||||
| CE310 | % | 14.609 | 11.970 | 16 | 14.127 | In range |
| CE310 | Minimum* Date | Nov 6 | ||||
| CE310 | Hour | 7 | ||||
| CE320 | COP2 | 3.961 | 3.940 | 5.143 | 4.424 | In range |
| CE320 | Maximum Date | Sep 16 | ||||
| CE320 | C O P 2 Hour | 15 | ||||
| CE320 | COP2 | 2.823 | 2.801 | 2.842 | 2.820 | In range |
| CE320 | Minimum Date | Mar 31 | ||||
| CE320 | Hour | 15 | ||||
| CE320 | °C | 31.915 | 31.500 | 32.360 | 31.858 | In range |
| CE320 | Indoor Drybulb Temperature Maximum Date | Jul 20 | ||||
| CE320 | Hour | 15 | ||||
| CE320 | °C | 7.470 | 6.990 | 10.830 | 8.714 | In range |
| CE320 | Minimum* Date | Jan 6 | ||||
| CE320 | Hour | 6 | ||||
| CE320 | kg/kg | 0.01775 | 0.01755 | 0.01802 | 0.01773 | In range |
| CE320 | Humidity Ratio Maximum Date | Jul 10 | ||||
| CE320 | Hour | 13 | ||||
| CE320 | kg/kg | 0.001905 | 0.001700 | 0.001970 | 0.001858 | In range |
| CE320 | Minimum* Date | Jan 11 | ||||
| CE320 | Hour | 3 | ||||
| CE320 | % | 82.717 | 81.836 | 83.670 | 82.794 | In range |
| CE320 | Relative Humidity Maximum* Date | Sep 18 | ||||
| CE320 | Hour | 10 | ||||
| CE320 | % | 14.128 | 11.970 | 15 | 13.305 | In range |
| CE320 | Minimum* Date | Nov 6 | ||||
| CE320 | Hour | 6 | ||||
| CE330 | COP2 | 4.092 | 4.050 | 5.595 | 4.353 | In range |
| CE330 | Maximum Date | Sep 16 | ||||
| CE330 | C O P 2 Hour | 14 | ||||
| CE330 | COP2 | 2.828 | 2.798 | 2.844 | 2.822 | In range |
| CE330 | Minimum Date | Mar 31 | ||||
| CE330 | Hour | 15 | ||||
| CE330 | °C | 31.586 | 31.069 | 32.232 | 31.703 | In range |
| CE330 | Indoor Drybulb Temperature Maximum Date | Jul 20 | ||||
| CE330 | Hour | 15 | ||||
| CE330 | °C | 8.458 | 6.990 | 8.890 | 8.226 | In range |
| CE330 | Minimum* Date | Jan 6 | ||||
| CE330 | Hour | 6 | ||||
| CE330 | kg/kg | 0.01778 | 0.01705 | 0.01793 | 0.01764 | In range |
| CE330 | Humidity Ratio Maximum Date | Jul 10 | ||||
| CE330 | Hour | 12 | ||||
| CE330 | kg/kg | 0.001902 | 0.001700 | 0.001970 | 0.001857 | In range |
| CE330 | Minimum* Date | Jan 11 | ||||
| CE330 | Hour | 3 | ||||
| CE330 | % | 76.642 | 76 | 78.700 | 77.439 | In range |
| CE330 | Relative Humidity Maximum* Date | Sep 22 | ||||
| CE330 | Hour | 20 | ||||
| CE330 | % | 13.852 | 11.970 | 15 | 13.602 | In range |
| CE330 | Minimum* Date | Nov 6 | ||||
| CE330 | Hour | 6 | ||||
| CE340 | COP2 | 4.015 | 3.950 | 5.339 | 4.347 | In range |
| CE340 | Maximum Date | Sep 16 | ||||
| CE340 | C O P 2 Hour | 15 | ||||
| CE340 | COP2 | 2.828 | 2.798 | 2.844 | 2.822 | In range |
| CE340 | Minimum Date | Mar 31 | ||||
| CE340 | Hour | 15 | ||||
| CE340 | °C | 31.846 | 31.498 | 32.307 | 31.784 | In range |
| CE340 | Indoor Drybulb Temperature Maximum Date | Jul 20 | ||||
| CE340 | Hour | 15 | ||||
| CE340 | °C | 8.458 | 6.990 | 8.890 | 8.226 | In range |
| CE340 | Minimum* Date | Jan 6 | ||||
| CE340 | Hour | 6 | ||||
| CE340 | kg/kg | 0.01771 | 0.01727 | 0.01787 | 0.01762 | In range |
| CE340 | Humidity Ratio Maximum Date | Jul 10 | ||||
| CE340 | Hour | 13 | ||||
| CE340 | kg/kg | 0.001902 | 0.001700 | 0.001970 | 0.001857 | In range |
| CE340 | Minimum* Date | Jan 11 | ||||
| CE340 | Hour | 3 | ||||
| CE340 | % | 80.545 | 79.929 | 81.370 | 80.601 | In range |
| CE340 | Relative Humidity Maximum* Date | Sep 18 | ||||
| CE340 | Hour | 10 | ||||
| CE340 | % | 13.852 | 11.970 | 15 | 13.602 | In range |
| CE340 | Minimum* Date | Nov 6 | ||||
| CE340 | Hour | 6 | ||||
| CE350 | COP2 | 4.454 | 3.863 | 4.555 | 4.048 | In range |
| CE350 | Maximum Date | Oct 13 | ||||
| CE350 | C O P 2 Hour | 1 | ||||
| CE350 | COP2 | 2.776 | 2.782 | 2.810 | 2.794 | Below range |
| CE350 | Minimum Date | Jun 13 | ||||
| CE350 | Hour | 17 | ||||
| CE350 | °C | 35.003 | 34.584 | 35.002 | 34.911 | Above range |
| CE350 | Indoor Drybulb Temperature Maximum Date | May 30 | ||||
| CE350 | Hour | 3 | ||||
| CE350 | °C | 8.458 | 6.990 | 8.890 | 8.226 | In range |
| CE350 | Minimum* Date | Jan 6 | ||||
| CE350 | Hour | 6 | ||||
| CE350 | kg/kg | 0.01698 | 0.01648 | 0.01990 | 0.01780 | In range |
| CE350 | Humidity Ratio Maximum Date | Oct 2 | ||||
| CE350 | Hour | 1 | ||||
| CE350 | kg/kg | 0.001902 | 0.001700 | 0.001970 | 0.001857 | In range |
| CE350 | Minimum* Date | Jan 11 | ||||
| CE350 | Hour | 3 | ||||
| CE350 | % | 67.864 | 68.367 | 81.120 | 73.674 | Below range |
| CE350 | Relative Humidity Maximum* Date | Nov 16 | ||||
| CE350 | Hour | 17 | ||||
| CE350 | % | 13.852 | 11.970 | 15 | 13.602 | In range |
| CE350 | Minimum* Date | Nov 6 | ||||
| CE350 | Hour | 6 | ||||
| CE360 | COP2 | 4.427 | 4.401 | 4.455 | 4.431 | In range |
| CE360 | Maximum Date | Oct 5 | ||||
| CE360 | C O P 2 Hour | 1 | ||||
| CE360 | COP2 | 2.828 | 2.799 | 2.844 | 2.822 | In range |
| CE360 | Minimum Date | Mar 31 | ||||
| CE360 | Hour | 15 | ||||
| CE360 | °C | 33.037 | 32.511 | 33.758 | 32.957 | In range |
| CE360 | Indoor Drybulb Temperature Maximum Date | Jul 10 | ||||
| CE360 | Hour | 13 | ||||
| CE360 | °C | 8.458 | 6.990 | 8.890 | 8.226 | In range |
| CE360 | Minimum* Date | Jan 6 | ||||
| CE360 | Hour | 6 | ||||
| CE360 | kg/kg | 0.01358 | 0.01340 | 0.01386 | 0.01361 | In range |
| CE360 | Humidity Ratio Maximum Date | Jul 10 | ||||
| CE360 | Hour | 13 | ||||
| CE360 | kg/kg | 0.001902 | 0.001700 | 0.001970 | 0.001857 | In range |
| CE360 | Minimum* Date | Jan 11 | ||||
| CE360 | Hour | 3 | ||||
| CE360 | % | 67.864 | 67.440 | 69.350 | 68.466 | In range |
| CE360 | Relative Humidity Maximum* Date | Nov 16 | ||||
| CE360 | Hour | 17 | ||||
| CE360 | % | 13.852 | 11.970 | 15 | 13.602 | In range |
| CE360 | Minimum* Date | Nov 6 | ||||
| CE360 | Hour | 6 | ||||
| CE400 | COP2 | 4.092 | 4.050 | 4.776 | 4.212 | In range |
| CE400 | Maximum Date | Sep 16 | ||||
| CE400 | C O P 2 Hour | 14 | ||||
| CE400 | COP2 | 2.776 | 2.734 | 2.810 | 2.768 | In range |
| CE400 | Minimum Date | Jun 13 | ||||
| CE400 | Hour | 17 | ||||
| CE400 | °C | 26.937 | 26.040 | 28.830 | 27.291 | In range |
| CE400 | Indoor Drybulb Temperature Maximum Date | Sep 16 | ||||
| CE400 | Hour | 16 | ||||
| CE400 | °C | 8.458 | 6.990 | 8.890 | 8.272 | In range |
| CE400 | Minimum* Date | Jan 6 | ||||
| CE400 | Hour | 6 | ||||
| CE400 | kg/kg | 0.01689 | 0.01688 | 0.01730 | 0.01702 | In range |
| CE400 | Humidity Ratio Maximum Date | Apr 5 | ||||
| CE400 | Hour | 22 | ||||
| CE400 | kg/kg | 0.001902 | 0.001700 | 0.001970 | 0.001835 | In range |
| CE400 | Minimum* Date | Jan 11 | ||||
| CE400 | Hour | 3 | ||||
| CE400 | % | 84.605 | 83.753 | 86.310 | 85.168 | In range |
| CE400 | Relative Humidity Maximum* Date | Apr 5 | ||||
| CE400 | Hour | 22 | ||||
| CE400 | % | 13.679 | 11.970 | 14.570 | 13.129 | In range |
| CE400 | Minimum* Date | Nov 6 | ||||
| CE400 | Hour | 6 | ||||
| CE410 | COP2 | 4.018 | 3.840 | 3.903 | 3.871 | Above range |
| CE410 | Maximum Date | Apr 30 | ||||
| CE410 | C O P 2 Hour | 15 | ||||
| CE410 | COP2 | 2.776 | 2.786 | 2.810 | 2.799 | Below range |
| CE410 | Minimum Date | Jun 13 | ||||
| CE410 | Hour | 17 | ||||
| CE410 | °C | 25.007 | 25.110 | 26.826 | 25.809 | Below range |
| CE410 | Indoor Drybulb Temperature Maximum Date | Oct 11 | ||||
| CE410 | Hour | 16 | ||||
| CE410 | °C | 8.458 | 6.990 | 8.890 | 8.160 | In range |
| CE410 | Minimum* Date | Jan 6 | ||||
| CE410 | Hour | 6 | ||||
| CE410 | kg/kg | 0.01643 | 0.01684 | 0.01730 | 0.01698 | Below range |
| CE410 | Humidity Ratio Maximum Date | Apr 5 | ||||
| CE410 | Hour | 24 | ||||
| CE410 | kg/kg | 0.001902 | 0.001700 | 0.001970 | 0.001812 | In range |
| CE410 | Minimum* Date | Jan 11 | ||||
| CE410 | Hour | 3 | ||||
| CE410 | % | 82.365 | 83.225 | 86.180 | 84.746 | Below range |
| CE410 | Relative Humidity Maximum* Date | Apr 6 | ||||
| CE410 | Hour | 1 | ||||
| CE410 | % | 13.679 | 11.970 | 14.580 | 12.932 | In range |
| CE410 | Minimum* Date | Nov 6 | ||||
| CE410 | Hour | 6 | ||||
| CE420 | COP2 | 3.831 | 3.759 | 3.940 | 3.822 | In range |
| CE420 | Maximum Date | May 21 | ||||
| CE420 | C O P 2 Hour | 15 | ||||
| CE420 | COP2 | 2.776 | 2.782 | 2.810 | 2.797 | Below range |
| CE420 | Minimum Date | Jun 13 | ||||
| CE420 | Hour | 17 | ||||
| CE420 | °C | 25.007 | 25.002 | 26.230 | 25.530 | In range |
| CE420 | Indoor Drybulb Temperature Maximum Date | Oct 11 | ||||
| CE420 | Hour | 16 | ||||
| CE420 | °C | 8.458 | 6.990 | 8.890 | 8.272 | In range |
| CE420 | Minimum* Date | Jan 6 | ||||
| CE420 | Hour | 6 | ||||
| CE420 | kg/kg | 0.01461 | 0.01410 | 0.01470 | 0.01448 | In range |
| CE420 | Humidity Ratio Maximum Date | Apr 2 | ||||
| CE420 | Hour | 18 | ||||
| CE420 | kg/kg | 0.001902 | 0.001700 | 0.001970 | 0.001835 | In range |
| CE420 | Minimum* Date | Jan 11 | ||||
| CE420 | Hour | 3 | ||||
| CE420 | % | 73.291 | 70.841 | 74.510 | 72.803 | In range |
| CE420 | Relative Humidity Maximum* Date | Apr 2 | ||||
| CE420 | Hour | 18 | ||||
| CE420 | % | 13.679 | 11.970 | 14.590 | 13.133 | In range |
| CE420 | Minimum* Date | Nov 6 | ||||
| CE420 | Hour | 6 | ||||
| CE430 | COP2 | 3.798 | 3.759 | 3.930 | 3.814 | In range |
| CE430 | Maximum Date | May 21 | ||||
| CE430 | C O P 2 Hour | 15 | ||||
| CE430 | COP2 | 2.776 | 2.734 | 2.810 | 2.766 | In range |
| CE430 | Minimum Date | Jun 13 | ||||
| CE430 | Hour | 17 | ||||
| CE430 | °C | 25.007 | 25.003 | 27.199 | 25.774 | In range |
| CE430 | Indoor Drybulb Temperature Maximum Date | Oct 11 | ||||
| CE430 | Hour | 16 | ||||
| CE430 | °C | 8.458 | 6.990 | 8.890 | 8.272 | In range |
| CE430 | Minimum* Date | Jan 6 | ||||
| CE430 | Hour | 6 | ||||
| CE430 | kg/kg | 0.01617 | 0.01560 | 0.01623 | 0.01587 | In range |
| CE430 | Humidity Ratio Maximum Date | Apr 2 | ||||
| CE430 | Hour | 5 | ||||
| CE430 | kg/kg | 0.001902 | 0.001700 | 0.001970 | 0.001835 | In range |
| CE430 | Minimum* Date | Jan 11 | ||||
| CE430 | Hour | 3 | ||||
| CE430 | % | 80.828 | 78.430 | 80.743 | 79.450 | Above range |
| CE430 | Relative Humidity Maximum* Date | Apr 2 | ||||
| CE430 | Hour | 5 | ||||
| CE430 | % | 13.679 | 11.970 | 14.580 | 13.131 | In range |
| CE430 | Minimum* Date | Nov 6 | ||||
| CE430 | Hour | 6 | ||||
| CE440 | COP2 | 3.798 | 3.759 | 3.883 | 3.806 | In range |
| CE440 | Maximum Date | May 21 | ||||
| CE440 | C O P 2 Hour | 15 | ||||
| CE440 | COP2 | 2.776 | 2.734 | 2.810 | 2.769 | In range |
| CE440 | Minimum Date | Jun 13 | ||||
| CE440 | Hour | 17 | ||||
| CE440 | °C | 25.007 | 25.003 | 27.045 | 25.706 | In range |
| CE440 | Indoor Drybulb Temperature Maximum Date | Oct 11 | ||||
| CE440 | Hour | 16 | ||||
| CE440 | °C | 8.458 | 7 | 8.890 | 8.274 | In range |
| CE440 | Minimum* Date | Jan 6 | ||||
| CE440 | Hour | 6 | ||||
| CE440 | kg/kg | 0.01354 | 0.01331 | 0.01380 | 0.01357 | In range |
| CE440 | Humidity Ratio Maximum Date | Nov 16 | ||||
| CE440 | Hour | 17 | ||||
| CE440 | kg/kg | 0.001902 | 0.001700 | 0.001970 | 0.001835 | In range |
| CE440 | Minimum* Date | Jan 11 | ||||
| CE440 | Hour | 3 | ||||
| CE440 | % | 67.864 | 67.510 | 69.350 | 68.560 | In range |
| CE440 | Relative Humidity Maximum* Date | Nov 16 | ||||
| CE440 | Hour | 17 | ||||
| CE440 | % | 13.679 | 11.970 | 14.540 | 13.122 | In range |
| CE440 | Minimum* Date | Nov 6 | ||||
| CE440 | Hour | 6 | ||||
| CE500 | COP2 | 4.230 | 4.140 | 7.367 | 4.911 | In range |
| CE500 | Maximum Date | Mar 16 | ||||
| CE500 | C O P 2 Hour | 10 | ||||
| CE500 | COP2 | 2.696 | 2.652 | 2.710 | 2.685 | In range |
| CE500 | Minimum Date | Jul 30 | ||||
| CE500 | Hour | 12 | ||||
| CE500 | °C | 25.002 | 25.000 | 25.805 | 25.174 | In range |
| CE500 | Indoor Drybulb Temperature Maximum Date | Apr 13 | ||||
| CE500 | Hour | 19 | ||||
| CE500 | °C | 11.010 | 7.940 | 24.040 | 11.009 | In range |
| CE500 | Minimum* Date | Dec 21 | ||||
| CE500 | Hour | 6 | ||||
| CE500 | kg/kg | 0.01136 | 0.01150 | 0.01190 | 0.01172 | Below range |
| CE500 | Humidity Ratio Maximum Date | Jul 20 | ||||
| CE500 | Hour | 15 | ||||
| CE500 | kg/kg | 0.008094 | 0.006828 | 0.01030 | 0.007760 | In range |
| CE500 | Minimum* Date | Dec 20 | ||||
| CE500 | Hour | 12 | ||||
| CE500 | % | 100 | 60.080 | 100 | 90.020 | In range |
| CE500 | Relative Humidity Maximum* Date | Dec 12 | ||||
| CE500 | Hour | 20 | ||||
| CE500 | % | 53.169 | 52.830 | 55.167 | 53.851 | In range |
| CE500 | Minimum* Date | May 4 | ||||
| CE500 | Hour | 3 | ||||
| CE510 | COP2 | 4.704 | 4.530 | 7.367 | 5.211 | In range |
| CE510 | Maximum Date | Oct 5 | ||||
| CE510 | C O P 2 Hour | 1 | ||||
| CE510 | COP2 | 2.781 | 2.652 | 2.900 | 2.834 | In range |
| CE510 | Minimum Date | Mar 31 | ||||
| CE510 | Hour | 17 | ||||
| CE510 | °C | 25.009 | 25.000 | 26.100 | 25.223 | In range |
| CE510 | Indoor Drybulb Temperature Maximum Date | Jul 30 | ||||
| CE510 | Hour | 15 | ||||
| CE510 | °C | 11.010 | 7.940 | 24.040 | 11.009 | In range |
| CE510 | Minimum* Date | Dec 21 | ||||
| CE510 | Hour | 6 | ||||
| CE510 | kg/kg | 0.01138 | 0.01150 | 0.01190 | 0.01176 | Below range |
| CE510 | Humidity Ratio Maximum Date | Jul 20 | ||||
| CE510 | Hour | 15 | ||||
| CE510 | kg/kg | 0.008094 | 0.006828 | 0.01050 | 0.007810 | In range |
| CE510 | Minimum* Date | Dec 20 | ||||
| CE510 | Hour | 12 | ||||
| CE510 | % | 100 | 57.510 | 100 | 89.377 | In range |
| CE510 | Relative Humidity Maximum* Date | Dec 12 | ||||
| CE510 | Hour | 20 | ||||
| CE510 | % | 53.248 | 52.088 | 55.288 | 53.632 | In range |
| CE510 | Minimum* Date | May 4 | ||||
| CE510 | Hour | 4 | ||||
| CE520 | COP2 | 3.840 | 3.802 | 4.896 | 4.157 | In range |
| CE520 | Maximum Date | Apr 30 | ||||
| CE520 | C O P 2 Hour | 15 | ||||
| CE520 | COP2 | 2.452 | 2.333 | 2.532 | 2.439 | In range |
| CE520 | Minimum Date | Jan 31 | ||||
| CE520 | Hour | 14 | ||||
| CE520 | °C | 15.517 | 15.000 | 18.620 | 16.296 | In range |
| CE520 | Indoor Drybulb Temperature Maximum Date | Jul 20 | ||||
| CE520 | Hour | 16 | ||||
| CE520 | °C | 10.755 | 7.890 | 13.570 | 9.203 | In range |
| CE520 | Minimum* Date | Dec 21 | ||||
| CE520 | Hour | 6 | ||||
| CE520 | kg/kg | 0.007181 | 0.007024 | 0.01060 | 0.008038 | In range |
| CE520 | Humidity Ratio Maximum Date | Jul 20 | ||||
| CE520 | Hour | 16 | ||||
| CE520 | kg/kg | 0.005581 | 0.006103 | 0.006570 | 0.006430 | Below range |
| CE520 | Minimum* Date | Dec 9 | ||||
| CE520 | Hour | 19 | ||||
| CE520 | % | 70.436 | 71.770 | 95 | 87.703 | Below range |
| CE520 | Relative Humidity Maximum* Date | Dec 20 | ||||
| CE520 | Hour | 11 | ||||
| CE520 | % | 52.892 | 61 | 61.900 | 61.474 | Below range |
| CE520 | Minimum* Date | Dec 1 | ||||
| CE520 | Hour | 18 | ||||
| CE522 | COP2 | 4.010 | 3.986 | 6.233 | 4.654 | In range |
| CE522 | Maximum Date | Apr 30 | ||||
| CE522 | C O P 2 Hour | 15 | ||||
| CE522 | COP2 | 2.580 | 2.429 | 2.613 | 2.556 | In range |
| CE522 | Minimum Date | Jul 30 | ||||
| CE522 | Hour | 12 | ||||
| CE522 | °C | 20.002 | 20.000 | 21.009 | 20.368 | In range |
| CE522 | Indoor Drybulb Temperature Maximum Date | Apr 16 | ||||
| CE522 | Hour | 24 | ||||
| CE522 | °C | 10.979 | 7.940 | 15.980 | 9.657 | In range |
| CE522 | Minimum* Date | Dec 21 | ||||
| CE522 | Hour | 6 | ||||
| CE522 | kg/kg | 0.008969 | 0.009111 | 0.01380 | 0.01032 | Below range |
| CE522 | Humidity Ratio Maximum Date | Jul 20 | ||||
| CE522 | Hour | 15 | ||||
| CE522 | kg/kg | 0.008077 | 0.006821 | 0.007830 | 0.007136 | Above range |
| CE522 | Minimum* Date | Dec 20 | ||||
| CE522 | Hour | 12 | ||||
| CE522 | % | 100 | 71.320 | 100 | 92.830 | In range |
| CE522 | Relative Humidity Maximum* Date | Dec 19 | ||||
| CE522 | Hour | 20 | ||||
| CE522 | % | 57.603 | 57.970 | 60 | 58.914 | Below range |
| CE522 | Minimum* Date | Apr 30 | ||||
| CE522 | Hour | 4 | ||||
| CE525 | COP2 | 4.679 | 4.400 | 6.325 | 5.136 | In range |
| CE525 | Maximum Date | Mar 16 | ||||
| CE525 | C O P 2 Hour | 10 | ||||
| CE525 | COP2 | 2.933 | 2.814 | 2.940 | 2.900 | In range |
| CE525 | Minimum Date | Jul 30 | ||||
| CE525 | Hour | 12 | ||||
| CE525 | °C | 35.000 | 34.999 | 36.080 | 35.200 | In range |
| CE525 | Indoor Drybulb Temperature Maximum Date | Jul 8 | ||||
| CE525 | Hour | 18 | ||||
| CE525 | °C | 11.055 | 7.940 | 33.010 | 12.520 | In range |
| CE525 | Minimum* Date | Dec 21 | ||||
| CE525 | Hour | 6 | ||||
| CE525 | kg/kg | 0.01779 | 0.01730 | 0.01849 | 0.01789 | In range |
| CE525 | Humidity Ratio Maximum Date | Jul 20 | ||||
| CE525 | Hour | 15 | ||||
| CE525 | kg/kg | 0.008120 | 0.006836 | 0.01540 | 0.009047 | In range |
| CE525 | Minimum* Date | Dec 20 | ||||
| CE525 | Hour | 12 | ||||
| CE525 | % | 100 | 51.120 | 100 | 87.780 | In range |
| CE525 | Relative Humidity Maximum* Date | Nov 13 | ||||
| CE525 | Hour | 10 | ||||
| CE525 | % | 45.791 | 44 | 47.852 | 45.445 | In range |
| CE525 | Minimum* Date | Oct 5 | ||||
| CE525 | Hour | 2 | ||||
| CE530 | COP2 | 3.812 | 3.840 | 4.006 | 3.914 | Below range |
| CE530 | Maximum Date | Mar 16 | ||||
| CE530 | C O P 2 Hour | 10 | ||||
| CE530 | COP2 | 2.445 | 2.473 | 2.532 | 2.503 | Below range |
| CE530 | Minimum Date | Jul 30 | ||||
| CE530 | Hour | 12 | ||||
| CE530 | °C | 25.002 | 25 | 26.116 | 25.209 | In range |
| CE530 | Indoor Drybulb Temperature Maximum Date | Apr 13 | ||||
| CE530 | Hour | 19 | ||||
| CE530 | °C | 11.006 | 7.940 | 24.040 | 11.008 | In range |
| CE530 | Minimum* Date | Dec 21 | ||||
| CE530 | Hour | 6 | ||||
| CE530 | kg/kg | 0.002841 | 0.005491 | 0.008100 | 0.007038 | Below range |
| CE530 | Humidity Ratio Maximum Date | Dec 30 | ||||
| CE530 | Hour | 13 | ||||
| CE530 | kg/kg | 0.002841 | 0.005454 | 0.006735 | 0.006257 | Below range |
| CE530 | Minimum* Date | Apr 1 | ||||
| CE530 | Hour | 2 | ||||
| CE530 | % | 35.383 | 36.010 | 96.160 | 75.554 | Below range |
| CE530 | Relative Humidity Maximum* Date | Dec 20 | ||||
| CE530 | Hour | 11 | ||||
| CE530 | % | 14.388 | 28 | 34.028 | 31.325 | Below range |
| CE530 | Minimum* Date | Apr 18 | ||||
| CE530 | Hour | 18 | ||||
| CE540 | COP2 | 3.478 | 3.455 | 3.696 | 3.570 | In range |
| CE540 | Maximum Date | Mar 16 | ||||
| CE540 | C O P 2 Hour | 10 | ||||
| CE540 | COP2 | 2.268 | 2.143 | 2.383 | 2.264 | In range |
| CE540 | Minimum Date | Jul 30 | ||||
| CE540 | Hour | 12 | ||||
| CE540 | °C | 15.002 | 15 | 16.146 | 15.236 | In range |
| CE540 | Indoor Drybulb Temperature Maximum Date | Oct 29 | ||||
| CE540 | Hour | 5 | ||||
| CE540 | °C | 10.754 | 7.890 | 14.950 | 9.420 | In range |
| CE540 | Minimum* Date | Dec 21 | ||||
| CE540 | Hour | 6 | ||||
| CE540 | kg/kg | 0.002841 | 0.003256 | 0.006776 | 0.005626 | Below range |
| CE540 | Humidity Ratio Maximum Date | Dec 30 | ||||
| CE540 | Hour | 22 | ||||
| CE540 | kg/kg | 0.002841 | 0.003253 | 0.004200 | 0.003845 | Below range |
| CE540 | Minimum* Date | Apr 1 | ||||
| CE540 | Hour | 1 | ||||
| CE540 | % | 36.008 | 39.960 | 61.275 | 50.854 | Below range |
| CE540 | Relative Humidity Maximum* Date | Dec 20 | ||||
| CE540 | Hour | 11 | ||||
| CE540 | % | 26.737 | 31 | 39.740 | 35.804 | Below range |
| CE540 | Minimum* Date | Apr 18 | ||||
| CE540 | Hour | 17 | ||||
| CE545 | COP2 | 4.121 | 4.156 | 4.428 | 4.241 | Below range |
| CE545 | Maximum Date | Mar 16 | ||||
| CE545 | C O P 2 Hour | 10 | ||||
| CE545 | COP2 | 2.605 | 2.660 | 2.733 | 2.708 | Below range |
| CE545 | Minimum Date | Jul 30 | ||||
| CE545 | Hour | 12 | ||||
| CE545 | °C | 35.000 | 35 | 35.672 | 35.112 | In range |
| CE545 | Indoor Drybulb Temperature Maximum Date | Jul 8 | ||||
| CE545 | Hour | 18 | ||||
| CE545 | °C | 11.051 | 7.940 | 33.010 | 12.520 | In range |
| CE545 | Minimum* Date | Dec 21 | ||||
| CE545 | Hour | 6 | ||||
| CE545 | kg/kg | 0.002841 | 0.006689 | 0.01220 | 0.008747 | Below range |
| CE545 | Humidity Ratio Maximum Date | Dec 31 | ||||
| CE545 | Hour | 12 | ||||
| CE545 | kg/kg | 0.002841 | 0.006208 | 0.007000 | 0.006667 | Below range |
| CE545 | Minimum* Date | Apr 1 | ||||
| CE545 | Hour | 10 | ||||
| CE545 | % | 35.272 | 24.140 | 97 | 77.063 | In range |
| CE545 | Relative Humidity Maximum* Date | Dec 20 | ||||
| CE545 | Hour | 11 | ||||
| CE545 | % | 8.102 | 17.124 | 20.140 | 18.873 | Below range |
| CE545 | Minimum* Date | Apr 18 | ||||
| CE545 | Hour | 17 |
CE b CE500 daily22 rows · 6 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Status |
|---|---|---|---|---|---|---|
| CE500 | APRIL 30 · Energy Consumption Total (Wh) | 4,023.4 | 3,892.9 | 4,073 | 3,974.4 | In range |
| CE500 | APRIL 30 · Compressor (Wh) | 3,115.4 | 3,014.6 | 3,509.9 | 3,157.2 | In range |
| CE500 | APRIL 30 · Cond Fan (Wh) | 388.81 | 376.08 | 391 | 384.51 | In range |
| CE500 | APRIL 30 · Indoor Fan (Wh) | 519.24 | 466.42 | 522 | 496.64 | In range |
| CE500 | APRIL 30 · Evaporator Coil Load Total (Wh) | 13,656.5 | 13,169.5 | 13,732.9 | 13,524.9 | In range |
| CE500 | APRIL 30 · Sensible (Wh) | 9,851.9 | 9,365.5 | 9,925.0 | 9,729.3 | In range |
| CE500 | APRIL 30 · Latent (Wh) | 3,804.7 | 3,770 | 3,810.9 | 3,795.4 | In range |
| CE500 | APRIL 30 · Zone Hum Rat (kg/kg) | 0.01061 | 0.01068 | 0.01600 | 0.01177 | Below range |
| CE500 | APRIL 30 · COP2 | 3.897 | 3.837 | 3.914 | 3.868 | In range |
| CE500 | APRIL 30 · ODB (°C) | 16.807 | 16.792 | 16.960 | 16.853 | In range |
| CE500 | APRIL 30 · EDB (°C) | 25.000 | 24.641 | 25 | 24.919 | Above range |
| CE500 | JUNE 25 · Energy Consumption Total (Wh) | 5,250.3 | 5,044.9 | 5,230 | 5,163.1 | Above range |
| CE500 | JUNE 25 · Compressor (Wh) | 4,254.5 | 4,083.9 | 4,663.2 | 4,269.8 | In range |
| CE500 | JUNE 25 · Cond Fan (Wh) | 426.36 | 411.33 | 426.33 | 419.90 | Above range |
| CE500 | JUNE 25 · Indoor Fan (Wh) | 569.40 | 514.33 | 566 | 543.18 | Above range |
| CE500 | JUNE 25 · Evaporator Coil Load Total (Wh) | 13,739.5 | 13,188.1 | 13,837.5 | 13,586.9 | In range |
| CE500 | JUNE 25 · Sensible (Wh) | 9,929.4 | 9,377.7 | 9,981.2 | 9,771.0 | In range |
| CE500 | JUNE 25 · Latent (Wh) | 3,810.1 | 3,780 | 3,856.3 | 3,815.6 | In range |
| CE500 | JUNE 25 · Zone Hum Rat (kg/kg) | 0.01112 | 0.01100 | 0.01150 | 0.01135 | In range |
| CE500 | JUNE 25 · COP2 | 2.935 | 2.921 | 2.951 | 2.939 | In range |
| CE500 | JUNE 25 · ODB (°C) | 29.517 | 29.500 | 29.517 | 29.508 | In range |
| CE500 | JUNE 25 · EDB (°C) | 25.000 | 24.548 | 25 | 24.922 | Above range |
CE b CE530 daily22 rows · 13 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Status |
|---|---|---|---|---|---|---|
| CE530 | APRIL 30 · Energy Consumption Total (Wh) | 3,218.4 | 3,022.8 | 3,144 | 3,080.6 | Above range |
| CE530 | APRIL 30 · Compressor (Wh) | 2,460.9 | 2,311.5 | 2,689.0 | 2,428.3 | In range |
| CE530 | APRIL 30 · Cond Fan (Wh) | 324.39 | 304.56 | 314 | 309.24 | Above range |
| CE530 | APRIL 30 · Indoor Fan (Wh) | 433.21 | 360.75 | 419 | 394.57 | Above range |
| CE530 | APRIL 30 · Evaporator Coil Load Total (Wh) | 9,796.8 | 9,353.2 | 9,798 | 9,622.4 | In range |
| CE530 | APRIL 30 · Sensible (Wh) | 9,796.8 | 9,353.2 | 9,798 | 9,622.4 | In range |
| CE530 | APRIL 30 · Latent (Wh) | −1.07e-13 | −5.48e-13 | 5.71e-13 | 3.93e-15 | In range |
| CE530 | APRIL 30 · Zone Hum Rat (kg/kg) | 0.002841 | 0.005485 | 0.007100 | 0.006564 | Below range |
| CE530 | APRIL 30 · COP2 | 3.517 | 3.441 | 3.599 | 3.539 | In range |
| CE530 | APRIL 30 · ODB (°C) | 16.807 | 16.792 | 16.960 | 16.853 | In range |
| CE530 | APRIL 30 · EDB (°C) | 25.000 | 24.365 | 25.000 | 24.829 | Above range |
| CE530 | JUNE 25 · Energy Consumption Total (Wh) | 4,198.4 | 3,894.1 | 4,043 | 3,976.1 | Above range |
| CE530 | JUNE 25 · Compressor (Wh) | 3,359.9 | 3,118.1 | 3,578.6 | 3,266.0 | In range |
| CE530 | JUNE 25 · Cond Fan (Wh) | 359.03 | 329.25 | 340 | 336.16 | Above range |
| CE530 | JUNE 25 · Indoor Fan (Wh) | 479.48 | 395.50 | 454 | 429.78 | Above range |
| CE530 | JUNE 25 · Evaporator Coil Load Total (Wh) | 9,867.5 | 9,376.3 | 9,835.1 | 9,659.1 | Above range |
| CE530 | JUNE 25 · Sensible (Wh) | 9,867.5 | 9,376.3 | 9,835.1 | 9,659.1 | Above range |
| CE530 | JUNE 25 · Latent (Wh) | −8.21e-14 | 0 | 0.02443 | 0.008142 | In range |
| CE530 | JUNE 25 · Zone Hum Rat (kg/kg) | 0.002841 | 0.005478 | 0.007800 | 0.006797 | Below range |
| CE530 | JUNE 25 · COP2 | 2.653 | 2.690 | 2.780 | 2.730 | Below range |
| CE530 | JUNE 25 · ODB (°C) | 29.517 | 29.500 | 29.517 | 29.508 | In range |
| CE530 | JUNE 25 · EDB (°C) | 25.000 | 24.354 | 25.000 | 24.874 | Above range |
Nothing in this suite fits the current filters.
Min, Max and Mean describe the example programs published with the standard. Analytical is the closed-form or quasi-analytical solution where the standard gives one.
Cooling Equipment
14 of 14 range cases inside; 12 required. Tables A3-5.
ASoftware information
1. SOFTWARE VENDOR:
Jared Bell, Roots Ontological Technologies, LLC
2. SOFTWARE NAME:
SIMsara
3. SOFTWARE VERSION (unique software version identifier):
SIMsara 0.1.0
4. OPERATING SYSTEM REQUIREMENTS:
macOS 13 or later on Apple silicon (arm64). This is the build that was
tested; other targets are listed only when they have been built and run
for these tests.
5. APPROX HARD DISK SPACE REQUIRED FOR INSTALLATION:
About 6.3 MB: the release binary s140_run, which needs no other runtime
files beyond the TOML input and the EPW weather file.
6. MINIMUM RAM REQUIRED FOR SOFTWARE OPERATION:
16 MB: the largest peak resident memory of any submitted test case,
measured with /usr/bin/time -l on the tested build.
7. MINIMUM DISPLAY MONITOR REQUIREMENTS:
None. SIMsara is a command-line program with no graphical display.
8. OTHER HARDWARE OR SOFTWARE-RELATED REQUIREMENTS:
Input is TOML (docs/TOML-INPUT.md in the source distribution) with EPW
weather. Building from source needs Rust 1.98.1. The Standard 140 harness
scripts that generate the test inputs and fill the output templates need
Python 3.11 or later, standard library only.BAlternative modeling methods
NOTE 1 - Unitary System Parent (Section 5.1.1.4, 9.2.3.10 and 9.2.4.2.2)
---------------------------------------------------------
1.1 Describe the Effect Being Simulated:
How the DX coil and the indoor fan follow the zone load in every case, and
whether the economizer can be locked out while the compressor runs (CE410).
1.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
1.2.1 AirLoopHVAC:UnitaryHeatCool
Physical Meaning: Heat-cool unitary on an air loop: supply fan, DX
cooling coil and heating coil controlled to the load of one zone; it
requests the economizer lockout of Controller:OutdoorAir
LockoutWithCompressor whenever its compressor runs.
1.2.2 AirLoopHVAC:UnitarySystem
Physical Meaning: Generic unitary system with load or setpoint control
and multi-speed fans and coils; with a single-speed DX coil it does not
request the economizer lockout.
1.2.3 ZoneHVAC:PackagedTerminalAirConditioner
Physical Meaning: Packaged terminal unit serving the zone directly,
without an air loop or an economizer.
1.3 Setting or Capability Used:
AirLoopHVAC:UnitaryHeatCool in all 20 cases, CE300-CE545: one modeling
method for all cases (5.1.1.4), and the parent that can model the
nonintegrated compressor of CE410 (9.2.4.2.2), which needs the economizer
locked out while the compressor runs. Its heating coil is never available
(heat off).
NOTE 2 - Cooling Coil Model (Section 9.2.3.10)
---------------------------------------------------------
2.1 Describe the Effect Being Simulated:
Total, sensible and latent capacity and compressor power at each entering
condition, and so every consumption, coil-load, COP2 and humidity result.
2.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
2.2.1 Coil:Cooling:DX:SingleSpeed
Physical Meaning: Rated gross capacity, sensible heat ratio, COP and
flow with capacity and energy-input-ratio curves of entering wet bulb
and outdoor dry bulb; the sensible and latent split by the apparatus
dew point and bypass factor method, with a dry-coil branch when the
entering air is dry.
2.2.2 Other DX coil objects
Physical Meaning: Multi-speed, variable-speed and performance-table
coils (not used).
2.3 Setting or Capability Used:
Coil:Cooling:DX:SingleSpeed, with the bypass factor derived by the program
at the rated point and applied through the apparatus dew point method.
NOTE 3 - Fan Operation and Part-Load Degradation (Section 9.2.3.10.4,
9.2.3.10.5 and 9.2.4.3.1.2)
---------------------------------------------------------
3.1 Describe the Effect Being Simulated:
Indoor-fan energy, fan heat and compressor energy at part load.
3.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
3.2.1 Fan operating mode schedule
Physical Meaning: 1: the supply fan runs continuously at the rated flow
while the compressor cycles; 0: the fan cycles with the compressor.
3.2.2 Part-load fraction curve
Physical Meaning: PLF(PLR) divides the runtime fraction of the
compressor and of the fans that cycle with it.
3.3 Setting or Capability Used:
Continuous fan (schedule 1) in CE300-CE440 and cycling fan (schedule 0) in
CE500-CE545; the outdoor fan always cycles with the compressor. PLF = 1 -
Cd (1 - PLR) with Cd 0.229, so the runtime fraction is PLR / PLF.
NOTE 4 - Outdoor Air and Infiltration (Section 9.2.3.10.6, 9.2.4.1 and 9.2.4.2)
---------------------------------------------------------
4.1 Describe the Effect Being Simulated:
Outdoor-air and infiltration loads of CE300-CE360, and the economizer
cooling of CE400-CE440.
4.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
4.2.1 Controller:OutdoorAir
Physical Meaning: Fixed or proportional minimum outdoor air with a
minimum-flow schedule; economizer controls: differential dry bulb or
enthalpy (outdoor against return air), fixed dry-bulb, enthalpy or
dew-point limits, electronic enthalpy; modulate-flow or
minimum-flow-with-bypass action; lockout with heating or with the
compressor, or no lockout.
4.2.2 SetpointManager:MixedAir
Physical Meaning: The mixed-air temperature the economizer holds: a
reference supply setpoint less the fan temperature rise.
4.2.3 SetpointManager:SingleZone:Cooling
Physical Meaning: The supply temperature that meets the zone's cooling
load, between a minimum and a maximum.
4.2.4 ZoneInfiltration:DesignFlowRate
Physical Meaning: Scheduled design flow with constant, temperature and
wind terms.
4.3 Setting or Capability Used:
A fixed minimum outdoor-air flow with its schedule; no economizer in
CE300-CE360. In CE400-CE440 the economizer modulates the outdoor air
between that minimum and the whole supply flow to hold a mixed-air
setpoint: CE400 differential dry bulb, CE420 a fixed 20 C outdoor dry-bulb
limit, CE430 differential enthalpy, CE440 differential enthalpy with a
47.25 kJ/kg outdoor enthalpy limit; no lockout. CE410 is CE400 with the
economizer locked out while the compressor runs (LockoutWithCompressor): in
a step where the compressor must run, the step is simulated again with the
outdoor air at its minimum (decided per ten-minute step, Block C note 7).
The mixed-air setpoint is the supply temperature that meets the zone's
cooling load (single-zone cooling setpoint manager, 1.46-50 C) less the
draw-through fan rise, so the outdoor air cools as far as the load needs
and, except in CE410, the compressor meets the rest. Infiltration as a
scheduled design flow with the constant term only.
NOTE 5 - Surface Convection, Time Step and Initialization (Section 9.2.3.8,
9.2.3.9 and 5.1.1.7.2)
---------------------------------------------------------
5.1 Describe the Effect Being Simulated:
Heat gain through the R 325 envelope, thermostat resolution, and the zone
state at the start of the year.
5.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
5.2.1 Inside: Simple, TARP, CeilingDiffuser, Adaptive, ASTMC1340
Physical Meaning: Constant or correlation-based interior coefficients.
5.2.2 Outside: SimpleCombined, TARP, DOE-2, MoWiTT
Physical Meaning: A combined coefficient to the outdoor air, or
convection with explicit long-wave exchange.
5.2.3 Zone time steps per hour; warmup days
Physical Meaning: 1 to 60 steps; warmup repeats the first day until
loads and temperatures converge (up to the maximum number of warmup
days).
5.3 Setting or Capability Used:
TARP inside; SimpleCombined outside; 6 zone steps per hour; warmup of at
least 6 and at most 50 days, starting from zone air at the outdoor
conditions of January 1. In CE500-CE545 the zone has no gains, fan heat,
outdoor air or infiltration before March 11, and the near-adiabatic zone
does not converge within 50 warmup days (the program reports it); it floats
from its warmup state until the gains begin.CEquivalent modeling methods
NOTE 1 - Unitary Split System Modeled as a Heat-Cool Unitary with Heat Always
Off (Section 9.2.3.10 and Figure 9-7)
-------------------------------------------------------------------------------
1.1 Describe the Effect Being Simulated:
All results.
1.2 Section(s) of the Standard where Relevant Inputs are Specified:
A single-speed split air conditioner with an air-cooled condenser, an
outdoor-air mixing system, a draw-through indoor fan, the outdoor fan
cycling with the compressor, heat always off.
1.3 Equivalent Input(s) Used:
One air loop whose branch holds an AirLoopHVAC:UnitaryHeatCool, controlled
to the zone's load, in every case (one modeling method for all cases,
5.1.1.4): a Coil:Cooling:DX:SingleSpeed, then a Coil:Heating:Electric whose
availability schedule is 0 all year, then a draw-through Fan:OnOff of 1242
W at the rated flow (total and motor efficiency 1, all heat to the air,
9.2.3.10.5.1.2); cooling, heating and no-load supply flows are the rated
flow and dehumidification control is none. An outdoor-air system with a
mixer precedes the unit in every case with outdoor air (CE300, CE310,
CE330, CE340, CE350, CE360 and CE400-CE440); CE320 and CE500-CE545 have
none (9.2.4.1.2.2, 9.2.4.3.1.3). A constant-volume terminal without reheat
delivers the air. The thermostat is ThermostatSetpoint:SingleCooling
(non-proportional, 9.2.1.10.2.4). This unit has no minimum supply air
temperature input; the 1.46 C of 9.2.3.10.3.3 is entered only in
CE400-CE440, as the lower limit of the economizer's supply-temperature
setpoint manager.
1.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
Same components, arrangement and control as the specified unit; heating is
never called for and the heating coil is never available, so it adds no
energy and no load.
NOTE 2 - Expanded Performance Map Fitted to Curves (Section 9.2.3.10.3 (Tables
9-16 and 9-17; CE300MAP.xls sheet ExpSI))
-------------------------------------------------------------------------------
2.1 Describe the Effect Being Simulated:
Capacity and power at every operating point.
2.2 Section(s) of the Standard where Relevant Inputs are Specified:
The expanded performance map of Table 9-16 (CE300MAP.xls), its rating row
and its compressor envelope; extrapolation by the program (9.2.3.10.3.1).
2.3 Equivalent Input(s) Used:
The map's gross total capacity and compressor-plus-outdoor-fan power are
fitted to biquadratics in entering wet bulb and outdoor dry bulb,
normalized and anchored at the rating row (SIMsara's scripts/s140/fit.py,
least squares), over the 31 wet-coil points inside the compressor envelope
at the rated entering dry bulb of 26.67 C. Fit errors: capacity RMS 0.354
percent, maximum 0.951 percent; power RMS 0.320 percent, maximum 0.723
percent; the rated point exactly. Rated values from the map: gross capacity
33277 W, gross SHR 0.7826, coil COP 3.043 (compressor and outdoor fan),
flow 1.88778 m3/s (6796 m3/h, 9.2.3.10.5.1). The flow-fraction curves are
1. The curve form has no entering dry-bulb term: at an entering dry bulb of
15.56 C the fitted model exceeds the map's wet-coil capacity by 3.8 percent
on average, and at 35 C it is 1.35 percent below, which bears on CE520,
CE522 and CE525; the dry-coil cases use the model's dry-coil branch. The
curves are entered without clamping; the weather file has 1623 hours below
the lowest fitted outdoor dry bulb (12.78 C). The bypass factor is derived
by the program from the rated SHR (9.2.3.10.3.2).
2.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The curve form is the program's; the fit reproduces the map within the
stated errors at the rated entering dry bulb.
NOTE 3 - Weather Data Converted from TMY2 (Section 9.2.3.1 and Annex A1, A1.2.2
and Table A1-7)
-------------------------------------------------------------------------------
3.1 Describe the Effect Being Simulated:
Outdoor dry bulb and humidity of every case.
3.2 Section(s) of the Standard where Relevant Inputs are Specified:
CE300.TM2.
3.3 Equivalent Input(s) Used:
SIMsara reads EPW. SIMsara's converter (scripts/s140/wx/tm2.py) writes
CE300.TM2 as an EPW; the processed file is archived with its sha256. The
location line carries the site of Table A1-7 (30.0 N, 90.3 W, time zone 6,
3 m), not the station of the file header. The program interpolates the
hourly records to the ten-minute steps, so hourly means of the outdoor
conditions differ slightly from the hourly records.
3.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The dry bulb and humidity are carried over unchanged (plan WP1); the annual
means and maxima of outdoor dry bulb and humidity ratio lie within the
weather-check tolerances.
NOTE 4 - Compressor and Condenser Fan Split; Coil Loads, COP2, RH and EWB
Post-Processed (Section 9.3.2 and Section 3.1 (COP2))
-------------------------------------------------------------------------------
4.1 Describe the Effect Being Simulated:
Reported compressor, condenser-fan and coil-load energies, COP2, relative
humidity and entering wet bulb.
4.2 Section(s) of the Standard where Relevant Inputs are Specified:
Annual, May-September, hourly-maximum, June 28 hourly and daily outputs.
4.3 Equivalent Input(s) Used:
The DX coil reports one electricity energy for compressor plus outdoor fan:
the condenser fan is 930 W times the coil runtime fraction times the step
length, and the compressor is the remainder. The coil loads are the
reported total, sensible and latent cooling rates times the step length.
COP2 is the evaporator coil total load divided by the compressor plus
condenser-fan energy (9.3.2.1.2): the annual and daily values are ratios of
the totals, the maxima, minima and June 28 values hourly. Zone relative
humidity is computed hourly from the zone air temperature and humidity
ratio at the step's barometric pressure, and the entering wet bulb from the
coil-inlet node state, with the program's psychrometric relations. Hourly
values are the time averages or sums of the six steps; the daily outputs
are the day's energies over 24 hours and the day's means (9.3.2.5). The
CE500-CE545 minimum IDB and humidity ratio and the RH extremes are taken
from April 1 to December 31 (9.3.2.3.2).
4.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
Exact for quantities held constant within each step; the COP2 definition
reproduces the COP2 column of every example sheet from its own energy
columns (within 0.32 percent).
NOTE 5 - Outdoor Air, Infiltration and Internal Gain Schedules (Section
9.2.3.5, 9.2.3.6, 9.2.3.10.6 and 9.2.4.1-9.2.4.3 (Tables 9-15, 9-20 to
9-23))
-------------------------------------------------------------------------------
5.1 Describe the Effect Being Simulated:
Internal gains of every case; outdoor-air and infiltration loads of
CE300-CE440.
5.2 Section(s) of the Standard where Relevant Inputs are Specified:
Hourly internal gains in watts by period; outdoor air as a fraction of the
supply flow; infiltration in m3/h; the CE350 set-up schedule.
5.3 Equivalent Input(s) Used:
The gains are two ElectricEquipment objects (sensible, and latent with
latent fraction 1), 100 percent convective, each with a design level equal
to the table's largest hourly value and a Schedule:Compact of the listed
watts over it, so every hour carries the listed value; April 11 and
November 6 - December 31 repeat the January 1 - March 10 schedule (footnote
b). The outdoor air is the controller's fixed minimum (the case's largest
outdoor-air fraction times the supply flow, 15 percent = 0.28317 m3/s)
times a schedule of the fraction over that peak: CE330 and CE340 rise to
100 and 50 percent from 08:00 to 20:00, April 21 - October 12. In
CE400-CE440 the economizer's maximum outdoor-air flow is the supply flow.
The infiltration of CE320 and CE340 is ZoneInfiltration:DesignFlowRate with
the listed m3/h as a scheduled design flow (constant term only). The CE350
set point is 35 C from 00:00 to 07:00 and 20:00 to 24:00, April 21 -
October 12, and 25 C otherwise. Time 0:00-8:00 in the tables is read as
hours 1 to 8 (hour 1 runs from 0:00 to 1:00, 9.3.2.2.2).
5.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
As specified; the outdoor-air and infiltration mass flows use the program's
air density (Block D note 1).
NOTE 6 - Simulation Period (Section 5.1.1.7.2, 5.1.1.8.1 and 9.3.2)
-------------------------------------------------------------------------------
6.1 Describe the Effect Being Simulated:
Annual results.
6.2 Section(s) of the Standard where Relevant Inputs are Specified:
Full annual simulation with preconditioning; May-September, April-December
and daily extracts.
6.3 Equivalent Input(s) Used:
Run January 1 to December 31 after warmup; the extracts are taken from the
annual run.
6.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
As specified.
NOTE 7 - Nonintegrated Economizer of CE410 Decided per Ten-Minute Step (Section
9.2.4.2.2, 9.2.4.2.2.1 and 9.2.4.2.1.1)
-------------------------------------------------------------------------------
7.1 Describe the Effect Being Simulated:
CE410: in which steps and hours the economizer and the compressor run, and
so CE410's consumption, coil loads, COP2 and zone humidity.
7.2 Section(s) of the Standard where Relevant Inputs are Specified:
CE410 is CE400 except that the compressor may not run while the economizer
operates, and the economizer operates only when it alone can meet the whole
cooling load (9.2.4.2.2 and 9.2.4.2.2.1). Economizer and compressor ON and
OFF are those of CE400 and hold for the hour: the economizer ON supplies
outdoor air as needed above the 15 percent minimum, OFF keeps the minimum,
and the compressor OFF does not run in that hour (9.2.4.2.1.1).
7.3 Equivalent Input(s) Used:
The CE400 inputs with Controller:OutdoorAir Lockout Type
LockoutWithCompressor on the AirLoopHVAC:UnitaryHeatCool parent (Block B
note 1). The program decides the control once per ten-minute system step,
not per hour: in a step where the compressor runs, the parent requests the
lockout and the step is simulated again with the outdoor air at its
minimum, so the compressor meets that step's whole load; in a step where
the outdoor air alone meets the load, the compressor stays off. The hour of
9.2.4.2.1.1 is read as the ten-minute step. No system step has the
economizer and the compressor on together (0 of 52,928 steps), but in 357
of 8,760 hours the economizer runs above its minimum in some steps and the
compressor in other steps of the same hour (CE400, whose compressor runs
together with the economizer: 2,204 hours). The compressor runs 62.7 of its
2,169.0 hours of runtime in those hours.
7.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The program has no hourly control decision. Per step, the control keeps the
intent of 9.2.4.2.2: the economizer runs above its minimum only when it
alone meets the load, and never while the compressor runs. An hourly
decision would hold the outdoor air at its minimum for the whole of each of
those hours, so the compressor would also meet the load that the outdoor
air meets in their economizer steps; CE410's compressor energy and coil
loads are lower than an hourly decision would give by that part.DUse of non-specified inputs
* Alternative constant exterior surface coefficients in Sections 7.2.1.9.3,
7.2.3.1.4.3, 7.2.3.3.2, and 9.2.1.8
* Alternative constant interior surface coefficients in Sections 7.2.1.10.3,
7.2.3.1.4.4, 7.2.3.2.2, and 9.2.1.9
* Alternative constant interior solar distribution fractions in Sections
7.2.1.12, 7.2.2.1.2.2, 7.2.2.1.6.2, 7.2.2.1.7.2, 7.2.2.2.7.4, 7.2.3.9.3,
7.2.3.10.2, and 7.2.3.12.2
* Air density given at specific altitudes for the space-cooling and space-
heating equipment cases in Sections 9.2.1.4.3, 9.2.3.4.3, and 10.2.1.4.3.
NOTE 1 - Air Density and Envelope Inputs (Section 9.2.3.4.2, 9.2.3.4.3,
9.2.3.8, 9.2.3.9)
-------------------------------------------------------------------------------
1.1 Describe the Effect Being Simulated:
Fan mass flow and power; outdoor-air and infiltration mass flow; envelope
heat gain.
1.2 Section(s) of the Standard where Relevant Inputs are Specified:
Air density at the site altitude; the constant combined surface
coefficients.
1.3 Nonspecified Input(s) Used:
The program converts the rated volume flow to mass flow with the density of
dry air at 20 C and the standard pressure of the site elevation, and uses
the state-dependent density elsewhere (9.2.3.4.3 lets a program that
calculates air density skip the 1.201 kg/m3). The combined surface
coefficients of 8.29 and 29.3 W/m2K are not entered; the envelope uses the
algorithms of Block B (9.2.3.8 and 9.2.3.9), with the single R 325
insulation layer entered as two Material:NoMass layers of R 162.3 (no
thermal or moisture capacitance, 9.2.3.4.2) so that the inner face carries
solar absorptance 0.6 and the outer 0.1, infrared emittance 0.9 on both
(Table 9-3).
1.4 Physical, Mathematical or Logical Justification for Use of the
Nonspecified Input(s)
� provide supporting calculations, if relevant:
The insulation resistance dominates the overall U-value (0.00308 W/m2K), so
the film coefficients change the envelope gain by well under 1 W.
NOTE 2 - Readings of the Economizer Specification and of the Gain Tables
(Section 9.2.4.2 and Tables 9-15, 9-20 to 9-23)
-------------------------------------------------------------------------------
2.1 Describe the Effect Being Simulated:
CE400, CE420, CE430 and CE440; the hourly gains of every case.
2.2 Section(s) of the Standard where Relevant Inputs are Specified:
The economizer and compressor control strategies of CE400, CE420, CE430 and
CE440, and the listed watts against the frac v. max columns.
2.3 Nonspecified Input(s) Used:
The economizer modulates the outdoor air to hold a mixed-air temperature
equal to the supply temperature that meets the zone load less the fan rise,
so outdoor air is supplied as needed up to 100 percent and is at 100
percent whenever the compressor must also run (9.2.4.2.1.1). CE420 uses a
fixed 20 C outdoor dry-bulb limit without the return-air comparison, as its
strategy list 9.2.4.2.3.1 states (with IDB above 25 C the comparison always
holds). CE440 keeps the CE430 enthalpy comparison and adds the 47.25 kJ/kg
outdoor limit, as 9.2.4.2.5 states (exactly as CE430 except for the limit);
its strategy list 9.2.4.2.5.1 names only the limit, and the two readings
differ only in hours with the return air enthalpy below the outdoor
enthalpy and the outdoor enthalpy at or below the limit. The enthalpy is
that of moist air per kg of dry air with dry air at 0 C as the zero, for
which 47.25 kJ/kg is the SI value of 28.0 Btu/lb. The gains use the listed
watts; the frac v. max columns, given for convenience, differ from them by
rounding only (under 1 W).
2.4 Physical, Mathematical or Logical Justification for Use of the
Nonspecified Input(s)
� provide supporting calculations, if relevant:
The text of 9.2.4.2 and of the table notes.EOmitted test cases and resultsNone
NONE
FChanges to source codeNone
NONE
GAnomalous results
NOTE 1 - Zone Humidity of the Dry-Coil Cases and Its Effect on Capacity
(Section 9.2.4.3 (Informative Annex B16.5.2))
-------------------------------------------------------------------------------
1.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
CE530, CE540 and CE545: zone humidity ratio and relative humidity (annual,
daily and extremes, 1.7 to 58 percent below the example results),
consumption (0.6 to 3.4 percent above), indoor and condenser fan energy (3
to 9.4 percent above), COP2 (0.6 to 2.1 percent below), coil loads (0.1 to
0.3 percent above), their hourly maxima and the CE530 daily values; CE540
coil latent load (zero).
1.2 Explanation of Reason for the Anomalous Results:
These cases have no latent gain, outdoor air or infiltration and the coil
stays dry, so nothing adds or removes moisture: the zone humidity ratio
keeps its initial value all year. The program starts the zone at the
outdoor conditions of January 1 hour 1, 0.00284 kg/kg, and applies its
preconditioning (5.1.1.7.2); Section 9 prescribes no initial zone humidity.
The value is below the example results. The lower entering wet bulb lowers
the dry-coil capacity of the fitted curves, so the unit runs longer. In a
diagnostic run (not submitted; made before the WP11 view-factor fix) with a
moisture source in the first week only, the CE530 zone humidity ratio is
0.0065 kg/kg, COP2 lies inside the example range and the consumption is
0.85 percent above it. The coil latent load is zero because the coil is
dry.
NOTE 2 - Zone Humidity of the No-Outdoor-Air Wet-Coil Cases (Section 9.2.4.3
(Informative Annex B16.5.2))
-------------------------------------------------------------------------------
2.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
CE500, CE520, CE522 and CE525 annual mean zone humidity ratio (1.4 to 2.6
percent below) and relative humidity (4.1 to 5.3 percent below); CE500
April 30 humidity ratio; the humidity-ratio and relative-humidity extremes
of CE500 to CE525 (0.6 to 14 percent outside, mostly CE520).
2.2 Explanation of Reason for the Anomalous Results:
From January 1 to March 10 these cases have no gains and the zone keeps the
initial humidity of Block G note 1, which lowers the annual means. The
humidity during operation follows the apparatus dew point and bypass factor
split at the entering dry bulb of each case; at 15 C and 20 C (CE520,
CE522) the curves, fitted at 26.67 C without an entering dry-bulb term,
depart from the map (Block C note 2), which moves the dehumidification and
the humidity extremes.
NOTE 3 - Consumption at Low Entering Dry Bulb (Section 9.2.4.3 (Informative
Annex B16.5.2))
-------------------------------------------------------------------------------
3.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
CE520 and CE522 annual consumption (0.21 and 0.22 percent above the example
results) and the CE520 hourly maximum consumption (1.0 percent above).
3.2 Explanation of Reason for the Anomalous Results:
The entering dry bulb of 15 C and 20 C lies below the 26.67 C at which the
curves are fitted (Block C note 2); the capacity and power there are
extrapolated by the curve form.
NOTE 4 - Cycling Fan Energy (Section 9.2.4.3 (Informative Annex B16.5.2))
-------------------------------------------------------------------------------
4.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
CE500 annual and May-September indoor and condenser fan energy and
consumption, the CE500 June 25 daily values, and the hourly maxima of
CE500, CE510 and CE525 (0.01 to 0.6 percent above the example results).
4.2 Explanation of Reason for the Anomalous Results:
With a cycling fan both fans run for the runtime fraction PLR / PLF of the
degradation curve (Block B note 2), so the fan energy includes the cycling
loss.
NOTE 5 - Results at the Thermostat Setpoint (Section 9.3.2 (Informative Annex
B16.5.2))
-------------------------------------------------------------------------------
5.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
Mean and maximum IDB and entering dry bulb at or within 0.04 percent of the
edge of the example range (CE340, CE350, CE500 May-September and daily,
CE530 daily, CE300 June 28).
5.2 Explanation of Reason for the Anomalous Results:
The zone temperature overshoots the setpoint by less than 0.001 K within
the ten-minute step, and the entering dry bulb of the continuous-fan cases
carries the fan-off part of each step; the values are within 0.04 percent
of the range.
NOTE 6 - Hourly Maxima and CE300 June 28 Hourly Values (Section 9.3.2
(Informative Annex B16.5.2))
-------------------------------------------------------------------------------
6.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
Hourly maxima of consumption and coil loads of CE300, CE310 and CE350 (0.01
to 0.58 percent above), the CE300 outdoor humidity maximum (0.09 percent
below), the CE320 annual sensible coil load (0.46 percent below), COP2
extremes of CE300, CE310 and CE350 (0.2 to 0.3 percent), the CE350 maximum
relative humidity (0.7 percent below) and CE300 June 28 hourly values (0.01
to 5.2 percent, the largest in the latent load of two hours).
6.2 Explanation of Reason for the Anomalous Results:
Single hours depend on the fitted curves (fit error up to 0.95 percent,
Block C note 2), on the sensible and latent split of the bypass-factor
method, on the cycling of the compressor within the hour, and on the
weather interpolated to ten-minute steps, so hourly outdoor values are
means of the interpolated steps rather than the hourly records.
NOTE 7 - Economizer Cases CE400, CE420, CE430 and CE440 (Section 9.2.4.2
(Informative Annex B16.5.2))
-------------------------------------------------------------------------------
7.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
Hourly maxima of consumption and coil loads of CE400-CE440 (up to 0.51
percent above; the CE440 latent maximum 1.6 percent above), the annual
sensible coil load of CE400 and CE420 (0.19 and 0.05 percent below), the
CE440 mean relative humidity (0.04 percent below), the CE420 minimum COP2
(0.19 percent below) and the CE430 maximum relative humidity (0.11 percent
above). Every annual consumption lies inside the range of the example
results.
7.2 Explanation of Reason for the Anomalous Results:
The hourly maxima occur in hot hours with the economizer closed, so they
equal CE300's maxima, which the note Hourly Maxima and CE300 June 28 Hourly
Values explains; the example ranges of these cases are narrower than
CE300's. The annual sensible coil load falls because the economizer meets
the sensible load of cool hours with outdoor air; the program meets exactly
the load that remains, and the fitted-curve and bypass-factor effects of
that note apply to it. The economizer's mixed-air setpoint and the CE420
and CE440 limit readings are those of Block D note 2.
NOTE 8 - Nonintegrated Economizer Case CE410 (Section 9.2.4.2.2 (Informative
Annex B16.5.2))
-------------------------------------------------------------------------------
8.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
CE410 annual consumption, compressor and condenser fan energy and
evaporator coil total load (0.05 to 1.2 percent above the example results),
annual mean zone humidity ratio and relative humidity (0.6 percent below),
the hourly maxima of consumption, sensible and total coil load (0.8 to 2.8
percent above), the maximum and minimum COP2 (2.9 percent above and 0.35
percent below), the maximum IDB (0.4 percent below) and the maximum
humidity ratio and relative humidity (2.4 and 1.0 percent below).
8.2 Explanation of Reason for the Anomalous Results:
The economizer and the compressor are decided per ten-minute step (Block C
note 7): in a step where the outdoor air at up to 100 percent cannot meet
the load, the step is simulated again with the outdoor air at its 15
percent minimum and the compressor meets the whole load, so no system step
has both on (0 of 52,928), while in 357 of 8,760 hours the economizer runs
above its minimum in some steps and the compressor in others. Against CE400
the compressor runs about 6 percent longer and the consumption is 2.8
percent higher; more of the load passes the coil, which dries the zone. The
compressor takes over whenever the economizer cannot hold the set point, so
the zone air never exceeds 25 C by more than 0.01 K. The hourly maxima and
the minimum COP2 fall in hot hours with the economizer closed and equal
CE300's (note Hourly Maxima and CE300 June 28 Hourly Values); the maximum
IDB, equal to CE300's too, falls in a mild October afternoon hour in which
the lockout keeps the outdoor air at its minimum while the compressor runs.
The maximum COP2 and the humidity maxima are single hours of the spring,
where the outdoor air the economizer brings in sets the coil's entering
humidity.Rendered from S140outNotes-SIMsara-CE_b.txt, the modeler report in the form Standard 140 prescribes. The template's own instructions are left out here.
The filled output template and the results workbook are the official record. They hold ASHRAE's licensed template content and are not published here.