Section 11 · Air-side equipment

Case AE206

Values compared
47
Outside example range
9
Run time
0.08 s
Input file
AE206.toml, 31.4 kB

Against the example programs

Each reported quantity next to the spread of the simulation programs published with the standard.

Position in the example range
Example rangeSIMsara
Sensible Cooling Load (QZClatent) (kWh/h)AE SZ coil and zone loads
1.4641.470
In range
Sensible Cooling Load (QZClatent) (kWh/h), AE SZ coil and zone loads: SIMsara 1.465 · range 1.464 to 1.470
Latent Load (QZlatent) (kWh/h)AE SZ coil and zone loads
0.58610.5900
In range
Latent Load (QZlatent) (kWh/h), AE SZ coil and zone loads: SIMsara 0.5861 · range 0.5861 to 0.5900
Loads Sensible (QCsensible) (kWh/h)AE SZ coil and zone loads
1.6461.731
In range
Loads Sensible (QCsensible) (kWh/h), AE SZ coil and zone loads: SIMsara 1.704 · range 1.646 to 1.731
Latent (QClatent) (kWh/h)AE SZ coil and zone loads
0.96321.087
In range
Latent (QClatent) (kWh/h), AE SZ coil and zone loads: SIMsara 0.9769 · range 0.9632 to 1.087
Total (QCtotal) (kWh/h)AE SZ coil and zone loads
2.6642.818
In range
Total (QCtotal) (kWh/h), AE SZ coil and zone loads: SIMsara 2.681 · range 2.664 to 2.818
Outlet RH (RHcco) (%)AE SZ coil and zone loads
99.025100
In range
Outlet RH (RHcco) (%), AE SZ coil and zone loads: SIMsara 99.877 · range 99.025 to 100
DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)AE SZ node states
2323.000
In range
DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa), AE SZ node states: SIMsara 23.000 · range 23 to 23.000
DRY BULB TEMPERATURE (°C) · Mixed Air (ma)AE SZ node states
23.40723.444
In range
DRY BULB TEMPERATURE (°C) · Mixed Air (ma), AE SZ node states: SIMsara 23.434 · range 23.407 to 23.444
DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)AE SZ node states
23.40723.444
In range
DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco), AE SZ node states: SIMsara 23.434 · range 23.407 to 23.444
DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)AE SZ node states
18.44418.589
In range
DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco), AE SZ node states: SIMsara 18.510 · range 18.444 to 18.589
DRY BULB TEMPERATURE (°C) · Supply Air (sa)AE SZ node states
19.04519.165
In range
DRY BULB TEMPERATURE (°C) · Supply Air (sa), AE SZ node states: SIMsara 19.094 · range 19.045 to 19.165
DRY BULB TEMPERATURE (°C) · Zone Air (z1)AE SZ node states
23.33023.338
In range
DRY BULB TEMPERATURE (°C) · Zone Air (z1), AE SZ node states: SIMsara 23.333 · range 23.330 to 23.338
DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)AE SZ node states
23.33023.338
In range
DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi), AE SZ node states: SIMsara 23.333 · range 23.330 to 23.338
DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)AE SZ node states
23.61123.648
In range
DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo), AE SZ node states: SIMsara 23.645 · range 23.611 to 23.648
HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)AE SZ node states
0.015520.01563
In range
HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa), AE SZ node states: SIMsara 0.01557 · range 0.01552 to 0.01563
HUMIDITY RATIO (G/GDA) · Mixed Air (ma)AE SZ node states
0.014480.01462
In range
HUMIDITY RATIO (G/GDA) · Mixed Air (ma), AE SZ node states: SIMsara 0.01454 · range 0.01448 to 0.01462
HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)AE SZ node states
0.014480.01462
In range
HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco), AE SZ node states: SIMsara 0.01454 · range 0.01448 to 0.01462
HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)AE SZ node states
0.013230.01342
In range
HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco), AE SZ node states: SIMsara 0.01335 · range 0.01323 to 0.01342
HUMIDITY RATIO (G/GDA) · Supply Air (sa)AE SZ node states
0.013230.01342
In range
HUMIDITY RATIO (G/GDA) · Supply Air (sa), AE SZ node states: SIMsara 0.01335 · range 0.01323 to 0.01342
HUMIDITY RATIO (G/GDA) · Zone Air (z1)AE SZ node states
0.013920.01413
In range
HUMIDITY RATIO (G/GDA) · Zone Air (z1), AE SZ node states: SIMsara 0.01404 · range 0.01392 to 0.01413
HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)AE SZ node states
0.013920.01413
In range
HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi), AE SZ node states: SIMsara 0.01404 · range 0.01392 to 0.01413
HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)AE SZ node states
0.013920.01413
In range
HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo), AE SZ node states: SIMsara 0.01404 · range 0.01392 to 0.01413
SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)AE SZ node states
830.35859.94
Above range
SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa), AE SZ node states: SIMsara 860.73 · range 830.35 to 859.94
SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)AE SZ node states
830.35859.84
Above range
SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma), AE SZ node states: SIMsara 860.60 · range 830.35 to 859.84
TableQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE SZ coil and zone loadsSensible Heating Load (QZHsensible) (kWh/h)00000In range
AE SZ coil and zone loadsSensible Cooling Load (QZClatent) (kWh/h)1.4651.4641.4701.4661.465In range
AE SZ coil and zone loadsLatent Load (QZlatent) (kWh/h)0.58610.58610.59000.58670.5861In range
AE SZ coil and zone loadsCoil Load (QH) (kWh/h)00000In range
AE SZ coil and zone loadsLoads Sensible (QCsensible) (kWh/h)1.7041.6461.7311.6991.706In range
AE SZ coil and zone loadsLatent (QClatent) (kWh/h)0.97690.96321.0871.0170.9704In range
AE SZ coil and zone loadsTotal (QCtotal) (kWh/h)2.6812.6642.8182.7172.677In range
AE SZ coil and zone loadsOutlet RH (RHcco) (%)99.87799.02510099.759100In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)23.0002323.0002323.000In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Mixed Air (ma)23.43423.40723.44423.42223.434In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)23.43423.40723.44423.42223.434In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)18.51018.44418.58918.51718.514In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Supply Air (sa)19.09419.04519.16519.11219.097In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Zone Air (z1)23.33323.33023.33823.33423.333In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.33323.33023.33823.33423.333In range
AE SZ node statesDRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)23.64523.61123.64823.62723.645In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.015570.015520.015630.015580.01556In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.014540.014480.014620.014540.01455In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.014540.014480.014620.014540.01455In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.013350.013230.013420.013340.01337In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Supply Air (sa)0.013350.013230.013420.013340.01337In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Zone Air (z1)0.014040.013920.014130.014030.01405In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.014040.013920.014130.014030.01405In range
AE SZ node statesHUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.014040.013920.014130.014030.01405In range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)860.73830.35859.94843.28859.94Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)860.60830.35859.84843.24859.83Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)860.60830.35859.84843.24859.83Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)844.74830.35844.05836.92844.00Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Supply Air (sa)846.43830.35845.57836.77845.69Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Zone Air (z1)859.63830.35858.91842.87858.88Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)859.63830.35858.91842.87858.88Above range
AE SZ node statesSPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)860.54830.35859.62842.78859.78Above range
AE SZ node statesENTHALPY (J/GDA) · Location Outdoor Air (oa)62.70562.66362.85162.73262.710In range
AE SZ node statesENTHALPY (J/GDA) · Mixed Air (ma)60.54260.36060.62560.50660.590In range
AE SZ node statesENTHALPY (J/GDA) · Heat Coil Outlet (hco)60.54260.36060.62560.50660.590In range
AE SZ node statesENTHALPY (J/GDA) · Cool Coil Outlet (cco)52.45152.06052.68352.42452.520In range
AE SZ node statesENTHALPY (J/GDA) · Supply Air (sa)53.05252.67053.29053.02653.121In range
AE SZ node statesENTHALPY (J/GDA) · Zone Air (z1)59.16658.85059.30259.10559.235In range
AE SZ node statesENTHALPY (J/GDA) · Return Fan Inlet (rfi)59.16658.85059.30259.10559.235In range
AE SZ node statesENTHALPY (J/GDA) · Return Fan Outlet (rfo)59.48859.16059.60659.41359.557In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.10980.10980.11370.11190.1099Below range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.33520.32950.34100.33730.3355In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.33520.32950.34100.33730.3355In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.33520.32950.34100.33730.3355In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Supply Air (sa)0.33520.32950.34100.33730.3355In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE SZ node statesMASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.22540.21970.22730.22540.2256In range
AE SZ node statesMASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.22540.21970.22730.22540.2256In range

Reported outputs

The values the engine wrote for this case, before they are placed in the output template.

OutputValue
Loads (kWh/h) · qZHsensible0
Loads (kWh/h) · qZCsensible1.465
Loads (kWh/h) · qZlatent0.5861
Loads (kWh/h) · qH0
Loads (kWh/h) · qCsensible1.704
Loads (kWh/h) · qClatent0.9769
Loads (kWh/h) · qCtotal2.681
Loads (kWh/h) · rHcco99.877
Nodes · oa · tdb (°C)23.000
Nodes · oa · w (g/g)0.01557
Nodes · oa · v (L/kg)860.73
Nodes · oa · h (J/g)62.705
Nodes · oa · m (kg/s)0.1098
Nodes · oa · rh (%)88
Nodes · ma · tdb (°C)23.434
Nodes · ma · w (g/g)0.01454
Nodes · ma · v (L/kg)860.60
Nodes · ma · h (J/g)60.542
Nodes · ma · m (kg/s)0.3352
Nodes · ma · rh (%)80.200
Nodes · hco · tdb (°C)23.434
Nodes · hco · w (g/g)0.01454
Nodes · hco · v (L/kg)860.60
Nodes · hco · h (J/g)60.542
Nodes · hco · m (kg/s)0.3352
Nodes · hco · rh (%)80.200
Nodes · cco · tdb (°C)18.510
Nodes · cco · w (g/g)0.01335
Nodes · cco · v (L/kg)844.74
Nodes · cco · h (J/g)52.451
Nodes · cco · m (kg/s)0.3352
Nodes · cco · rh (%)99.877
Nodes · sa · tdb (°C)19.094
Nodes · sa · w (g/g)0.01335
Nodes · sa · v (L/kg)846.43
Nodes · sa · h (J/g)53.052
Nodes · sa · m (kg/s)0.3352
Nodes · sa · rh (%)96.298
Nodes · z1 · tdb (°C)23.333
Nodes · z1 · w (g/g)0.01404
Nodes · z1 · v (L/kg)859.63
Nodes · z1 · h (J/g)59.166
Nodes · z1 · rh (%)77.976
Nodes · rfi · tdb (°C)23.333
Nodes · rfi · w (g/g)0.01404
Nodes · rfi · v (L/kg)859.63
Nodes · rfi · h (J/g)59.166
Nodes · rfi · m (kg/s)0.2254
Nodes · rfi · rh (%)77.976
Nodes · rfo · tdb (°C)23.645
Nodes · rfo · w (g/g)0.01404
Nodes · rfo · v (L/kg)860.54
Nodes · rfo · h (J/g)59.488
Nodes · rfo · m (kg/s)0.2254
Nodes · rfo · rh (%)76.520
Pressure pa101,300
Fans · supply (W)201.46
Fans · return (W)72.620
Fans · exhaust (kg/s)0.1098
Fan power (W)201.46
Zone tdb (°C)23.333
Economizer status0
Oa fraction0.3276
Program outputs · cooling coil total (W)2,712.0
Program outputs · cooling coil sensible (W)1,703.0
Program outputs · heating coil (W)0
Program outputs · condensate · kg (s)3.98e-4
Program outputs · condensate · temp (°C)18.510
Program outputs · condensate · h j kg77,372.4
Program outputs · condensate · w30.791
Program outputs · condensate · entering dew point (°C)19.827
Program outputs · condensate · sensible (W)1.216
Balance · residual (W) · return fan7.82e-13
Balance · residual (W) · mixer−3.64e-12
Balance · residual (W) · heating coil0
Balance · residual (W) · cooling coil3.64e-12
Balance · residual (W) · supply fan2.98e-12
Balance · residual (W) · zone1.815
Balance · residual (W) · system1.815
Balance · relative · return fan2.88e-16
Balance · relative · mixer1.34e-15
Balance · relative · heating coil0
Balance · relative · cooling coil1.34e-15
Balance · relative · supply fan1.10e-15
Balance · relative · zone6.69e-4
Balance · relative · system6.69e-4
Balance · max relative6.69e-4
Balance · reference (W)2,712.0
Cycling · steps6
Flows · supply std (m³/s)0.2783
Flows · exhaust std (m³/s)0.09118
Flows · oa std (m³/s)0.09118
Flows · supply fan dp pa506.63
Flows · return fan max std (m³/s)0.2783
Flows · return fan dp pa600.63
Flows · setpoint offset k0.003994
Flow iterations5
Flow record · convergedtrue
Flow record · iterations5
Flow record · relative change9.73e-9
Flow record · zone tdb error k−2.69e-7

Input file

sha256 767d32eaf6fe3140975da13d0ad3fa6a393c8efd99477858420d890a56e1146a

AE206.tomlDownload
[version]
version_identifier = "26.1"

[simulation-control]
do_zone_sizing_calculation = "No"
do_system_sizing_calculation = "No"
do_plant_sizing_calculation = "No"
run_simulation_for_sizing_periods = "No"
run_simulation_for_weather_file_run_periods = "Yes"
do_hvac_sizing_simulation_for_sizing_periods = "No"
maximum_number_of_hvac_sizing_simulation_passes = 1

[building."ASHRAE 140 AE206"]
north_axis = 0.0
terrain = "Suburbs"
loads_convergence_tolerance_value = 0.04
temperature_convergence_tolerance_value = 0.4
solar_distribution = "FullExterior"
maximum_number_of_warmup_days = 25
minimum_number_of_warmup_days = 6

[building.surface.detailed."South Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."East Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."North Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."West Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."Floor"]
surface_type = "Floor"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
]

[building.surface.detailed."Roof"]
surface_type = "Roof"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[timestep]
number_of_timesteps_per_hour = 6

[heat-balance-algorithm]
algorithm = "ConductionTransferFunction"
surface_temperature_upper_limit = 200.0

[surface.convection.algorithm.inside]
algorithm = "TARP"

[surface.convection.algorithm.outside]
algorithm = "DOE-2"

[global-geometry-rules]
starting_vertex_position = "UpperLeftCorner"
vertex_entry_direction = "Counterclockwise"
coordinate_system = "Relative"

[site.location."AE artificial site"]
latitude = 25.8
longitude = -80.3
time_zone = -5.0
elevation = 0.0

[schedule-type-limits."Any Number"]

[schedule-type-limits."Fraction"]
lower_limit_value = 0.0
upper_limit_value = 1.0
numeric_type = "Continuous"

[schedule-type-limits."Temperature"]
lower_limit_value = -60.0
upper_limit_value = 200.0
numeric_type = "Continuous"
unit_type = "Temperature"

[schedule-type-limits."Control Type"]
lower_limit_value = 0.0
upper_limit_value = 4.0
numeric_type = "Discrete"

[schedule.compact."Always On"]
schedule_type_limits_name = "Fraction"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 1.0 },
]

[schedule.compact."Heating Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 18.336993781621633 },
]

[schedule.compact."Cooling Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 23.336993781621633 },
]

[schedule.compact."Dual Setpoint Control"]
schedule_type_limits_name = "Control Type"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 4 },
]

[schedule.compact."CHW Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 6.67 },
]

[material."Gypsum Board 13mm"]
roughness = "Smooth"
thickness = 0.0127
conductivity = 0.16
density = 800.0
specific_heat = 1090.0
thermal_absorptance = 0.9
solar_absorptance = 0.5
visible_absorptance = 0.5

[construction."Adiabatic Panel"]
outside_layer = "Gypsum Board 13mm"

[zone."Zone One"]
direction_of_relative_north = 0.0
x_origin = 0.0
y_origin = 0.0
z_origin = 0.0
type = 1
multiplier = 1
ceiling_height = "Autocalculate"
volume = "Autocalculate"
floor_area = "Autocalculate"
zone_inside_convection_algorithm = "TARP"
zone_outside_convection_algorithm = "DOE-2"
part_of_total_floor_area = "Yes"

[zone.control.thermostat."Zone One Thermostat"]
zone_or_zonelist_name = "Zone One"
control_type_schedule_name = "Dual Setpoint Control"
control_1_object_type = "ThermostatSetpoint:DualSetpoint"
control_1_name = "Zone One Dual Setpoint"

[zone.hvac.air-distribution-unit."Zone One ADU"]
air_distribution_unit_outlet_node_name = "Zone One Supply Inlet"
air_terminal_object_type = "AirTerminal:SingleDuct:ConstantVolume:NoReheat"
air_terminal_name = "Zone One Terminal"
nominal_upstream_leakage_fraction = 0.0
constant_downstream_leakage_fraction = 0.0

[zone.hvac.equipment-list."Zone One Equipment List"]
load_distribution_scheme = "SequentialLoad"
equipment = [
  { zone_equipment_object_type = "ZoneHVAC:AirDistributionUnit", zone_equipment_name = "Zone One ADU", zone_equipment_cooling_sequence = 1, zone_equipment_heating_or_no_load_sequence = 1 },
  { zone_equipment_object_type = "Fan:ZoneExhaust", zone_equipment_name = "Zone Exhaust Fan", zone_equipment_cooling_sequence = 2, zone_equipment_heating_or_no_load_sequence = 2 },
]

[[zone.hvac.equipment-connections]]
zone_name = "Zone One"
zone_conditioning_equipment_list_name = "Zone One Equipment List"
zone_air_inlet_node_or_nodelist_name = "Zone One Supply Inlet"
zone_air_node_name = "Zone One Air Node"
zone_return_air_node_or_nodelist_name = "Zone One Return Outlet"
zone_air_exhaust_node_or_nodelist_name = "Zone One Exhaust Node"

[other-equipment."Zone Sensible Cooling Load"]
fuel_type = "None"
zone_or_zonelist_or_space_or_spacelist_name = "Zone One"
schedule_name = "Always On"
design_level_calculation_method = "EquipmentLevel"
design_level = 1465.0
fraction_latent = 0.0
fraction_radiant = 0.0
fraction_lost = 0.0

[other-equipment."Zone Latent Load"]
fuel_type = "None"
zone_or_zonelist_or_space_or_spacelist_name = "Zone One"
schedule_name = "Always On"
design_level_calculation_method = "EquipmentLevel"
design_level = 586.1
fraction_latent = 1.0
fraction_radiant = 0.0
fraction_lost = 0.0

[thermostat.setpoint.dual-setpoint."Zone One Dual Setpoint"]
heating_setpoint_temperature_schedule_name = "Heating Setpoint"
cooling_setpoint_temperature_schedule_name = "Cooling Setpoint"

[air-loop-hvac."SZ Air Loop"]
controller_list_name = "SZ Controllers"
availability_manager_list_name = "SZ Availability"
design_supply_air_flow_rate = 0.2783458899992101
branch_list_name = "SZ Branches"
supply_side_inlet_node_name = "Air Loop Inlet Node"
demand_side_outlet_node_name = "Zone Equipment Outlet Node"
demand_side_inlet_node_names = "Zone Equipment Inlet Node"
supply_side_outlet_node_names = "Supply Outlet Node"
design_return_air_flow_fraction_of_supply_air_flow = 1.0

[branch-list."SZ Branches"]
branches = [
  { branch_name = "SZ Branch" },
]

[branch-list."CHW Supply Branches"]
branches = [
  { branch_name = "CHW Supply Inlet Branch" },
  { branch_name = "CHW Chiller Branch" },
  { branch_name = "CHW Supply Bypass Branch" },
  { branch_name = "CHW Supply Outlet Branch" },
]

[branch-list."CHW Demand Branches"]
branches = [
  { branch_name = "CHW Demand Inlet Branch" },
  { branch_name = "CHW Cooling Coil Branch" },
  { branch_name = "CHW Demand Bypass Branch" },
  { branch_name = "CHW Demand Outlet Branch" },
]

[branch."SZ Branch"]
components = [
  { component_object_type = "Fan:VariableVolume", component_name = "SZ Return Fan", component_inlet_node_name = "Air Loop Inlet Node", component_outlet_node_name = "Return Fan Outlet Node" },
  { component_object_type = "AirLoopHVAC:OutdoorAirSystem", component_name = "SZ OA System", component_inlet_node_name = "Return Fan Outlet Node", component_outlet_node_name = "Mixed Air Node" },
  { component_object_type = "Coil:Heating:Electric", component_name = "SZ Heating Coil", component_inlet_node_name = "Mixed Air Node", component_outlet_node_name = "Heating Coil Outlet Node" },
  { component_object_type = "Coil:Cooling:Water", component_name = "SZ Cooling Coil", component_inlet_node_name = "Heating Coil Outlet Node", component_outlet_node_name = "Cooling Coil Outlet Node" },
  { component_object_type = "Fan:ConstantVolume", component_name = "SZ Supply Fan", component_inlet_node_name = "Cooling Coil Outlet Node", component_outlet_node_name = "Supply Outlet Node" },
]

[branch."CHW Supply Inlet Branch"]
components = [
  { component_object_type = "Pump:VariableSpeed", component_name = "CHW Pump", component_inlet_node_name = "CHW Supply Inlet Node", component_outlet_node_name = "CHW Pump Outlet Node" },
]

[branch."CHW Chiller Branch"]
components = [
  { component_object_type = "Chiller:Electric:EIR", component_name = "CHW Chiller", component_inlet_node_name = "CHW Chiller Inlet Node", component_outlet_node_name = "CHW Chiller Outlet Node" },
]

[branch."CHW Supply Bypass Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Supply Bypass Pipe", component_inlet_node_name = "CHW Supply Bypass Inlet Node", component_outlet_node_name = "CHW Supply Bypass Outlet Node" },
]

[branch."CHW Supply Outlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Supply Outlet Pipe", component_inlet_node_name = "CHW Supply Outlet Pipe Inlet Node", component_outlet_node_name = "CHW Supply Outlet Node" },
]

[branch."CHW Demand Inlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Inlet Pipe", component_inlet_node_name = "CHW Demand Inlet Node", component_outlet_node_name = "CHW Demand Inlet Pipe Outlet Node" },
]

[branch."CHW Cooling Coil Branch"]
components = [
  { component_object_type = "Coil:Cooling:Water", component_name = "SZ Cooling Coil", component_inlet_node_name = "Cooling Coil Water Inlet Node", component_outlet_node_name = "Cooling Coil Water Outlet Node" },
]

[branch."CHW Demand Bypass Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Bypass Pipe", component_inlet_node_name = "CHW Demand Bypass Inlet Node", component_outlet_node_name = "CHW Demand Bypass Outlet Node" },
]

[branch."CHW Demand Outlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Outlet Pipe", component_inlet_node_name = "CHW Demand Outlet Pipe Inlet Node", component_outlet_node_name = "CHW Demand Outlet Node" },
]

[air.loop.hvac.controller-list."SZ Controllers"]
controller_1_object_type = "Controller:WaterCoil"
controller_1_name = "Cooling Coil Controller"

[air.loop.hvac.controller-list."SZ OA Controllers"]
controller_1_object_type = "Controller:OutdoorAir"
controller_1_name = "SZ OA Controller"

[air.loop.hvac.outdoor-air-system."SZ OA System"]
controller_list_name = "SZ OA Controllers"
outdoor_air_equipment_list_name = "SZ OA Equipment"

[air.loop.hvac.outdoor.air.system.equipment-list."SZ OA Equipment"]
component_1_object_type = "OutdoorAir:Mixer"
component_1_name = "SZ OA Mixer"

[air.loop.hvac.supply-path."SZ Supply Path"]
supply_air_path_inlet_node_name = "Zone Equipment Inlet Node"
components = [
  { component_object_type = "AirLoopHVAC:ZoneSplitter", component_name = "Zone Supply Air Splitter" },
]

[air.loop.hvac.zone-splitter."Zone Supply Air Splitter"]
inlet_node_name = "Zone Equipment Inlet Node"
nodes = [
  { outlet_node_name = "Zone One Terminal Inlet" },
]

[air.loop.hvac.return-path."SZ Return Path"]
return_air_path_outlet_node_name = "Zone Equipment Outlet Node"
components = [
  { component_object_type = "AirLoopHVAC:ZoneMixer", component_name = "Zone Return Air Mixer" },
]

[air.loop.hvac.zone-mixer."Zone Return Air Mixer"]
outlet_node_name = "Zone Equipment Outlet Node"
nodes = [
  { inlet_node_name = "Zone One Return Outlet" },
]

[air.terminal.single.duct.constant.volume.no-reheat."Zone One Terminal"]
availability_schedule_name = "Always On"
air_inlet_node_name = "Zone One Terminal Inlet"
air_outlet_node_name = "Zone One Supply Inlet"
maximum_air_flow_rate = 0.2783458899992101

[availability-manager-assignment-list."SZ Availability"]
managers = [
  { availability_manager_object_type = "AvailabilityManager:Scheduled", availability_manager_name = "SZ Avail" },
]

[availability.manager.scheduled."SZ Avail"]
schedule_name = "Always On"

[fan.variable-volume."SZ Return Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.7
pressure_rise = 600.6307718937625
maximum_flow_rate = 0.2783458899992101
fan_power_minimum_flow_rate_input_method = "Fraction"
fan_power_minimum_flow_fraction = 0.0
motor_efficiency = 1.0
motor_in_airstream_fraction = 0.0
fan_power_coefficient_1 = 0.0
fan_power_coefficient_2 = 0.0
fan_power_coefficient_3 = 0.0
fan_power_coefficient_4 = 1.0
fan_power_coefficient_5 = 0.0
air_inlet_node_name = "Air Loop Inlet Node"
air_outlet_node_name = "Return Fan Outlet Node"
end_use_subcategory = "Return Fans"

[fan.constant-volume."SZ Supply Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.7
pressure_rise = 506.63101222870637
maximum_flow_rate = 0.2783458899992101
motor_efficiency = 1.0
motor_in_airstream_fraction = 0.0
air_inlet_node_name = "Cooling Coil Outlet Node"
air_outlet_node_name = "Supply Outlet Node"
end_use_subcategory = "General"

[fan.zone-exhaust."Zone Exhaust Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.5
pressure_rise = 160.0
maximum_flow_rate = 0.09117500513544062
air_inlet_node_name = "Zone One Exhaust Node"
air_outlet_node_name = "Zone Exhaust Fan Outlet"
end_use_subcategory = "General Exhaust"
system_availability_manager_coupling_mode = "Coupled"

[outdoor.air.mixer."SZ OA Mixer"]
mixed_air_node_name = "Mixed Air Node"
outdoor_air_stream_node_name = "Outdoor Air Inlet Node"
relief_air_stream_node_name = "Relief Air Outlet Node"
return_air_stream_node_name = "Return Fan Outlet Node"

[[outdoor.air.node-list]]
nodes = [
  { node_or_nodelist_name = "Outdoor Air Inlet Node" },
  { node_or_nodelist_name = "CHW Chiller Condenser Inlet Node" },
]

[controller.outdoor-air."SZ OA Controller"]
relief_air_outlet_node_name = "Relief Air Outlet Node"
return_air_node_name = "Return Fan Outlet Node"
mixed_air_node_name = "Mixed Air Node"
actuator_node_name = "Outdoor Air Inlet Node"
minimum_outdoor_air_flow_rate = 0.09117500513544062
maximum_outdoor_air_flow_rate = 0.2783458899992101
economizer_control_type = "NoEconomizer"
economizer_control_action_type = "ModulateFlow"
lockout_type = "NoLockout"
minimum_limit_type = "FixedMinimum"

[controller.water-coil."Cooling Coil Controller"]
control_variable = "Temperature"
action = "Reverse"
actuator_variable = "Flow"
sensor_node_name = "Cooling Coil Outlet Node"
actuator_node_name = "Cooling Coil Water Inlet Node"
controller_convergence_tolerance = 1e-06
maximum_actuated_flow = 0.00023
minimum_actuated_flow = 0.0

[coil.heating.electric."SZ Heating Coil"]
availability_schedule_name = "Always On"
efficiency = 1.0
nominal_capacity = 20000.0
air_inlet_node_name = "Mixed Air Node"
air_outlet_node_name = "Heating Coil Outlet Node"
temperature_setpoint_node_name = "Heating Coil Outlet Node"

[coil.cooling.water."SZ Cooling Coil"]
availability_schedule_name = "Always On"
design_water_flow_rate = 0.00023
design_air_flow_rate = 0.2783458899992101
design_inlet_water_temperature = 12.0
design_inlet_air_temperature = 26.0
design_outlet_air_temperature = 14.0
design_inlet_air_humidity_ratio = 0.0135
design_outlet_air_humidity_ratio = 0.0099
water_inlet_node_name = "Cooling Coil Water Inlet Node"
water_outlet_node_name = "Cooling Coil Water Outlet Node"
air_inlet_node_name = "Heating Coil Outlet Node"
air_outlet_node_name = "Cooling Coil Outlet Node"
type_of_analysis = "SimpleAnalysis"
heat_exchanger_configuration = "CrossFlow"

[setpoint.manager.single.zone.heating."Heating Supply Air Temp Manager"]
control_variable = "Temperature"
minimum_supply_air_temperature = -99.0
maximum_supply_air_temperature = 99.0
control_zone_name = "Zone One"
zone_node_name = "Zone One Air Node"
zone_inlet_node_name = "Zone One Supply Inlet"
setpoint_node_or_nodelist_name = "Zone Equipment Inlet Node"

[setpoint.manager.single.zone.cooling."Cooling Supply Air Temp Manager"]
control_variable = "Temperature"
minimum_supply_air_temperature = -99.0
maximum_supply_air_temperature = 99.0
control_zone_name = "Zone One"
zone_node_name = "Zone One Air Node"
zone_inlet_node_name = "Zone One Supply Inlet"
setpoint_node_or_nodelist_name = "Supply Outlet Node"

[setpoint.manager.mixed-air."Heating Coil Air Temp Manager"]
control_variable = "Temperature"
reference_setpoint_node_name = "Zone Equipment Inlet Node"
fan_inlet_node_name = "Cooling Coil Outlet Node"
fan_outlet_node_name = "Supply Outlet Node"
setpoint_node_or_nodelist_name = "Heating Coil Outlet Node"

[setpoint.manager.mixed-air."Cooling Coil Air Temp Manager"]
control_variable = "Temperature"
reference_setpoint_node_name = "Supply Outlet Node"
fan_inlet_node_name = "Cooling Coil Outlet Node"
fan_outlet_node_name = "Supply Outlet Node"
setpoint_node_or_nodelist_name = "Cooling Setpoint Nodes"

[setpoint.manager.scheduled."CHW Loop Setpoint Manager"]
control_variable = "Temperature"
schedule_name = "CHW Setpoint"
setpoint_node_or_nodelist_name = "CHW Supply Outlet Node"

[node-list."Cooling Setpoint Nodes"]
nodes = [
  { node_name = "Cooling Coil Outlet Node" },
  { node_name = "Mixed Air Node" },
]

[plant-loop."Chilled Water Loop"]
fluid_type = "Water"
plant_equipment_operation_scheme_name = "CHW Loop Operation"
loop_temperature_setpoint_node_name = "CHW Supply Outlet Node"
maximum_loop_temperature = 98.0
minimum_loop_temperature = 1.0
maximum_loop_flow_rate = 0.0006
minimum_loop_flow_rate = 0.0
plant_loop_volume = 0.5
plant_side_inlet_node_name = "CHW Supply Inlet Node"
plant_side_outlet_node_name = "CHW Supply Outlet Node"
plant_side_branch_list_name = "CHW Supply Branches"
plant_side_connector_list_name = "CHW Supply Connectors"
demand_side_inlet_node_name = "CHW Demand Inlet Node"
demand_side_outlet_node_name = "CHW Demand Outlet Node"
demand_side_branch_list_name = "CHW Demand Branches"
demand_side_connector_list_name = "CHW Demand Connectors"
load_distribution_scheme = "SequentialLoad"

[plant-equipment-operation-schemes."CHW Loop Operation"]
control_scheme_1_object_type = "PlantEquipmentOperation:CoolingLoad"
control_scheme_1_name = "CHW Cooling Scheme"
control_scheme_1_schedule_name = "Always On"

[plant.equipment.operation.cooling-load."CHW Cooling Scheme"]
load_range_1_lower_limit = 0.0
load_range_1_upper_limit = 1000000000.0
range_1_equipment_list_name = "CHW Chillers"

[plant-equipment-list."CHW Chillers"]
equipment = [
  { equipment_object_type = "Chiller:Electric:EIR", equipment_name = "CHW Chiller" },
]

[connector-list."CHW Supply Connectors"]
connector_1_object_type = "Connector:Splitter"
connector_1_name = "CHW Supply Splitter"
connector_2_object_type = "Connector:Mixer"
connector_2_name = "CHW Supply Mixer"

[connector-list."CHW Demand Connectors"]
connector_1_object_type = "Connector:Splitter"
connector_1_name = "CHW Demand Splitter"
connector_2_object_type = "Connector:Mixer"
connector_2_name = "CHW Demand Mixer"

[connector.splitter."CHW Supply Splitter"]
inlet_branch_name = "CHW Supply Inlet Branch"
branches = [
  { outlet_branch_name = "CHW Chiller Branch" },
  { outlet_branch_name = "CHW Supply Bypass Branch" },
]

[connector.splitter."CHW Demand Splitter"]
inlet_branch_name = "CHW Demand Inlet Branch"
branches = [
  { outlet_branch_name = "CHW Cooling Coil Branch" },
  { outlet_branch_name = "CHW Demand Bypass Branch" },
]

[connector.mixer."CHW Supply Mixer"]
outlet_branch_name = "CHW Supply Outlet Branch"
branches = [
  { inlet_branch_name = "CHW Chiller Branch" },
  { inlet_branch_name = "CHW Supply Bypass Branch" },
]

[connector.mixer."CHW Demand Mixer"]
outlet_branch_name = "CHW Demand Outlet Branch"
branches = [
  { inlet_branch_name = "CHW Cooling Coil Branch" },
  { inlet_branch_name = "CHW Demand Bypass Branch" },
]

[pump.variable-speed."CHW Pump"]
inlet_node_name = "CHW Supply Inlet Node"
outlet_node_name = "CHW Pump Outlet Node"
design_maximum_flow_rate = 0.0006
design_pump_head = 1000.0
design_power_consumption = 1.0
motor_efficiency = 0.9
fraction_of_motor_inefficiencies_to_fluid_stream = 0.0
coefficient_1_of_the_part_load_performance_curve = 0.0
coefficient_2_of_the_part_load_performance_curve = 1.0
coefficient_3_of_the_part_load_performance_curve = 0.0
coefficient_4_of_the_part_load_performance_curve = 0.0
design_minimum_flow_rate = 0.0
pump_control_type = "Intermittent"

[chiller.electric.eir."CHW Chiller"]
reference_capacity = 20000.0
reference_cop = 3.0
reference_leaving_chilled_water_temperature = 6.67
reference_entering_condenser_fluid_temperature = 35.0
reference_chilled_water_flow_rate = 0.0006
cooling_capacity_function_of_temperature_curve_name = "CHW Chiller Cap FT"
electric_input_to_cooling_output_ratio_function_of_temperature_curve_name = "CHW Chiller EIR FT"
electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name = "CHW Chiller EIR FPLR"
minimum_part_load_ratio = 0.1
maximum_part_load_ratio = 1.0
optimum_part_load_ratio = 1.0
minimum_unloading_ratio = 0.2
chilled_water_inlet_node_name = "CHW Chiller Inlet Node"
chilled_water_outlet_node_name = "CHW Chiller Outlet Node"
condenser_inlet_node_name = "CHW Chiller Condenser Inlet Node"
condenser_outlet_node_name = "CHW Chiller Condenser Outlet Node"
condenser_type = "AirCooled"
condenser_fan_power_ratio = 0.0
fraction_of_compressor_electric_consumption_rejected_by_condenser = 1.0
leaving_chilled_water_lower_temperature_limit = 2.0
chiller_flow_mode = "ConstantFlow"

[curve.biquadratic."CHW Chiller Cap FT"]
coefficient1_constant = 0.507883
coefficient2_x = 0.145228
coefficient3_x_2 = -0.00625644
coefficient4_y = -0.0011178
coefficient5_y_2 = -0.0001296
coefficient6_x_y = -0.00028188
minimum_value_of_x = 5.0
maximum_value_of_x = 10.0
minimum_value_of_y = 24.0
maximum_value_of_y = 35.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.biquadratic."CHW Chiller EIR FT"]
coefficient1_constant = 1.03076
coefficient2_x = -0.103536
coefficient3_x_2 = 0.00710208
coefficient4_y = 0.0093186
coefficient5_y_2 = 0.00031752
coefficient6_x_y = -0.00104328
minimum_value_of_x = 5.0
maximum_value_of_x = 10.0
minimum_value_of_y = 24.0
maximum_value_of_y = 35.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.quadratic."CHW Chiller EIR FPLR"]
coefficient1_constant = 0.088065
coefficient2_x = 1.137742
coefficient3_x_2 = -0.225806
minimum_value_of_x = 0.0
maximum_value_of_x = 1.0

[pipe.adiabatic."CHW Supply Bypass Pipe"]
inlet_node_name = "CHW Supply Bypass Inlet Node"
outlet_node_name = "CHW Supply Bypass Outlet Node"

[pipe.adiabatic."CHW Supply Outlet Pipe"]
inlet_node_name = "CHW Supply Outlet Pipe Inlet Node"
outlet_node_name = "CHW Supply Outlet Node"

[pipe.adiabatic."CHW Demand Inlet Pipe"]
inlet_node_name = "CHW Demand Inlet Node"
outlet_node_name = "CHW Demand Inlet Pipe Outlet Node"

[pipe.adiabatic."CHW Demand Bypass Pipe"]
inlet_node_name = "CHW Demand Bypass Inlet Node"
outlet_node_name = "CHW Demand Bypass Outlet Node"

[pipe.adiabatic."CHW Demand Outlet Pipe"]
inlet_node_name = "CHW Demand Outlet Pipe Inlet Node"
outlet_node_name = "CHW Demand Outlet Node"

[[output.variable-dictionary]]
key_field = "IDF"

[[output.variable]]
key_value = "*"
variable_name = "Zone Air System Sensible Heating Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Air System Sensible Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Total Internal Latent Gain Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Mean Air Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Heating Coil Heating Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Cooling Coil Total Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Cooling Coil Sensible Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Site Outdoor Air Barometric Pressure"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Supply Fan"
variable_name = "Fan Electricity Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Return Fan"
variable_name = "Fan Electricity Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone Exhaust Fan"
variable_name = "Fan Air Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Air Loop"
variable_name = "Air System Outdoor Air Economizer Status"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Air Loop"
variable_name = "Air System Outdoor Air Flow Fraction"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Heating Coil Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Heating Coil Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Heating Coil Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Return Fan Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Return Fan Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Return Fan Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[run-period."AE206 Run"]
begin_month = 1
begin_day_of_month = 1
end_month = 1
end_day_of_month = 7
use_weather_file_holidays_and_special_days = "No"
use_weather_file_daylight_saving_period = "No"
apply_weekend_holiday_rule = "No"
use_weather_file_rain_indicators = "Yes"
use_weather_file_snow_indicators = "Yes"