Section 11 · Air-side equipment

Case AE345

Values compared
66
Outside example range
13
Run time
0.08 s
Input file
AE345.toml, 41.5 kB

Against the example programs

Each reported quantity next to the spread of the simulation programs published with the standard.

Position in the example range
Example rangeSIMsara
Sensible Cooling Load (QZC1sensible) (kWh/h)AE CV coil and zone loads
1.4651.466
In range
Sensible Cooling Load (QZC1sensible) (kWh/h), AE CV coil and zone loads: SIMsara 1.465 · range 1.465 to 1.466
Latent Load (QZ1latent) (kWh/h)AE CV coil and zone loads
0.58610.5897
In range
Latent Load (QZ1latent) (kWh/h), AE CV coil and zone loads: SIMsara 0.5861 · range 0.5861 to 0.5897
Sensible Cooling Load (QZC2sensible) (kWh/h)AE CV coil and zone loads
2.3442.345
In range
Sensible Cooling Load (QZC2sensible) (kWh/h), AE CV coil and zone loads: SIMsara 2.345 · range 2.344 to 2.345
Latent Load (QZ2latent) (kWh/h)AE CV coil and zone loads
0.87910.8909
In range
Latent Load (QZ2latent) (kWh/h), AE CV coil and zone loads: SIMsara 0.8792 · range 0.8791 to 0.8909
Loads Sensible (QCsensible) (kWh/h)AE CV coil and zone loads
9.2859.707
In range
Loads Sensible (QCsensible) (kWh/h), AE CV coil and zone loads: SIMsara 9.683 · range 9.285 to 9.707
Total (QCtotal) (kWh/h)AE CV coil and zone loads
9.2859.707
In range
Total (QCtotal) (kWh/h), AE CV coil and zone loads: SIMsara 9.683 · range 9.285 to 9.707
Coil Outlet RH (RHcco) (%)AE CV coil and zone loads
50.70751.330
In range
Coil Outlet RH (RHcco) (%), AE CV coil and zone loads: SIMsara 50.966 · range 50.707 to 51.330
Reheat Coil Load (QH1reheat) (kWh/h)AE CV coil and zone loads
2.0892.261
In range
Reheat Coil Load (QH1reheat) (kWh/h), AE CV coil and zone loads: SIMsara 2.253 · range 2.089 to 2.261
Reheat Coil Load (QH2reheat) (kWh/h)AE CV coil and zone loads
2.2412.461
In range
Reheat Coil Load (QH2reheat) (kWh/h), AE CV coil and zone loads: SIMsara 2.450 · range 2.241 to 2.461
DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)AE CV node states
24.88924.900
In range
DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa), AE CV node states: SIMsara 24.900 · range 24.889 to 24.900
DRY BULB TEMPERATURE (°C) · Mixed Air (ma)AE CV node states
24.88924.900
In range
DRY BULB TEMPERATURE (°C) · Mixed Air (ma), AE CV node states: SIMsara 24.900 · range 24.889 to 24.900
DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)AE CV node states
24.88924.900
In range
DRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco), AE CV node states: SIMsara 24.900 · range 24.889 to 24.900
DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)AE CV node states
12.19712.222
In range
DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco), AE CV node states: SIMsara 12.206 · range 12.197 to 12.222
DRY BULB TEMPERATURE (°C) · Supply Air (sa)AE CV node states
12.77112.795
In range
DRY BULB TEMPERATURE (°C) · Supply Air (sa), AE CV node states: SIMsara 12.778 · range 12.771 to 12.795
DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)AE CV node states
19.05219.180
In range
DRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s), AE CV node states: SIMsara 19.177 · range 19.052 to 19.180
DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)AE CV node states
18.57218.750
In range
DRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s), AE CV node states: SIMsara 18.743 · range 18.572 to 18.750
DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)AE CV node states
23.32823.339
In range
DRY BULB TEMPERATURE (°C) · Zone 1 Air (z1), AE CV node states: SIMsara 23.333 · range 23.328 to 23.339
DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)AE CV node states
24.43824.452
In range
DRY BULB TEMPERATURE (°C) · Zone 2 Air (z2), AE CV node states: SIMsara 24.444 · range 24.438 to 24.452
DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)AE CV node states
23.88723.946
In range
DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi), AE CV node states: SIMsara 23.892 · range 23.887 to 23.946
DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)AE CV node states
24.16724.241
In range
DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo), AE CV node states: SIMsara 24.232 · range 24.167 to 24.241
HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)AE CV node states
0.0044570.004510
In range
HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa), AE CV node states: SIMsara 0.004481 · range 0.004457 to 0.004510
HUMIDITY RATIO (G/GDA) · Mixed Air (ma)AE CV node states
0.0044570.004510
In range
HUMIDITY RATIO (G/GDA) · Mixed Air (ma), AE CV node states: SIMsara 0.004481 · range 0.004457 to 0.004510
HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)AE CV node states
0.0044570.004510
In range
HUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco), AE CV node states: SIMsara 0.004481 · range 0.004457 to 0.004510
HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)AE CV node states
0.0044570.004510
In range
HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco), AE CV node states: SIMsara 0.004481 · range 0.004457 to 0.004510
TableQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE CV coil and zone loadsSensible Heating Load (QZH1sensible) (kWh/h)00000In range
AE CV coil and zone loadsSensible Cooling Load (QZC1sensible) (kWh/h)1.4651.4651.4661.4651.465In range
AE CV coil and zone loadsLatent Load (QZ1latent) (kWh/h)0.58610.58610.58970.58670.5861In range
AE CV coil and zone loadsSensible Heating Load (QZH2sensible) (kWh/h)00000In range
AE CV coil and zone loadsSensible Cooling Load (QZC2sensible) (kWh/h)2.3452.3442.3452.3452.345In range
AE CV coil and zone loadsLatent Load (QZ2latent) (kWh/h)0.87920.87910.89090.88110.8792In range
AE CV coil and zone loadsCoil Load (QHpreheat) (kWh/h)00000In range
AE CV coil and zone loadsLoads Sensible (QCsensible) (kWh/h)9.6839.2859.7079.5319.703In range
AE CV coil and zone loadsLatent (QClatent) (kWh/h)00000In range
AE CV coil and zone loadsTotal (QCtotal) (kWh/h)9.6839.2859.7079.5319.703In range
AE CV coil and zone loadsCoil Outlet RH (RHcco) (%)50.96650.70751.33051.06351.089In range
AE CV coil and zone loadsReheat Coil Load (QH1reheat) (kWh/h)2.2532.0892.2612.1862.259In range
AE CV coil and zone loadsReheat Coil Load (QH2reheat) (kWh/h)2.4502.2412.4612.3642.457In range
AE CV node statesDRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)24.90024.88924.90024.89624.900In range
AE CV node statesDRY BULB TEMPERATURE (°C) · Mixed Air (ma)24.90024.88924.90024.89624.900In range
AE CV node statesDRY BULB TEMPERATURE (°C) · Preheat Coil Outlet (pco)24.90024.88924.90024.89624.900In range
AE CV node statesDRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)12.20612.19712.22212.20512.207In range
AE CV node statesDRY BULB TEMPERATURE (°C) · Supply Air (sa)12.77812.77112.79512.78012.778In range
AE CV node statesDRY BULB TEMPERATURE (°C) · Zone 1 Supply Air (z1s)19.17719.05219.18019.12219.180In range
AE CV node statesDRY BULB TEMPERATURE (°C) · Zone 2 Supply Air (z2s)18.74318.57218.75018.66918.748In range
AE CV node statesDRY BULB TEMPERATURE (°C) · Zone 1 Air (z1)23.33323.32823.33923.33323.333In range
AE CV node statesDRY BULB TEMPERATURE (°C) · Zone 2 Air (z2)24.44424.43824.45224.44424.444In range
AE CV node statesDRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)23.89223.88723.94623.90123.892In range
AE CV node statesDRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)24.23224.16724.24124.19824.232In range
AE CV node statesHUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.0044810.0044570.0045100.0044910.004491In range
AE CV node statesHUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0044810.0044570.0045100.0044910.004491In range
AE CV node statesHUMIDITY RATIO (G/GDA) · Preheat Coil Outlet (pco)0.0044810.0044570.0045100.0044910.004491In range
AE CV node statesHUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0044810.0044570.0045100.0044910.004491In range
AE CV node statesHUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0044810.0044570.0045100.0044910.004491In range
AE CV node statesHUMIDITY RATIO (G/GDA) · Zone 1 Supply Air (z1s)0.0044810.0044570.0045100.0044910.004491In range
AE CV node statesHUMIDITY RATIO (G/GDA) · Zone 2 Supply Air (z2s)0.0044810.0044570.0045100.0044910.004491In range
AE CV node statesHUMIDITY RATIO (G/GDA) · Zone 1 Air (z1)0.0051440.0051190.0052120.0051690.005153In range
AE CV node statesHUMIDITY RATIO (G/GDA) · Zone 2 Air (z2)0.0053330.0053080.0054130.0053650.005342In range
AE CV node statesHUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)0.0052390.0052140.0053150.0052740.005248In range
AE CV node statesHUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)0.0052390.0052140.0053150.0052740.005248In range
AE CV node statesSPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)851.19830.35850.44841.09850.43Above range
AE CV node statesSPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)851.19830.35850.44841.09850.43Above range
AE CV node statesSPECIFIC VOLUME (L/KGDA) · Preheat Coil Outlet (pco)851.19830.35850.44841.09850.43Above range
AE CV node statesSPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)814.95814.06833.33822.99814.21In range
AE CV node statesSPECIFIC VOLUME (L/KGDA) · Supply Air (sa)816.59811.84833.33822.80815.84In range
AE CV node statesSPECIFIC VOLUME (L/KGDA) · Zone 1 Supply Air (z1s)834.85830.35834.12832.94834.11Above range
AE CV node statesSPECIFIC VOLUME (L/KGDA) · Zone 2 Supply Air (z2s)833.61830.35833.33832.32832.88Above range
AE CV node statesSPECIFIC VOLUME (L/KGDA) · Zone 1 Air (z1)847.61830.35846.85839.31846.86Above range
AE CV node statesSPECIFIC VOLUME (L/KGDA) · Zone 2 Air (z2)851.04830.35850.28841.02850.28Above range
AE CV node statesSPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi)849.33830.35848.57840.17848.58Above range
AE CV node statesSPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo)850.31830.35849.27840.03849.55Above range
AE CV node statesENTHALPY (J/GDA) · Location Outdoor Air (oa)36.43536.43536.50636.47736.491In range
AE CV node statesENTHALPY (J/GDA) · Mixed Air (ma)36.43536.43536.50636.47736.491In range
AE CV node statesENTHALPY (J/GDA) · Preheat Coil Outlet (pco)36.43536.43536.50636.47736.491In range
AE CV node statesENTHALPY (J/GDA) · Cool Coil Outlet (cco)23.57323.56423.64023.60423.615In range
AE CV node statesENTHALPY (J/GDA) · Supply Air (sa)24.15324.15524.24024.19424.194Below range
AE CV node statesENTHALPY (J/GDA) · Zone 1 Supply Air (z1s)30.63630.55030.68730.60030.688In range
AE CV node statesENTHALPY (J/GDA) · Zone 2 Supply Air (z2s)30.19730.07030.25130.13930.251In range
AE CV node statesENTHALPY (J/GDA) · Zone 1 Air (z1)36.53436.57136.68036.61236.587Below range
AE CV node statesENTHALPY (J/GDA) · Zone 2 Air (z2)38.14138.19038.33038.23938.196Below range
AE CV node statesENTHALPY (J/GDA) · Return Fan Inlet (rfi)37.34337.38137.59037.45637.396Below range
AE CV node statesENTHALPY (J/GDA) · Return Fan Outlet (rfo)37.68837.59037.74137.66937.741In range
AE CV node statesMASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.75280.72170.75370.74000.7535In range
AE CV node statesMASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.75280.72170.75370.74000.7535In range
AE CV node statesMASS FLOW RATE (KGDA/S) · Preheat Coil Outlet (pco)0.75280.72170.75370.74000.7535In range
AE CV node statesMASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.75280.72170.75370.74000.7535In range
AE CV node statesMASS FLOW RATE (KGDA/S) · Supply Air (sa)0.75280.72170.75370.74000.7535In range
AE CV node statesMASS FLOW RATE (KGDA/S) · Zone 1 Supply Air (z1s)0.34750.33310.34780.34160.3478In range
AE CV node statesMASS FLOW RATE (KGDA/S) · Zone 2 Supply Air (z2s)0.40540.38860.40580.39850.4057In range
AE CV node statesMASS FLOW RATE (KGDA/S) · Zone 1 Air (z1)n/a*
AE CV node statesMASS FLOW RATE (KGDA/S) · Zone 2 Air (z2)n/a*
AE CV node statesMASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi)0.47510.44410.47570.45940.4756In range
AE CV node statesMASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo)0.47510.44410.47570.45940.4756In range

Reported outputs

The values the engine wrote for this case, before they are placed in the output template.

OutputValue
SeriesAE300
Loads (kWh/h) · qZH1sensible0
Loads (kWh/h) · qZC1sensible1.465
Loads (kWh/h) · qZ1latent0.5861
Loads (kWh/h) · qZH2sensible0
Loads (kWh/h) · qZC2sensible2.345
Loads (kWh/h) · qZ2latent0.8792
Loads (kWh/h) · qPH0
Loads (kWh/h) · qCsensible9.683
Loads (kWh/h) · qClatent0
Loads (kWh/h) · qCtotal9.683
Loads (kWh/h) · rHcco50.966
Loads (kWh/h) · qRH12.253
Loads (kWh/h) · qRH22.450
Nodes · oa · tdb (°C)24.900
Nodes · oa · w (g/g)0.004481
Nodes · oa · v (L/kg)851.19
Nodes · oa · h (J/g)36.435
Nodes · oa · m (kg/s)0.7528
Nodes · oa · rh (%)23.000
Nodes · ma · tdb (°C)24.900
Nodes · ma · w (g/g)0.004481
Nodes · ma · v (L/kg)851.19
Nodes · ma · h (J/g)36.435
Nodes · ma · m (kg/s)0.7528
Nodes · ma · rh (%)23.000
Nodes · pco · tdb (°C)24.900
Nodes · pco · w (g/g)0.004481
Nodes · pco · v (L/kg)851.19
Nodes · pco · h (J/g)36.435
Nodes · pco · m (kg/s)0.7528
Nodes · pco · rh (%)23.000
Nodes · cco · tdb (°C)12.206
Nodes · cco · w (g/g)0.004481
Nodes · cco · v (L/kg)814.95
Nodes · cco · h (J/g)23.573
Nodes · cco · m (kg/s)0.7528
Nodes · cco · rh (%)50.966
Nodes · sa · tdb (°C)12.778
Nodes · sa · w (g/g)0.004481
Nodes · sa · v (L/kg)816.59
Nodes · sa · h (J/g)24.153
Nodes · sa · m (kg/s)0.7528
Nodes · sa · rh (%)49.085
Nodes · z1s · tdb (°C)19.177
Nodes · z1s · w (g/g)0.004481
Nodes · z1s · v (L/kg)834.85
Nodes · z1s · h (J/g)30.636
Nodes · z1s · m (kg/s)0.3475
Nodes · z1s · rh (%)32.608
Nodes · z2s · tdb (°C)18.743
Nodes · z2s · w (g/g)0.004481
Nodes · z2s · v (L/kg)833.61
Nodes · z2s · h (J/g)30.197
Nodes · z2s · m (kg/s)0.4054
Nodes · z2s · rh (%)33.502
Nodes · z1 · tdb (°C)23.333
Nodes · z1 · w (g/g)0.005144
Nodes · z1 · v (L/kg)847.61
Nodes · z1 · h (J/g)36.534
Nodes · z1 · rh (%)28.976
Nodes · z2 · tdb (°C)24.444
Nodes · z2 · w (g/g)0.005333
Nodes · z2 · v (L/kg)851.04
Nodes · z2 · h (J/g)38.141
Nodes · z2 · rh (%)28.090
Nodes · rfi · tdb (°C)23.892
Nodes · rfi · w (g/g)0.005239
Nodes · rfi · v (L/kg)849.33
Nodes · rfi · h (J/g)37.343
Nodes · rfi · m (kg/s)0.4751
Nodes · rfi · rh (%)28.529
Nodes · rfo · tdb (°C)24.232
Nodes · rfo · w (g/g)0.005239
Nodes · rfo · v (L/kg)850.31
Nodes · rfo · h (J/g)37.688
Nodes · rfo · m (kg/s)0.4751
Nodes · rfo · rh (%)27.952
Pressure pa101,300
Zones · z1 · tdb (°C)23.333
Zones · z1 · sensible heating (W)0
Zones · z1 · sensible cooling (W)1,465.0
Zones · z1 · latent (W)586.10
Zones · z2 · tdb (°C)24.444
Zones · z2 · sensible heating (W)0
Zones · z2 · sensible cooling (W)2,345.0
Zones · z2 · latent (W)879.20
Fans · supply (W)436.48
Fans · return (W)163.97
Fans · exhaust (kg/s) · z10.1114
Fans · exhaust (kg/s) · z20.1664
Fan power (W)436.48
Program outputs · preheat coil (W)0
Program outputs · reheat coil (W) · z12,252.6
Program outputs · reheat coil (W) · z22,450.1
Program outputs · cooling coil total (W)9,682.8
Program outputs · cooling coil sensible (W)9,682.8
Program outputs · condensate · kg (s)0
Program outputs · condensate · temp (°C)12.206
Program outputs · condensate · h j kg51,019.1
Program outputs · condensate · w0
Program outputs · condensate · entering dew point (°C)2.365
Program outputs · condensate · sensible (W)0
Balance · residual (W) · return mixer2.91e-11
Balance · residual (W) · return fan8.81e-13
Balance · residual (W) · mixer0
Balance · residual (W) · preheat coil0
Balance · residual (W) · cooling coil−3.64e-12
Balance · residual (W) · supply fan−1.76e-12
Balance · residual (W) · reheat coil 10
Balance · residual (W) · zone 11.780
Balance · residual (W) · reheat coil 2−9.09e-13
Balance · residual (W) · zone 23.659
Balance · residual (W) · system5.439
Balance · relative · return mixer3.01e-15
Balance · relative · return fan9.10e-17
Balance · relative · mixer0
Balance · relative · preheat coil0
Balance · relative · cooling coil3.76e-16
Balance · relative · supply fan1.82e-16
Balance · relative · reheat coil 10
Balance · relative · zone 11.84e-4
Balance · relative · reheat coil 29.39e-17
Balance · relative · zone 23.78e-4
Balance · relative · system5.62e-4
Balance · max relative5.62e-4
Balance · reference (W)9,682.8
Economizer status1.000
Oa fraction1.000
Cycling · steps6
Flows · zone supply std (m³/s)2 values
Flows · exhaust std (m³/s)2 values
Flows · oa std (m³/s)0.2306
Flows · supply fan dp pa488.77
Flows · return fan dp pa730.48
Flows · setpoint offsets k2 values
Flow iterations4
Flow record · convergedtrue
Flow record · iterations4
Flow record · relative change2.53e-9
Flow record · zone tdb error k−1.48e-9
Flow record · zone tdb errors k2 values
Econo min · caseAE345
Econo min · odb econo min (°C)−8.448
Econo min · iterations6
Econo min · outer iterations3
Econo min · m supply (kg/s)0.7545
Econo min · m zone supply (kg/s)2 values
Econo min · m exhaust (kg/s)2 values
Econo min · m oa (kg/s)0.2783
Econo min · m return (kg/s)0.4761
Econo min · supply fan (W)436.48
Econo min · return fan (W)163.97
Econo min · mixed air (°C)12.205
Econo min · supply fan rise k0.5724
Econo min · oa w case0.004492
Econo min · oa (W)0.001835
Econo min · outdoor saturatedtrue
Econo min · w over saturation · supply0.3402
Econo min · w over saturation · mixed0.3535
Econo min · w over saturation · zone10.2092
Econo min · w over saturation · zone20.2050
Econo min · w over saturation · return fan inlet0.2071
Econo min · w over saturation · return fan outlet0.2028
Econo min · w over saturation · outdoor1
Econo min · physicaltrue
Econo min · inputs · pressure pa101,300
Econo min · inputs · supply setpoint (°C)12.778
Econo min · inputs · zone setpoint (°C)2 values
Econo min · inputs · zone latent (W)2 values
Econo min · inputs · oa (W)0.004492
Econo min · inputs · supply (m³/s)0.6135
Econo min · inputs · zone fraction2 values
Econo min · inputs · exhaust (m³/s)2 values
Econo min · inputs · supply fan pa498
Econo min · inputs · supply fan eff0.7000
Econo min · arithmeticm_w = (586.1 / hg(23.333), 879.2 / hg(24.444)) = (0.000230356708, 0.000345274445) kg/s; supply fan 436.482771 W; h_ma = h(12.7777778 C, 0.0031293405) - 436.482771 / 0.754468339 = 20161.7168 J/kg (T_ma 12.2053481 C); m_sup = 0.754468339, zones (0.348216156, 0.406252182), exhausts (0.111601112, 0.16672102), m_oa = 0.278322132, m_ret = 0.476146207 kg/s (6 iterations); w_oa = min(0.00449224554, w_sat(-8.44776629 C) = 0.00183549164) = 0.00183549164 (3 outer iterations); zones w = (0.00379087416, 0.00397924226); return fan inlet 23.8919982 C, 0.00388563503; return fan 163.97313 W; h_oa = (0.754468339 x 20161.7168 - 0.476146207 x 34242.3279) / 0.278322132 = -3927.02354 J/kg; ODBecono,min = -8.44776629 C

Input file

sha256 bdf36847808e8cb8e818e664b5c1b986e95d5e5f9bf53eae225a02ba02a7c820

AE345.tomlDownload
[version]
version_identifier = "26.1"

[simulation-control]
do_zone_sizing_calculation = "No"
do_system_sizing_calculation = "No"
do_plant_sizing_calculation = "No"
run_simulation_for_sizing_periods = "No"
run_simulation_for_weather_file_run_periods = "Yes"
do_hvac_sizing_simulation_for_sizing_periods = "No"
maximum_number_of_hvac_sizing_simulation_passes = 1

[building."ASHRAE 140 AE345"]
north_axis = 0.0
terrain = "Suburbs"
loads_convergence_tolerance_value = 0.04
temperature_convergence_tolerance_value = 0.4
solar_distribution = "FullExterior"
maximum_number_of_warmup_days = 25
minimum_number_of_warmup_days = 6

[building.surface.detailed."South Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."East Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."North Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."West Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."Floor"]
surface_type = "Floor"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
]

[building.surface.detailed."Roof"]
surface_type = "Roof"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."Zone Two South Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone Two"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 6.3, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 6.3, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."Zone Two East Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone Two"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 6.3, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 6.3, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 6.3, vertex_y_coordinate = 10.2, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 6.3, vertex_y_coordinate = 10.2, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."Zone Two North Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone Two"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 6.3, vertex_y_coordinate = 10.2, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 6.3, vertex_y_coordinate = 10.2, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 10.2, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 10.2, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."Zone Two West Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone Two"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 10.2, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 10.2, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."Zone Two Floor"]
surface_type = "Floor"
construction_name = "Adiabatic Panel"
zone_name = "Zone Two"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 6.3, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 10.2, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 6.3, vertex_y_coordinate = 10.2, vertex_z_coordinate = 0.0 },
]

[building.surface.detailed."Zone Two Roof"]
surface_type = "Roof"
construction_name = "Adiabatic Panel"
zone_name = "Zone Two"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 10.2, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 6.3, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 6.3, vertex_y_coordinate = 10.2, vertex_z_coordinate = 2.9 },
]

[timestep]
number_of_timesteps_per_hour = 6

[heat-balance-algorithm]
algorithm = "ConductionTransferFunction"
surface_temperature_upper_limit = 200.0

[surface.convection.algorithm.inside]
algorithm = "TARP"

[surface.convection.algorithm.outside]
algorithm = "DOE-2"

[global-geometry-rules]
starting_vertex_position = "UpperLeftCorner"
vertex_entry_direction = "Counterclockwise"
coordinate_system = "Relative"

[site.location."AE artificial site"]
latitude = 25.8
longitude = -80.3
time_zone = -5.0
elevation = 0.0

[schedule-type-limits."Any Number"]

[schedule-type-limits."Fraction"]
lower_limit_value = 0.0
upper_limit_value = 1.0
numeric_type = "Continuous"

[schedule-type-limits."Temperature"]
lower_limit_value = -60.0
upper_limit_value = 200.0
numeric_type = "Continuous"
unit_type = "Temperature"

[schedule-type-limits."Control Type"]
lower_limit_value = 0.0
upper_limit_value = 4.0
numeric_type = "Discrete"

[schedule.compact."Always On"]
schedule_type_limits_name = "Fraction"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 1.0 },
]

[schedule.compact."Zone One Heating Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 23.33194148508965 },
]

[schedule.compact."Zone One Cooling Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 28.33194148508965 },
]

[schedule.compact."Zone Two Heating Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 24.443738739939196 },
]

[schedule.compact."Zone Two Cooling Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 29.443738739939196 },
]

[schedule.compact."Dual Setpoint Control"]
schedule_type_limits_name = "Control Type"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 4 },
]

[schedule.compact."Preheat Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 7.222222222222222 },
]

[schedule.compact."Supply Air Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 12.777777777777777 },
]

[schedule.compact."CHW Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 6.67 },
]

[material."Gypsum Board 13mm"]
roughness = "Smooth"
thickness = 0.0127
conductivity = 0.16
density = 800.0
specific_heat = 1090.0
thermal_absorptance = 0.9
solar_absorptance = 0.5
visible_absorptance = 0.5

[construction."Adiabatic Panel"]
outside_layer = "Gypsum Board 13mm"

[zone."Zone One"]
direction_of_relative_north = 0.0
x_origin = 0.0
y_origin = 0.0
z_origin = 0.0
type = 1
multiplier = 1
ceiling_height = "Autocalculate"
volume = "Autocalculate"
floor_area = "Autocalculate"
zone_inside_convection_algorithm = "TARP"
zone_outside_convection_algorithm = "DOE-2"
part_of_total_floor_area = "Yes"

[zone."Zone Two"]
direction_of_relative_north = 0.0
x_origin = 0.0
y_origin = 0.0
z_origin = 0.0
type = 1
multiplier = 1
ceiling_height = "Autocalculate"
volume = "Autocalculate"
floor_area = "Autocalculate"
zone_inside_convection_algorithm = "TARP"
zone_outside_convection_algorithm = "DOE-2"
part_of_total_floor_area = "Yes"

[zone.control.thermostat."Zone One Thermostat"]
zone_or_zonelist_name = "Zone One"
control_type_schedule_name = "Dual Setpoint Control"
control_1_object_type = "ThermostatSetpoint:DualSetpoint"
control_1_name = "Zone One Dual Setpoint"

[zone.control.thermostat."Zone Two Thermostat"]
zone_or_zonelist_name = "Zone Two"
control_type_schedule_name = "Dual Setpoint Control"
control_1_object_type = "ThermostatSetpoint:DualSetpoint"
control_1_name = "Zone Two Dual Setpoint"

[zone.hvac.air-distribution-unit."Zone One ADU"]
air_distribution_unit_outlet_node_name = "Zone One Supply Inlet"
air_terminal_object_type = "AirTerminal:SingleDuct:VAV:Reheat"
air_terminal_name = "Zone One Terminal"
nominal_upstream_leakage_fraction = 0.0
constant_downstream_leakage_fraction = 0.0

[zone.hvac.air-distribution-unit."Zone Two ADU"]
air_distribution_unit_outlet_node_name = "Zone Two Supply Inlet"
air_terminal_object_type = "AirTerminal:SingleDuct:VAV:Reheat"
air_terminal_name = "Zone Two Terminal"
nominal_upstream_leakage_fraction = 0.0
constant_downstream_leakage_fraction = 0.0

[zone.hvac.equipment-list."Zone One Equipment List"]
load_distribution_scheme = "SequentialLoad"
equipment = [
  { zone_equipment_object_type = "ZoneHVAC:AirDistributionUnit", zone_equipment_name = "Zone One ADU", zone_equipment_cooling_sequence = 1, zone_equipment_heating_or_no_load_sequence = 1 },
  { zone_equipment_object_type = "Fan:ZoneExhaust", zone_equipment_name = "Zone One Exhaust Fan", zone_equipment_cooling_sequence = 2, zone_equipment_heating_or_no_load_sequence = 2 },
]

[zone.hvac.equipment-list."Zone Two Equipment List"]
load_distribution_scheme = "SequentialLoad"
equipment = [
  { zone_equipment_object_type = "ZoneHVAC:AirDistributionUnit", zone_equipment_name = "Zone Two ADU", zone_equipment_cooling_sequence = 1, zone_equipment_heating_or_no_load_sequence = 1 },
  { zone_equipment_object_type = "Fan:ZoneExhaust", zone_equipment_name = "Zone Two Exhaust Fan", zone_equipment_cooling_sequence = 2, zone_equipment_heating_or_no_load_sequence = 2 },
]

[[zone.hvac.equipment-connections]]
zone_name = "Zone One"
zone_conditioning_equipment_list_name = "Zone One Equipment List"
zone_air_inlet_node_or_nodelist_name = "Zone One Supply Inlet"
zone_air_node_name = "Zone One Air Node"
zone_return_air_node_or_nodelist_name = "Zone One Return Outlet"
zone_air_exhaust_node_or_nodelist_name = "Zone One Exhaust Node"

[[zone.hvac.equipment-connections]]
zone_name = "Zone Two"
zone_conditioning_equipment_list_name = "Zone Two Equipment List"
zone_air_inlet_node_or_nodelist_name = "Zone Two Supply Inlet"
zone_air_node_name = "Zone Two Air Node"
zone_return_air_node_or_nodelist_name = "Zone Two Return Outlet"
zone_air_exhaust_node_or_nodelist_name = "Zone Two Exhaust Node"

[other-equipment."Zone One Sensible Cooling Load"]
fuel_type = "None"
zone_or_zonelist_or_space_or_spacelist_name = "Zone One"
schedule_name = "Always On"
design_level_calculation_method = "EquipmentLevel"
design_level = 1465.0
fraction_latent = 0.0
fraction_radiant = 0.0
fraction_lost = 0.0

[other-equipment."Zone One Latent Load"]
fuel_type = "None"
zone_or_zonelist_or_space_or_spacelist_name = "Zone One"
schedule_name = "Always On"
design_level_calculation_method = "EquipmentLevel"
design_level = 586.1
fraction_latent = 1.0
fraction_radiant = 0.0
fraction_lost = 0.0

[other-equipment."Zone Two Sensible Cooling Load"]
fuel_type = "None"
zone_or_zonelist_or_space_or_spacelist_name = "Zone Two"
schedule_name = "Always On"
design_level_calculation_method = "EquipmentLevel"
design_level = 2345.0
fraction_latent = 0.0
fraction_radiant = 0.0
fraction_lost = 0.0

[other-equipment."Zone Two Latent Load"]
fuel_type = "None"
zone_or_zonelist_or_space_or_spacelist_name = "Zone Two"
schedule_name = "Always On"
design_level_calculation_method = "EquipmentLevel"
design_level = 879.2
fraction_latent = 1.0
fraction_radiant = 0.0
fraction_lost = 0.0

[thermostat.setpoint.dual-setpoint."Zone One Dual Setpoint"]
heating_setpoint_temperature_schedule_name = "Zone One Heating Setpoint"
cooling_setpoint_temperature_schedule_name = "Zone One Cooling Setpoint"

[thermostat.setpoint.dual-setpoint."Zone Two Dual Setpoint"]
heating_setpoint_temperature_schedule_name = "Zone Two Heating Setpoint"
cooling_setpoint_temperature_schedule_name = "Zone Two Cooling Setpoint"

[air-loop-hvac."AHU"]
controller_list_name = "AHU Controllers"
availability_manager_list_name = "AHU Availability"
design_supply_air_flow_rate = 0.625122080244837
branch_list_name = "AHU Branches"
supply_side_inlet_node_name = "Air Loop Inlet Node"
demand_side_outlet_node_name = "Zone Equipment Outlet Node"
demand_side_inlet_node_names = "Zone Equipment Inlet Node"
supply_side_outlet_node_names = "Supply Outlet Node"
design_return_air_flow_fraction_of_supply_air_flow = 1.0

[branch-list."AHU Branches"]
branches = [
  { branch_name = "AHU Branch" },
]

[branch-list."CHW Supply Branches"]
branches = [
  { branch_name = "CHW Supply Inlet Branch" },
  { branch_name = "CHW Chiller Branch" },
  { branch_name = "CHW Supply Bypass Branch" },
  { branch_name = "CHW Supply Outlet Branch" },
]

[branch-list."CHW Demand Branches"]
branches = [
  { branch_name = "CHW Demand Inlet Branch" },
  { branch_name = "CHW Cooling Coil Branch" },
  { branch_name = "CHW Demand Bypass Branch" },
  { branch_name = "CHW Demand Outlet Branch" },
]

[branch."AHU Branch"]
components = [
  { component_object_type = "Fan:VariableVolume", component_name = "AHU Return Fan", component_inlet_node_name = "Air Loop Inlet Node", component_outlet_node_name = "Return Fan Outlet Node" },
  { component_object_type = "AirLoopHVAC:OutdoorAirSystem", component_name = "AHU OA System", component_inlet_node_name = "Return Fan Outlet Node", component_outlet_node_name = "Mixed Air Node" },
  { component_object_type = "Coil:Heating:Electric", component_name = "AHU Preheat Coil", component_inlet_node_name = "Mixed Air Node", component_outlet_node_name = "Preheat Coil Outlet Node" },
  { component_object_type = "Coil:Cooling:Water", component_name = "AHU Cooling Coil", component_inlet_node_name = "Preheat Coil Outlet Node", component_outlet_node_name = "Cooling Coil Outlet Node" },
  { component_object_type = "Fan:ConstantVolume", component_name = "AHU Supply Fan", component_inlet_node_name = "Cooling Coil Outlet Node", component_outlet_node_name = "Supply Outlet Node" },
]

[branch."CHW Supply Inlet Branch"]
components = [
  { component_object_type = "Pump:VariableSpeed", component_name = "CHW Pump", component_inlet_node_name = "CHW Supply Inlet Node", component_outlet_node_name = "CHW Pump Outlet Node" },
]

[branch."CHW Chiller Branch"]
components = [
  { component_object_type = "Chiller:Electric:EIR", component_name = "CHW Chiller", component_inlet_node_name = "CHW Chiller Inlet Node", component_outlet_node_name = "CHW Chiller Outlet Node" },
]

[branch."CHW Supply Bypass Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Supply Bypass Pipe", component_inlet_node_name = "CHW Supply Bypass Inlet Node", component_outlet_node_name = "CHW Supply Bypass Outlet Node" },
]

[branch."CHW Supply Outlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Supply Outlet Pipe", component_inlet_node_name = "CHW Supply Outlet Pipe Inlet Node", component_outlet_node_name = "CHW Supply Outlet Node" },
]

[branch."CHW Demand Inlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Inlet Pipe", component_inlet_node_name = "CHW Demand Inlet Node", component_outlet_node_name = "CHW Demand Inlet Pipe Outlet Node" },
]

[branch."CHW Cooling Coil Branch"]
components = [
  { component_object_type = "Coil:Cooling:Water", component_name = "AHU Cooling Coil", component_inlet_node_name = "Cooling Coil Water Inlet Node", component_outlet_node_name = "Cooling Coil Water Outlet Node" },
]

[branch."CHW Demand Bypass Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Bypass Pipe", component_inlet_node_name = "CHW Demand Bypass Inlet Node", component_outlet_node_name = "CHW Demand Bypass Outlet Node" },
]

[branch."CHW Demand Outlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Outlet Pipe", component_inlet_node_name = "CHW Demand Outlet Pipe Inlet Node", component_outlet_node_name = "CHW Demand Outlet Node" },
]

[air.loop.hvac.controller-list."AHU Controllers"]
controller_1_object_type = "Controller:WaterCoil"
controller_1_name = "Cooling Coil Controller"

[air.loop.hvac.controller-list."AHU OA Controllers"]
controller_1_object_type = "Controller:OutdoorAir"
controller_1_name = "AHU OA Controller"

[air.loop.hvac.outdoor-air-system."AHU OA System"]
controller_list_name = "AHU OA Controllers"
outdoor_air_equipment_list_name = "AHU OA Equipment"

[air.loop.hvac.outdoor.air.system.equipment-list."AHU OA Equipment"]
component_1_object_type = "OutdoorAir:Mixer"
component_1_name = "AHU OA Mixer"

[air.loop.hvac.supply-path."AHU Supply Path"]
supply_air_path_inlet_node_name = "Zone Equipment Inlet Node"
components = [
  { component_object_type = "AirLoopHVAC:ZoneSplitter", component_name = "Zone Supply Air Splitter" },
]

[air.loop.hvac.zone-splitter."Zone Supply Air Splitter"]
inlet_node_name = "Zone Equipment Inlet Node"
nodes = [
  { outlet_node_name = "Zone One Terminal Inlet" },
  { outlet_node_name = "Zone Two Terminal Inlet" },
]

[air.loop.hvac.return-path."AHU Return Path"]
return_air_path_outlet_node_name = "Zone Equipment Outlet Node"
components = [
  { component_object_type = "AirLoopHVAC:ZoneMixer", component_name = "Zone Return Air Mixer" },
]

[air.loop.hvac.zone-mixer."Zone Return Air Mixer"]
outlet_node_name = "Zone Equipment Outlet Node"
nodes = [
  { inlet_node_name = "Zone One Return Outlet" },
  { inlet_node_name = "Zone Two Return Outlet" },
]

[air.terminal.single.duct.vav.reheat."Zone One Terminal"]
availability_schedule_name = "Always On"
damper_air_outlet_node_name = "Zone One Damper Outlet"
air_inlet_node_name = "Zone One Terminal Inlet"
maximum_air_flow_rate = 0.2885178831899247
zone_minimum_air_flow_input_method = "Constant"
constant_minimum_air_flow_fraction = 1.0
reheat_coil_object_type = "Coil:Heating:Electric"
reheat_coil_name = "Zone One Reheat Coil"
minimum_hot_water_or_steam_flow_rate = 0.0
air_outlet_node_name = "Zone One Supply Inlet"
convergence_tolerance = 0.001
damper_heating_action = "Normal"
maximum_flow_per_zone_floor_area_during_reheat = 0.0
maximum_flow_fraction_during_reheat = 0.0
maximum_reheat_air_temperature = 46.5

[air.terminal.single.duct.vav.reheat."Zone Two Terminal"]
availability_schedule_name = "Always On"
damper_air_outlet_node_name = "Zone Two Damper Outlet"
air_inlet_node_name = "Zone Two Terminal Inlet"
maximum_air_flow_rate = 0.3366041970549122
zone_minimum_air_flow_input_method = "Constant"
constant_minimum_air_flow_fraction = 1.0
reheat_coil_object_type = "Coil:Heating:Electric"
reheat_coil_name = "Zone Two Reheat Coil"
minimum_hot_water_or_steam_flow_rate = 0.0
air_outlet_node_name = "Zone Two Supply Inlet"
convergence_tolerance = 0.001
damper_heating_action = "Normal"
maximum_flow_per_zone_floor_area_during_reheat = 0.0
maximum_flow_fraction_during_reheat = 0.0
maximum_reheat_air_temperature = 46.5

[availability-manager-assignment-list."AHU Availability"]
managers = [
  { availability_manager_object_type = "AvailabilityManager:Scheduled", availability_manager_name = "AHU Avail" },
]

[availability.manager.scheduled."AHU Avail"]
schedule_name = "Always On"

[fan.variable-volume."AHU Return Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.7
pressure_rise = 730.4779607894109
maximum_flow_rate = 0.625122080244837
fan_power_minimum_flow_rate_input_method = "Fraction"
fan_power_minimum_flow_fraction = 0.0
motor_efficiency = 1.0
motor_in_airstream_fraction = 0.0
fan_power_coefficient_1 = 0.0
fan_power_coefficient_2 = 0.0
fan_power_coefficient_3 = 0.0
fan_power_coefficient_4 = 1.0
fan_power_coefficient_5 = 0.0
air_inlet_node_name = "Air Loop Inlet Node"
air_outlet_node_name = "Return Fan Outlet Node"
end_use_subcategory = "Return Fans"

[fan.constant-volume."AHU Supply Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.7
pressure_rise = 488.76523427285156
maximum_flow_rate = 0.625122080244837
motor_efficiency = 1.0
motor_in_airstream_fraction = 0.0
air_inlet_node_name = "Cooling Coil Outlet Node"
air_outlet_node_name = "Supply Outlet Node"
end_use_subcategory = "General"

[fan.zone-exhaust."Zone One Exhaust Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.5
pressure_rise = 150.0
maximum_flow_rate = 0.09246824642261958
air_inlet_node_name = "Zone One Exhaust Node"
air_outlet_node_name = "Zone One Exhaust Fan Outlet"
end_use_subcategory = "General Exhaust"
system_availability_manager_coupling_mode = "Coupled"

[fan.zone-exhaust."Zone Two Exhaust Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.53
pressure_rise = 140.0
maximum_flow_rate = 0.1381384115985403
air_inlet_node_name = "Zone Two Exhaust Node"
air_outlet_node_name = "Zone Two Exhaust Fan Outlet"
end_use_subcategory = "General Exhaust"
system_availability_manager_coupling_mode = "Coupled"

[outdoor.air.mixer."AHU OA Mixer"]
mixed_air_node_name = "Mixed Air Node"
outdoor_air_stream_node_name = "Outdoor Air Inlet Node"
relief_air_stream_node_name = "Relief Air Outlet Node"
return_air_stream_node_name = "Return Fan Outlet Node"

[[outdoor.air.node-list]]
nodes = [
  { node_or_nodelist_name = "Outdoor Air Inlet Node" },
  { node_or_nodelist_name = "CHW Chiller Condenser Inlet Node" },
]

[controller.outdoor-air."AHU OA Controller"]
relief_air_outlet_node_name = "Relief Air Outlet Node"
return_air_node_name = "Return Fan Outlet Node"
mixed_air_node_name = "Mixed Air Node"
actuator_node_name = "Outdoor Air Inlet Node"
minimum_outdoor_air_flow_rate = 0.23060665802115984
maximum_outdoor_air_flow_rate = 0.625122080244837
economizer_control_type = "DifferentialEnthalpy"
economizer_control_action_type = "ModulateFlow"
lockout_type = "NoLockout"
minimum_limit_type = "FixedMinimum"
economizer_minimum_limit_dry_bulb_temperature = -8.447766292657132

[controller.water-coil."Cooling Coil Controller"]
control_variable = "Temperature"
action = "Reverse"
actuator_variable = "Flow"
sensor_node_name = "Cooling Coil Outlet Node"
actuator_node_name = "Cooling Coil Water Inlet Node"
controller_convergence_tolerance = 1e-06
maximum_actuated_flow = 0.000498329272168662
minimum_actuated_flow = 0.0

[coil.heating.electric."AHU Preheat Coil"]
availability_schedule_name = "Always On"
efficiency = 1.0
nominal_capacity = 20000.0
air_inlet_node_name = "Mixed Air Node"
air_outlet_node_name = "Preheat Coil Outlet Node"
temperature_setpoint_node_name = "Preheat Coil Outlet Node"

[coil.heating.electric."Zone One Reheat Coil"]
availability_schedule_name = "Always On"
efficiency = 1.0
nominal_capacity = 20000.0
air_inlet_node_name = "Zone One Damper Outlet"
air_outlet_node_name = "Zone One Supply Inlet"

[coil.heating.electric."Zone Two Reheat Coil"]
availability_schedule_name = "Always On"
efficiency = 1.0
nominal_capacity = 20000.0
air_inlet_node_name = "Zone Two Damper Outlet"
air_outlet_node_name = "Zone Two Supply Inlet"

[coil.cooling.water."AHU Cooling Coil"]
availability_schedule_name = "Always On"
design_water_flow_rate = 0.000498329272168662
design_air_flow_rate = 0.625122080244837
design_inlet_water_temperature = 12.0
design_inlet_air_temperature = 26.0
design_outlet_air_temperature = 14.0
design_inlet_air_humidity_ratio = 0.0135
design_outlet_air_humidity_ratio = 0.0099
water_inlet_node_name = "Cooling Coil Water Inlet Node"
water_outlet_node_name = "Cooling Coil Water Outlet Node"
air_inlet_node_name = "Preheat Coil Outlet Node"
air_outlet_node_name = "Cooling Coil Outlet Node"
type_of_analysis = "SimpleAnalysis"
heat_exchanger_configuration = "CrossFlow"

[setpoint.manager.scheduled."Preheat Temp Manager"]
control_variable = "Temperature"
schedule_name = "Preheat Setpoint"
setpoint_node_or_nodelist_name = "Preheat Coil Outlet Node"

[setpoint.manager.scheduled."Supply Air Temp Manager"]
control_variable = "Temperature"
schedule_name = "Supply Air Setpoint"
setpoint_node_or_nodelist_name = "Supply Outlet Node"

[setpoint.manager.scheduled."CHW Loop Setpoint Manager"]
control_variable = "Temperature"
schedule_name = "CHW Setpoint"
setpoint_node_or_nodelist_name = "CHW Supply Outlet Node"

[setpoint.manager.mixed-air."Mixed Air Temp Manager"]
control_variable = "Temperature"
reference_setpoint_node_name = "Supply Outlet Node"
fan_inlet_node_name = "Cooling Coil Outlet Node"
fan_outlet_node_name = "Supply Outlet Node"
setpoint_node_or_nodelist_name = "Cooling Setpoint Nodes"

[node-list."Cooling Setpoint Nodes"]
nodes = [
  { node_name = "Cooling Coil Outlet Node" },
  { node_name = "Mixed Air Node" },
]

[plant-loop."Chilled Water Loop"]
fluid_type = "Water"
plant_equipment_operation_scheme_name = "CHW Loop Operation"
loop_temperature_setpoint_node_name = "CHW Supply Outlet Node"
maximum_loop_temperature = 98.0
minimum_loop_temperature = 1.0
maximum_loop_flow_rate = 0.0006
minimum_loop_flow_rate = 0.0
plant_loop_volume = 0.5
plant_side_inlet_node_name = "CHW Supply Inlet Node"
plant_side_outlet_node_name = "CHW Supply Outlet Node"
plant_side_branch_list_name = "CHW Supply Branches"
plant_side_connector_list_name = "CHW Supply Connectors"
demand_side_inlet_node_name = "CHW Demand Inlet Node"
demand_side_outlet_node_name = "CHW Demand Outlet Node"
demand_side_branch_list_name = "CHW Demand Branches"
demand_side_connector_list_name = "CHW Demand Connectors"
load_distribution_scheme = "SequentialLoad"

[plant-equipment-operation-schemes."CHW Loop Operation"]
control_scheme_1_object_type = "PlantEquipmentOperation:CoolingLoad"
control_scheme_1_name = "CHW Cooling Scheme"
control_scheme_1_schedule_name = "Always On"

[plant.equipment.operation.cooling-load."CHW Cooling Scheme"]
load_range_1_lower_limit = 0.0
load_range_1_upper_limit = 1000000000.0
range_1_equipment_list_name = "CHW Chillers"

[plant-equipment-list."CHW Chillers"]
equipment = [
  { equipment_object_type = "Chiller:Electric:EIR", equipment_name = "CHW Chiller" },
]

[connector-list."CHW Supply Connectors"]
connector_1_object_type = "Connector:Splitter"
connector_1_name = "CHW Supply Splitter"
connector_2_object_type = "Connector:Mixer"
connector_2_name = "CHW Supply Mixer"

[connector-list."CHW Demand Connectors"]
connector_1_object_type = "Connector:Splitter"
connector_1_name = "CHW Demand Splitter"
connector_2_object_type = "Connector:Mixer"
connector_2_name = "CHW Demand Mixer"

[connector.splitter."CHW Supply Splitter"]
inlet_branch_name = "CHW Supply Inlet Branch"
branches = [
  { outlet_branch_name = "CHW Chiller Branch" },
  { outlet_branch_name = "CHW Supply Bypass Branch" },
]

[connector.splitter."CHW Demand Splitter"]
inlet_branch_name = "CHW Demand Inlet Branch"
branches = [
  { outlet_branch_name = "CHW Cooling Coil Branch" },
  { outlet_branch_name = "CHW Demand Bypass Branch" },
]

[connector.mixer."CHW Supply Mixer"]
outlet_branch_name = "CHW Supply Outlet Branch"
branches = [
  { inlet_branch_name = "CHW Chiller Branch" },
  { inlet_branch_name = "CHW Supply Bypass Branch" },
]

[connector.mixer."CHW Demand Mixer"]
outlet_branch_name = "CHW Demand Outlet Branch"
branches = [
  { inlet_branch_name = "CHW Cooling Coil Branch" },
  { inlet_branch_name = "CHW Demand Bypass Branch" },
]

[pump.variable-speed."CHW Pump"]
inlet_node_name = "CHW Supply Inlet Node"
outlet_node_name = "CHW Pump Outlet Node"
design_maximum_flow_rate = 0.0006
design_pump_head = 1000.0
design_power_consumption = 1.0
motor_efficiency = 0.9
fraction_of_motor_inefficiencies_to_fluid_stream = 0.0
coefficient_1_of_the_part_load_performance_curve = 0.0
coefficient_2_of_the_part_load_performance_curve = 1.0
coefficient_3_of_the_part_load_performance_curve = 0.0
coefficient_4_of_the_part_load_performance_curve = 0.0
design_minimum_flow_rate = 0.0
pump_control_type = "Intermittent"

[chiller.electric.eir."CHW Chiller"]
reference_capacity = 40000.0
reference_cop = 3.0
reference_leaving_chilled_water_temperature = 6.67
reference_entering_condenser_fluid_temperature = 35.0
reference_chilled_water_flow_rate = 0.0006
cooling_capacity_function_of_temperature_curve_name = "CHW Chiller Cap FT"
electric_input_to_cooling_output_ratio_function_of_temperature_curve_name = "CHW Chiller EIR FT"
electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name = "CHW Chiller EIR FPLR"
minimum_part_load_ratio = 0.1
maximum_part_load_ratio = 1.0
optimum_part_load_ratio = 1.0
minimum_unloading_ratio = 0.2
chilled_water_inlet_node_name = "CHW Chiller Inlet Node"
chilled_water_outlet_node_name = "CHW Chiller Outlet Node"
condenser_inlet_node_name = "CHW Chiller Condenser Inlet Node"
condenser_outlet_node_name = "CHW Chiller Condenser Outlet Node"
condenser_type = "AirCooled"
condenser_fan_power_ratio = 0.0
fraction_of_compressor_electric_consumption_rejected_by_condenser = 1.0
leaving_chilled_water_lower_temperature_limit = 2.0
chiller_flow_mode = "ConstantFlow"

[curve.biquadratic."CHW Chiller Cap FT"]
coefficient1_constant = 0.507883
coefficient2_x = 0.145228
coefficient3_x_2 = -0.00625644
coefficient4_y = -0.0011178
coefficient5_y_2 = -0.0001296
coefficient6_x_y = -0.00028188
minimum_value_of_x = 5.0
maximum_value_of_x = 10.0
minimum_value_of_y = 24.0
maximum_value_of_y = 35.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.biquadratic."CHW Chiller EIR FT"]
coefficient1_constant = 1.03076
coefficient2_x = -0.103536
coefficient3_x_2 = 0.00710208
coefficient4_y = 0.0093186
coefficient5_y_2 = 0.00031752
coefficient6_x_y = -0.00104328
minimum_value_of_x = 5.0
maximum_value_of_x = 10.0
minimum_value_of_y = 24.0
maximum_value_of_y = 35.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.quadratic."CHW Chiller EIR FPLR"]
coefficient1_constant = 0.088065
coefficient2_x = 1.137742
coefficient3_x_2 = -0.225806
minimum_value_of_x = 0.0
maximum_value_of_x = 1.0

[pipe.adiabatic."CHW Supply Bypass Pipe"]
inlet_node_name = "CHW Supply Bypass Inlet Node"
outlet_node_name = "CHW Supply Bypass Outlet Node"

[pipe.adiabatic."CHW Supply Outlet Pipe"]
inlet_node_name = "CHW Supply Outlet Pipe Inlet Node"
outlet_node_name = "CHW Supply Outlet Node"

[pipe.adiabatic."CHW Demand Inlet Pipe"]
inlet_node_name = "CHW Demand Inlet Node"
outlet_node_name = "CHW Demand Inlet Pipe Outlet Node"

[pipe.adiabatic."CHW Demand Bypass Pipe"]
inlet_node_name = "CHW Demand Bypass Inlet Node"
outlet_node_name = "CHW Demand Bypass Outlet Node"

[pipe.adiabatic."CHW Demand Outlet Pipe"]
inlet_node_name = "CHW Demand Outlet Pipe Inlet Node"
outlet_node_name = "CHW Demand Outlet Node"

[[output.variable-dictionary]]
key_field = "IDF"

[[output.variable]]
key_value = "*"
variable_name = "Zone Air System Sensible Heating Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Air System Sensible Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Total Internal Latent Gain Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Mean Air Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Heating Coil Heating Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Cooling Coil Total Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Cooling Coil Sensible Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Site Outdoor Air Barometric Pressure"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "AHU Supply Fan"
variable_name = "Fan Electricity Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "AHU Return Fan"
variable_name = "Fan Electricity Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Exhaust Fan"
variable_name = "Fan Air Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone Two Exhaust Fan"
variable_name = "Fan Air Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "AHU"
variable_name = "Air System Outdoor Air Economizer Status"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "AHU"
variable_name = "Air System Outdoor Air Flow Fraction"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Preheat Coil Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Preheat Coil Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Preheat Coil Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Supply Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Supply Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Supply Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone Two Supply Inlet"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone Two Supply Inlet"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone Two Supply Inlet"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone Two Air Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone Two Air Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone Two Air Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Return Fan Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Return Fan Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Return Fan Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[run-period."AE345 Run"]
begin_month = 1
begin_day_of_month = 1
end_month = 1
end_day_of_month = 7
use_weather_file_holidays_and_special_days = "No"
use_weather_file_daylight_saving_period = "No"
apply_weekend_holiday_rule = "No"
use_weather_file_rain_indicators = "Yes"
use_weather_file_snow_indicators = "Yes"