Section 11 · Air-side equipment

Case AE103

Values compared
42
Outside example range
6
Run time
0.07 s
Input file
AE103.toml, 30.1 kB

Against the example programs

Each reported quantity next to the spread of the simulation programs published with the standard.

Position in the example range
Example rangeSIMsara
Sensible Cooling Load (QZClatent) (kWh/h)AE coil and zone loads
1.4651.467
In range
Sensible Cooling Load (QZClatent) (kWh/h), AE coil and zone loads: SIMsara 1.465 · range 1.465 to 1.467
Latent Load (QZlatent) (kWh/h)AE coil and zone loads
0.58600.5897
In range
Latent Load (QZlatent) (kWh/h), AE coil and zone loads: SIMsara 0.5861 · range 0.5860 to 0.5897
Loads Sensible (QCsensible) (kWh/h)AE coil and zone loads
0.75230.7841
In range
Loads Sensible (QCsensible) (kWh/h), AE coil and zone loads: SIMsara 0.7832 · range 0.7523 to 0.7841
Latent (QClatent) (kWh/h)AE coil and zone loads
00.01033
In range
Latent (QClatent) (kWh/h), AE coil and zone loads: SIMsara 0 · range 0 to 0.01033
Total (QCtotal) (kWh/h)AE coil and zone loads
0.76200.7841
In range
Total (QCtotal) (kWh/h), AE coil and zone loads: SIMsara 0.7832 · range 0.7620 to 0.7841
Outlet RH (RHcco) (%)AE coil and zone loads
31.65433.030
In range
Outlet RH (RHcco) (%), AE coil and zone loads: SIMsara 32.833 · range 31.654 to 33.030
DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)AE node states
15.50015.500
In range
DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa), AE node states: SIMsara 15.500 · range 15.500 to 15.500
DRY BULB TEMPERATURE (°C) · Mixed Air (ma)AE node states
20.68920.774
In range
DRY BULB TEMPERATURE (°C) · Mixed Air (ma), AE node states: SIMsara 20.774 · range 20.689 to 20.774
DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)AE node states
20.72121.278
In range
DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco), AE node states: SIMsara 20.774 · range 20.721 to 21.278
DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)AE node states
18.46219
In range
DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco), AE node states: SIMsara 18.500 · range 18.462 to 19
DRY BULB TEMPERATURE (°C) · Supply Air (sa)AE node states
1919.101
In range
DRY BULB TEMPERATURE (°C) · Supply Air (sa), AE node states: SIMsara 19.085 · range 19 to 19.101
DRY BULB TEMPERATURE (°C) · Zone Air (z1)AE node states
23.32923.348
In range
DRY BULB TEMPERATURE (°C) · Zone Air (z1), AE node states: SIMsara 23.333 · range 23.329 to 23.348
DRY BULB TEMPERATURE (°C) · Return Air (ra)AE node states
23.32923.348
In range
DRY BULB TEMPERATURE (°C) · Return Air (ra), AE node states: SIMsara 23.333 · range 23.329 to 23.348
HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)AE node states
0.0028950.002948
In range
HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa), AE node states: SIMsara 0.002933 · range 0.002895 to 0.002948
HUMIDITY RATIO (G/GDA) · Mixed Air (ma)AE node states
0.0042840.004355
In range
HUMIDITY RATIO (G/GDA) · Mixed Air (ma), AE node states: SIMsara 0.004324 · range 0.004284 to 0.004355
HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)AE node states
0.0042840.004355
In range
HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco), AE node states: SIMsara 0.004324 · range 0.004284 to 0.004355
HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)AE node states
0.0042840.004355
In range
HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco), AE node states: SIMsara 0.004324 · range 0.004284 to 0.004355
HUMIDITY RATIO (G/GDA) · Supply Air (sa)AE node states
0.0042840.004355
In range
HUMIDITY RATIO (G/GDA) · Supply Air (sa), AE node states: SIMsara 0.004324 · range 0.004284 to 0.004355
HUMIDITY RATIO (G/GDA) · Zone Air (z1)AE node states
0.0049600.005059
In range
HUMIDITY RATIO (G/GDA) · Zone Air (z1), AE node states: SIMsara 0.005001 · range 0.004960 to 0.005059
HUMIDITY RATIO (G/GDA) · Return Air (ra)AE node states
0.0049600.005059
In range
HUMIDITY RATIO (G/GDA) · Return Air (ra), AE node states: SIMsara 0.005001 · range 0.004960 to 0.005059
SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)AE node states
821.41833.33
In range
SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa), AE node states: SIMsara 822.32 · range 821.41 to 833.33
SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)AE node states
830.35838.44
Above range
SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma), AE node states: SIMsara 839.20 · range 830.35 to 838.44
SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)AE node states
830.35838.44
Above range
SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco), AE node states: SIMsara 839.20 · range 830.35 to 838.44
SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)AE node states
830.35833.33
In range
SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco), AE node states: SIMsara 832.71 · range 830.35 to 833.33
TableQuantitySIMsaraMinMaxMeanAnalyticalStatus
AE coil and zone loadsSensible Heating Load (QZHsensible) (kWh/h)00000In range
AE coil and zone loadsSensible Cooling Load (QZClatent) (kWh/h)1.4651.4651.4671.4651.465In range
AE coil and zone loadsLatent Load (QZlatent) (kWh/h)0.58610.58600.58970.58660.5861In range
AE coil and zone loadsCoil Load (QH) (kWh/h)00000In range
AE coil and zone loadsLoads Sensible (QCsensible) (kWh/h)0.78320.75230.78410.77120.7835In range
AE coil and zone loadsLatent (QClatent) (kWh/h)000.010330.0014760In range
AE coil and zone loadsTotal (QCtotal) (kWh/h)0.78320.76200.78410.77270.7835In range
AE coil and zone loadsOutlet RH (RHcco) (%)32.83331.65433.03032.58132.843In range
AE node statesDRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)15.50015.50015.50015.50015.500In range
AE node statesDRY BULB TEMPERATURE (°C) · Mixed Air (ma)20.77420.68920.77420.73220.774In range
AE node statesDRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)20.77420.72121.27820.81620.774In range
AE node statesDRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)18.50018.4621918.57318.504In range
AE node statesDRY BULB TEMPERATURE (°C) · Supply Air (sa)19.0851919.10119.07419.088In range
AE node statesDRY BULB TEMPERATURE (°C) · Zone Air (z1)23.33323.32923.34823.33423.333In range
AE node statesDRY BULB TEMPERATURE (°C) · Return Air (ra)23.33323.32923.34823.33523.333In range
AE node statesHUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)0.0029330.0028950.0029480.0029280.002936In range
AE node statesHUMIDITY RATIO (G/GDA) · Mixed Air (ma)0.0043240.0042840.0043550.0043110.004325In range
AE node statesHUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)0.0043240.0042840.0043550.0043110.004325In range
AE node statesHUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)0.0043240.0042840.0043550.0043110.004325In range
AE node statesHUMIDITY RATIO (G/GDA) · Supply Air (sa)0.0043240.0042840.0043550.0043110.004325In range
AE node statesHUMIDITY RATIO (G/GDA) · Zone Air (z1)0.0050010.0049600.0050590.0049970.005002In range
AE node statesHUMIDITY RATIO (G/GDA) · Return Air (ra)0.0050010.0049600.0050590.0050030.005002In range
AE node statesSPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)822.32821.41833.33827.93821.57In range
AE node statesSPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)839.20830.35838.44834.68838.44Above range
AE node statesSPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco)839.20830.35838.44834.68838.44Above range
AE node statesSPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco)832.71830.35833.33832.09831.96In range
AE node statesSPECIFIC VOLUME (L/KGDA) · Supply Air (sa)834.38829.58833.45831.94833.63Above range
AE node statesSPECIFIC VOLUME (L/KGDA) · Zone Air (z1)847.42830.35846.66837.97846.65Above range
AE node statesSPECIFIC VOLUME (L/KGDA) · Return Air (ra)847.42830.35846.66835.84846.65Above range
AE node statesENTHALPY (J/GDA) · Location Outdoor Air (oa)22.99622.99623.03223.01523.020In range
AE node statesENTHALPY (J/GDA) · Mixed Air (ma)31.85631.70631.89031.78731.883In range
AE node statesENTHALPY (J/GDA) · Heat Coil Outlet (hco)31.85631.70631.89031.78731.883In range
AE node statesENTHALPY (J/GDA) · Cool Coil Outlet (cco)29.55329.46129.59829.52029.582In range
AE node statesENTHALPY (J/GDA) · Supply Air (sa)30.14530.05230.19030.11530.174In range
AE node statesENTHALPY (J/GDA) · Zone Air (z1)36.17136.06236.26036.15636.200In range
AE node statesENTHALPY (J/GDA) · Return Air (ra)36.17136.06236.26036.15636.200In range
AE node statesMASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa)0.11140.11150.11370.11270.1115Below range
AE node statesMASS FLOW RATE (KGDA/S) · Mixed Air (ma)0.34010.33720.34100.33980.3404In range
AE node statesMASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco)0.34010.33720.34100.33980.3404In range
AE node statesMASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco)0.34010.33720.34100.33980.3404In range
AE node statesMASS FLOW RATE (KGDA/S) · Supply Air (sa)0.34010.33720.34100.33980.3404In range
AE node statesMASS FLOW RATE (KGDA/S) · Zone Air (z1)n/a*
AE node statesMASS FLOW RATE (KGDA/S) · Return Air (ra)0.22870.22480.22890.22680.2289In range

Reported outputs

The values the engine wrote for this case, before they are placed in the output template.

OutputValue
Loads (kWh/h) · qZHsensible0
Loads (kWh/h) · qZCsensible1.465
Loads (kWh/h) · qZlatent0.5861
Loads (kWh/h) · qH0
Loads (kWh/h) · qCsensible0.7832
Loads (kWh/h) · qClatent0
Loads (kWh/h) · qCtotal0.7832
Loads (kWh/h) · rHcco32.833
Nodes · oa · tdb (°C)15.500
Nodes · oa · w (g/g)0.002933
Nodes · oa · v (L/kg)822.32
Nodes · oa · h (J/g)22.996
Nodes · oa · m (kg/s)0.1114
Nodes · oa · rh (%)27.000
Nodes · ma · tdb (°C)20.774
Nodes · ma · w (g/g)0.004324
Nodes · ma · v (L/kg)839.20
Nodes · ma · h (J/g)31.856
Nodes · ma · m (kg/s)0.3401
Nodes · ma · rh (%)28.508
Nodes · hco · tdb (°C)20.774
Nodes · hco · w (g/g)0.004324
Nodes · hco · v (L/kg)839.20
Nodes · hco · h (J/g)31.856
Nodes · hco · m (kg/s)0.3401
Nodes · hco · rh (%)28.508
Nodes · cco · tdb (°C)18.500
Nodes · cco · w (g/g)0.004324
Nodes · cco · v (L/kg)832.71
Nodes · cco · h (J/g)29.553
Nodes · cco · m (kg/s)0.3401
Nodes · cco · rh (%)32.833
Nodes · sa · tdb (°C)19.085
Nodes · sa · w (g/g)0.004324
Nodes · sa · v (L/kg)834.38
Nodes · sa · h (J/g)30.145
Nodes · sa · m (kg/s)0.3401
Nodes · sa · rh (%)31.654
Nodes · z1 · tdb (°C)23.333
Nodes · z1 · w (g/g)0.005001
Nodes · z1 · v (L/kg)847.42
Nodes · z1 · h (J/g)36.171
Nodes · z1 · rh (%)28.180
Nodes · ra · tdb (°C)23.333
Nodes · ra · w (g/g)0.005001
Nodes · ra · v (L/kg)847.42
Nodes · ra · h (J/g)36.171
Nodes · ra · m (kg/s)0.2287
Nodes · ra · rh (%)28.180
Pressure pa101,300
Fans · supply (W)201.46
Fans · exhaust (kg/s)0.1114
Fan power (W)201.46
Zone tdb (°C)23.333
Economizer status0
Oa fraction0.3275
Program outputs · cooling coil total (W)783.17
Program outputs · cooling coil sensible (W)783.17
Program outputs · heating coil (W)0
Program outputs · condensate · kg (s)0
Program outputs · condensate · temp (°C)18.500
Program outputs · condensate · h j kg77,330.4
Program outputs · condensate · w0
Program outputs · condensate · entering dew point (°C)1.869
Program outputs · condensate · sensible (W)0
Balance · residual (W) · mixer−1.82e-12
Balance · residual (W) · heating coil0
Balance · residual (W) · cooling coil1.25e-12
Balance · residual (W) · fan1.51e-12
Balance · residual (W) · zone1.819
Balance · residual (W) · system1.819
Balance · relative · mixer2.32e-15
Balance · relative · heating coil0
Balance · relative · cooling coil1.60e-15
Balance · relative · fan1.92e-15
Balance · relative · zone0.002323
Balance · relative · system0.002323
Balance · max relative0.002323
Balance · reference (W)783.17
Cycling · steps6
Flows · supply std (m³/s)0.2824
Flows · exhaust std (m³/s)0.09249
Flows · oa std (m³/s)0.09249
Flows · supply fan dp pa499.41
Flows · setpoint offset k0.004011
Flow iterations4
Flow record · convergedtrue
Flow record · iterations4
Flow record · relative change3.99e-9
Flow record · zone tdb error k1.62e-7

Input file

sha256 0920ab08528602c6ee79ff3465b26f0ec7fd5d357eace87d9bdc2c3597f4589b

AE103.tomlDownload
[version]
version_identifier = "26.1"

[simulation-control]
do_zone_sizing_calculation = "No"
do_system_sizing_calculation = "No"
do_plant_sizing_calculation = "No"
run_simulation_for_sizing_periods = "No"
run_simulation_for_weather_file_run_periods = "Yes"
do_hvac_sizing_simulation_for_sizing_periods = "No"
maximum_number_of_hvac_sizing_simulation_passes = 1

[building."ASHRAE 140 AE103"]
north_axis = 0.0
terrain = "Suburbs"
loads_convergence_tolerance_value = 0.04
temperature_convergence_tolerance_value = 0.4
solar_distribution = "FullExterior"
maximum_number_of_warmup_days = 25
minimum_number_of_warmup_days = 6

[building.surface.detailed."South Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."East Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."North Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."West Wall"]
surface_type = "Wall"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
]

[building.surface.detailed."Floor"]
surface_type = "Floor"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 },
]

[building.surface.detailed."Roof"]
surface_type = "Roof"
construction_name = "Adiabatic Panel"
zone_name = "Zone One"
outside_boundary_condition = "Adiabatic"
sun_exposure = "NoSun"
wind_exposure = "NoWind"
view_factor_to_ground = 0.0
number_of_vertices = 4
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 },
  { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 },
]

[timestep]
number_of_timesteps_per_hour = 6

[heat-balance-algorithm]
algorithm = "ConductionTransferFunction"
surface_temperature_upper_limit = 200.0

[surface.convection.algorithm.inside]
algorithm = "TARP"

[surface.convection.algorithm.outside]
algorithm = "DOE-2"

[global-geometry-rules]
starting_vertex_position = "UpperLeftCorner"
vertex_entry_direction = "Counterclockwise"
coordinate_system = "Relative"

[site.location."AE artificial site"]
latitude = 25.8
longitude = -80.3
time_zone = -5.0
elevation = 0.0

[schedule-type-limits."Any Number"]

[schedule-type-limits."Fraction"]
lower_limit_value = 0.0
upper_limit_value = 1.0
numeric_type = "Continuous"

[schedule-type-limits."Temperature"]
lower_limit_value = -60.0
upper_limit_value = 200.0
numeric_type = "Continuous"
unit_type = "Temperature"

[schedule-type-limits."Control Type"]
lower_limit_value = 0.0
upper_limit_value = 4.0
numeric_type = "Discrete"

[schedule.compact."Always On"]
schedule_type_limits_name = "Fraction"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 1.0 },
]

[schedule.compact."Heating Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 18.337010630880442 },
]

[schedule.compact."Cooling Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 23.337010630880442 },
]

[schedule.compact."Dual Setpoint Control"]
schedule_type_limits_name = "Control Type"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 4 },
]

[schedule.compact."CHW Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 6.67 },
]

[material."Gypsum Board 13mm"]
roughness = "Smooth"
thickness = 0.0127
conductivity = 0.16
density = 800.0
specific_heat = 1090.0
thermal_absorptance = 0.9
solar_absorptance = 0.5
visible_absorptance = 0.5

[construction."Adiabatic Panel"]
outside_layer = "Gypsum Board 13mm"

[zone."Zone One"]
direction_of_relative_north = 0.0
x_origin = 0.0
y_origin = 0.0
z_origin = 0.0
type = 1
multiplier = 1
ceiling_height = "Autocalculate"
volume = "Autocalculate"
floor_area = "Autocalculate"
zone_inside_convection_algorithm = "TARP"
zone_outside_convection_algorithm = "DOE-2"
part_of_total_floor_area = "Yes"

[zone.control.thermostat."Zone One Thermostat"]
zone_or_zonelist_name = "Zone One"
control_type_schedule_name = "Dual Setpoint Control"
control_1_object_type = "ThermostatSetpoint:DualSetpoint"
control_1_name = "Zone One Dual Setpoint"

[zone.hvac.air-distribution-unit."Zone One ADU"]
air_distribution_unit_outlet_node_name = "Zone One Supply Inlet"
air_terminal_object_type = "AirTerminal:SingleDuct:ConstantVolume:NoReheat"
air_terminal_name = "Zone One Terminal"
nominal_upstream_leakage_fraction = 0.0
constant_downstream_leakage_fraction = 0.0

[zone.hvac.equipment-list."Zone One Equipment List"]
load_distribution_scheme = "SequentialLoad"
equipment = [
  { zone_equipment_object_type = "ZoneHVAC:AirDistributionUnit", zone_equipment_name = "Zone One ADU", zone_equipment_cooling_sequence = 1, zone_equipment_heating_or_no_load_sequence = 1 },
  { zone_equipment_object_type = "Fan:ZoneExhaust", zone_equipment_name = "Zone Exhaust Fan", zone_equipment_cooling_sequence = 2, zone_equipment_heating_or_no_load_sequence = 2 },
]

[[zone.hvac.equipment-connections]]
zone_name = "Zone One"
zone_conditioning_equipment_list_name = "Zone One Equipment List"
zone_air_inlet_node_or_nodelist_name = "Zone One Supply Inlet"
zone_air_node_name = "Zone One Air Node"
zone_return_air_node_or_nodelist_name = "Zone One Return Outlet"
zone_air_exhaust_node_or_nodelist_name = "Zone One Exhaust Node"

[other-equipment."Zone Sensible Cooling Load"]
fuel_type = "None"
zone_or_zonelist_or_space_or_spacelist_name = "Zone One"
schedule_name = "Always On"
design_level_calculation_method = "EquipmentLevel"
design_level = 1465.0
fraction_latent = 0.0
fraction_radiant = 0.0
fraction_lost = 0.0

[other-equipment."Zone Latent Load"]
fuel_type = "None"
zone_or_zonelist_or_space_or_spacelist_name = "Zone One"
schedule_name = "Always On"
design_level_calculation_method = "EquipmentLevel"
design_level = 586.1
fraction_latent = 1.0
fraction_radiant = 0.0
fraction_lost = 0.0

[thermostat.setpoint.dual-setpoint."Zone One Dual Setpoint"]
heating_setpoint_temperature_schedule_name = "Heating Setpoint"
cooling_setpoint_temperature_schedule_name = "Cooling Setpoint"

[air-loop-hvac."SZ Air Loop"]
controller_list_name = "SZ Controllers"
availability_manager_list_name = "SZ Availability"
design_supply_air_flow_rate = 0.28236786591747814
branch_list_name = "SZ Branches"
supply_side_inlet_node_name = "Air Loop Inlet Node"
demand_side_outlet_node_name = "Zone Equipment Outlet Node"
demand_side_inlet_node_names = "Zone Equipment Inlet Node"
supply_side_outlet_node_names = "Supply Outlet Node"
design_return_air_flow_fraction_of_supply_air_flow = 1.0

[branch-list."SZ Branches"]
branches = [
  { branch_name = "SZ Branch" },
]

[branch-list."CHW Supply Branches"]
branches = [
  { branch_name = "CHW Supply Inlet Branch" },
  { branch_name = "CHW Chiller Branch" },
  { branch_name = "CHW Supply Bypass Branch" },
  { branch_name = "CHW Supply Outlet Branch" },
]

[branch-list."CHW Demand Branches"]
branches = [
  { branch_name = "CHW Demand Inlet Branch" },
  { branch_name = "CHW Cooling Coil Branch" },
  { branch_name = "CHW Demand Bypass Branch" },
  { branch_name = "CHW Demand Outlet Branch" },
]

[branch."SZ Branch"]
components = [
  { component_object_type = "AirLoopHVAC:OutdoorAirSystem", component_name = "SZ OA System", component_inlet_node_name = "Air Loop Inlet Node", component_outlet_node_name = "Mixed Air Node" },
  { component_object_type = "Coil:Heating:Electric", component_name = "SZ Heating Coil", component_inlet_node_name = "Mixed Air Node", component_outlet_node_name = "Heating Coil Outlet Node" },
  { component_object_type = "Coil:Cooling:Water", component_name = "SZ Cooling Coil", component_inlet_node_name = "Heating Coil Outlet Node", component_outlet_node_name = "Cooling Coil Outlet Node" },
  { component_object_type = "Fan:ConstantVolume", component_name = "SZ Supply Fan", component_inlet_node_name = "Cooling Coil Outlet Node", component_outlet_node_name = "Supply Outlet Node" },
]

[branch."CHW Supply Inlet Branch"]
components = [
  { component_object_type = "Pump:VariableSpeed", component_name = "CHW Pump", component_inlet_node_name = "CHW Supply Inlet Node", component_outlet_node_name = "CHW Pump Outlet Node" },
]

[branch."CHW Chiller Branch"]
components = [
  { component_object_type = "Chiller:Electric:EIR", component_name = "CHW Chiller", component_inlet_node_name = "CHW Chiller Inlet Node", component_outlet_node_name = "CHW Chiller Outlet Node" },
]

[branch."CHW Supply Bypass Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Supply Bypass Pipe", component_inlet_node_name = "CHW Supply Bypass Inlet Node", component_outlet_node_name = "CHW Supply Bypass Outlet Node" },
]

[branch."CHW Supply Outlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Supply Outlet Pipe", component_inlet_node_name = "CHW Supply Outlet Pipe Inlet Node", component_outlet_node_name = "CHW Supply Outlet Node" },
]

[branch."CHW Demand Inlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Inlet Pipe", component_inlet_node_name = "CHW Demand Inlet Node", component_outlet_node_name = "CHW Demand Inlet Pipe Outlet Node" },
]

[branch."CHW Cooling Coil Branch"]
components = [
  { component_object_type = "Coil:Cooling:Water", component_name = "SZ Cooling Coil", component_inlet_node_name = "Cooling Coil Water Inlet Node", component_outlet_node_name = "Cooling Coil Water Outlet Node" },
]

[branch."CHW Demand Bypass Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Bypass Pipe", component_inlet_node_name = "CHW Demand Bypass Inlet Node", component_outlet_node_name = "CHW Demand Bypass Outlet Node" },
]

[branch."CHW Demand Outlet Branch"]
components = [
  { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Outlet Pipe", component_inlet_node_name = "CHW Demand Outlet Pipe Inlet Node", component_outlet_node_name = "CHW Demand Outlet Node" },
]

[air.loop.hvac.controller-list."SZ Controllers"]
controller_1_object_type = "Controller:WaterCoil"
controller_1_name = "Cooling Coil Controller"

[air.loop.hvac.controller-list."SZ OA Controllers"]
controller_1_object_type = "Controller:OutdoorAir"
controller_1_name = "SZ OA Controller"

[air.loop.hvac.outdoor-air-system."SZ OA System"]
controller_list_name = "SZ OA Controllers"
outdoor_air_equipment_list_name = "SZ OA Equipment"

[air.loop.hvac.outdoor.air.system.equipment-list."SZ OA Equipment"]
component_1_object_type = "OutdoorAir:Mixer"
component_1_name = "SZ OA Mixer"

[air.loop.hvac.supply-path."SZ Supply Path"]
supply_air_path_inlet_node_name = "Zone Equipment Inlet Node"
components = [
  { component_object_type = "AirLoopHVAC:ZoneSplitter", component_name = "Zone Supply Air Splitter" },
]

[air.loop.hvac.zone-splitter."Zone Supply Air Splitter"]
inlet_node_name = "Zone Equipment Inlet Node"
nodes = [
  { outlet_node_name = "Zone One Terminal Inlet" },
]

[air.loop.hvac.return-path."SZ Return Path"]
return_air_path_outlet_node_name = "Zone Equipment Outlet Node"
components = [
  { component_object_type = "AirLoopHVAC:ZoneMixer", component_name = "Zone Return Air Mixer" },
]

[air.loop.hvac.zone-mixer."Zone Return Air Mixer"]
outlet_node_name = "Zone Equipment Outlet Node"
nodes = [
  { inlet_node_name = "Zone One Return Outlet" },
]

[air.terminal.single.duct.constant.volume.no-reheat."Zone One Terminal"]
availability_schedule_name = "Always On"
air_inlet_node_name = "Zone One Terminal Inlet"
air_outlet_node_name = "Zone One Supply Inlet"
maximum_air_flow_rate = 0.28236786591747814

[availability-manager-assignment-list."SZ Availability"]
managers = [
  { availability_manager_object_type = "AvailabilityManager:Scheduled", availability_manager_name = "SZ Avail" },
]

[availability.manager.scheduled."SZ Avail"]
schedule_name = "Always On"

[fan.constant-volume."SZ Supply Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.7
pressure_rise = 499.41468920975814
maximum_flow_rate = 0.28236786591747814
motor_efficiency = 1.0
motor_in_airstream_fraction = 0.0
air_inlet_node_name = "Cooling Coil Outlet Node"
air_outlet_node_name = "Supply Outlet Node"
end_use_subcategory = "General"

[fan.zone-exhaust."Zone Exhaust Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 0.5
pressure_rise = 160.0
maximum_flow_rate = 0.0924892578843271
air_inlet_node_name = "Zone One Exhaust Node"
air_outlet_node_name = "Zone Exhaust Fan Outlet"
end_use_subcategory = "General Exhaust"
system_availability_manager_coupling_mode = "Coupled"

[outdoor.air.mixer."SZ OA Mixer"]
mixed_air_node_name = "Mixed Air Node"
outdoor_air_stream_node_name = "Outdoor Air Inlet Node"
relief_air_stream_node_name = "Relief Air Outlet Node"
return_air_stream_node_name = "Air Loop Inlet Node"

[[outdoor.air.node-list]]
nodes = [
  { node_or_nodelist_name = "Outdoor Air Inlet Node" },
  { node_or_nodelist_name = "CHW Chiller Condenser Inlet Node" },
]

[controller.outdoor-air."SZ OA Controller"]
relief_air_outlet_node_name = "Relief Air Outlet Node"
return_air_node_name = "Air Loop Inlet Node"
mixed_air_node_name = "Mixed Air Node"
actuator_node_name = "Outdoor Air Inlet Node"
minimum_outdoor_air_flow_rate = 0.0924892578843271
maximum_outdoor_air_flow_rate = 0.28236786591747814
economizer_control_type = "NoEconomizer"
economizer_control_action_type = "ModulateFlow"
lockout_type = "NoLockout"
minimum_limit_type = "FixedMinimum"

[controller.water-coil."Cooling Coil Controller"]
control_variable = "Temperature"
action = "Reverse"
actuator_variable = "Flow"
sensor_node_name = "Cooling Coil Outlet Node"
actuator_node_name = "Cooling Coil Water Inlet Node"
controller_convergence_tolerance = 1e-06
maximum_actuated_flow = 0.00023
minimum_actuated_flow = 0.0

[coil.heating.electric."SZ Heating Coil"]
availability_schedule_name = "Always On"
efficiency = 1.0
nominal_capacity = 20000.0
air_inlet_node_name = "Mixed Air Node"
air_outlet_node_name = "Heating Coil Outlet Node"
temperature_setpoint_node_name = "Heating Coil Outlet Node"

[coil.cooling.water."SZ Cooling Coil"]
availability_schedule_name = "Always On"
design_water_flow_rate = 0.00023
design_air_flow_rate = 0.28236786591747814
design_inlet_water_temperature = 12.0
design_inlet_air_temperature = 26.0
design_outlet_air_temperature = 14.0
design_inlet_air_humidity_ratio = 0.0135
design_outlet_air_humidity_ratio = 0.0099
water_inlet_node_name = "Cooling Coil Water Inlet Node"
water_outlet_node_name = "Cooling Coil Water Outlet Node"
air_inlet_node_name = "Heating Coil Outlet Node"
air_outlet_node_name = "Cooling Coil Outlet Node"
type_of_analysis = "SimpleAnalysis"
heat_exchanger_configuration = "CrossFlow"

[setpoint.manager.single.zone.heating."Heating Supply Air Temp Manager"]
control_variable = "Temperature"
minimum_supply_air_temperature = -99.0
maximum_supply_air_temperature = 99.0
control_zone_name = "Zone One"
zone_node_name = "Zone One Air Node"
zone_inlet_node_name = "Zone One Supply Inlet"
setpoint_node_or_nodelist_name = "Zone Equipment Inlet Node"

[setpoint.manager.single.zone.cooling."Cooling Supply Air Temp Manager"]
control_variable = "Temperature"
minimum_supply_air_temperature = -99.0
maximum_supply_air_temperature = 99.0
control_zone_name = "Zone One"
zone_node_name = "Zone One Air Node"
zone_inlet_node_name = "Zone One Supply Inlet"
setpoint_node_or_nodelist_name = "Supply Outlet Node"

[setpoint.manager.mixed-air."Heating Coil Air Temp Manager"]
control_variable = "Temperature"
reference_setpoint_node_name = "Zone Equipment Inlet Node"
fan_inlet_node_name = "Cooling Coil Outlet Node"
fan_outlet_node_name = "Supply Outlet Node"
setpoint_node_or_nodelist_name = "Heating Coil Outlet Node"

[setpoint.manager.mixed-air."Cooling Coil Air Temp Manager"]
control_variable = "Temperature"
reference_setpoint_node_name = "Supply Outlet Node"
fan_inlet_node_name = "Cooling Coil Outlet Node"
fan_outlet_node_name = "Supply Outlet Node"
setpoint_node_or_nodelist_name = "Cooling Setpoint Nodes"

[setpoint.manager.scheduled."CHW Loop Setpoint Manager"]
control_variable = "Temperature"
schedule_name = "CHW Setpoint"
setpoint_node_or_nodelist_name = "CHW Supply Outlet Node"

[node-list."Cooling Setpoint Nodes"]
nodes = [
  { node_name = "Cooling Coil Outlet Node" },
  { node_name = "Mixed Air Node" },
]

[plant-loop."Chilled Water Loop"]
fluid_type = "Water"
plant_equipment_operation_scheme_name = "CHW Loop Operation"
loop_temperature_setpoint_node_name = "CHW Supply Outlet Node"
maximum_loop_temperature = 98.0
minimum_loop_temperature = 1.0
maximum_loop_flow_rate = 0.0006
minimum_loop_flow_rate = 0.0
plant_loop_volume = 0.5
plant_side_inlet_node_name = "CHW Supply Inlet Node"
plant_side_outlet_node_name = "CHW Supply Outlet Node"
plant_side_branch_list_name = "CHW Supply Branches"
plant_side_connector_list_name = "CHW Supply Connectors"
demand_side_inlet_node_name = "CHW Demand Inlet Node"
demand_side_outlet_node_name = "CHW Demand Outlet Node"
demand_side_branch_list_name = "CHW Demand Branches"
demand_side_connector_list_name = "CHW Demand Connectors"
load_distribution_scheme = "SequentialLoad"

[plant-equipment-operation-schemes."CHW Loop Operation"]
control_scheme_1_object_type = "PlantEquipmentOperation:CoolingLoad"
control_scheme_1_name = "CHW Cooling Scheme"
control_scheme_1_schedule_name = "Always On"

[plant.equipment.operation.cooling-load."CHW Cooling Scheme"]
load_range_1_lower_limit = 0.0
load_range_1_upper_limit = 1000000000.0
range_1_equipment_list_name = "CHW Chillers"

[plant-equipment-list."CHW Chillers"]
equipment = [
  { equipment_object_type = "Chiller:Electric:EIR", equipment_name = "CHW Chiller" },
]

[connector-list."CHW Supply Connectors"]
connector_1_object_type = "Connector:Splitter"
connector_1_name = "CHW Supply Splitter"
connector_2_object_type = "Connector:Mixer"
connector_2_name = "CHW Supply Mixer"

[connector-list."CHW Demand Connectors"]
connector_1_object_type = "Connector:Splitter"
connector_1_name = "CHW Demand Splitter"
connector_2_object_type = "Connector:Mixer"
connector_2_name = "CHW Demand Mixer"

[connector.splitter."CHW Supply Splitter"]
inlet_branch_name = "CHW Supply Inlet Branch"
branches = [
  { outlet_branch_name = "CHW Chiller Branch" },
  { outlet_branch_name = "CHW Supply Bypass Branch" },
]

[connector.splitter."CHW Demand Splitter"]
inlet_branch_name = "CHW Demand Inlet Branch"
branches = [
  { outlet_branch_name = "CHW Cooling Coil Branch" },
  { outlet_branch_name = "CHW Demand Bypass Branch" },
]

[connector.mixer."CHW Supply Mixer"]
outlet_branch_name = "CHW Supply Outlet Branch"
branches = [
  { inlet_branch_name = "CHW Chiller Branch" },
  { inlet_branch_name = "CHW Supply Bypass Branch" },
]

[connector.mixer."CHW Demand Mixer"]
outlet_branch_name = "CHW Demand Outlet Branch"
branches = [
  { inlet_branch_name = "CHW Cooling Coil Branch" },
  { inlet_branch_name = "CHW Demand Bypass Branch" },
]

[pump.variable-speed."CHW Pump"]
inlet_node_name = "CHW Supply Inlet Node"
outlet_node_name = "CHW Pump Outlet Node"
design_maximum_flow_rate = 0.0006
design_pump_head = 1000.0
design_power_consumption = 1.0
motor_efficiency = 0.9
fraction_of_motor_inefficiencies_to_fluid_stream = 0.0
coefficient_1_of_the_part_load_performance_curve = 0.0
coefficient_2_of_the_part_load_performance_curve = 1.0
coefficient_3_of_the_part_load_performance_curve = 0.0
coefficient_4_of_the_part_load_performance_curve = 0.0
design_minimum_flow_rate = 0.0
pump_control_type = "Intermittent"

[chiller.electric.eir."CHW Chiller"]
reference_capacity = 20000.0
reference_cop = 3.0
reference_leaving_chilled_water_temperature = 6.67
reference_entering_condenser_fluid_temperature = 35.0
reference_chilled_water_flow_rate = 0.0006
cooling_capacity_function_of_temperature_curve_name = "CHW Chiller Cap FT"
electric_input_to_cooling_output_ratio_function_of_temperature_curve_name = "CHW Chiller EIR FT"
electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name = "CHW Chiller EIR FPLR"
minimum_part_load_ratio = 0.1
maximum_part_load_ratio = 1.0
optimum_part_load_ratio = 1.0
minimum_unloading_ratio = 0.2
chilled_water_inlet_node_name = "CHW Chiller Inlet Node"
chilled_water_outlet_node_name = "CHW Chiller Outlet Node"
condenser_inlet_node_name = "CHW Chiller Condenser Inlet Node"
condenser_outlet_node_name = "CHW Chiller Condenser Outlet Node"
condenser_type = "AirCooled"
condenser_fan_power_ratio = 0.0
fraction_of_compressor_electric_consumption_rejected_by_condenser = 1.0
leaving_chilled_water_lower_temperature_limit = 2.0
chiller_flow_mode = "ConstantFlow"

[curve.biquadratic."CHW Chiller Cap FT"]
coefficient1_constant = 0.507883
coefficient2_x = 0.145228
coefficient3_x_2 = -0.00625644
coefficient4_y = -0.0011178
coefficient5_y_2 = -0.0001296
coefficient6_x_y = -0.00028188
minimum_value_of_x = 5.0
maximum_value_of_x = 10.0
minimum_value_of_y = 24.0
maximum_value_of_y = 35.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.biquadratic."CHW Chiller EIR FT"]
coefficient1_constant = 1.03076
coefficient2_x = -0.103536
coefficient3_x_2 = 0.00710208
coefficient4_y = 0.0093186
coefficient5_y_2 = 0.00031752
coefficient6_x_y = -0.00104328
minimum_value_of_x = 5.0
maximum_value_of_x = 10.0
minimum_value_of_y = 24.0
maximum_value_of_y = 35.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.quadratic."CHW Chiller EIR FPLR"]
coefficient1_constant = 0.088065
coefficient2_x = 1.137742
coefficient3_x_2 = -0.225806
minimum_value_of_x = 0.0
maximum_value_of_x = 1.0

[pipe.adiabatic."CHW Supply Bypass Pipe"]
inlet_node_name = "CHW Supply Bypass Inlet Node"
outlet_node_name = "CHW Supply Bypass Outlet Node"

[pipe.adiabatic."CHW Supply Outlet Pipe"]
inlet_node_name = "CHW Supply Outlet Pipe Inlet Node"
outlet_node_name = "CHW Supply Outlet Node"

[pipe.adiabatic."CHW Demand Inlet Pipe"]
inlet_node_name = "CHW Demand Inlet Node"
outlet_node_name = "CHW Demand Inlet Pipe Outlet Node"

[pipe.adiabatic."CHW Demand Bypass Pipe"]
inlet_node_name = "CHW Demand Bypass Inlet Node"
outlet_node_name = "CHW Demand Bypass Outlet Node"

[pipe.adiabatic."CHW Demand Outlet Pipe"]
inlet_node_name = "CHW Demand Outlet Pipe Inlet Node"
outlet_node_name = "CHW Demand Outlet Node"

[[output.variable-dictionary]]
key_field = "IDF"

[[output.variable]]
key_value = "*"
variable_name = "Zone Air System Sensible Heating Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Air System Sensible Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Total Internal Latent Gain Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Zone Mean Air Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Heating Coil Heating Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Cooling Coil Total Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Cooling Coil Sensible Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "*"
variable_name = "Site Outdoor Air Barometric Pressure"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Supply Fan"
variable_name = "Fan Electricity Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone Exhaust Fan"
variable_name = "Fan Air Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Air Loop"
variable_name = "Air System Outdoor Air Economizer Status"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "SZ Air Loop"
variable_name = "Air System Outdoor Air Flow Fraction"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Outdoor Air Inlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Mixed Air Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Heating Coil Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Heating Coil Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Heating Coil Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Cooling Coil Outlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Supply Inlet"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Zone One Air Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Air Loop Inlet Node"
variable_name = "System Node Mass Flow Rate"
reporting_frequency = "Timestep"

[run-period."AE103 Run"]
begin_month = 1
begin_day_of_month = 1
end_month = 1
end_day_of_month = 7
use_weather_file_holidays_and_special_days = "No"
use_weather_file_daylight_saving_period = "No"
apply_weekend_holiday_rule = "No"
use_weather_file_rain_indicators = "Yes"
use_weather_file_snow_indicators = "Yes"