MODELING NOTES FOR ASHRAE STANDARD 140 =============================================================================== INTRODUCTION =============================================================================== This document shall include supplemental information about the ASHRAE Standard 140 tests performed. One S140outNotes document shall be provided for each set of tests (e.g., one for the building thermal and fabric load tests of Section 7.2; one for the space cooling equipment analytical verification tests of Sections 9.2; etc.) The types of information listed below shall be provided in this document, each in a separate section: a. Software information b. Alternative modeling methods c. Equivalent modeling methods d. Nonspecified inputs e. Omitted test cases and results f. Changes made to source code for the purpose of running the tests, where such changes are not available in publicly released versions of the software g. Anomalous results. Notes in this document shall be limited to the topics shown above. Notes must be factual and objective and shall only refer to the software being tested. Notes shall not refer to any other software program. INFORMATIVE NOTE: Text at the start of each section describes the content of the section for the reader and provides instructions for supplying the content. Sample notes are provided in a separate document (S140outNotes_Examples.TXT). =============================================================================== A. SOFTWARE INFORMATION =============================================================================== CONTENT: This section shall include reference information for the software - the vendor, name, and version of the software, plus operating system and computer hardware requirements. INSTRUCTIONS: Information for items 1 through 7 below shall be provided. Information for Item 8 shall be permitted but is not required. 1. SOFTWARE VENDOR: Jared Bell, Roots Ontological Technologies, LLC 2. SOFTWARE NAME: SIMsara 3. SOFTWARE VERSION (unique software version identifier): SIMsara 0.1.0 4. OPERATING SYSTEM REQUIREMENTS: macOS 13 or later on Apple silicon (arm64). This is the build that was tested; other targets are listed only when they have been built and run for these tests. 5. APPROX HARD DISK SPACE REQUIRED FOR INSTALLATION: About 6.6 MB: the release binary s140_run, which needs no other runtime files beyond the TOML input and the EPW weather file. 6. MINIMUM RAM REQUIRED FOR SOFTWARE OPERATION: 16 MB: the largest peak resident memory of any submitted test case, measured with /usr/bin/time -l on the tested build. 7. MINIMUM DISPLAY MONITOR REQUIREMENTS: None. SIMsara is a command-line program with no graphical display. 8. OTHER HARDWARE OR SOFTWARE-RELATED REQUIREMENTS: Input is TOML (docs/TOML-INPUT.md in the source distribution) with EPW weather. Building from source needs Rust 1.98.1. The Standard 140 harness scripts that generate the test inputs and fill the output templates need Python 3.11 or later, standard library only. INFORMATIVE NOTE: Item 8 can be used to supply additional relevant information. =============================================================================== B. REPORT BLOCK FOR ALTERNATIVE MODELING METHODS =============================================================================== CONTENT: If the software being tested provides alternative modeling methods or algorithms for performing the tests, this section shall describe modeling methods used for the tests. INSTRUCTIONS: If alternative modeling methods are applicable, a separate note for each alternative modeling method or algorithm situation shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If alternative modeling methods are not applicable, specify "NONE" in place of the information below. NOTE 1 - Cooling-Coil Model and Bypass Factor (Section 11.2.1.1.3 d, 11.2.2.1.3, 11.2.3.1.3 f and 11.2.4.1.4 (140-2014a 5.5.1.1.3 d)) --------------------------------------------------------- 1.1 Describe the Effect Being Simulated: Cooling-coil leaving-air humidity, and with it the coil latent load, the zone humidity and the mixed-air state. 1.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 1.2.1 Coil:Cooling:Water, SimpleAnalysis Physical Meaning: one wet or dry regime per call; the air-side UA is derived from a user design point, and the leaving air lies exp(-UA/(m cp)) of the way from the effective coil-surface state back to the entering state (an effective bypass factor). 1.2.2 Coil:Cooling:Water, DetailedAnalysis Physical Meaning: a fin-and-tube geometry model with a part-wet, part-dry regime; the UA follows from the geometry. 1.3 Setting or Capability Used: SimpleAnalysis in every case. The design point (26 C and 0.0135 entering, 14 C and 0.0099 leaving, 12 C entering water at 0.00023 m3/s) forces a large air-side UA, so the leaving air is practically saturated whenever the coil is wet (at least 99.87 percent RH in AE104, AE204, AE206, AE226, AE304, AE306, AE326, AE404, AE406 and AE426). It is the tightest design point at which the program's design UA calculation still converges. In the constant-volume cases the coil's design air flow is the system supply, and its design water flow and the controller's maximum water flow are 2.1666 times the single-zone values (the ratio of the system supply volumes), so the derived air-side UA scales with the flows and the coil's air-side NTU, and with it the effective bypass factor, is the single-zone coil's. The variable-air-volume cases use the same coil, its design air flow the loop design flow (the constant-volume supply, 11.2.4.1.2 informative note); at their smaller flows its NTU is larger still. SIMsara has no bypass-factor input; this is the lowest effective bypass factor the model allows, as 11.2.1.1.3 d and 11.2.3.1.3 f ask. NOTE 2 - Coil Control and Convergence Tolerance (Section 11.2.1.1.3 a, 11.2.2.1.3, 11.2.3.1.3 a and 11.2.4.1.3 a (140-2014a 5.5.1.1.3 a)) --------------------------------------------------------- 2.1 Describe the Effect Being Simulated: How exactly each coil holds its leaving-air or zone setpoint. 2.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 2.2.1 Controller:WaterCoil convergence tolerance Physical Meaning: any positive temperature tolerance, in kelvin, on the sensed coil leaving-air temperature; the controller modulates the coil water flow until the sensed temperature is within it. 2.2.2 Coil:Heating:Electric with a temperature setpoint node Physical Meaning: the coil delivers exactly the heat that brings its leaving air to the setpoint, up to its capacity; no controller. 2.3 Setting or Capability Used: 1e-06 K for the cooling-coil controller (no throttling range; the smallest practical value). The electric heating coil, and the electric preheat coil of the constant-volume and variable-air-volume cases, hold their leaving-air setpoints exactly; each zone's electric reheat coil delivers exactly the heat that holds its zone at the heating setpoint (11.2.3.1.3 e and 11.2.4.1.3 e). Each variable-air-volume terminal holds its zone at the cooling setpoint by its damper, which the program sets each iteration to the flow that meets the zone's load (11.2.4.1.3 a and f). Every capacity is well above the loads. NOTE 3 - Economizer Control (Section 11.2.2.3.1.1.1, 11.2.2.3.2.1.1, 11.2.3.3.1.1.1, 11.2.3.3.2.1.1, 11.2.4.3.1.1 and 11.2.4.3.2.1) --------------------------------------------------------- 3.1 Describe the Effect Being Simulated: Outdoor-air fraction, mixed-air state and cooling-coil loads of AE226, AE245, AE326, AE345, AE426 and AE445. 3.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 3.2.1 DifferentialDryBulb Physical Meaning: the economizer runs while the outdoor dry bulb is below the return-air dry bulb. 3.2.2 DifferentialEnthalpy Physical Meaning: the economizer runs while the outdoor enthalpy is below the return-air enthalpy. 3.2.3 Minimum limit dry bulb Physical Meaning: the economizer is off when the outdoor dry bulb is below this limit. 3.2.4 ModulateFlow Physical Meaning: while it runs, the outdoor-air flow is raised from the minimum toward the full supply flow to reach the mixed-air setpoint. 3.3 Setting or Capability Used: DifferentialDryBulb for AE226, AE326 and AE426 and DifferentialEnthalpy for AE245, AE345 and AE445, each comparing the outdoor air with the return air at the return fan outlet (the return-air node of the outdoor-air controller), with ModulateFlow and the minimum limit dry bulb set to ODBecono,min (Block C notes 9, 14 and 19). No economizer in the other cases. In the last hour of AE226, AE245, AE326, AE345, AE426 and AE445 the economizer runs at 100 percent outdoor air and the cooling coil meets the rest of the load; in AE426 and AE445 the supply fan keeps the flow the terminals set (11.2.4.3.1.1 informative note). NOTE 4 - Time Step and Run Length (Section 11.3.1, 11.3.2, 11.3.3 and 11.3.4 (140-2014a 6.5.1)) --------------------------------------------------------- 4.1 Describe the Effect Being Simulated: Convergence to the steady state that the last-hour outputs report. 4.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 4.2.1 Zone time steps per hour Physical Meaning: 1 to 60; the HVAC system may sub-step within a zone step. 4.3 Setting or Capability Used: 6 zone time steps per hour. Each case runs 7 days (January 1-7, a modeling choice; the specification sets no run length) on its constant weather file; the last hour is reported only after every output agrees with the previous hour to 1e-6 relative (or 1e-6 absolute). The reported values are hourly means; in every case no reported quantity varies between the time steps of the last hour. NOTE 5 - Outputs That Are Not Direct Program Outputs (Section 11.3, 11.3.1, 11.3.2, 11.3.3 and 11.3.4 (140-2014a 6.5 and 6.5.1)) --------------------------------------------------------- 5.1 Describe the Effect Being Simulated: Reported values computed from program outputs by the SIMsara post-processor. 5.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 5.2.1 Direct program outputs Physical Meaning: zone air system sensible heating and cooling rates, zone total internal latent gain rate, heating-coil heating rate, cooling-coil total and sensible cooling rates, fan electricity rate, zone exhaust fan mass flow rate, and the temperature, humidity ratio and mass flow rate of every system node. 5.2.2 Post-processed outputs Physical Meaning: quantities computed from the direct outputs with the program's own psychrometric fits (after the ASHRAE Fundamentals psychrometrics chapter), for example h = 1.00484 t + W (2500.94 + 1.85895 t) kJ/kg dry air. 5.3 Setting or Capability Used: Post-processed (scripts/s140/suites/ae_sz.py, ae_cv.py, ae_vav.py and psy.py): node specific volume and enthalpy, and RHcco, from each node's temperature, humidity ratio and the outdoor barometric pressure; each zone's sensible and latent loads from that zone's system sensible heating and cooling rates and its total internal latent gain rate; the cooling-coil total load as the program's total cooling rate (the air-side enthalpy drop) minus the enthalpy the condensate carries away, taken to leave at the coil leaving-air temperature (52 W in AE104); the cooling-coil sensible load as the program's sensible cooling rate plus a condensate term. The program's sensible rate is the air mass flow times the moist-air specific heat at the entering humidity times the dry-bulb drop, so it cools the vapour that condenses, as vapour, all the way to the leaving temperature. Section 3.1 cools that vapour only to the condensation temperature, here the entering-air dew point, and the condensate from there to the leaving temperature (items b and c of the definition; the condensate temperatures of 11.2.1.1.3 d and 11.2.3.1.3 f informative note 1). The term is therefore the condensate mass flow times the liquid-water less the vapour specific heat (4.18 and 1.85895 kJ/(kg K), the program's) times the entering dew point less the leaving temperature: 6.2 W in AE104, at most 1.21 percent of the sensible load (AE326), and 0 on a dry coil. The cooling-coil latent load is the total less that sensible load, so the total, sensible and latent loads all follow the Section 3.1 definitions. The psychrometric relations are the ones the program uses internally for its node states. In AE401 both variable-air-volume terminals sit at their minimum flow, so the return fan carries no air (11.2.4.1.2.4 informative note 1); the return fan inlet and outlet states are then reported as n/a, as the quasi-analytical solution has them, and their mass flow is the program's. Units: loads in kWh/h are the rates in kW; humidity ratio in g/g dry air. =============================================================================== C. REPORT BLOCK FOR EQUIVALENT MODELING METHODS =============================================================================== CONTENT: This section shall describe equivalent modeling methods used to perform the tests. When the software does not model an effect exactly as stated in the standard or does not permit the input values required, equivalent modeling methods shall be permitted to perform the test. INSTRUCTIONS: If equivalent modeling methods are applied, a separate note for each instance of equivalent modeling shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If equivalent modeling methods are not applicable, specify "NONE" in place of the information below. NOTE 1 - Four-Pipe Fan Coil as a One-Zone Air Loop (Section 11.2.1.1, Figure 11-1 (140-2014a 5.5.1.1, Figure 5-25)) ------------------------------------------------------------------------------- 1.1 Describe the Effect Being Simulated: System configuration; none on the specified loads. 1.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.1.1, 11.2.1.1.1.1 and Figure 11-1. 1.3 Equivalent Input(s) Used: One air loop serving one zone: outdoor-air mixer, electric heating coil, chilled-water cooling coil, draw-through constant-volume supply fan (total efficiency 0.7, motor and drive losses outside the airstream, so all 0.28317 m3/s x 498 Pa / 0.7 = 201.46 W of fan power enters the air), a constant-volume terminal without reheat, the zone exhaust fan of note 3, and single-zone heating and cooling supply-air setpoint managers carried to the coil outlets (lowered by the fan's temperature rise). 1.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The same components in the same order as Figure 11-1; the program has no dedicated fan-coil unit with an outdoor-air mixer and a draw-through fan. The heating coil is electric, the same coil type as in the single-zone series (5.1.1.4); it holds its setpoint exactly, as 11.2.1.1.3 a asks, and the coil type is free (Figure 11-1 informative note). NOTE 2 - Single-Zone System as a One-Zone Air Loop with a Return Fan (Section 11.2.2.1, Figure 11-3) ------------------------------------------------------------------------------- 2.1 Describe the Effect Being Simulated: System configuration; none on the specified loads. 2.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.2.1, 11.2.2.1.1 and Figure 11-3. 2.3 Equivalent Input(s) Used: The air loop of note 1 with a return fan as the first component of the loop branch, between the zone return and the outdoor-air mixer (note 4). The mixer's return stream and the economizer's return-air sensor are the return fan outlet. 2.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The same components in the same order as Figure 11-3; the program treats a fan ahead of the outdoor-air system on the branch as the system's return fan. NOTE 3 - Zone Exhaust Fan (Section 11.2.1.1.1.2, 11.2.1.1.2.3, 11.2.2.1.1.3, 11.2.2.1.2.3-11.2.2.1.2.4, 11.2.3.1.1.3, 11.2.3.1.2.3-11.2.3.1.2.5, 11.2.4.1.1.3 and 11.2.4.1.2.3-11.2.4.1.2.5 (140-2014a 5.5.1.1.1.2, 5.5.1.1.2.3)) ------------------------------------------------------------------------------- 3.1 Describe the Effect Being Simulated: None on the zone or mixed-air energy balance. 3.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.1.1.1.2, 11.2.1.1.2.2-11.2.1.1.2.3, 11.2.2.1.1.3, 11.2.2.1.2.2-11.2.2.1.2.4, 11.2.3.1.1.3, 11.2.3.1.2.3-11.2.3.1.2.5, 11.2.4.1.1.3 and 11.2.4.1.2.3-11.2.4.1.2.5. 3.3 Equivalent Input(s) Used: A zone exhaust fan draws the specified exhaust from the zone at the zone air state (one per zone in the two-zone cases). The outdoor-air controller's minimum flow equals the exhaust mass flow (the sum of both zones' in the two-zone cases), so the return air is the supply less the exhaust mass and no air is relieved at the mixer; while an economizer raises the outdoor air above the minimum, the surplus return air is relieved there. In the variable-air-volume cases each zone's exhaust flow is also its terminal's minimum flow (note 16). The exhaust fan's power goes to the exhausted air. 3.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The specification leaves the exhaust fan undefined because it does not affect the results (informative notes of 11.2.1.1.1.2, 11.2.2.1.1.3, 11.2.3.1.1.3 and 11.2.4.1.1.3); its heat leaves the building with the exhaust. (The first fan-coil submission relieved the exhaust mass at the mixer instead, which gives the same coil and zone loads.) NOTE 4 - Return Fan Pressure Rise as a Cubic Power Curve (Section 11.2.2.1.1.2, 11.2.3.1.1.2 and 11.2.4.1.1.2) ------------------------------------------------------------------------------- 4.1 Describe the Effect Being Simulated: Return fan heat, and with it the return-air state, the mixed-air state and the coil loads. 4.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.2.1.1.2 b, c, g, h, 11.2.2.1.1.4, 11.2.3.1.1.2 b, c, g, h, 11.2.3.1.1.4, 11.2.4.1.1.2 b, c, g, h and 11.2.4.1.1.4. 4.3 Equivalent Input(s) Used: A variable-volume fan whose power is its maximum-flow power times the cube of the flow fraction (power coefficients 0, 0, 0, 1, 0, no minimum flow), so its pressure rise varies with the square of the flow; efficiency 0.7 with motor and drive losses outside the airstream. Its maximum flow is the loop design flow, and its pressure input is the specified rise (249 Pa at 0.18878 m3/s, or at 0.37756 m3/s in the two-zone cases, varying with the square of the volume at the return fan inlet) evaluated at that maximum, in the units of note 7. At the steady return flow the fan then draws exactly V_ret x P(V_ret) / 0.7 (59.6 to 172.0 W across the single-zone and constant-volume cases, 0.28 to 28.9 W in the variable-air-volume cases, 0 in AE401, which returns no air), all of it to the air. The variable-air-volume supply fan is the same kind of fan (note 15). 4.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: 11.2.2.1.1.2 c gives the pressure rise as the square of the actual return volume over the design return volume; at constant efficiency the fan power is then cubic in the flow. The maximum at the loop design flow keeps the program's flow limit above the return flow. The same fan-heat convention as the supply fan (note 1). NOTE 5 - Adiabatic Zone and Ideal Plant (Section 11.2.1.1.3 b, 11.2.1.1.4, 11.2.2.1.4, 11.2.3.1.4 and 11.2.4.1.5 (140-2014a 5.5.1.1.3 b, 5.5.1.1.4)) ------------------------------------------------------------------------------- 5.1 Describe the Effect Being Simulated: None on the reported loads. 5.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.1.1.3 b, 11.2.1.1.4, 11.2.2.1.4, 11.2.3.1.3 b, 11.2.3.1.4, 11.2.4.1.3 b, 11.2.4.1.4 and 11.2.4.1.5. 5.3 Equivalent Input(s) Used: Each zone has only adiabatic surfaces; the sensible load is a constant internal gain (negative for AE101, AE201, AE301 and AE401) and the latent load a constant latent gain of 586.1 W (586.1 W and 879.2 W in the two zones of the two-zone cases), both fully convective. The cooling coil is served by an oversized chilled-water loop held at 6.67 C, with a pump of 1 W (its chiller sized as note 13 says in the two-zone cases); the heating, preheat and reheat coils are electric. 5.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: 11.2.1.1.4 prefers an adiabatic zone with negative internal gains; the plant only supplies the cooling coil, whose capacity exceeds the loads (11.2.1.1.3 b). NOTE 6 - Constant Weather Files Converted to EPW (Section 11.2.1.1.7, 11.2.2.1.7, Annex A1 (140-2014a 5.5.1.1.7, Annex A1)) ------------------------------------------------------------------------------- 6.1 Describe the Effect Being Simulated: None; the converted fields are identical hour by hour. 6.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.1.1.7, 11.2.1.2.1.1 b, 11.2.1.2.2.1 b, 11.2.2.2.1.1 b to 11.2.2.2.4.1 b, 11.2.3.1.7, 11.2.3.2.1.1 b to 11.2.3.2.4.1 b, 11.2.4.1.8, 11.2.4.2.1.1 b to 11.2.4.2.4.1 b and Annex A1. 6.3 Equivalent Input(s) Used: AE101.TM2, AE103.TM2, AE104.TM2, AE105.TM2 and AE106.TM2 converted to EPW by the SIMsara converter (dry bulb, dew point, relative humidity, 101300 Pa station pressure, wind; no solar), with the specified site in the location record and the checksums archived. Each case runs on the file its case table names (AE201, AE301 and AE401 on AE101.TM2, AE226, AE326 and AE426 on AE106.TM2, AE245, AE345 and AE445 on AE105.TM2) for 7 days until the last hour repeats. 6.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The program reads EPW weather. The TM2 pressure of 1013 mbar is used as given (11.2.1.1.7, Table 11-4 note b: the effect is below 0.05 percent). NOTE 7 - Volumetric Flows Converted to Mass Flow at the Specified States (Section 11.2.1.1.1.1, 11.2.1.1.2, 11.2.2.1.1.1 and 11.2.2.1.2 (140-2014a 5.5.1.1.1.1, 5.5.1.1.2)) ------------------------------------------------------------------------------- 7.1 Describe the Effect Being Simulated: Supply, exhaust, outdoor-air and return mass flows, and the fan heat. 7.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.1.1.1.1 b and g, 11.2.1.1.2.1-11.2.1.1.2.3, 11.2.2.1.1.1-11.2.2.1.1.2 and 11.2.2.1.2.1-11.2.2.1.2.4. 7.3 Equivalent Input(s) Used: The program takes volume flows at standard density (1.2043 kg/m3). For each case the supply mass flow is 0.28317 m3/s divided by the specific volume at the supply-fan inlet (the cooling-coil outlet), the exhaust mass flow 0.09439 m3/s divided by the specific volume of the zone air; both are entered as mass flow / 1.2043 (the supply flow also as the terminal, coil and return-fan maximum), and the outdoor-air minimum equals the exhaust, so the return air carries the supply less the exhaust mass. The supply fan pressure input is 498 Pa x 1.2043 x the fan-inlet specific volume, so the fan power is 0.28317 x 498 / 0.7 W; the return fan pressure input is its specified rise at the loop design flow in the same units (note 4). The states come from the case's own converged run; the conversion is repeated until every input changes by less than 1e-7 relative (4 to 5 runs). The arithmetic of each step is archived with the results. 7.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: 11.2.1.1.2 and 11.2.2.1.2 define the flows at the supply fan inlet, the exhaust fan inlet (the zone air) and the return fan inlet, and set the outdoor-air mass flow equal to the exhaust mass flow. The two-zone conversions are notes 12 (constant volume) and 17 (variable air volume). NOTE 8 - Thermostat Setpoint Adjustment (Section 11.2.1.1.6.3, 11.2.2.1.6, 11.2.3.1.6 and 11.2.4.1.7 (140-2014a 5.5.1.1.6.3)) ------------------------------------------------------------------------------- 8.1 Describe the Effect Being Simulated: Removes a zone temperature offset of up to 0.0418 K. 8.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.1.1.6, 11.2.1.1.6.3, 11.2.2.1.6, 11.2.3.1.6 and 11.2.4.1.7. 8.3 Equivalent Input(s) Used: The active setpoint, the specified zone temperature of each case (of each zone in the two-zone cases: in the constant-volume cases the heating setpoint the reheat coil holds, in the variable-air-volume cases the heating setpoint of a heated zone and the cooling setpoint of a cooled zone, the side of the zone's load), is shifted by the offset between the specified and the modeled zone temperature of the previous run, in the same iteration as the flow conversion, until the zone is within 1e-5 K of the specified temperature. The unused setpoint is 5 K beyond the active one. The specified zone temperature is the case table's SI value, which the tables give to three decimals beside the I-P value; the preheat and supply-air setpoints, which 11.2.3.1.3 c and d give in I-P with a two-decimal SI value, are the exact conversion of the I-P value. Each input takes the more precise of its two given forms; the two conventions differ by less than 4.5e-4 K. 8.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: 11.2.1.1.6.3 permits adjusting the modeled thermostat setpoint, case by case, so that the modeled zone temperature agrees with the specification. NOTE 9 - Economizer Minimum Limit at ODBecono,min (Section 11.2.2.3.1.1.1 and 11.2.2.3.2.1.1) ------------------------------------------------------------------------------- 9.1 Describe the Effect Being Simulated: None in the reported hour; the limit decides only at outdoor states far from the cases'. 9.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.2.3.1.1.1 and 11.2.2.3.2.1.1. 9.3 Equivalent Input(s) Used: The economizer's minimum limit dry bulb is ODBecono,min: the outdoor dry bulb at which the minimum outdoor air (the exhaust mass) gives the zone setpoint with both coils off, computed from the case's loads, flows and fan heat with the program's own psychrometric relations (the latent gain as moisture at the zone temperature, both fans' heat to the air, the mixer conserving dry air, moisture and enthalpy): 7.91 C for AE226 and 7.90 C for AE245, with the arithmetic archived with the results. The outdoor humidity ratio is the case's (its specified dew point at the weather file's station pressure), limited to saturation at that dry bulb: AE245's dew point lies below its limit, so its outdoor air keeps the case's humidity ratio; AE226's dew point lies far above its limit, so its outdoor air is saturated there. No state of either calculation is supersaturated. The program keeps the economizer off below the limit. 9.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The specification sets the economizer off at or below ODBecono,min and defines it by the dry bulb alone; at a dry bulb below the case's dew point the case's own humidity ratio is not a physical outdoor state, so the saturation limit is used. The program's limit is a dry-bulb input, and both cases run far above it. NOTE 10 - Constant-Volume Terminal Reheat System as a Two-Zone Air Loop (Section 11.2.3.1, 11.2.3.1.1, 11.2.3.1.3 and Figure 11-4) ------------------------------------------------------------------------------- 10.1 Describe the Effect Being Simulated: System configuration; none on the specified loads. 10.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.3.1, 11.2.3.1.1.1-11.2.3.1.1.3, 11.2.3.1.3 c-e and Figure 11-4. 10.3 Equivalent Input(s) Used: One air loop serving two zones: the return fan first on the branch (note 4), the outdoor-air mixer, an electric preheat coil holding its leaving air at the preheat setpoint whenever the mixed air is colder, the chilled-water cooling coil holding the supply fan's leaving air at the supply-air setpoint (its own setpoint lowered by the fan's temperature rise), a draw-through constant-volume supply fan (total efficiency 0.7, motor and drive losses outside the airstream, so all 0.61353 m3/s x 498 Pa / 0.7 = 436.48 W of fan power enters the air), a splitter to one terminal per zone with an electric reheat coil (note 11), the zone exhaust fans of note 3, and a mixer of the two zone returns ahead of the return fan. The mixer's return stream and the economizer's return-air sensor are the return fan outlet. 10.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The same components in the same order as Figure 11-4. The preheat and reheat coils are electric, the coil type of the other series (5.1.1.4). NOTE 11 - Constant-Volume Reheat Terminal as a Variable-Air-Volume Terminal at a Constant Flow Fraction of 1 (Section 11.2.3.1.2.2 and 11.2.3.1.3 e) ------------------------------------------------------------------------------- 11.1 Describe the Effect Being Simulated: None; each terminal delivers its specified constant flow in every regime. 11.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.3.1.2.1, 11.2.3.1.2.2 and 11.2.3.1.3 e. 11.3 Equivalent Input(s) Used: Each zone's terminal is the program's variable-air-volume terminal with reheat (AirTerminal:SingleDuct:VAV:Reheat) with a constant minimum flow fraction of 1, so its flow is its maximum in every regime; the maximum is the zone's supply mass flow of note 12 over the standard density. Its electric reheat coil modulates to hold the zone at its heating setpoint, delivering the supply air at the temperature above the system supply air that the zone needs; every zone of the series is held by its reheat coil, since the supply air at the supply-air setpoint is colder than each zone needs, in the cooling cases too. 11.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: SIMsara has no dedicated constant-volume reheat terminal; at a minimum flow fraction of 1 the variable-air-volume terminal is a constant-volume terminal with reheat, as 11.2.3.1.3 e describes. NOTE 12 - Two-Zone Flows from the Table 11-18 Zone Fractions (Section 11.2.3.1.2) ------------------------------------------------------------------------------- 12.1 Describe the Effect Being Simulated: System, zone supply, exhaust, outdoor-air and return mass flows, and the fan heat. 12.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.3.1.1.1-11.2.3.1.1.2 and 11.2.3.1.2.1-11.2.3.1.2.5, Table 11-18 and its notes. 12.3 Equivalent Input(s) Used: The system supply mass flow is 0.61353 m3/s divided by the specific volume at the supply-fan inlet (the cooling-coil outlet). Each zone's supply mass flow is its Table 11-18 fraction of it (0.4615 and 0.5385, the nominal zone volumes over the system volume, notes d and e), entered as its terminal's maximum over the standard density; the loop, supply fan, return fan and cooling-coil design flows are their sum. Each zone's exhaust is its specified volume (0.09439 and 0.14158 m3/s) divided by the specific volume of that zone's air, and the outdoor-air minimum is the sum of the two exhaust mass flows, so the return fan carries the supply less both exhausts. The fan pressure inputs follow notes 4 and 7. The conversion is repeated with each zone's thermostat adjustment (note 8) until every input changes by less than 1e-7 relative and both zones are within 1e-5 K of their specified temperatures (4 runs); the arithmetic of each step is archived with the results. 12.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: 11.2.3.1.2.2 defines each zone's supply mass flow by its nominal volume at the supply-fan inlet state, and Table 11-18 gives it as a fraction of the system supply mass flow; 11.2.3.1.2.3-11.2.3.1.2.5 define the exhaust at the zone air, the return at the return fan inlet, and the outdoor air as the sum of the zone exhaust mass flows. NOTE 13 - Chilled-Water Plant and Cooling-Coil Water Flow of the Two-Zone Cases (Section 11.2.3.1.3 b and f, and 11.2.4.1.4) ------------------------------------------------------------------------------- 13.1 Describe the Effect Being Simulated: None on the loads; the cooling coil holds its setpoint in every case. 13.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.3.1.3 b, d and f, and 11.2.4.1.4. 13.3 Equivalent Input(s) Used: The air-cooled chiller of the chilled-water loop has a reference capacity of 40 kW, above every cooling-coil load of the series (at most 20.77 kW, in AE326; at most 13.31 kW in the variable-air-volume cases), and the cooling coil holds the supply-air setpoint in every case. The coil's design water flow and its controller's maximum water flow are the single-zone values scaled with the supply volume (Block B note 1); the variable-air-volume cases use the same plant and coil. 13.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: 11.2.3.1.3 b asks for coil capacities at least equal to the coil loads. With a smaller chiller the chilled water would leave warm at the largest load and the coil could fall short of the supply-air setpoint. NOTE 14 - Economizer Minimum Limit at ODBecono,min, Constant-Volume Cases (Section 11.2.3.3.1.1.1 and 11.2.3.3.2.1.1) ------------------------------------------------------------------------------- 14.1 Describe the Effect Being Simulated: None in the reported hour; the limit decides only at outdoor states far from the cases'. 14.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.3.3.1.1.1 and 11.2.3.3.2.1.1. 14.3 Equivalent Input(s) Used: The economizer's minimum limit dry bulb is ODBecono,min: the outdoor dry bulb at which the minimum outdoor air (the sum of the two exhaust mass flows) gives a mixed-air temperature equal to the supply-air setpoint less the supply fan's temperature rise, with the coils off and each zone at its setpoint. It is computed from the case's loads, flows and fan heat with the program's own psychrometric relations: the supply fan's whole power to the air, each zone's supply its Table 11-18 fraction, each zone's latent gain as moisture at its temperature, the zone returns mixed by mass, the return fan's power to the return air, and the mixer conserving dry air, moisture and enthalpy. The result is -8.45 C for AE326 and -8.45 C for AE345, with the arithmetic archived with the results. As in note 9 the outdoor humidity ratio is the case's, limited to saturation at that dry bulb; both cases' dew points lie above the limit, so their outdoor air is saturated there. No state of either calculation is supersaturated. The program keeps the economizer off below the limit. 14.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The specification sets the economizer off at or below ODBecono,min and defines it by the mixed-air temperature at minimum outdoor air; at a dry bulb below the case's dew point the case's own humidity ratio is not a physical outdoor state, so the saturation limit is used. The program's limit is a dry-bulb input, and both cases run far above it. NOTE 15 - Variable-Air-Volume Terminal Reheat System as a Two-Zone Air Loop (Section 11.2.4.1, 11.2.4.1.1 and Figure 11-5) ------------------------------------------------------------------------------- 15.1 Describe the Effect Being Simulated: System configuration; none on the specified loads. 15.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.4.1, 11.2.4.1.1.1-11.2.4.1.1.3, 11.2.4.1.4 and Figure 11-5. 15.3 Equivalent Input(s) Used: The air loop of note 10 with a variable-volume supply fan: like the return fan of note 4, its power is its maximum-flow power times the cube of the flow fraction, so its pressure rise varies with the square of the flow (11.2.4.1.1.1 c); its maximum is the loop design flow, the terminals' maxima summed (note 16), which is the design system supply (0.61353 m3/s, at the supply-fan inlet state as each nominal zone supply is, Table 11-31 note c), and its pressure input is the specified rise (498 Pa at 0.61353 m3/s, 11.2.4.1.1.1 b and Table 11-31 note a) at that maximum in the units of note 7, so at the steady supply it draws exactly V_sup x P(V_sup) / 0.7 (21.1 to 164.0 W across the cases), all of it to the air. The return fan, preheat coil, cooling coil and setpoints are those of the constant-volume cases (notes 4 and 10), each zone's terminal the variable-air-volume terminal of note 16. 15.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The same components in the same order as Figure 11-5; the supply and return fans modulate with the flow the terminals set (11.2.4.1.1.1 d and 11.2.4.1.1.2 d). NOTE 16 - Variable-Air-Volume Terminals with the Zone Exhaust as Their Minimum Flow (Section 11.2.4.1.2.2 and 11.2.4.1.3) ------------------------------------------------------------------------------- 16.1 Describe the Effect Being Simulated: None; each terminal delivers the specified flow. 16.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.4.1.2.2 and 11.2.4.1.3 a-f, Table 11-31 notes c and d. 16.3 Equivalent Input(s) Used: Each zone's terminal is the program's variable-air-volume terminal with an electric reheat coil, a fixed minimum flow and normal damper action. Its minimum flow input is the zone exhaust fan's flow input, the zone's exhaust mass flow over the standard density (note 17), so the terminal's minimum mass flow is the exhaust mass flow; the flow conversion keeps both at the zone's exhaust as the zone state changes. Its maximum is the zone's nominal supply volume at the supply-fan inlet state. Above the minimum the damper opens until the supply air at the supply-air setpoint meets the zone's sensible load (AE403 to AE445, both zones); at the minimum the reheat coil heats the supply air to the temperature the zone needs (AE401, both zones), with no limit on the reheat coil's leaving-air temperature (AE401's zone 1 needs 46.9 C). 16.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: 11.2.4.1.3 c and d set each terminal's minimum to its zone's exhaust mass flow, which varies with the zone state; the program takes a volume at the standard density, so the volume is converted with the run's own zone state, as for the exhaust itself. Table 11-31 note c permits any maximum that meets the zone loads, and 11.2.4.1.3 b asks for a reheat capacity at least the load. NOTE 17 - Two-Zone Variable-Air-Volume Flows (Section 11.2.4.1.2) ------------------------------------------------------------------------------- 17.1 Describe the Effect Being Simulated: Terminal, exhaust, outdoor-air and return mass flows, and the fan heat. 17.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.4.1.1.1-11.2.4.1.1.2, 11.2.4.1.2.1-11.2.4.1.2.5 and Table 11-31 with its notes. 17.3 Equivalent Input(s) Used: Each zone's terminal maximum is its nominal supply volume divided by the specific volume at the supply-fan inlet (the cooling-coil outlet), over the standard density. Each zone's exhaust is its specified volume (0.09439 and 0.14158 m3/s) divided by the specific volume of that zone's air, entered over the standard density as the exhaust fan's flow and the terminal's minimum (note 16), and the outdoor-air minimum is the sum of the two exhaust mass flows. The supply is what the terminals deliver, and the return fan carries it less both exhausts, nothing when both terminals sit at their minimum (AE401). The fan pressure inputs follow notes 4 and 15, the air loop's design supply note 18. The conversion is repeated with each zone's thermostat adjustment (note 8) until every input changes by less than 1e-7 relative and both zones are within 1e-5 K of their specified temperatures (4 to 5 runs); the arithmetic of each step is archived with the results. 17.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: 11.2.4.1.2 and 11.2.4.1.3 define the zone supply by the terminals, the exhaust at the zone air, the return at the return fan inlet and the outdoor air as the sum of the zone exhaust mass flows; Table 11-31 note c defines the nominal zone supply at the supply-fan inlet state. NOTE 18 - Air-Loop Design Supply Flow at the Steady Supply Flow (Section 11.2.4.1.1.1 b and c, 11.2.4.1.2.1 and Table 11-31) ------------------------------------------------------------------------------- 18.1 Describe the Effect Being Simulated: The supply-air state the zones receive in AE403, AE405 and AE445, and with it their zone air and return humidity ratios: the program's zone supply air in these cases depends on this input, which the specification does not set. As used, the zone supply air is 0.039 g/kg moister than the supply-fan outlet in AE445 and 0.0018 g/kg in AE403 and AE405, and at most 0.0055 K warmer in any case. With the input at the design system supply flow, AE403 and AE405 would be about 0.07 g/kg off (their zone air and return humidity ratios up to about 0.085 g/kg above the quasi-analytical solution) and AE445 not at all; 5 percent above the steady flow, AE403 and AE405 would be about 0.043 g/kg off and AE445 not at all. 18.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.4.1.1.1 b and c, 11.2.4.1.2.1 and Table 11-31 notes a and c. 18.3 Equivalent Input(s) Used: The air system's design supply flow, a program input distinct from the specified design system supply, is set 0.1 percent above the steady supply of the case's previous conversion run, and the outdoor-air maximum to the same flow. The specified design system supply is applied where the specification uses it, as both fans' maximum and the flow at which their pressure rises are entered (note 15). The program starts each time step's HVAC iteration at its design supply flow input, which also caps the supply flow, and it re-simulates the zone equipment only while the supply-air state it hands to the zones changes by more than its loop convergence tolerances (0.01 kg/s, 0.0001 kg/kg, 0.01 K, 260 J/kg and 10 W), so the zones can keep the supply air of an earlier iteration, and the starting flow decides in which cases they do. No starting flow gives every case the supply-fan outlet air: at the design system supply (up to about 2.7 times a case's steady flow) AE403 and AE405 are 0.07 g/kg off, 5 percent above the steady flow 0.043 g/kg, 1 percent above it 0.017 g/kg with AE445 at 0.023 g/kg, and at the steady flow itself AE445 stays 0.040 g/kg off while the supply reaches the design supply input in AE403 and AE405. Every one of these differences is within the program's 0.0001 kg/kg tolerance. 18.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The specification defines the system supply by the terminals' flows (11.2.4.1.2.1) and the design system supply as the basis of the supply fan's pressure rise (Table 11-31 note a, 11.2.4.1.1.1 b and c), and both are used that way; the program's iteration starting flow has no specified value. Starting at the steady flow makes the first iteration's outdoor-air fraction and fan heat the steady ones, and the margin keeps the design supply input above the flow the terminals ask for. The remaining differences come from the program's loop convergence tolerances, not from a case input; the six example-range flags they cause (the AE403 and AE445 zone supply air) are reported in Block G. NOTE 19 - Economizer Minimum Limit at ODBecono,min, Variable-Air-Volume Cases (Section 11.2.4.3.1.1 and 11.2.4.3.2.1 (11.2.3.3.1.1.1 and 11.2.3.3.2.1.1)) ------------------------------------------------------------------------------- 19.1 Describe the Effect Being Simulated: None in the reported hour; the limit decides only at outdoor states far from the cases'. 19.2 Section(s) of the Standard where Relevant Inputs are Specified: 11.2.3.3.1.1.1, 11.2.3.3.2.1.1, 11.2.4.3.1.1 and 11.2.4.3.2.1. 19.3 Equivalent Input(s) Used: As note 14 on Figure 11-5: the outdoor dry bulb at which the minimum outdoor air gives a mixed-air temperature equal to the supply-air setpoint less the supply fan's temperature rise, with the coils off and each zone at its setpoint, now with each terminal at the flow its zone needs (at least its exhaust mass flow) and the supply fan's power at that supply's volume. The result is 10.35 C for AE426 and 10.34 C for AE445, with the arithmetic archived with the results. The outdoor humidity ratio is the case's, limited to saturation at that dry bulb (AE426's dew point lies above the limit, AE445's below it). No state of either calculation is supersaturated. 19.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The specification applies the constant-volume economizer controls to the variable-air-volume system (11.2.4.3.1.1 and 11.2.4.3.2.1), whose supply fan keeps modulating with the zone loads; the program's limit is a dry-bulb input, and both cases run far above it. =============================================================================== D. REPORT BLOCK FOR USE OF NON-SPECIFIED INPUTS =============================================================================== CONTENT: This section shall describe nonspecified inputs used to perform the tests. Use of nonspecified inputs shall be permitted only for the following specified sections relating to the following topics: * Alternative constant exterior surface coefficients in Sections 7.2.1.9.3, 7.2.3.1.4.3, 7.2.3.3.2, and 9.2.1.8 * Alternative constant interior surface coefficients in Sections 7.2.1.10.3, 7.2.3.1.4.4, 7.2.3.2.2, and 9.2.1.9 * Alternative constant interior solar distribution fractions in Sections 7.2.1.12, 7.2.2.1.2.2, 7.2.2.1.6.2, 7.2.2.1.7.2, 7.2.2.2.7.4, 7.2.3.9.3, 7.2.3.10.2, and 7.2.3.12.2 * Air density given at specific altitudes for the space-cooling and space- heating equipment cases in Sections 9.2.1.4.3, 9.2.3.4.3, and 10.2.1.4.3. INSTRUCTIONS: If nonspecified inputs are applied, a separate note for each use of nonspecified inputs shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If nonspecified inputs are not applied, specify "NONE" in place of the information below. NONE =============================================================================== =============================================================================== E. REPORT BLOCK FOR OMITTED TEST CASES AND RESULTS =============================================================================== CONTENT: This section shall describe test cases that were omitted and/or individual results of test cases that were omitted along with the reason for the omission. INSTRUCTIONS: If test cases were omitted, a separate note to describe each type of omission shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If there are no omitted test cases, specify "NONE" in place of the information below. NONE =============================================================================== F. REPORT BLOCK FOR CHANGES TO SOURCE CODE FOR THE PURPOSE OF RUNNING THE TESTS, WHERE SUCH CHANGES ARE NOT AVAILABLE IN PUBLICLY RELEASED VERSIONS OF THE SOFTWARE =============================================================================== CONTENT: This section shall describe changes to software source code made to allow the software to run a test, where such changes are not available in a publicly released version of the software. INFORMATIVE NOTE: This section addresses special situations where a change to source code is necessary to activate a feature or to permit inputs needed for a test when these features are not available in the publicly released version of the software. INSTRUCTIONS: If changes to the source code for the purpose of running a test are applied, separate notes to describe each source code modification shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If changes to source code are not applied, specify "NONE" in place of the information below. NOTE 1 - Other Equipment Internal Gains (Section 11.2.1.1.4, 11.2.2.1.4, 11.2.3.1.4 and 11.2.4.1.5 (140-2014a 5.5.1.1.4)) ------------------------------------------------------------------------------- 1.1 List the Change(s) to the Source Code: The OtherEquipment internal-gain input is read and applied as a zone heat gain (sensible convective, radiant and latent fractions), including a negative design level, without adding it to the electric equipment output or meter. 1.2 List the Test Case(s) Relevant to the Change(s) in the Source Code: Every case of this report (the zone sensible and latent loads). 1.3 Explanation of Why the Change is Not Included in the Publicly Released Version of the Software: The tested build carries this change but no tagged public release includes it yet. Remove this note when the release tag used for the submission run (user action U4) contains it. NOTE 2 - Zone Exhaust Fan and Return Fan (Section 11.2.1.1.1.2, 11.2.2.1.1.2, 11.2.2.1.1.3, 11.2.3.1.1.2, 11.2.3.1.1.3, 11.2.4.1.1.2 and 11.2.4.1.1.3) ------------------------------------------------------------------------------- 2.1 List the Change(s) to the Source Code: A zone exhaust fan (Fan:ZoneExhaust) on a zone's equipment list, with the zone air mass balance that returns the supply less the exhaust, was added; and the program now identifies the supply and return fans of an air loop, a fan ahead of the outdoor-air system being the return fan. 2.2 List the Test Case(s) Relevant to the Change(s) in the Source Code: Every case of this report (the exhaust fan); AE201 to AE245, AE301 to AE345 and AE401 to AE445 (the return fan). 2.3 Explanation of Why the Change is Not Included in the Publicly Released Version of the Software: The tested build carries these changes but no tagged public release includes them yet. Remove this note when the release tag used for the submission run (user action U4) contains them. =============================================================================== G. REPORT BLOCK FOR ANOMALOUS RESULTS =============================================================================== CONTENT: Describing anomalous results shall be permitted but is not required. If anomalous test results are described, this section shall be used. INSTRUCTIONS: If anomalous test results are described, each type of anomalous result shall be described in a separate note. The standard format shown below and a separate number and title for each note item shall be applied. If anomalous results are not discussed, it shall be permitted to specify "NONE" in place of the information below. NOTE 1 - Node Specific Volume, Enthalpy and Mass Flow Just Outside the Example Range (Section 11.3.1.3 and 11.3.2.3 (140-2014a 6.5.1.3)) ------------------------------------------------------------------------------- 1.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: Detailed outputs (11.3.1.3 and 11.3.2.3) of AE101, AE103, AE104 and AE201 to AE245: the specific volume of several nodes is up to 0.12 percent above the largest example result, the AE101 and AE201 heating-coil outlet, cooling-coil outlet and supply enthalpies up to 0.021 percent above the largest, and some outdoor-air, supply and return dry-air mass flows of AE101, AE103, AE201, AE203 and AE206 up to 0.10 percent below the smallest. Every other coil and zone load, RHcco, node dry bulb and humidity ratio is inside the example range, or explained in note 2 or 3. 1.2 Explanation of Reason for the Anomalous Results: The specific volume is the program's psychrometric relation v = 159.473 (1 + 1.6078 W)(1.8 T + 492) / P (ideal gas, with the 1.8 T + 492 absolute-temperature form) at the station pressure of the weather files, 101300 Pa (1013 mbar in the TM2 files, 11.2.1.1.7 Table 11-4 note b), where the specification's reference values use 101325 Pa and a real-gas model. Together these make v about 0.09 percent larger. Because the supply and exhaust mass flows are the specified volumetric flows divided by this v (11.2.1.1.2, 11.2.2.1.2), they are about 0.09 percent smaller. The heating-coil outlet, cooling-coil outlet and supply enthalpies of AE101 and AE201 are within 0.08 percent of the quasi-analytical solution, which lies 0.088 to 0.097 percent above the largest example result, so SIMsara sits between the example programs and the quasi-analytical solution. The differences are the consistent use of the program's own psychrometrics, not a modeling error. Every coil load is within 2 percent of the quasi-analytical solution. NOTE 2 - Mixed-Air and Return-Fan-Outlet Temperatures and AE203 Coil Loads at the Edge of the Example Range (Section 11.3.2.1, 11.3.2.2 and 11.3.2.3) ------------------------------------------------------------------------------- 2.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: AE201 mixed-air and return-fan-outlet dry bulbs, AE203 and AE205 mixed-air and heating-coil outlet dry bulbs (at most 0.003 K outside the range of the example results), and the AE203 cooling-coil sensible and total loads (up to 0.33 percent above the largest example result). 2.2 Explanation of Reason for the Anomalous Results: Each of these values agrees with the quasi-analytical solution, to within 0.001 K for the temperatures and 0.04 percent for the loads, and the quasi-analytical solution lies outside the example range by about the same margin; the example results cluster closely in these quantities. AE203's loads include the return fan's heat, all of it delivered to the return air (Block C note 4). Every value is within the tolerances of the quasi-analytical solution applied to these results (2 percent on coil loads, 0.1 K on node temperatures). NOTE 3 - AE245 Cooling-Coil Outlet and Supply Enthalpy Just Below the Example Range (Section 11.3.2.3) ------------------------------------------------------------------------------- 3.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: AE245 detailed outputs: the cooling-coil outlet and supply-air enthalpies are 0.04 and 0.03 percent below the smallest example result; their dry bulbs and humidity ratios, and every AE245 coil load, are inside the example range. 3.2 Explanation of Reason for the Anomalous Results: At 100 percent outdoor air these nodes carry the outdoor humidity ratio, which the program computes from the weather file's dry bulb, relative humidity and station pressure. The weather file holds the relative humidity as an integer percent (Table 11-14 note b), which puts the humidity ratio 0.2 percent below the quasi-analytical solution's, and the program's ideal-gas enthalpy relation adds a smaller difference of the same sign. The humidity ratio and dry bulb of both nodes are within 0.05 g/kg and 0.1 K of the quasi-analytical solution. NOTE 4 - Constant-Volume Cases: Node Specific Volume and Outdoor-Air Mass Flow Just Outside the Example Range (Section 11.3.3.3) ------------------------------------------------------------------------------- 4.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: Detailed outputs (11.3.3.3) of AE301 to AE345: the specific volume of several nodes is up to 0.13 percent above the largest example result, and the outdoor-air dry-air mass flows of AE301, AE303 and AE305 up to 0.10 percent below the smallest. 4.2 Explanation of Reason for the Anomalous Results: The same cause as note 1: the program's ideal-gas specific volume at the weather files' station pressure, 101300 Pa, is about 0.09 percent larger than the specification's reference values, and the dry-air mass flows, the specified volumes divided by it (11.2.3.1.2), are about 0.09 percent smaller. Each of these specific volumes is within 0.10 percent, and each of these mass flows within 0.10 percent, of the quasi-analytical solution. NOTE 5 - AE301 Supply-Path Humidity, Enthalpy, RHcco and Preheat-Coil Load at the Edge of the Example Range (Section 11.3.3.2 and 11.3.3.3) ------------------------------------------------------------------------------- 5.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: AE301: the humidity ratios of the mixed air and of every node from the preheat-coil outlet to the zone supply air (0.046 percent above the largest example result), the mixed-air, preheat-coil outlet, cooling-coil outlet and supply-air enthalpies (up to 0.24 percent above the largest), RHcco (0.015 points above the largest) and the preheat-coil load (0.21 percent below the smallest). 5.2 Explanation of Reason for the Anomalous Results: AE301's outdoor air is nearly dry, so the humidity of the mixed and supply air comes from the two zones' latent gains returned with the return air. With the dry-air mass flows about 0.09 percent smaller (note 4), each kilogram of supply air picks up about 0.09 percent more moisture: these humidity ratios are 0.090 percent above the quasi-analytical solution, and RHcco, at the same dry bulb, 0.015 points above it. The enthalpies are within 0.06 percent of the quasi-analytical solution, which lies 0.14 to 0.25 percent above the largest example result, so SIMsara sits between the example programs and the quasi-analytical solution. The preheat-coil load is the supply mass flow times the enthalpy rise from the mixed air to the preheat setpoint: the mass flow is about 0.09 percent smaller, and the program's enthalpy fit (Block B note 5) uses a dry-air specific heat of 1.00484 kJ/(kg K), about 0.12 percent below the 1.006 kJ/(kg K) of the current Handbook equation, so the load is 0.22 percent below the quasi-analytical solution, well within the 2 percent applied to these results. NOTE 6 - Constant-Volume Cases: Mixed-Air, Preheat-Coil Outlet, Return-Fan Outlet and Supply Dry Bulbs at the Edge of the Example Range (Section 11.3.3.3) ------------------------------------------------------------------------------- 6.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: The mixed-air dry bulbs of AE301, AE303 and AE306, the preheat-coil outlet dry bulbs of AE303 and AE306 and the return-fan outlet dry bulbs of AE301 and AE306 (at most 0.0036 K outside the range of the example results), and the AE304 supply-air dry bulb. 6.2 Explanation of Reason for the Anomalous Results: Each of the first seven agrees with the quasi-analytical solution to within 0.0005 K, and the quasi-analytical solution lies outside the example range by about the same margin; the example results cluster closely in these quantities (as in note 2). The AE304 supply-air dry bulb lies 5.4e-07 K below the supply-air setpoint (11.2.3.1.3 d), within the cooling-coil controller tolerance of Block B note 2, which puts it just outside the example range. NOTE 7 - AE345 Supply, Zone and Return Enthalpies Just Below the Example Range (Section 11.3.3.3) ------------------------------------------------------------------------------- 7.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: AE345 detailed outputs: the supply-air, zone 1, zone 2 and return-fan inlet enthalpies are up to 0.13 percent below the smallest example result; their dry bulbs and humidity ratios, and every AE345 coil load, are inside the example range. 7.2 Explanation of Reason for the Anomalous Results: As in note 3: at 100 percent outdoor air the supply air carries the outdoor humidity ratio, which the program computes from the weather file's dry bulb, relative humidity and station pressure. The weather file holds the relative humidity as an integer percent (Table 11-27 note b), which puts the outdoor humidity ratio 0.22 percent below the quasi-analytical solution's; each zone adds its latent moisture to it, so these enthalpies are 0.14 to 0.17 percent below the quasi-analytical solution; the program's enthalpy fit, with its dry-air specific heat about 0.12 percent below the current Handbook equation's (note 5), adds a difference of the same sign. The humidity ratio and dry bulb of every AE345 node are within 0.05 g/kg and 0.1 K of the quasi-analytical solution. NOTE 8 - Variable-Air-Volume Cases: Node Specific Volume and Dry-Air Mass Flow Just Outside the Example Range (Section 11.3.4.3) ------------------------------------------------------------------------------- 8.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: Detailed outputs (11.3.4.3) of AE401 to AE445: the specific volume of several nodes is up to 0.11 percent above the largest example result, and the dry-air mass flows of AE401's supply path and the outdoor-air mass flows of AE403 and AE405 up to 0.10 percent below the smallest. 8.2 Explanation of Reason for the Anomalous Results: The same cause as notes 1 and 4: the program's ideal-gas specific volume at the weather files' station pressure, 101300 Pa, is about 0.09 percent larger than the specification's reference values, and the dry-air mass flows, the specified volumes divided by it (11.2.4.1.2), are about 0.09 percent smaller. Each of these specific volumes is within 0.10 percent, and each of these mass flows within 0.10 percent, of the quasi-analytical solution. NOTE 9 - AE401 Preheat and Reheat Loads, RHcco and Supply-Path Humidity Just Below the Example Range (Section 11.3.4.2 and 11.3.4.3) ------------------------------------------------------------------------------- 9.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: AE401: the preheat-coil load and both reheat-coil loads (up to 0.12 percent below the smallest example result), RHcco (0.004 points below the smallest) and the humidity ratios of the mixed air, the preheat-coil outlet and the cooling-coil outlet (0.045 percent below the smallest). 9.2 Explanation of Reason for the Anomalous Results: Both terminals sit at their minimum flow, so the system supplies only the outdoor air that replaces the two exhausts, about 0.09 percent less dry air than the quasi-analytical solution's (note 8). The preheat-coil load is that mass flow times the enthalpy rise, and the program's enthalpy fit (Block B note 5) has a dry-air specific heat about 0.12 percent below the current Handbook equation's: the load is 0.22 percent below the quasi-analytical solution. Each reheat coil heats the supply air at the specific heat of the supply humidity, while the program holds the zone with its system sensible rate, the mass flow times the specific heat at the zone humidity times the supply-to-zone temperature difference (the zone's reported load). A reheat load is therefore the zone load scaled by the ratio of the two specific heats plus the supply's rise to the zone temperature: the ratio takes 8.9 to 11.1 W off the two reheat loads, 63 to 78 percent of their gaps to the quasi-analytical solution; the rest of each gap, at most 0.21 percent of the rise, comes from the same mass flow and specific heat differences as the preheat load's. The reheat loads are 0.29 to 0.31 percent below the quasi-analytical solution, well within the 2 percent applied to these results. The outdoor-air node itself, at 100.00 percent relative humidity from the weather file's dry bulb, relative humidity and station pressure, is inside the example range, 0.031 percent above the quasi-analytical solution. With no return air the mixer finds that air at or above saturation by the program's saturation-temperature fit at its enthalpy and pressure, and moves it to that saturation temperature at constant enthalpy, 0.00032 K warmer and 0.050 percent drier. The mixed-air, preheat-coil outlet and cooling-coil outlet humidity ratios are therefore 0.020 percent below the quasi-analytical solution, which lies below the example range too, and RHcco, at the same dry bulb, 0.003 points below it. NOTE 10 - Variable-Air-Volume Cases: Supply-Air Dry Bulbs and Mixed-Air and Supply Enthalpies at the Edge of the Example Range (Section 11.3.4.3) ------------------------------------------------------------------------------- 10.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: The supply-air dry bulbs of AE405, AE426 and AE445, the AE406 mixed-air and preheat-coil outlet enthalpies, and the AE445 supply-air enthalpy. 10.2 Explanation of Reason for the Anomalous Results: The three supply-air dry bulbs lie at most 4.6e-07 K below the supply-air setpoint (11.2.3.1.3 d, which 11.2.4.1.4 applies), within the cooling-coil controller tolerance of Block B note 2, which puts them just outside the example range. The AE406 enthalpies are within 0.013 percent of the quasi-analytical solution, which lies outside the example range too. As in note 7: at 100 percent outdoor air the AE445 supply air carries the outdoor humidity ratio from the weather file's integer relative humidity (Table 11-36 note b), 0.22 percent below the quasi-analytical solution's, and its enthalpy is 0.17 percent below the quasi-analytical solution. NOTE 11 - AE403 and AE445 Zone Supply-Air Humidity and Enthalpy Just Above the Example Range (Section 11.3.4.3) ------------------------------------------------------------------------------- 11.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: The zone 1 and zone 2 supply-air humidity ratios of AE403 (0.027 percent above the largest example result) and AE445 (0.21 percent above), and the AE445 zone supply-air enthalpies (0.059 percent above). 11.2 Explanation of Reason for the Anomalous Results: All six come from the zone supply air lagging the supply-fan outlet within the program's loop convergence tolerances (Block C note 18): the zones receive the supply air of an earlier HVAC iteration of the time step, and which cases do depends on the air system's design supply flow input, which the specification does not set. The supply-fan outlet air's humidity ratio lies inside the example range of each of these humidity cells, and at that humidity the AE445 zone supply enthalpies would lie inside theirs. In AE403 the zone supply air is 0.0018 g/kg moister than the supply-fan outlet, just enough to lift both zone supply humidity ratios above the range; they remain 0.026 percent below the quasi-analytical solution, which lies above the example range. In AE445 the zone supply air is 0.039 g/kg moister and 0.0054 K warmer than the supply-fan outlet, and the moisture alone lifts its enthalpy above the range; with the design supply input 1 percent or more above the steady flow these four cells fall inside the example range, while AE403 and AE405 then carry a larger lag (Block C note 18). The zone supply humidity ratio and dry bulb are within 0.05 g/kg and 0.1 K of the quasi-analytical solution in every case, and every AE445 coil load is inside the example range. =============================================================================== ===============================================================================