Sections 9.2.1 to 9.2.2 · CE a
Space cooling A
A unitary cooling system at steady state, compared with analytical solutions for energy use, coil loads and zone conditions.
- Cases run
- 14
- Values compared
- 266
- Outside example range
- 28
- Harness checks passed
- 143 of 143
- Run date
- 2026-10-02
Cases
Each case page shows its results, where they sit in the reference range, and the input file.
CE a February results266 rows · 28 outside
| Case | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| CE100 | Cooling Energy Consumption Total (kWh) | 1,522.6 | 1,511.9 | 1,531 | 1,522.1 | 1,530.5 to 1,530.8 | In range |
| CE100 | Compressor (kWh) | 1,311.7 | 1,302.7 | 1,319 | 1,311.6 | 1,318.9 to 1,319 | In range |
| CE100 | Supply Fan (kWh) | 143.52 | 141 | 145.19 | 143.39 | 144 to 144.10 | In range |
| CE100 | Condenser Fan (kWh) | 67.391 | 66.849 | 68.174 | 67.579 | 67.600 to 67.643 | In range |
| CE100 | Evaporator Coil Load Total (kWh) | 3,799.1 | 3,794.0 | 3,841.5 | 3,804.4 | 3,800.4 | In range |
| CE100 | Sensible (kWh) | 3,799.1 | 3,794.0 | 3,841.5 | 3,804.4 | 3,800.4 | In range |
| CE100 | Latent (kWh) | −6.06e-16 | 0 | 0.004946 | 7.07e-4 | 0 | In range |
| CE100 | Total (kWh) | 3,655.6 | 3,654.1 | 3,656.1 | 3,655.4 | 3,656.3 | In range |
| CE100 | Zone Load Sensible (kWh) | 3,655.6 | 3,654.1 | 3,656.1 | 3,655.4 | 3,656.3 | In range |
| CE100 | Latent (kWh) | −6.06e-16 | 0 | 0 | 0 | 0 | In range |
| CE100 | COP | 2.401 | 2.389 | 2.430 | 2.406 | 2.389 to 2.390 | In range |
| CE100 | IDB (°C) | 22.207 | 22.200 | 22.635 | 22.295 | 22.200 to 22.216 | In range |
| CE100 | Humidity Ratio (kg/kg) | 0.007409 | 0.006910 | 0.007600 | 0.007414 | 0.007339 to 0.007427 | In range |
| CE100 | COP | 2.403 | 2.390 | 2.432 | 2.407 | 2.389 | In range |
| CE100 | IDB (°C) | 22.209 | 22.200 | 23.210 | 22.378 | 22.200 to 22.235 | In range |
| CE100 | Humidity Ratio (kg/kg) | 0.007409 | 0.006990 | 0.007600 | 0.007425 | 0.007339 to 0.007427 | In range |
| CE100 | COP | 2.395 | 2.390 | 2.429 | 2.405 | 2.389 | In range |
| CE100 | IDB (°C) | 22.207 | 22.090 | 22.333 | 22.218 | 22.197 to 22.200 | In range |
| CE100 | Humidity Ratio (kg/kg) | 0.007409 | 0.006840 | 0.007600 | 0.007403 | 0.007339 to 0.007427 | In range |
| CE110 | Cooling Energy Consumption Total (kWh) | 1,068.1 | 1,061.2 | 1,089 | 1,070.0 | 1,076.2 to 1,077.4 | In range |
| CE110 | Compressor (kWh) | 880.88 | 865.87 | 899 | 882.00 | 887.94 to 889.40 | In range |
| CE110 | Supply Fan (kWh) | 127.42 | 122 | 132.92 | 127.69 | 127.90 to 128.13 | In range |
| CE110 | Condenser Fan (kWh) | 59.830 | 59.475 | 62.413 | 60.474 | 60.100 to 60.166 | In range |
| CE110 | Evaporator Coil Load Total (kWh) | 3,764.6 | 3,755.6 | 3,803.6 | 3,768.7 | 3,765 to 3,765.3 | In range |
| CE110 | Sensible (kWh) | 3,764.6 | 3,755.6 | 3,803.6 | 3,768.7 | 3,765 to 3,765.3 | In range |
| CE110 | Latent (kWh) | −8.03e-15 | 0 | 0.003710 | 5.30e-4 | 0 | In range |
| CE110 | Total (kWh) | 3,637.1 | 3,635.5 | 3,637 | 3,636.5 | 3,637.1 | Above range |
| CE110 | Zone Load Sensible (kWh) | 3,637.1 | 3,635.5 | 3,637 | 3,636.5 | 3,637.1 | Above range |
| CE110 | Latent (kWh) | −8.03e-15 | 0 | 0 | 0 | 0 | In range |
| CE110 | COP | 3.405 | 3.342 | 3.459 | 3.405 | 3.379 to 3.380 | In range |
| CE110 | IDB (°C) | 22.200 | 22.200 | 22.524 | 22.272 | 22.200 to 22.214 | In range |
| CE110 | Humidity Ratio (kg/kg) | 0.006506 | 0.006400 | 0.007030 | 0.006680 | 0.006400 to 0.006519 | In range |
| CE110 | COP | 3.408 | 3.357 | 3.463 | 3.412 | 3.378 to 3.379 | In range |
| CE110 | IDB (°C) | 22.200 | 22.200 | 23.060 | 22.348 | 22.200 to 22.235 | In range |
| CE110 | Humidity Ratio (kg/kg) | 0.006506 | 0.006400 | 0.007100 | 0.006700 | 0.006411 to 0.006519 | In range |
| CE110 | COP | 3.399 | 3.322 | 3.457 | 3.399 | 3.377 to 3.379 | In range |
| CE110 | IDB (°C) | 22.200 | 21.980 | 22.300 | 22.194 | 22.193 to 22.200 | In range |
| CE110 | Humidity Ratio (kg/kg) | 0.006506 | 0.006400 | 0.007000 | 0.006664 | 0.006411 to 0.006519 | In range |
| CE120 | Cooling Energy Consumption Total (kWh) | 1,008.0 | 1,001.7 | 1,012 | 1,007.6 | 1,011 to 1,012.7 | In range |
| CE120 | Compressor (kWh) | 836.88 | 831.93 | 850.07 | 839.31 | 839.10 to 840.87 | In range |
| CE120 | Supply Fan (kWh) | 116.45 | 109.58 | 117 | 114.59 | 116.90 to 116.91 | In range |
| CE120 | Condenser Fan (kWh) | 54.679 | 51.455 | 55 | 54.246 | 54.898 to 54.900 | In range |
| CE120 | Evaporator Coil Load Total (kWh) | 3,748.4 | 3,739.2 | 3,763.5 | 3,749.0 | 3,748.5 to 3,748.9 | In range |
| CE120 | Sensible (kWh) | 3,748.4 | 3,739.2 | 3,763.5 | 3,749.0 | 3,748.5 to 3,748.9 | In range |
| CE120 | Latent (kWh) | 3.73e-14 | 0 | 0.004229 | 6.04e-4 | 0 | In range |
| CE120 | Total (kWh) | 3,632.0 | 3,630.5 | 3,632 | 3,631.4 | 3,631.9 to 3,632.0 | In range |
| CE120 | Zone Load Sensible (kWh) | 3,632.0 | 3,630.5 | 3,632 | 3,631.4 | 3,631.9 to 3,632.0 | In range |
| CE120 | Latent (kWh) | 3.73e-14 | 0 | 0 | 0 | 0 | In range |
| CE120 | COP | 3.603 | 3.590 | 3.631 | 3.609 | 3.587 to 3.590 | In range |
| CE120 | IDB (°C) | 26.700 | 26.700 | 27.078 | 26.772 | 26.700 to 26.712 | In range |
| CE120 | Humidity Ratio (kg/kg) | 0.007952 | 0.007000 | 0.008040 | 0.007792 | 0.007860 to 0.007878 | In range |
| CE120 | COP | 3.606 | 3.590 | 3.654 | 3.614 | 3.587 to 3.594 | In range |
| CE120 | IDB (°C) | 26.700 | 26.700 | 28.260 | 26.940 | 26.700 to 26.735 | In range |
| CE120 | Humidity Ratio (kg/kg) | 0.007952 | 0.007000 | 0.008040 | 0.007792 | 0.007873 to 0.007878 | In range |
| CE120 | COP | 3.597 | 3.583 | 3.621 | 3.603 | 3.587 to 3.593 | In range |
| CE120 | IDB (°C) | 26.700 | 26.170 | 26.800 | 26.642 | 26.689 to 26.700 | In range |
| CE120 | Humidity Ratio (kg/kg) | 0.007952 | 0.007000 | 0.008036 | 0.007791 | 0.007873 to 0.007878 | In range |
| CE130 | Cooling Energy Consumption Total (kWh) | 109.55 | 105.42 | 110.12 | 108.27 | 109.50 to 110.58 | In range |
| CE130 | Compressor (kWh) | 94.378 | 93 | 95 | 93.949 | 94.300 to 95.287 | In range |
| CE130 | Supply Fan (kWh) | 10.326 | 8 | 10.389 | 9.603 | 10.300 to 10.408 | In range |
| CE130 | Condenser Fan (kWh) | 4.849 | 3.905 | 5 | 4.767 | 4.800 to 4.887 | In range |
| CE130 | Evaporator Coil Load Total (kWh) | 218.56 | 215.12 | 219.77 | 217.81 | 219.20 to 219.35 | In range |
| CE130 | Sensible (kWh) | 218.56 | 215.12 | 219.77 | 217.81 | 219.20 to 219.35 | In range |
| CE130 | Latent (kWh) | 5.12e-16 | 0 | 7.95e-4 | 1.14e-4 | 0 | In range |
| CE130 | Total (kWh) | 208.23 | 206.75 | 209.37 | 208.24 | 208.95 to 209 | In range |
| CE130 | Zone Load Sensible (kWh) | 208.23 | 206.75 | 209.37 | 208.24 | 208.95 to 209 | In range |
| CE130 | Latent (kWh) | 5.12e-16 | 0 | 0 | 0 | 0 | In range |
| CE130 | COP | 1.901 | 1.904 | 1.975 | 1.927 | 1.890 to 1.910 | Below range |
| CE130 | IDB (°C) | 22.200 | 21.638 | 22.200 | 22.093 | 22.187 to 22.200 | Above range |
| CE130 | Humidity Ratio (kg/kg) | 0.007412 | 0.006910 | 0.007600 | 0.007401 | 0.007339 to 0.007427 | In range |
| CE130 | COP | 1.903 | 1.907 | 2.003 | 1.944 | 1.890 to 1.908 | Below range |
| CE130 | IDB (°C) | 22.200 | 22.100 | 22.250 | 22.180 | 22.200 to 22.202 | In range |
| CE130 | Humidity Ratio (kg/kg) | 0.007412 | 0.006910 | 0.007600 | 0.007401 | 0.007339 to 0.007427 | In range |
| CE130 | COP | 1.895 | 1.674 | 1.956 | 1.879 | 1.890 to 1.908 | In range |
| CE130 | IDB (°C) | 22.200 | 21.030 | 22.200 | 22.006 | 22.172 to 22.200 | Above range |
| CE130 | Humidity Ratio (kg/kg) | 0.007412 | 0.006840 | 0.007600 | 0.007391 | 0.007339 to 0.007427 | In range |
| CE140 | Cooling Energy Consumption Total (kWh) | 68.388 | 65.008 | 69 | 67.474 | 68.300 to 68.995 | In range |
| CE140 | Compressor (kWh) | 56.401 | 54.799 | 57 | 56.203 | 56.400 to 56.924 | In range |
| CE140 | Supply Fan (kWh) | 8.157 | 6 | 8.213 | 7.624 | 8.100 to 8.214 | In range |
| CE140 | Condenser Fan (kWh) | 3.830 | 3.262 | 4 | 3.821 | 3.800 to 3.857 | In range |
| CE140 | Evaporator Coil Load Total (kWh) | 197.94 | 194.61 | 198.56 | 196.95 | 197.30 to 197.97 | In range |
| CE140 | Sensible (kWh) | 197.94 | 194.61 | 198.56 | 196.95 | 197.30 to 197.97 | In range |
| CE140 | Latent (kWh) | −8.34e-16 | −2.75e-16 | 6.78e-4 | 9.69e-5 | 0 | In range |
| CE140 | Total (kWh) | 189.79 | 188.18 | 190.36 | 189.29 | 189.70 to 189.75 | In range |
| CE140 | Zone Load Sensible (kWh) | 189.79 | 188.18 | 190.36 | 189.29 | 189.70 to 189.75 | In range |
| CE140 | Latent (kWh) | −8.34e-16 | 0 | 0 | 0 | 0 | In range |
| CE140 | COP | 2.775 | 2.734 | 2.915 | 2.806 | 2.750 to 2.770 | In range |
| CE140 | IDB (°C) | 22.200 | 21.510 | 22.200 | 22.074 | 22.185 to 22.200 | Above range |
| CE140 | Humidity Ratio (kg/kg) | 0.006512 | 0.006400 | 0.007060 | 0.006665 | 0.006400 to 0.006519 | In range |
| CE140 | COP | 2.778 | 2.770 | 2.928 | 2.839 | 2.750 to 2.770 | In range |
| CE140 | IDB (°C) | 22.200 | 22.100 | 22.250 | 22.180 | 22.200 to 22.202 | In range |
| CE140 | Humidity Ratio (kg/kg) | 0.006512 | 0.006400 | 0.007100 | 0.006671 | 0.006402 to 0.006519 | In range |
| CE140 | COP | 2.769 | 2.313 | 2.896 | 2.721 | 2.750 to 2.770 | In range |
| CE140 | IDB (°C) | 22.200 | 20.760 | 22.200 | 21.967 | 22.168 to 22.200 | Above range |
| CE140 | Humidity Ratio (kg/kg) | 0.006512 | 0.006400 | 0.007000 | 0.006644 | 0.006402 to 0.006519 | In range |
| CE150 | Cooling Energy Consumption Total (kWh) | 1,197.4 | 1,183 | 1,208 | 1,198.3 | 1,206.5 | In range |
| CE150 | Compressor (kWh) | 991.42 | 982 | 1,007.1 | 994.48 | 998.96 to 999.20 | In range |
| CE150 | Supply Fan (kWh) | 140.19 | 132.92 | 141 | 138.78 | 141.10 to 141.22 | In range |
| CE150 | Condenser Fan (kWh) | 65.829 | 62.413 | 66.149 | 65.170 | 66.200 to 66.312 | In range |
| CE150 | Evaporator Coil Load Total (kWh) | 4,510.2 | 4,508.7 | 4,542.8 | 4,520.7 | 4,517.4 to 4,518.3 | In range |
| CE150 | Sensible (kWh) | 3,771.0 | 3,775.8 | 3,803.6 | 3,782.2 | 3,778.2 to 3,779 | Below range |
| CE150 | Latent (kWh) | 739.20 | 732.70 | 741.50 | 738.54 | 739.20 to 739.40 | In range |
| CE150 | Total (kWh) | 4,376.3 | 4,374.7 | 4,376.1 | 4,375.6 | 4,376.3 | Above range |
| CE150 | Zone Load Sensible (kWh) | 3,637.1 | 3,635.6 | 3,637 | 3,636.4 | 3,637.1 | Above range |
| CE150 | Latent (kWh) | 739.20 | 739 | 739.45 | 739.18 | 739.20 | In range |
| CE150 | COP | 3.649 | 3.620 | 3.700 | 3.656 | 3.627 to 3.630 | In range |
| CE150 | IDB (°C) | 22.200 | 22.200 | 22.677 | 22.301 | 22.200 to 22.216 | In range |
| CE150 | Humidity Ratio (kg/kg) | 0.008362 | 0.008200 | 0.008530 | 0.008370 | 0.008200 to 0.008227 | In range |
| CE150 | COP | 3.653 | 3.630 | 3.709 | 3.666 | 3.627 to 3.630 | In range |
| CE150 | IDB (°C) | 22.200 | 22.200 | 23.280 | 22.388 | 22.200 to 22.235 | In range |
| CE150 | Humidity Ratio (kg/kg) | 0.008383 | 0.008200 | 0.008566 | 0.008395 | 0.008212 to 0.008227 | In range |
| CE150 | COP | 3.644 | 3.620 | 3.691 | 3.649 | 3.626 to 3.627 | In range |
| CE150 | IDB (°C) | 22.200 | 22.060 | 22.333 | 22.213 | 22.197 to 22.200 | In range |
| CE150 | Humidity Ratio (kg/kg) | 0.008290 | 0.008200 | 0.008530 | 0.008349 | 0.008209 to 0.008227 | In range |
| CE160 | Cooling Energy Consumption Total (kWh) | 1,134.3 | 1,107 | 1,140 | 1,132.1 | 1,138.9 to 1,140.4 | In range |
| CE160 | Compressor (kWh) | 945.73 | 926 | 962.67 | 946.50 | 949.10 to 950.41 | In range |
| CE160 | Supply Fan (kWh) | 128.30 | 119.05 | 129.11 | 126.25 | 129.20 to 129.31 | In range |
| CE160 | Condenser Fan (kWh) | 60.245 | 55.903 | 61 | 59.795 | 60.700 to 60.719 | In range |
| CE160 | Evaporator Coil Load Total (kWh) | 4,492.4 | 4,491.0 | 4,516.4 | 4,502.3 | 4,499.9 to 4,500.5 | In range |
| CE160 | Sensible (kWh) | 3,753.2 | 3,759.0 | 3,777.2 | 3,764.0 | 3,760.8 to 3,761.3 | Below range |
| CE160 | Latent (kWh) | 739.20 | 732.01 | 740 | 738.29 | 739.10 to 739.24 | In range |
| CE160 | Total (kWh) | 4,371.2 | 4,369.7 | 4,371.0 | 4,370.6 | 4,371.1 to 4,371.2 | Above range |
| CE160 | Zone Load Sensible (kWh) | 3,632.0 | 3,630.5 | 3,632 | 3,631.4 | 3,631.9 to 3,632.0 | In range |
| CE160 | Latent (kWh) | 739.20 | 739 | 739.45 | 739.18 | 739.20 | In range |
| CE160 | COP | 3.848 | 3.840 | 3.950 | 3.866 | 3.833 to 3.840 | In range |
| CE160 | IDB (°C) | 26.700 | 26.700 | 26.995 | 26.760 | 26.700 to 26.714 | In range |
| CE160 | Humidity Ratio (kg/kg) | 0.01020 | 0.009701 | 0.01028 | 0.01007 | 0.009940 to 0.009969 | In range |
| CE160 | COP | 3.851 | 3.840 | 3.957 | 3.872 | 3.833 to 3.838 | In range |
| CE160 | IDB (°C) | 26.700 | 26.700 | 27.610 | 26.848 | 26.700 to 26.735 | In range |
| CE160 | Humidity Ratio (kg/kg) | 0.01023 | 0.009800 | 0.01031 | 0.01011 | 0.009948 to 0.009969 | In range |
| CE160 | COP | 3.842 | 3.821 | 3.944 | 3.854 | 3.833 to 3.837 | In range |
| CE160 | IDB (°C) | 26.700 | 26.390 | 26.800 | 26.673 | 26.693 to 26.700 | In range |
| CE160 | Humidity Ratio (kg/kg) | 0.01011 | 0.009700 | 0.01018 | 0.01002 | 0.009944 to 0.009969 | In range |
| CE165 | Cooling Energy Consumption Total (kWh) | 1,493.4 | 1,470 | 1,502 | 1,493.3 | 1,497.8 to 1,499.7 | In range |
| CE165 | Compressor (kWh) | 1,275.1 | 1,256 | 1,291.2 | 1,277.3 | 1,278.7 to 1,280.2 | In range |
| CE165 | Supply Fan (kWh) | 148.56 | 141.68 | 150 | 147.36 | 149.10 to 149.30 | In range |
| CE165 | Condenser Fan (kWh) | 69.759 | 66.527 | 70.133 | 69.191 | 70.011 to 70.100 | In range |
| CE165 | Evaporator Coil Load Total (kWh) | 4,530.1 | 4,528.7 | 4,567.5 | 4,541.9 | 4,537.0 to 4,537.9 | In range |
| CE165 | Sensible (kWh) | 3,790.9 | 3,795.5 | 3,828.3 | 3,803.2 | 3,797.8 to 3,798.6 | Below range |
| CE165 | Latent (kWh) | 739.20 | 733.17 | 740.33 | 738.58 | 739.20 to 739.30 | In range |
| CE165 | Total (kWh) | 4,387.5 | 4,385.9 | 4,388 | 4,387.2 | 4,387.8 to 4,387.9 | In range |
| CE165 | Zone Load Sensible (kWh) | 3,648.3 | 3,646.7 | 3,649 | 3,648.0 | 3,648.6 to 3,648.7 | In range |
| CE165 | Latent (kWh) | 739.20 | 739 | 739.45 | 739.18 | 739.20 | In range |
| CE165 | COP | 2.934 | 2.920 | 2.985 | 2.941 | 2.930 | In range |
| CE165 | IDB (°C) | 23.304 | 23.300 | 23.780 | 23.404 | 23.300 to 23.317 | In range |
| CE165 | Humidity Ratio (kg/kg) | 0.009338 | 0.009004 | 0.009850 | 0.009366 | 0.009200 to 0.009269 | In range |
| CE165 | COP | 2.937 | 2.926 | 2.989 | 2.951 | 2.927 to 2.930 | In range |
| CE165 | IDB (°C) | 23.305 | 22.200 | 24.480 | 23.346 | 23.300 to 23.335 | In range |
| CE165 | Humidity Ratio (kg/kg) | 0.009363 | 0.009100 | 0.009850 | 0.009403 | 0.009210 to 0.009269 | In range |
| CE165 | COP | 2.928 | 2.910 | 2.981 | 2.935 | 2.926 to 2.930 | In range |
| CE165 | IDB (°C) | 23.304 | 22.200 | 23.444 | 23.172 | 23.299 to 23.300 | In range |
| CE165 | Humidity Ratio (kg/kg) | 0.009256 | 0.009000 | 0.009840 | 0.009339 | 0.009207 to 0.009269 | In range |
| CE170 | Cooling Energy Consumption Total (kWh) | 636.54 | 620 | 638 | 633.17 | 637.70 to 641.12 | In range |
| CE170 | Compressor (kWh) | 529.23 | 523 | 538.96 | 529.99 | 530 to 532.97 | In range |
| CE170 | Supply Fan (kWh) | 73.025 | 61.322 | 73.159 | 69.924 | 73.200 to 73.592 | In range |
| CE170 | Condenser Fan (kWh) | 34.290 | 28.795 | 34.353 | 33.236 | 34.400 to 34.556 | In range |
| CE170 | Evaporator Coil Load Total (kWh) | 2,226.4 | 2,224.9 | 2,236.5 | 2,230.8 | 2,231.9 to 2,232.5 | In range |
| CE170 | Sensible (kWh) | 1,487.2 | 1,486.9 | 1,497.7 | 1,492.4 | 1,492.7 to 1,493.1 | In range |
| CE170 | Latent (kWh) | 739.20 | 733.65 | 740 | 738.45 | 739.20 to 739.40 | In range |
| CE170 | Total (kWh) | 2,158.7 | 2,157.1 | 2,159 | 2,158.2 | 2,158.7 | In range |
| CE170 | Zone Load Sensible (kWh) | 1,419.5 | 1,417.9 | 1,420 | 1,419.1 | 1,419.5 | In range |
| CE170 | Latent (kWh) | 739.20 | 739 | 739.45 | 739.18 | 739.20 | In range |
| CE170 | COP | 3.383 | 3.380 | 3.477 | 3.412 | 3.367 to 3.390 | In range |
| CE170 | IDB (°C) | 22.200 | 22.117 | 22.222 | 22.191 | 22.199 to 22.200 | In range |
| CE170 | Humidity Ratio (kg/kg) | 0.01053 | 0.01047 | 0.01070 | 0.01055 | 0.01037 to 0.01045 | In range |
| CE170 | COP | 3.386 | 3.380 | 3.485 | 3.428 | 3.367 to 3.386 | In range |
| CE170 | IDB (°C) | 22.200 | 22.200 | 22.670 | 22.270 | 22.200 to 22.214 | In range |
| CE170 | Humidity Ratio (kg/kg) | 0.01056 | 0.01047 | 0.1060 | 0.02420 | 0.01037 to 0.01045 | In range |
| CE170 | COP | 3.377 | 3.317 | 3.471 | 3.393 | 3.367 to 3.385 | In range |
| CE170 | IDB (°C) | 22.200 | 21.570 | 22.222 | 22.113 | 22.185 to 22.200 | In range |
| CE170 | Humidity Ratio (kg/kg) | 0.01044 | 0.01040 | 0.1060 | 0.02413 | 0.01037 to 0.01045 | In range |
| CE180 | Cooling Energy Consumption Total (kWh) | 1,084.0 | 1,077.1 | 1,083 | 1,080.8 | 1,081.9 to 1,082.7 | Above range |
| CE180 | Compressor (kWh) | 910.38 | 906.44 | 914.26 | 909.47 | 907.70 to 908.12 | In range |
| CE180 | Supply Fan (kWh) | 118.14 | 110.81 | 119 | 116.40 | 118.50 to 118.77 | In range |
| CE180 | Condenser Fan (kWh) | 55.472 | 52.034 | 56 | 55.190 | 55.700 to 55.772 | In range |
| CE180 | Evaporator Coil Load Total (kWh) | 4,482.4 | 4,481.2 | 4,534.6 | 4,500.6 | 4,493.8 to 4,495.3 | In range |
| CE180 | Sensible (kWh) | 1,525.6 | 1,537 | 1,606.7 | 1,549.6 | 1,537.7 to 1,538.1 | Below range |
| CE180 | Latent (kWh) | 2,956.8 | 2,927.9 | 2,958 | 2,951.0 | 2,956.1 to 2,957.5 | In range |
| CE180 | Total (kWh) | 4,376.4 | 4,374.7 | 4,376.1 | 4,375.7 | 4,376.3 | Above range |
| CE180 | Zone Load Sensible (kWh) | 1,419.5 | 1,418.0 | 1,420 | 1,419.0 | 1,419.5 | In range |
| CE180 | Latent (kWh) | 2,956.8 | 2,956.8 | 2,957.5 | 2,957.0 | 2,956.8 | In range |
| CE180 | COP | 4.026 | 4.026 | 4.084 | 4.048 | 4.040 to 4.042 | In range |
| CE180 | IDB (°C) | 22.200 | 22.200 | 22.334 | 22.245 | 22.200 to 22.205 | In range |
| CE180 | Humidity Ratio (kg/kg) | 0.01619 | 0.01619 | 0.01661 | 0.01639 | 0.01619 to 0.01623 | Below range |
| CE180 | COP | 4.031 | 4.047 | 4.105 | 4.067 | 4.042 to 4.044 | Below range |
| CE180 | IDB (°C) | 22.200 | 22.200 | 22.790 | 22.310 | 22.200 to 22.214 | In range |
| CE180 | Humidity Ratio (kg/kg) | 0.01624 | 0.01622 | 0.01679 | 0.01649 | 0.01619 to 0.01624 | In range |
| CE180 | COP | 4.020 | 3.987 | 4.080 | 4.032 | 4.042 to 4.044 | In range |
| CE180 | IDB (°C) | 22.200 | 22.010 | 22.300 | 22.198 | 22.196 to 22.200 | In range |
| CE180 | Humidity Ratio (kg/kg) | 0.01607 | 0.01606 | 0.01650 | 0.01627 | 0.01619 to 0.01622 | In range |
| CE185 | Cooling Energy Consumption Total (kWh) | 1,541.2 | 1,538.4 | 1,547 | 1,542.2 | 1,542.9 to 1,544.6 | In range |
| CE185 | Compressor (kWh) | 1,337.2 | 1,334.4 | 1,344 | 1,339.5 | 1,338.2 to 1,339.8 | In range |
| CE185 | Supply Fan (kWh) | 138.82 | 135.06 | 139.24 | 138.18 | 139.30 to 139.40 | In range |
| CE185 | Condenser Fan (kWh) | 65.184 | 63.418 | 66 | 64.998 | 65.400 to 65.452 | In range |
| CE185 | Evaporator Coil Load Total (kWh) | 4,523.6 | 4,507 | 4,582.6 | 4,540.1 | 4,533.9 to 4,535.1 | In range |
| CE185 | Sensible (kWh) | 1,566.8 | 1,548 | 1,652.7 | 1,588.3 | 1,577.6 to 1,578.1 | In range |
| CE185 | Latent (kWh) | 2,956.8 | 2,930.0 | 2,959 | 2,951.8 | 2,956.2 to 2,957.5 | In range |
| CE185 | Total (kWh) | 4,394.8 | 4,393.3 | 4,396 | 4,394.9 | 4,395.5 | In range |
| CE185 | Zone Load Sensible (kWh) | 1,438.0 | 1,436.5 | 1,439 | 1,437.9 | 1,438.7 | In range |
| CE185 | Latent (kWh) | 2,956.8 | 2,956.8 | 2,957.5 | 2,957.0 | 2,956.8 | In range |
| CE185 | COP | 2.845 | 2.823 | 2.874 | 2.851 | 2.846 to 2.850 | In range |
| CE185 | IDB (°C) | 22.200 | 22.200 | 22.368 | 22.257 | 22.200 to 22.206 | In range |
| CE185 | Humidity Ratio (kg/kg) | 0.01607 | 0.01607 | 0.01710 | 0.01635 | 0.01605 to 0.01606 | In range |
| CE185 | COP | 2.849 | 2.844 | 2.903 | 2.864 | 2.846 to 2.849 | In range |
| CE185 | IDB (°C) | 22.200 | 22.200 | 22.610 | 22.292 | 22.200 to 22.214 | In range |
| CE185 | Humidity Ratio (kg/kg) | 0.01615 | 0.01610 | 0.01710 | 0.01643 | 0.01606 | In range |
| CE185 | COP | 2.838 | 2.805 | 2.871 | 2.837 | 2.846 to 2.848 | In range |
| CE185 | IDB (°C) | 22.200 | 22.130 | 22.333 | 22.223 | 22.198 to 22.200 | In range |
| CE185 | Humidity Ratio (kg/kg) | 0.01594 | 0.01592 | 0.01700 | 0.01624 | 0.01605 to 0.01606 | In range |
| CE190 | Cooling Energy Consumption Total (kWh) | 165.09 | 160 | 165.12 | 163.10 | 164.10 to 165.17 | In range |
| CE190 | Compressor (kWh) | 138.56 | 137.51 | 139.42 | 138.23 | 137.60 to 138.47 | In range |
| CE190 | Supply Fan (kWh) | 18.051 | 14 | 18.143 | 16.907 | 18 to 18.170 | In range |
| CE190 | Condenser Fan (kWh) | 8.476 | 6.645 | 9 | 8.105 | 8.500 to 8.532 | In range |
| CE190 | Evaporator Coil Load Total (kWh) | 575.88 | 572.61 | 578.55 | 576.47 | 577.30 to 577.70 | In range |
| CE190 | Sensible (kWh) | 206.28 | 203.01 | 212.19 | 207.60 | 207.70 to 207.90 | In range |
| CE190 | Latent (kWh) | 369.60 | 366.35 | 370 | 369.02 | 369.60 to 369.80 | In range |
| CE190 | Total (kWh) | 559.39 | 557 | 559.46 | 558.36 | 559.30 to 559.35 | In range |
| CE190 | Zone Load Sensible (kWh) | 189.79 | 188.18 | 190 | 189.22 | 189.70 to 189.75 | In range |
| CE190 | Latent (kWh) | 369.60 | 367 | 370 | 369.28 | 369.60 | In range |
| CE190 | COP | 3.379 | 3.394 | 3.486 | 3.425 | 3.386 to 3.410 | Below range |
| CE190 | IDB (°C) | 22.200 | 21.947 | 22.200 | 22.137 | 22.194 to 22.200 | Above range |
| CE190 | Humidity Ratio (kg/kg) | 0.01582 | 0.01571 | 0.01625 | 0.01596 | 0.01580 to 0.01590 | In range |
| CE190 | COP | 3.391 | 3.410 | 3.508 | 3.460 | 3.386 to 3.409 | Below range |
| CE190 | IDB (°C) | 22.200 | 22.100 | 22.250 | 22.180 | 22.200 to 22.202 | In range |
| CE190 | Humidity Ratio (kg/kg) | 0.01611 | 0.01591 | 0.01640 | 0.01605 | 0.01580 to 0.01590 | In range |
| CE190 | COP | 3.371 | 3.165 | 3.475 | 3.367 | 3.386 to 3.409 | In range |
| CE190 | IDB (°C) | 22.200 | 21.630 | 22.200 | 22.092 | 22.186 to 22.200 | Above range |
| CE190 | Humidity Ratio (kg/kg) | 0.01565 | 0.01546 | 0.01610 | 0.01587 | 0.01580 to 0.01588 | In range |
| CE195 | Cooling Energy Consumption Total (kWh) | 251.05 | 244.92 | 251.58 | 248.92 | 250 to 252.16 | In range |
| CE195 | Compressor (kWh) | 217.72 | 216.48 | 218.87 | 217.41 | 216.80 to 218.62 | In range |
| CE195 | Supply Fan (kWh) | 22.681 | 17.728 | 23 | 21.400 | 22.600 to 22.821 | In range |
| CE195 | Condenser Fan (kWh) | 10.650 | 8.324 | 11 | 10.441 | 10.600 to 10.716 | In range |
| CE195 | Evaporator Coil Load Total (kWh) | 599.18 | 595.24 | 602 | 599.99 | 601.20 to 601.37 | In range |
| CE195 | Sensible (kWh) | 229.56 | 225.64 | 235.05 | 231.05 | 231.60 to 231.64 | In range |
| CE195 | Latent (kWh) | 369.62 | 366.65 | 370 | 369.09 | 369.60 to 369.73 | In range |
| CE195 | Total (kWh) | 577.85 | 576 | 579 | 577.46 | 578.55 to 578.60 | In range |
| CE195 | Zone Load Sensible (kWh) | 208.23 | 206.75 | 209 | 208.18 | 208.95 to 209 | In range |
| CE195 | Latent (kWh) | 369.62 | 367 | 370 | 369.28 | 369.60 | In range |
| CE195 | COP | 2.296 | 2.303 | 2.360 | 2.320 | 2.294 to 2.310 | Below range |
| CE195 | IDB (°C) | 22.200 | 22.011 | 22.200 | 22.146 | 22.195 to 22.200 | Above range |
| CE195 | Humidity Ratio (kg/kg) | 0.01542 | 0.01533 | 0.01640 | 0.01564 | 0.01537 to 0.01544 | In range |
| CE195 | COP | 2.315 | 2.310 | 2.457 | 2.356 | 2.294 to 2.314 | In range |
| CE195 | IDB (°C) | 22.200 | 22.100 | 22.260 | 22.182 | 22.200 to 22.202 | In range |
| CE195 | Humidity Ratio (kg/kg) | 0.01591 | 0.01547 | 0.01650 | 0.01572 | 0.01537 to 0.01544 | In range |
| CE195 | COP | 2.287 | 2.250 | 2.350 | 2.299 | 2.294 to 2.314 | In range |
| CE195 | IDB (°C) | 22.200 | 21.760 | 22.200 | 22.110 | 22.188 to 22.200 | Above range |
| CE195 | Humidity Ratio (kg/kg) | 0.01524 | 0.01514 | 0.01640 | 0.01554 | 0.01537 to 0.01543 | In range |
| CE200 | Cooling Energy Consumption Total (kWh) | 1,467.5 | 1,440 | 1,480.0 | 1,467.7 | 1,475.8 to 1,477.4 | In range |
| CE200 | Compressor (kWh) | 1,242.1 | 1,218 | 1,252.9 | 1,243.6 | 1,248.8 to 1,250.2 | In range |
| CE200 | Supply Fan (kWh) | 153.34 | 149.15 | 154.56 | 152.80 | 154.46 to 154.60 | In range |
| CE200 | Condenser Fan (kWh) | 72.003 | 70.036 | 73 | 71.865 | 72.530 to 72.600 | In range |
| CE200 | Evaporator Coil Load Total (kWh) | 5,485.9 | 5,436 | 5,534.2 | 5,495.7 | 5,497.8 | In range |
| CE200 | Sensible (kWh) | 4,264.9 | 4,215 | 4,313.2 | 4,276.3 | 4,276.7 to 4,276.8 | In range |
| CE200 | Latent (kWh) | 1,221.0 | 1,210.2 | 1,222 | 1,219.4 | 1,221 to 1,221.1 | In range |
| CE200 | Total (kWh) | 5,343.1 | 5,283 | 5,343.0 | 5,334.0 | 5,343.2 to 5,343.3 | Above range |
| CE200 | Zone Load Sensible (kWh) | 4,122.0 | 4,062 | 4,122 | 4,112.9 | 4,122.2 | Above range |
| CE200 | Latent (kWh) | 1,221.0 | 1,221.0 | 1,221.3 | 1,221.0 | 1,221 to 1,221.0 | In range |
| CE200 | COP | 3.634 | 3.610 | 3.708 | 3.639 | 3.620 to 3.621 | In range |
| CE200 | IDB (°C) | 26.701 | 26.700 | 26.800 | 26.735 | 26.700 to 26.713 | In range |
| CE200 | Humidity Ratio (kg/kg) | 0.01139 | 0.01093 | 0.01150 | 0.01128 | 0.01109 to 0.01113 | In range |
| CE200 | COP | 3.638 | 3.610 | 3.717 | 3.646 | 3.617 to 3.621 | In range |
| CE200 | IDB (°C) | 26.701 | 26.700 | 26.800 | 26.735 | 26.700 to 26.713 | In range |
| CE200 | Humidity Ratio (kg/kg) | 0.01142 | 0.01100 | 0.01150 | 0.01131 | 0.01110 to 0.01113 | In range |
| CE200 | COP | 3.628 | 3.610 | 3.698 | 3.634 | 3.617 to 3.621 | In range |
| CE200 | IDB (°C) | 26.701 | 26.699 | 26.800 | 26.734 | 26.700 to 26.713 | In range |
| CE200 | Humidity Ratio (kg/kg) | 0.01129 | 0.01090 | 0.01150 | 0.01123 | 0.01110 to 0.01113 | In range |
Nothing in this suite fits the current filters.
Min, Max and Mean describe the example programs published with the standard. Analytical is the closed-form or quasi-analytical solution where the standard gives one.
Annex A3 of Standard 140-2023 sets criteria for thermal fabric, cooling, heating and air-side equipment only.
ASoftware information
1. SOFTWARE VENDOR:
Jared Bell, Roots Ontological Technologies, LLC
2. SOFTWARE NAME:
SIMsara
3. SOFTWARE VERSION (unique software version identifier):
SIMsara 0.1.0
4. OPERATING SYSTEM REQUIREMENTS:
macOS 13 or later on Apple silicon (arm64). This is the build that was
tested; other targets are listed only when they have been built and run
for these tests.
5. APPROX HARD DISK SPACE REQUIRED FOR INSTALLATION:
About 6.3 MB: the release binary s140_run, which needs no other runtime
files beyond the TOML input and the EPW weather file.
6. MINIMUM RAM REQUIRED FOR SOFTWARE OPERATION:
16 MB: the largest peak resident memory of any submitted test case,
measured with /usr/bin/time -l on the tested build.
7. MINIMUM DISPLAY MONITOR REQUIREMENTS:
None. SIMsara is a command-line program with no graphical display.
8. OTHER HARDWARE OR SOFTWARE-RELATED REQUIREMENTS:
Input is TOML (docs/TOML-INPUT.md in the source distribution) with EPW
weather. Building from source needs Rust 1.98.1. The Standard 140 harness
scripts that generate the test inputs and fill the output templates need
Python 3.11 or later, standard library only.BAlternative modeling methods
NOTE 1 - Unitary System Parent (Section 5.1.1.4 and 9.2.1.10)
---------------------------------------------------------
1.1 Describe the Effect Being Simulated:
How the DX coil and the indoor fan follow the zone load, and which loads
the program reports for the zone.
1.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
1.2.1 AirLoopHVAC:UnitaryHeatCool
Physical Meaning: Heat-cool unitary on an air loop: supply fan, DX
cooling coil and heating coil controlled to the load of one zone.
1.2.2 AirLoopHVAC:UnitarySystem
Physical Meaning: Generic unitary system with load or setpoint control
and multi-speed fans and coils.
1.2.3 ZoneHVAC:PackagedTerminalAirConditioner
Physical Meaning: Packaged terminal unit serving the zone directly,
without an air loop; it reports the cooling it delivers to the zone.
1.3 Setting or Capability Used:
AirLoopHVAC:UnitaryHeatCool on an air loop without outdoor air, the parent
of the CE b cases (CE300-CE545), so that all Section 9 cases use one
modeling method (5.1.1.4). Its heating coil is never available (heat off).
NOTE 2 - Cooling Coil Model (Section 9.2.1.10.3)
---------------------------------------------------------
2.1 Describe the Effect Being Simulated:
Total, sensible and latent capacity and compressor power of the unit at
each entering condition, and so every consumption, coil-load, COP and
humidity result.
2.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
2.2.1 Coil:Cooling:DX:SingleSpeed
Physical Meaning: Rated gross capacity, sensible heat ratio, COP and
flow with capacity and energy-input-ratio curves of entering wet bulb
and outdoor dry bulb; the sensible and latent split by the apparatus
dew point and bypass factor method, with a dry-coil branch when the
entering air is dry.
2.2.2 Other DX coil objects
Physical Meaning: Multi-speed, variable-speed and performance-table
coils (not used).
2.3 Setting or Capability Used:
Coil:Cooling:DX:SingleSpeed, with the bypass factor derived by the program
at the rated point and applied through the apparatus dew point method,
independent of the part-load ratio (9.2.1.10.3.3 lets a program that
calculates the bypass factor skip that input; 9.2.1.10.4.4).
NOTE 3 - Cycling Fan and Part-Load Degradation (Section 9.2.1.10.1 d and e, and
9.2.1.10.4)
---------------------------------------------------------
3.1 Describe the Effect Being Simulated:
Compressor and fan energy at part load.
3.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
3.2.1 Fan operating mode
Physical Meaning: Cycling with the compressor (operating-mode schedule
0) or continuous (1).
3.2.2 Part-load fraction curve
Physical Meaning: PLF(PLR) divides the runtime fraction; the indoor fan
runs for the same runtime fraction.
3.3 Setting or Capability Used:
Cycling fan; PLF = 1 - Cd (1 - PLR) with Cd 0.229, the COP degradation
factor of Figure 9-3, so the runtime fraction is PLR / PLF (9.2.1.10.4.2)
for the compressor, the outdoor fan and the indoor fan; PLR on the gross
basis of Equation 9-2.
NOTE 4 - Surface Convection and Time Step (Section 9.2.1.8, 9.2.1.9)
---------------------------------------------------------
4.1 Describe the Effect Being Simulated:
Heat gain through the R 100 envelope (a few percent of the load in the
low-load cases) and the resolution of the thermostat.
4.2 Optional Settings or Modeling Capabilities
(list setting or capability and its physical meaning):
4.2.1 Inside: Simple, TARP, CeilingDiffuser, Adaptive, ASTMC1340
Physical Meaning: Constant or correlation-based interior coefficients.
4.2.2 Outside: SimpleCombined, TARP, DOE-2, MoWiTT
Physical Meaning: A combined convection and radiation coefficient to
the outdoor air (SimpleCombined), or convection with explicit long-wave
exchange to sky and ground.
4.2.3 Zone time steps per hour
Physical Meaning: 1 to 60.
4.3 Setting or Capability Used:
TARP inside; SimpleCombined outside, the form of the specified combined
exterior coefficient (exchange with the outdoor air only); 6 zone steps per
hour, the unit cycling within each step through its part-load ratio.CEquivalent modeling methods
NOTE 1 - Split System Modeled as a Heat-Cool Unitary with Heat Always Off
(Section 9.2.1.10)
-------------------------------------------------------------------------------
1.1 Describe the Effect Being Simulated:
All results.
1.2 Section(s) of the Standard where Relevant Inputs are Specified:
A single-speed split air conditioner with an air-cooled condenser, a
draw-through indoor fan, indoor and outdoor fans cycling with the
compressor, no outdoor air, heat always off.
1.3 Equivalent Input(s) Used:
One air loop without outdoor air whose branch holds an
AirLoopHVAC:UnitaryHeatCool, controlled to the zone's load (the parent of
the CE b cases, Block B note 1): a Coil:Cooling:DX:SingleSpeed, then a
Coil:Heating:Electric that the unit object requires, with an availability
schedule of 0, then a draw-through Fan:OnOff of 230 W at the rated flow
(total and motor efficiency 1, so that the power is exactly the specified
230 W, all heat to the air as 9.2.1.10.6.1.2 specifies; the specified 0.5
efficiency and 271 Pa give 230.2 W at this flow) with an operating-mode
schedule of 0 (cycling); cooling, heating and no-load supply flows are the
rated flow and dehumidification control is none. A constant-volume terminal
without reheat delivers the air and the zone air returns to the unit. The
thermostat is ThermostatSetpoint:SingleCooling (non-proportional).
1.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
Same components, arrangement and control as the specified unit; the heating
coil never operates.
NOTE 2 - Performance Map Fitted to Curves (Section 9.2.1.10.3 (Tables 9-5 to
9-10; CE100MAP.xls))
-------------------------------------------------------------------------------
2.1 Describe the Effect Being Simulated:
Capacity and power at every operating point.
2.2 Section(s) of the Standard where Relevant Inputs are Specified:
Tables 9-5 to 9-10 in their electronic file CE100MAP.xls (Table 9-7, gross
capacities in SI units, is fitted) and the rated block.
2.3 Equivalent Input(s) Used:
The map's gross total capacity and compressor-plus-outdoor-fan power are
fitted to biquadratics in entering wet bulb and outdoor dry bulb,
normalized and anchored at the rated point (SIMsara's scripts/s140/fit.py,
standard least squares). Fit errors over the 24 wet-coil points: capacity
RMS 0.120 percent, maximum 0.214 percent; power RMS 0.232 percent, maximum
0.549 percent; the rated point exactly. Rated values from the map: gross
capacity 8181 W, gross SHR 0.778, coil COP 4.161 (compressor and outdoor
fan), flow 0.42475 m3/s. The flow-fraction curves are 1 (constant flow).
The curves are entered without clamping: the dry-coil cases evaluate them
at an entering wet bulb of 13.9 to 14.8 C, slightly below the 15.0 C lowest
map point, as 9.2.1.10.3.1 requires (the program extrapolates the
performance data).
2.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The curve form is the program's; the fit reproduces the map within the
stated errors.
NOTE 3 - Weather Data Converted from TMY2 (Section 9.2.1.1 and Annex A1.2.1
(Tables A1-4 and A1-6))
-------------------------------------------------------------------------------
3.1 Describe the Effect Being Simulated:
Outdoor dry bulb and humidity of every case.
3.2 Section(s) of the Standard where Relevant Inputs are Specified:
CE100A.TM2, CE110A.TM2, CE165A.TM2 and CE200A.TM2.
3.3 Equivalent Input(s) Used:
SIMsara reads EPW. SIMsara's converter (scripts/s140/wx/tm2.py) writes each
TM2 file as an EPW; the processed files are archived with their sha256. The
location line carries the site of Table A1-6: latitude 25.8 N, longitude
80.3 W, altitude 2 m, time zone 5 (75 W).
3.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
The dry bulb and humidity are carried over unchanged (plan WP1).
NOTE 4 - Compressor and Condenser Fan Split; Coil Loads from Rates (Section
9.3.1)
-------------------------------------------------------------------------------
4.1 Describe the Effect Being Simulated:
Reported compressor, condenser-fan and coil-load energies.
4.2 Section(s) of the Standard where Relevant Inputs are Specified:
February compressor and condenser-fan consumption and evaporator coil
loads.
4.3 Equivalent Input(s) Used:
The DX coil reports one electricity energy for compressor plus outdoor fan:
the condenser fan is 108 W times the coil runtime fraction times the time
step, and the compressor is the remainder. The DX coil reports its total,
sensible and latent cooling rates but no energies, so the coil loads are
the rates times the step length summed over February. The unit reports no
zone loads (9.3.1.3): the zone sensible load is the sensible cooling the
supply air delivers to the zone (the zone's air-system sensible cooling
rate), the zone latent load is the coil's latent cooling rate, since with
no outdoor air and no infiltration the coil removes all the moisture that
leaves the zone, and the zone total load is their sum, each times the step
length summed over February. COP is the net refrigeration effect over the
total cooling energy consumption (9.3.1.4 a): the evaporator coil total
load less the indoor fan energy, divided by compressor plus both fans
(Section 3); the February mean is the ratio of the February totals and the
maximum and minimum are hourly.
4.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
Exact for quantities held constant within each step; the COP definition
reproduces the COP columns of the analytical solutions from their own
energy columns.
NOTE 5 - Simulation Period (Section 5.1.1.8.3)
-------------------------------------------------------------------------------
5.1 Describe the Effect Being Simulated:
Initialization.
5.2 Section(s) of the Standard where Relevant Inputs are Specified:
At least the first two months; results for February.
5.3 Equivalent Input(s) Used:
Run January 1 to February 28 with warmup to convergence; February reported.
5.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s)
� provide supporting calculations, if relevant:
As specified.DUse of non-specified inputs
* Alternative constant exterior surface coefficients in Sections 7.2.1.9.3,
7.2.3.1.4.3, 7.2.3.3.2, and 9.2.1.8
* Alternative constant interior surface coefficients in Sections 7.2.1.10.3,
7.2.3.1.4.4, 7.2.3.2.2, and 9.2.1.9
* Alternative constant interior solar distribution fractions in Sections
7.2.1.12, 7.2.2.1.2.2, 7.2.2.1.6.2, 7.2.2.1.7.2, 7.2.2.2.7.4, 7.2.3.9.3,
7.2.3.10.2, and 7.2.3.12.2
* Air density given at specific altitudes for the space-cooling and space-
heating equipment cases in Sections 9.2.1.4.3, 9.2.3.4.3, and 10.2.1.4.3.
NOTE 1 - Air Density and Envelope Inputs (Section 9.2.1.4.3, 9.2.1.8, 9.2.1.9)
-------------------------------------------------------------------------------
1.1 Describe the Effect Being Simulated:
Fan mass flow and power; envelope heat gain.
1.2 Section(s) of the Standard where Relevant Inputs are Specified:
Air density at the site altitude; the constant combined surface
coefficients.
1.3 Nonspecified Input(s) Used:
The program converts the rated volume flow to mass flow with the density of
dry air at 20 C and the standard pressure of the site elevation, and uses
the state-dependent density elsewhere (9.2.1.4.3 lets a program that
calculates air density skip the 1.201 kg/m3). The combined surface
coefficients of 8.29 and 29.3 W/m2K are not entered (9.2.1.8 and 9.2.1.9
let a program that calculates surface radiation and convection skip them);
the envelope uses the algorithms of Block B, with the single R 100
insulation layer entered as two Material:NoMass layers of R 50 so that the
inner face carries solar absorptance 0.6 and the outer 0.1 (infrared
emittance 0.9 on both, Table 9-3), because the materials have no thermal
capacitance (9.2.1.4.2).
1.4 Physical, Mathematical or Logical Justification for Use of the
Nonspecified Input(s)
� provide supporting calculations, if relevant:
The insulation resistance dominates the overall U-value (0.010 W/m2K), so
the film coefficients change the envelope gain by well under 1 W.EOmitted test cases and resultsNone
NONE
FChanges to source codeNone
NONE
GAnomalous results
NOTE 1 - Coil Sensible Load of the Wet-Coil Cases (Section 9.3.1 (Annex B16,
Section B16.5.1; evaporator coil sensible load))
-------------------------------------------------------------------------------
1.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
CE150, CE160, CE165 and CE180 evaporator coil sensible load (0.12 to 0.74
percent below the example results); CE180 consumption (0.09 percent above)
and maximum COP (0.41 percent below).
1.2 Explanation of Reason for the Anomalous Results:
The sensible and latent split of a wet coil follows the apparatus dew point
and bypass factor method with the bypass factor derived at the rated point,
so the split at other entering conditions differs slightly from the map's
own sensible capacities; CE180 has the lowest sensible heat ratio. The coil
total and latent loads lie within 0.3 percent of the analytical solutions.
NOTE 2 - Low Part-Load COP and Results at the Edge of the Example Range
(Section 9.3.1 (Annex B16, Section B16.5.1))
-------------------------------------------------------------------------------
2.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous:
CE130, CE190 and CE195 mean and maximum COP (0.16 to 0.54 percent below the
example results, inside or within 0.23 percent of the analytical range);
zone sensible and total loads of CE110, CE150, CE160, CE180 and CE200
(0.001 to 0.005 percent above); mean and minimum IDB of CE130, CE140, CE190
and CE195 (22.2000 to 22.2002 C, against a setpoint of 22.2 C); CE180 mean
humidity ratio (0.023 percent below).
2.2 Explanation of Reason for the Anomalous Results:
At part-load ratios below 0.1 the COP depends on the degradation curve and
on how the indoor fan's runtime is counted; SIMsara runs both fans for the
runtime fraction PLR / PLF. The other items are within 0.005 percent of the
range and within 0.005 percent of the analytical solutions; the zone
temperature overshoots the setpoint by less than 0.001 K within the
ten-minute step.Rendered from S140outNotes-SIMsara-CE_a.txt, the modeler report in the form Standard 140 prescribes. The template's own instructions are left out here.
The filled output template and the results workbook are the official record. They hold ASHRAE's licensed template content and are not published here.