Section 11 · Air-side equipment
Case AE245
- Values compared
- 47
- Outside example range
- 9
- Run time
- 0.07 s
- Input file
- AE245.toml, 31.5 kB
Against the example programs
Each reported quantity next to the spread of the simulation programs published with the standard.
Position in the example range
Example rangeSIMsara
Sensible Cooling Load (QZClatent) (kWh/h)AE SZ coil and zone loads
1.4641.564
In rangeSensible Cooling Load (QZClatent) (kWh/h), AE SZ coil and zone loads: SIMsara 1.465 · range 1.464 to 1.564
Latent Load (QZlatent) (kWh/h)AE SZ coil and zone loads
0.58610.5897
In rangeLatent Load (QZlatent) (kWh/h), AE SZ coil and zone loads: SIMsara 0.5861 · range 0.5861 to 0.5897
Loads Sensible (QCsensible) (kWh/h)AE SZ coil and zone loads
2.1712.216
In rangeLoads Sensible (QCsensible) (kWh/h), AE SZ coil and zone loads: SIMsara 2.204 · range 2.171 to 2.216
Latent (QClatent) (kWh/h)AE SZ coil and zone loads
00.03061
In rangeLatent (QClatent) (kWh/h), AE SZ coil and zone loads: SIMsara 0 · range 0 to 0.03061
Total (QCtotal) (kWh/h)AE SZ coil and zone loads
2.1882.216
In rangeTotal (QCtotal) (kWh/h), AE SZ coil and zone loads: SIMsara 2.204 · range 2.188 to 2.216
Outlet RH (RHcco) (%)AE SZ coil and zone loads
33.83934.330
In rangeOutlet RH (RHcco) (%), AE SZ coil and zone loads: SIMsara 34.016 · range 33.839 to 34.330
DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa)AE SZ node states
24.88924.900
In rangeDRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa), AE SZ node states: SIMsara 24.900 · range 24.889 to 24.900
DRY BULB TEMPERATURE (°C) · Mixed Air (ma)AE SZ node states
24.88924.900
In rangeDRY BULB TEMPERATURE (°C) · Mixed Air (ma), AE SZ node states: SIMsara 24.900 · range 24.889 to 24.900
DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco)AE SZ node states
24.88924.900
In rangeDRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco), AE SZ node states: SIMsara 24.900 · range 24.889 to 24.900
DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco)AE SZ node states
18.44418.519
In rangeDRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco), AE SZ node states: SIMsara 18.500 · range 18.444 to 18.519
DRY BULB TEMPERATURE (°C) · Supply Air (sa)AE SZ node states
19.05319.101
In rangeDRY BULB TEMPERATURE (°C) · Supply Air (sa), AE SZ node states: SIMsara 19.085 · range 19.053 to 19.101
DRY BULB TEMPERATURE (°C) · Zone Air (z1)AE SZ node states
23.32323.348
In rangeDRY BULB TEMPERATURE (°C) · Zone Air (z1), AE SZ node states: SIMsara 23.333 · range 23.323 to 23.348
DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi)AE SZ node states
23.32323.348
In rangeDRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi), AE SZ node states: SIMsara 23.333 · range 23.323 to 23.348
DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo)AE SZ node states
23.62123.667
In rangeDRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo), AE SZ node states: SIMsara 23.646 · range 23.621 to 23.667
HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa)AE SZ node states
0.0044570.004510
In rangeHUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa), AE SZ node states: SIMsara 0.004481 · range 0.004457 to 0.004510
HUMIDITY RATIO (G/GDA) · Mixed Air (ma)AE SZ node states
0.0044570.004510
In rangeHUMIDITY RATIO (G/GDA) · Mixed Air (ma), AE SZ node states: SIMsara 0.004481 · range 0.004457 to 0.004510
HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco)AE SZ node states
0.0044570.004510
In rangeHUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco), AE SZ node states: SIMsara 0.004481 · range 0.004457 to 0.004510
HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco)AE SZ node states
0.0044570.004510
In rangeHUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco), AE SZ node states: SIMsara 0.004481 · range 0.004457 to 0.004510
HUMIDITY RATIO (G/GDA) · Supply Air (sa)AE SZ node states
0.0044570.004510
In rangeHUMIDITY RATIO (G/GDA) · Supply Air (sa), AE SZ node states: SIMsara 0.004481 · range 0.004457 to 0.004510
HUMIDITY RATIO (G/GDA) · Zone Air (z1)AE SZ node states
0.0051340.005212
In rangeHUMIDITY RATIO (G/GDA) · Zone Air (z1), AE SZ node states: SIMsara 0.005159 · range 0.005134 to 0.005212
HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi)AE SZ node states
0.0051340.005212
In rangeHUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi), AE SZ node states: SIMsara 0.005159 · range 0.005134 to 0.005212
HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo)AE SZ node states
0.0051340.005212
In rangeHUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo), AE SZ node states: SIMsara 0.005159 · range 0.005134 to 0.005212
SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa)AE SZ node states
830.35850.44
Above rangeSPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa), AE SZ node states: SIMsara 851.19 · range 830.35 to 850.44
SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma)AE SZ node states
830.35850.44
Above rangeSPECIFIC VOLUME (L/KGDA) · Mixed Air (ma), AE SZ node states: SIMsara 851.19 · range 830.35 to 850.44
| Table | Quantity | SIMsara | Min | Max | Mean | Analytical | Status |
|---|---|---|---|---|---|---|---|
| AE SZ coil and zone loads | Sensible Heating Load (QZHsensible) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE SZ coil and zone loads | Sensible Cooling Load (QZClatent) (kWh/h) | 1.465 | 1.464 | 1.564 | 1.479 | 1.465 | In range |
| AE SZ coil and zone loads | Latent Load (QZlatent) (kWh/h) | 0.5861 | 0.5861 | 0.5897 | 0.5866 | 0.5861 | In range |
| AE SZ coil and zone loads | Coil Load (QH) (kWh/h) | 0 | 0 | 0 | 0 | 0 | In range |
| AE SZ coil and zone loads | Loads Sensible (QCsensible) (kWh/h) | 2.204 | 2.171 | 2.216 | 2.200 | 2.208 | In range |
| AE SZ coil and zone loads | Latent (QClatent) (kWh/h) | 0 | 0 | 0.03061 | 0.004374 | 0 | In range |
| AE SZ coil and zone loads | Total (QCtotal) (kWh/h) | 2.204 | 2.188 | 2.216 | 2.205 | 2.208 | In range |
| AE SZ coil and zone loads | Outlet RH (RHcco) (%) | 34.016 | 33.839 | 34.330 | 34.097 | 34.091 | In range |
| AE SZ node states | DRY BULB TEMPERATURE (°C) · Location Outdoor Air (oa) | 24.900 | 24.889 | 24.900 | 24.897 | 24.900 | In range |
| AE SZ node states | DRY BULB TEMPERATURE (°C) · Mixed Air (ma) | 24.900 | 24.889 | 24.900 | 24.897 | 24.900 | In range |
| AE SZ node states | DRY BULB TEMPERATURE (°C) · Heat Coil Outlet (hco) | 24.900 | 24.889 | 24.900 | 24.897 | 24.900 | In range |
| AE SZ node states | DRY BULB TEMPERATURE (°C) · Cool Coil Outlet (cco) | 18.500 | 18.444 | 18.519 | 18.493 | 18.504 | In range |
| AE SZ node states | DRY BULB TEMPERATURE (°C) · Supply Air (sa) | 19.085 | 19.053 | 19.101 | 19.087 | 19.088 | In range |
| AE SZ node states | DRY BULB TEMPERATURE (°C) · Zone Air (z1) | 23.333 | 23.323 | 23.348 | 23.333 | 23.333 | In range |
| AE SZ node states | DRY BULB TEMPERATURE (°C) · Return Fan Inlet (rfi) | 23.333 | 23.323 | 23.348 | 23.333 | 23.333 | In range |
| AE SZ node states | DRY BULB TEMPERATURE (°C) · Return Fan Outlet (rfo) | 23.646 | 23.621 | 23.667 | 23.635 | 23.646 | In range |
| AE SZ node states | HUMIDITY RATIO (G/GDA) · Location Outdoor Air (oa) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE SZ node states | HUMIDITY RATIO (G/GDA) · Mixed Air (ma) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE SZ node states | HUMIDITY RATIO (G/GDA) · Heat Coil Outlet (hco) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE SZ node states | HUMIDITY RATIO (G/GDA) · Cool Coil Outlet (cco) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE SZ node states | HUMIDITY RATIO (G/GDA) · Supply Air (sa) | 0.004481 | 0.004457 | 0.004510 | 0.004491 | 0.004491 | In range |
| AE SZ node states | HUMIDITY RATIO (G/GDA) · Zone Air (z1) | 0.005159 | 0.005134 | 0.005212 | 0.005177 | 0.005168 | In range |
| AE SZ node states | HUMIDITY RATIO (G/GDA) · Return Fan Inlet (rfi) | 0.005159 | 0.005134 | 0.005212 | 0.005177 | 0.005168 | In range |
| AE SZ node states | HUMIDITY RATIO (G/GDA) · Return Fan Outlet (rfo) | 0.005159 | 0.005134 | 0.005212 | 0.005177 | 0.005168 | In range |
| AE SZ node states | SPECIFIC VOLUME (L/KGDA) · Location Outdoor Air (oa) | 851.19 | 830.35 | 850.44 | 839.47 | 850.43 | Above range |
| AE SZ node states | SPECIFIC VOLUME (L/KGDA) · Mixed Air (ma) | 851.19 | 830.35 | 850.44 | 839.47 | 850.43 | Above range |
| AE SZ node states | SPECIFIC VOLUME (L/KGDA) · Heat Coil Outlet (hco) | 851.19 | 830.35 | 850.44 | 839.47 | 850.43 | Above range |
| AE SZ node states | SPECIFIC VOLUME (L/KGDA) · Cool Coil Outlet (cco) | 832.92 | 830.35 | 833.33 | 832.18 | 832.18 | In range |
| AE SZ node states | SPECIFIC VOLUME (L/KGDA) · Supply Air (sa) | 834.59 | 829.76 | 833.70 | 832.03 | 833.85 | Above range |
| AE SZ node states | SPECIFIC VOLUME (L/KGDA) · Zone Air (z1) | 847.63 | 830.35 | 846.85 | 838.05 | 846.88 | Above range |
| AE SZ node states | SPECIFIC VOLUME (L/KGDA) · Return Fan Inlet (rfi) | 847.63 | 830.35 | 846.85 | 838.05 | 846.88 | Above range |
| AE SZ node states | SPECIFIC VOLUME (L/KGDA) · Return Fan Outlet (rfo) | 848.52 | 830.35 | 847.57 | 837.96 | 847.77 | Above range |
| AE SZ node states | ENTHALPY (J/GDA) · Location Outdoor Air (oa) | 36.435 | 36.435 | 36.510 | 36.477 | 36.491 | In range |
| AE SZ node states | ENTHALPY (J/GDA) · Mixed Air (ma) | 36.435 | 36.435 | 36.510 | 36.477 | 36.491 | In range |
| AE SZ node states | ENTHALPY (J/GDA) · Heat Coil Outlet (hco) | 36.435 | 36.435 | 36.510 | 36.477 | 36.491 | In range |
| AE SZ node states | ENTHALPY (J/GDA) · Cool Coil Outlet (cco) | 29.951 | 29.962 | 29.997 | 29.983 | 30.003 | Below range |
| AE SZ node states | ENTHALPY (J/GDA) · Supply Air (sa) | 30.543 | 30.553 | 30.589 | 30.578 | 30.596 | Below range |
| AE SZ node states | ENTHALPY (J/GDA) · Zone Air (z1) | 36.571 | 36.562 | 36.700 | 36.620 | 36.624 | In range |
| AE SZ node states | ENTHALPY (J/GDA) · Return Fan Inlet (rfi) | 36.571 | 36.562 | 36.700 | 36.620 | 36.624 | In range |
| AE SZ node states | ENTHALPY (J/GDA) · Return Fan Outlet (rfo) | 36.889 | 36.700 | 36.934 | 36.848 | 36.942 | In range |
| AE SZ node states | MASS FLOW RATE (KGDA/S) · Location Outdoor Air (oa) | 0.3400 | 0.3331 | 0.3410 | 0.3392 | 0.3403 | In range |
| AE SZ node states | MASS FLOW RATE (KGDA/S) · Mixed Air (ma) | 0.3400 | 0.3331 | 0.3410 | 0.3392 | 0.3403 | In range |
| AE SZ node states | MASS FLOW RATE (KGDA/S) · Heat Coil Outlet (hco) | 0.3400 | 0.3331 | 0.3410 | 0.3392 | 0.3403 | In range |
| AE SZ node states | MASS FLOW RATE (KGDA/S) · Cool Coil Outlet (cco) | 0.3400 | 0.3331 | 0.3410 | 0.3392 | 0.3403 | In range |
| AE SZ node states | MASS FLOW RATE (KGDA/S) · Supply Air (sa) | 0.3400 | 0.3331 | 0.3410 | 0.3392 | 0.3403 | In range |
| AE SZ node states | MASS FLOW RATE (KGDA/S) · Zone Air (z1) | n/a* | |||||
| AE SZ node states | MASS FLOW RATE (KGDA/S) · Return Fan Inlet (rfi) | 0.2286 | 0.2221 | 0.2289 | 0.2267 | 0.2288 | In range |
| AE SZ node states | MASS FLOW RATE (KGDA/S) · Return Fan Outlet (rfo) | 0.2286 | 0.2221 | 0.2289 | 0.2267 | 0.2288 | In range |
Reported outputs
The values the engine wrote for this case, before they are placed in the output template.
| Output | Value |
|---|---|
| Loads (kWh/h) · qZHsensible | 0 |
| Loads (kWh/h) · qZCsensible | 1.465 |
| Loads (kWh/h) · qZlatent | 0.5861 |
| Loads (kWh/h) · qH | 0 |
| Loads (kWh/h) · qCsensible | 2.204 |
| Loads (kWh/h) · qClatent | 0 |
| Loads (kWh/h) · qCtotal | 2.204 |
| Loads (kWh/h) · rHcco | 34.016 |
| Nodes · oa · tdb (°C) | 24.900 |
| Nodes · oa · w (g/g) | 0.004481 |
| Nodes · oa · v (L/kg) | 851.19 |
| Nodes · oa · h (J/g) | 36.435 |
| Nodes · oa · m (kg/s) | 0.3400 |
| Nodes · oa · rh (%) | 23.000 |
| Nodes · ma · tdb (°C) | 24.900 |
| Nodes · ma · w (g/g) | 0.004481 |
| Nodes · ma · v (L/kg) | 851.19 |
| Nodes · ma · h (J/g) | 36.435 |
| Nodes · ma · m (kg/s) | 0.3400 |
| Nodes · ma · rh (%) | 23.000 |
| Nodes · hco · tdb (°C) | 24.900 |
| Nodes · hco · w (g/g) | 0.004481 |
| Nodes · hco · v (L/kg) | 851.19 |
| Nodes · hco · h (J/g) | 36.435 |
| Nodes · hco · m (kg/s) | 0.3400 |
| Nodes · hco · rh (%) | 23.000 |
| Nodes · cco · tdb (°C) | 18.500 |
| Nodes · cco · w (g/g) | 0.004481 |
| Nodes · cco · v (L/kg) | 832.92 |
| Nodes · cco · h (J/g) | 29.951 |
| Nodes · cco · m (kg/s) | 0.3400 |
| Nodes · cco · rh (%) | 34.016 |
| Nodes · sa · tdb (°C) | 19.085 |
| Nodes · sa · w (g/g) | 0.004481 |
| Nodes · sa · v (L/kg) | 834.59 |
| Nodes · sa · h (J/g) | 30.543 |
| Nodes · sa · m (kg/s) | 0.3400 |
| Nodes · sa · rh (%) | 32.794 |
| Nodes · z1 · tdb (°C) | 23.333 |
| Nodes · z1 · w (g/g) | 0.005159 |
| Nodes · z1 · v (L/kg) | 847.63 |
| Nodes · z1 · h (J/g) | 36.571 |
| Nodes · z1 · rh (%) | 29.057 |
| Nodes · rfi · tdb (°C) | 23.333 |
| Nodes · rfi · w (g/g) | 0.005159 |
| Nodes · rfi · v (L/kg) | 847.63 |
| Nodes · rfi · h (J/g) | 36.571 |
| Nodes · rfi · m (kg/s) | 0.2286 |
| Nodes · rfi · rh (%) | 29.057 |
| Nodes · rfo · tdb (°C) | 23.646 |
| Nodes · rfo · w (g/g) | 0.005159 |
| Nodes · rfo · v (L/kg) | 848.52 |
| Nodes · rfo · h (J/g) | 36.889 |
| Nodes · rfo · m (kg/s) | 0.2286 |
| Nodes · rfo · rh (%) | 28.514 |
| Pressure pa | 101,300 |
| Fans · supply (W) | 201.46 |
| Fans · return (W) | 72.631 |
| Fans · exhaust (kg/s) | 0.1114 |
| Fan power (W) | 201.46 |
| Zone tdb (°C) | 23.333 |
| Economizer status | 1.000 |
| Oa fraction | 1.000 |
| Program outputs · cooling coil total (W) | 2,204.4 |
| Program outputs · cooling coil sensible (W) | 2,204.4 |
| Program outputs · heating coil (W) | 0 |
| Program outputs · condensate · kg (s) | 0 |
| Program outputs · condensate · temp (°C) | 18.500 |
| Program outputs · condensate · h j kg | 77,331.1 |
| Program outputs · condensate · w | 0 |
| Program outputs · condensate · entering dew point (°C) | 2.365 |
| Program outputs · condensate · sensible (W) | 0 |
| Balance · residual (W) · return fan | −5.97e-13 |
| Balance · residual (W) · mixer | 0 |
| Balance · residual (W) · heating coil | 0 |
| Balance · residual (W) · cooling coil | 4.55e-13 |
| Balance · residual (W) · supply fan | 1.05e-12 |
| Balance · residual (W) · zone | 1.819 |
| Balance · residual (W) · system | 1.819 |
| Balance · relative · return fan | 2.71e-16 |
| Balance · relative · mixer | 0 |
| Balance · relative · heating coil | 0 |
| Balance · relative · cooling coil | 2.06e-16 |
| Balance · relative · supply fan | 4.77e-16 |
| Balance · relative · zone | 8.25e-4 |
| Balance · relative · system | 8.25e-4 |
| Balance · max relative | 8.25e-4 |
| Balance · reference (W) | 2,204.4 |
| Cycling · steps | 6 |
| Flows · supply std (m³/s) | 0.2823 |
| Flows · exhaust std (m³/s) | 0.09247 |
| Flows · oa std (m³/s) | 0.09247 |
| Flows · supply fan dp pa | 499.54 |
| Flows · return fan max std (m³/s) | 0.2823 |
| Flows · return fan dp pa | 592.28 |
| Flows · setpoint offset k | 0.004010 |
| Flow iterations | 4 |
| Flow record · converged | true |
| Flow record · iterations | 4 |
| Flow record · relative change | 2.39e-8 |
| Flow record · zone tdb error k | 2.69e-9 |
| Econo min · case | AE245 |
| Econo min · odb econo min (°C) | 7.901 |
| Econo min · iterations | 8 |
| Econo min · outer iterations | 1 |
| Econo min · m supply (kg/s) | 0.3392 |
| Econo min · m oa (kg/s) | 0.1111 |
| Econo min · m return (kg/s) | 0.2281 |
| Econo min · supply fan (W) | 201.46 |
| Econo min · return fan (W) | 72.629 |
| Econo min · oa w case | 0.004492 |
| Econo min · oa (W) | 0.004492 |
| Econo min · outdoor saturated | false |
| Econo min · w over saturation · supply | 0.4244 |
| Econo min · w over saturation · mixed | 0.4406 |
| Econo min · w over saturation · zone | 0.3623 |
| Econo min · w over saturation · return fan outlet | 0.3554 |
| Econo min · w over saturation · outdoor | 0.6794 |
| Econo min · physical | true |
| Econo min · inputs · pressure pa | 101,300 |
| Econo min · inputs · setpoint (°C) | 23.333 |
| Econo min · inputs · zone sensible (W) | 1,465 |
| Econo min · inputs · zone latent (W) | 586.10 |
| Econo min · inputs · oa (W) | 0.004492 |
| Econo min · inputs · supply (m³/s) | 0.2832 |
| Econo min · inputs · exhaust (m³/s) | 0.09439 |
| Econo min · inputs · supply fan pa | 498 |
| Econo min · inputs · supply fan eff | 0.7000 |
| Econo min · arithmetic | m_w = 586.1 / hg(23.333) = 0.000230356708 kg/s; m_sup = 0.339209852, m_oa = 0.111108454, m_ret = 0.228101398 kg/s (8 iterations); w_oa = min(0.00449224554, w_sat(7.9007983 C) = 0.00661242384) = 0.00449224554 (1 outer iterations); w_zone = 0.0065655055, w_supply = 0.00588640757; T_supply = 23.333 - 1465.0 / (0.339209852 x 1017.04495) = 19.0865206 C; supply fan 201.455229 W, return fan 72.6289604 W; h_oa = (0.339209852 x 33515.4109 - 0.228101398 x 40469.0515) / 0.111108454 = 19239.8532 J/kg; ODBecono,min = 7.9007983 C |
Input file
sha256 398b3c095b79c13ab71a13ad982e286f0a492e2cd9e5a3adb1fd8adaa52ff7c7
[version] version_identifier = "26.1" [simulation-control] do_zone_sizing_calculation = "No" do_system_sizing_calculation = "No" do_plant_sizing_calculation = "No" run_simulation_for_sizing_periods = "No" run_simulation_for_weather_file_run_periods = "Yes" do_hvac_sizing_simulation_for_sizing_periods = "No" maximum_number_of_hvac_sizing_simulation_passes = 1 [building."ASHRAE 140 AE245"] north_axis = 0.0 terrain = "Suburbs" loads_convergence_tolerance_value = 0.04 temperature_convergence_tolerance_value = 0.4 solar_distribution = "FullExterior" maximum_number_of_warmup_days = 25 minimum_number_of_warmup_days = 6 [building.surface.detailed."South Wall"] surface_type = "Wall" construction_name = "Adiabatic Panel" zone_name = "Zone One" outside_boundary_condition = "Adiabatic" sun_exposure = "NoSun" wind_exposure = "NoWind" view_factor_to_ground = 0.0 number_of_vertices = 4 vertices = [ { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 }, ] [building.surface.detailed."East Wall"] surface_type = "Wall" construction_name = "Adiabatic Panel" zone_name = "Zone One" outside_boundary_condition = "Adiabatic" sun_exposure = "NoSun" wind_exposure = "NoWind" view_factor_to_ground = 0.0 number_of_vertices = 4 vertices = [ { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 }, { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 }, ] [building.surface.detailed."North Wall"] surface_type = "Wall" construction_name = "Adiabatic Panel" zone_name = "Zone One" outside_boundary_condition = "Adiabatic" sun_exposure = "NoSun" wind_exposure = "NoWind" view_factor_to_ground = 0.0 number_of_vertices = 4 vertices = [ { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 }, { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 }, ] [building.surface.detailed."West Wall"] surface_type = "Wall" construction_name = "Adiabatic Panel" zone_name = "Zone One" outside_boundary_condition = "Adiabatic" sun_exposure = "NoSun" wind_exposure = "NoWind" view_factor_to_ground = 0.0 number_of_vertices = 4 vertices = [ { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 }, ] [building.surface.detailed."Floor"] surface_type = "Floor" construction_name = "Adiabatic Panel" zone_name = "Zone One" outside_boundary_condition = "Adiabatic" sun_exposure = "NoSun" wind_exposure = "NoWind" view_factor_to_ground = 0.0 number_of_vertices = 4 vertices = [ { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 0.0 }, ] [building.surface.detailed."Roof"] surface_type = "Roof" construction_name = "Adiabatic Panel" zone_name = "Zone One" outside_boundary_condition = "Adiabatic" sun_exposure = "NoSun" wind_exposure = "NoWind" view_factor_to_ground = 0.0 number_of_vertices = 4 vertices = [ { vertex_x_coordinate = 0.0, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 }, { vertex_x_coordinate = 7.5, vertex_y_coordinate = 0.0, vertex_z_coordinate = 2.9 }, { vertex_x_coordinate = 7.5, vertex_y_coordinate = 5.5, vertex_z_coordinate = 2.9 }, ] [timestep] number_of_timesteps_per_hour = 6 [heat-balance-algorithm] algorithm = "ConductionTransferFunction" surface_temperature_upper_limit = 200.0 [surface.convection.algorithm.inside] algorithm = "TARP" [surface.convection.algorithm.outside] algorithm = "DOE-2" [global-geometry-rules] starting_vertex_position = "UpperLeftCorner" vertex_entry_direction = "Counterclockwise" coordinate_system = "Relative" [site.location."AE artificial site"] latitude = 25.8 longitude = -80.3 time_zone = -5.0 elevation = 0.0 [schedule-type-limits."Any Number"] [schedule-type-limits."Fraction"] lower_limit_value = 0.0 upper_limit_value = 1.0 numeric_type = "Continuous" [schedule-type-limits."Temperature"] lower_limit_value = -60.0 upper_limit_value = 200.0 numeric_type = "Continuous" unit_type = "Temperature" [schedule-type-limits."Control Type"] lower_limit_value = 0.0 upper_limit_value = 4.0 numeric_type = "Discrete" [schedule.compact."Always On"] schedule_type_limits_name = "Fraction" data = [ { field = "Through: 12/31" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 1.0 }, ] [schedule.compact."Heating Setpoint"] schedule_type_limits_name = "Temperature" data = [ { field = "Through: 12/31" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 18.337009633805454 }, ] [schedule.compact."Cooling Setpoint"] schedule_type_limits_name = "Temperature" data = [ { field = "Through: 12/31" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 23.337009633805454 }, ] [schedule.compact."Dual Setpoint Control"] schedule_type_limits_name = "Control Type" data = [ { field = "Through: 12/31" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 4 }, ] [schedule.compact."CHW Setpoint"] schedule_type_limits_name = "Temperature" data = [ { field = "Through: 12/31" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 6.67 }, ] [material."Gypsum Board 13mm"] roughness = "Smooth" thickness = 0.0127 conductivity = 0.16 density = 800.0 specific_heat = 1090.0 thermal_absorptance = 0.9 solar_absorptance = 0.5 visible_absorptance = 0.5 [construction."Adiabatic Panel"] outside_layer = "Gypsum Board 13mm" [zone."Zone One"] direction_of_relative_north = 0.0 x_origin = 0.0 y_origin = 0.0 z_origin = 0.0 type = 1 multiplier = 1 ceiling_height = "Autocalculate" volume = "Autocalculate" floor_area = "Autocalculate" zone_inside_convection_algorithm = "TARP" zone_outside_convection_algorithm = "DOE-2" part_of_total_floor_area = "Yes" [zone.control.thermostat."Zone One Thermostat"] zone_or_zonelist_name = "Zone One" control_type_schedule_name = "Dual Setpoint Control" control_1_object_type = "ThermostatSetpoint:DualSetpoint" control_1_name = "Zone One Dual Setpoint" [zone.hvac.air-distribution-unit."Zone One ADU"] air_distribution_unit_outlet_node_name = "Zone One Supply Inlet" air_terminal_object_type = "AirTerminal:SingleDuct:ConstantVolume:NoReheat" air_terminal_name = "Zone One Terminal" nominal_upstream_leakage_fraction = 0.0 constant_downstream_leakage_fraction = 0.0 [zone.hvac.equipment-list."Zone One Equipment List"] load_distribution_scheme = "SequentialLoad" equipment = [ { zone_equipment_object_type = "ZoneHVAC:AirDistributionUnit", zone_equipment_name = "Zone One ADU", zone_equipment_cooling_sequence = 1, zone_equipment_heating_or_no_load_sequence = 1 }, { zone_equipment_object_type = "Fan:ZoneExhaust", zone_equipment_name = "Zone Exhaust Fan", zone_equipment_cooling_sequence = 2, zone_equipment_heating_or_no_load_sequence = 2 }, ] [[zone.hvac.equipment-connections]] zone_name = "Zone One" zone_conditioning_equipment_list_name = "Zone One Equipment List" zone_air_inlet_node_or_nodelist_name = "Zone One Supply Inlet" zone_air_node_name = "Zone One Air Node" zone_return_air_node_or_nodelist_name = "Zone One Return Outlet" zone_air_exhaust_node_or_nodelist_name = "Zone One Exhaust Node" [other-equipment."Zone Sensible Cooling Load"] fuel_type = "None" zone_or_zonelist_or_space_or_spacelist_name = "Zone One" schedule_name = "Always On" design_level_calculation_method = "EquipmentLevel" design_level = 1465.0 fraction_latent = 0.0 fraction_radiant = 0.0 fraction_lost = 0.0 [other-equipment."Zone Latent Load"] fuel_type = "None" zone_or_zonelist_or_space_or_spacelist_name = "Zone One" schedule_name = "Always On" design_level_calculation_method = "EquipmentLevel" design_level = 586.1 fraction_latent = 1.0 fraction_radiant = 0.0 fraction_lost = 0.0 [thermostat.setpoint.dual-setpoint."Zone One Dual Setpoint"] heating_setpoint_temperature_schedule_name = "Heating Setpoint" cooling_setpoint_temperature_schedule_name = "Cooling Setpoint" [air-loop-hvac."SZ Air Loop"] controller_list_name = "SZ Controllers" availability_manager_list_name = "SZ Availability" design_supply_air_flow_rate = 0.28229697009349275 branch_list_name = "SZ Branches" supply_side_inlet_node_name = "Air Loop Inlet Node" demand_side_outlet_node_name = "Zone Equipment Outlet Node" demand_side_inlet_node_names = "Zone Equipment Inlet Node" supply_side_outlet_node_names = "Supply Outlet Node" design_return_air_flow_fraction_of_supply_air_flow = 1.0 [branch-list."SZ Branches"] branches = [ { branch_name = "SZ Branch" }, ] [branch-list."CHW Supply Branches"] branches = [ { branch_name = "CHW Supply Inlet Branch" }, { branch_name = "CHW Chiller Branch" }, { branch_name = "CHW Supply Bypass Branch" }, { branch_name = "CHW Supply Outlet Branch" }, ] [branch-list."CHW Demand Branches"] branches = [ { branch_name = "CHW Demand Inlet Branch" }, { branch_name = "CHW Cooling Coil Branch" }, { branch_name = "CHW Demand Bypass Branch" }, { branch_name = "CHW Demand Outlet Branch" }, ] [branch."SZ Branch"] components = [ { component_object_type = "Fan:VariableVolume", component_name = "SZ Return Fan", component_inlet_node_name = "Air Loop Inlet Node", component_outlet_node_name = "Return Fan Outlet Node" }, { component_object_type = "AirLoopHVAC:OutdoorAirSystem", component_name = "SZ OA System", component_inlet_node_name = "Return Fan Outlet Node", component_outlet_node_name = "Mixed Air Node" }, { component_object_type = "Coil:Heating:Electric", component_name = "SZ Heating Coil", component_inlet_node_name = "Mixed Air Node", component_outlet_node_name = "Heating Coil Outlet Node" }, { component_object_type = "Coil:Cooling:Water", component_name = "SZ Cooling Coil", component_inlet_node_name = "Heating Coil Outlet Node", component_outlet_node_name = "Cooling Coil Outlet Node" }, { component_object_type = "Fan:ConstantVolume", component_name = "SZ Supply Fan", component_inlet_node_name = "Cooling Coil Outlet Node", component_outlet_node_name = "Supply Outlet Node" }, ] [branch."CHW Supply Inlet Branch"] components = [ { component_object_type = "Pump:VariableSpeed", component_name = "CHW Pump", component_inlet_node_name = "CHW Supply Inlet Node", component_outlet_node_name = "CHW Pump Outlet Node" }, ] [branch."CHW Chiller Branch"] components = [ { component_object_type = "Chiller:Electric:EIR", component_name = "CHW Chiller", component_inlet_node_name = "CHW Chiller Inlet Node", component_outlet_node_name = "CHW Chiller Outlet Node" }, ] [branch."CHW Supply Bypass Branch"] components = [ { component_object_type = "Pipe:Adiabatic", component_name = "CHW Supply Bypass Pipe", component_inlet_node_name = "CHW Supply Bypass Inlet Node", component_outlet_node_name = "CHW Supply Bypass Outlet Node" }, ] [branch."CHW Supply Outlet Branch"] components = [ { component_object_type = "Pipe:Adiabatic", component_name = "CHW Supply Outlet Pipe", component_inlet_node_name = "CHW Supply Outlet Pipe Inlet Node", component_outlet_node_name = "CHW Supply Outlet Node" }, ] [branch."CHW Demand Inlet Branch"] components = [ { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Inlet Pipe", component_inlet_node_name = "CHW Demand Inlet Node", component_outlet_node_name = "CHW Demand Inlet Pipe Outlet Node" }, ] [branch."CHW Cooling Coil Branch"] components = [ { component_object_type = "Coil:Cooling:Water", component_name = "SZ Cooling Coil", component_inlet_node_name = "Cooling Coil Water Inlet Node", component_outlet_node_name = "Cooling Coil Water Outlet Node" }, ] [branch."CHW Demand Bypass Branch"] components = [ { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Bypass Pipe", component_inlet_node_name = "CHW Demand Bypass Inlet Node", component_outlet_node_name = "CHW Demand Bypass Outlet Node" }, ] [branch."CHW Demand Outlet Branch"] components = [ { component_object_type = "Pipe:Adiabatic", component_name = "CHW Demand Outlet Pipe", component_inlet_node_name = "CHW Demand Outlet Pipe Inlet Node", component_outlet_node_name = "CHW Demand Outlet Node" }, ] [air.loop.hvac.controller-list."SZ Controllers"] controller_1_object_type = "Controller:WaterCoil" controller_1_name = "Cooling Coil Controller" [air.loop.hvac.controller-list."SZ OA Controllers"] controller_1_object_type = "Controller:OutdoorAir" controller_1_name = "SZ OA Controller" [air.loop.hvac.outdoor-air-system."SZ OA System"] controller_list_name = "SZ OA Controllers" outdoor_air_equipment_list_name = "SZ OA Equipment" [air.loop.hvac.outdoor.air.system.equipment-list."SZ OA Equipment"] component_1_object_type = "OutdoorAir:Mixer" component_1_name = "SZ OA Mixer" [air.loop.hvac.supply-path."SZ Supply Path"] supply_air_path_inlet_node_name = "Zone Equipment Inlet Node" components = [ { component_object_type = "AirLoopHVAC:ZoneSplitter", component_name = "Zone Supply Air Splitter" }, ] [air.loop.hvac.zone-splitter."Zone Supply Air Splitter"] inlet_node_name = "Zone Equipment Inlet Node" nodes = [ { outlet_node_name = "Zone One Terminal Inlet" }, ] [air.loop.hvac.return-path."SZ Return Path"] return_air_path_outlet_node_name = "Zone Equipment Outlet Node" components = [ { component_object_type = "AirLoopHVAC:ZoneMixer", component_name = "Zone Return Air Mixer" }, ] [air.loop.hvac.zone-mixer."Zone Return Air Mixer"] outlet_node_name = "Zone Equipment Outlet Node" nodes = [ { inlet_node_name = "Zone One Return Outlet" }, ] [air.terminal.single.duct.constant.volume.no-reheat."Zone One Terminal"] availability_schedule_name = "Always On" air_inlet_node_name = "Zone One Terminal Inlet" air_outlet_node_name = "Zone One Supply Inlet" maximum_air_flow_rate = 0.28229697009349275 [availability-manager-assignment-list."SZ Availability"] managers = [ { availability_manager_object_type = "AvailabilityManager:Scheduled", availability_manager_name = "SZ Avail" }, ] [availability.manager.scheduled."SZ Avail"] schedule_name = "Always On" [fan.variable-volume."SZ Return Fan"] availability_schedule_name = "Always On" fan_total_efficiency = 0.7 pressure_rise = 592.2843575864893 maximum_flow_rate = 0.28229697009349275 fan_power_minimum_flow_rate_input_method = "Fraction" fan_power_minimum_flow_fraction = 0.0 motor_efficiency = 1.0 motor_in_airstream_fraction = 0.0 fan_power_coefficient_1 = 0.0 fan_power_coefficient_2 = 0.0 fan_power_coefficient_3 = 0.0 fan_power_coefficient_4 = 1.0 fan_power_coefficient_5 = 0.0 air_inlet_node_name = "Air Loop Inlet Node" air_outlet_node_name = "Return Fan Outlet Node" end_use_subcategory = "Return Fans" [fan.constant-volume."SZ Supply Fan"] availability_schedule_name = "Always On" fan_total_efficiency = 0.7 pressure_rise = 499.5401117953785 maximum_flow_rate = 0.28229697009349275 motor_efficiency = 1.0 motor_in_airstream_fraction = 0.0 air_inlet_node_name = "Cooling Coil Outlet Node" air_outlet_node_name = "Supply Outlet Node" end_use_subcategory = "General" [fan.zone-exhaust."Zone Exhaust Fan"] availability_schedule_name = "Always On" fan_total_efficiency = 0.5 pressure_rise = 160.0 maximum_flow_rate = 0.09246609227361628 air_inlet_node_name = "Zone One Exhaust Node" air_outlet_node_name = "Zone Exhaust Fan Outlet" end_use_subcategory = "General Exhaust" system_availability_manager_coupling_mode = "Coupled" [outdoor.air.mixer."SZ OA Mixer"] mixed_air_node_name = "Mixed Air Node" outdoor_air_stream_node_name = "Outdoor Air Inlet Node" relief_air_stream_node_name = "Relief Air Outlet Node" return_air_stream_node_name = "Return Fan Outlet Node" [[outdoor.air.node-list]] nodes = [ { node_or_nodelist_name = "Outdoor Air Inlet Node" }, { node_or_nodelist_name = "CHW Chiller Condenser Inlet Node" }, ] [controller.outdoor-air."SZ OA Controller"] relief_air_outlet_node_name = "Relief Air Outlet Node" return_air_node_name = "Return Fan Outlet Node" mixed_air_node_name = "Mixed Air Node" actuator_node_name = "Outdoor Air Inlet Node" minimum_outdoor_air_flow_rate = 0.09246609227361628 maximum_outdoor_air_flow_rate = 0.28229697009349275 economizer_control_type = "DifferentialEnthalpy" economizer_control_action_type = "ModulateFlow" lockout_type = "NoLockout" minimum_limit_type = "FixedMinimum" economizer_minimum_limit_dry_bulb_temperature = 7.900798302791234 [controller.water-coil."Cooling Coil Controller"] control_variable = "Temperature" action = "Reverse" actuator_variable = "Flow" sensor_node_name = "Cooling Coil Outlet Node" actuator_node_name = "Cooling Coil Water Inlet Node" controller_convergence_tolerance = 1e-06 maximum_actuated_flow = 0.00023 minimum_actuated_flow = 0.0 [coil.heating.electric."SZ Heating Coil"] availability_schedule_name = "Always On" efficiency = 1.0 nominal_capacity = 20000.0 air_inlet_node_name = "Mixed Air Node" air_outlet_node_name = "Heating Coil Outlet Node" temperature_setpoint_node_name = "Heating Coil Outlet Node" [coil.cooling.water."SZ Cooling Coil"] availability_schedule_name = "Always On" design_water_flow_rate = 0.00023 design_air_flow_rate = 0.28229697009349275 design_inlet_water_temperature = 12.0 design_inlet_air_temperature = 26.0 design_outlet_air_temperature = 14.0 design_inlet_air_humidity_ratio = 0.0135 design_outlet_air_humidity_ratio = 0.0099 water_inlet_node_name = "Cooling Coil Water Inlet Node" water_outlet_node_name = "Cooling Coil Water Outlet Node" air_inlet_node_name = "Heating Coil Outlet Node" air_outlet_node_name = "Cooling Coil Outlet Node" type_of_analysis = "SimpleAnalysis" heat_exchanger_configuration = "CrossFlow" [setpoint.manager.single.zone.heating."Heating Supply Air Temp Manager"] control_variable = "Temperature" minimum_supply_air_temperature = -99.0 maximum_supply_air_temperature = 99.0 control_zone_name = "Zone One" zone_node_name = "Zone One Air Node" zone_inlet_node_name = "Zone One Supply Inlet" setpoint_node_or_nodelist_name = "Zone Equipment Inlet Node" [setpoint.manager.single.zone.cooling."Cooling Supply Air Temp Manager"] control_variable = "Temperature" minimum_supply_air_temperature = -99.0 maximum_supply_air_temperature = 99.0 control_zone_name = "Zone One" zone_node_name = "Zone One Air Node" zone_inlet_node_name = "Zone One Supply Inlet" setpoint_node_or_nodelist_name = "Supply Outlet Node" [setpoint.manager.mixed-air."Heating Coil Air Temp Manager"] control_variable = "Temperature" reference_setpoint_node_name = "Zone Equipment Inlet Node" fan_inlet_node_name = "Cooling Coil Outlet Node" fan_outlet_node_name = "Supply Outlet Node" setpoint_node_or_nodelist_name = "Heating Coil Outlet Node" [setpoint.manager.mixed-air."Cooling Coil Air Temp Manager"] control_variable = "Temperature" reference_setpoint_node_name = "Supply Outlet Node" fan_inlet_node_name = "Cooling Coil Outlet Node" fan_outlet_node_name = "Supply Outlet Node" setpoint_node_or_nodelist_name = "Cooling Setpoint Nodes" [setpoint.manager.scheduled."CHW Loop Setpoint Manager"] control_variable = "Temperature" schedule_name = "CHW Setpoint" setpoint_node_or_nodelist_name = "CHW Supply Outlet Node" [node-list."Cooling Setpoint Nodes"] nodes = [ { node_name = "Cooling Coil Outlet Node" }, { node_name = "Mixed Air Node" }, ] [plant-loop."Chilled Water Loop"] fluid_type = "Water" plant_equipment_operation_scheme_name = "CHW Loop Operation" loop_temperature_setpoint_node_name = "CHW Supply Outlet Node" maximum_loop_temperature = 98.0 minimum_loop_temperature = 1.0 maximum_loop_flow_rate = 0.0006 minimum_loop_flow_rate = 0.0 plant_loop_volume = 0.5 plant_side_inlet_node_name = "CHW Supply Inlet Node" plant_side_outlet_node_name = "CHW Supply Outlet Node" plant_side_branch_list_name = "CHW Supply Branches" plant_side_connector_list_name = "CHW Supply Connectors" demand_side_inlet_node_name = "CHW Demand Inlet Node" demand_side_outlet_node_name = "CHW Demand Outlet Node" demand_side_branch_list_name = "CHW Demand Branches" demand_side_connector_list_name = "CHW Demand Connectors" load_distribution_scheme = "SequentialLoad" [plant-equipment-operation-schemes."CHW Loop Operation"] control_scheme_1_object_type = "PlantEquipmentOperation:CoolingLoad" control_scheme_1_name = "CHW Cooling Scheme" control_scheme_1_schedule_name = "Always On" [plant.equipment.operation.cooling-load."CHW Cooling Scheme"] load_range_1_lower_limit = 0.0 load_range_1_upper_limit = 1000000000.0 range_1_equipment_list_name = "CHW Chillers" [plant-equipment-list."CHW Chillers"] equipment = [ { equipment_object_type = "Chiller:Electric:EIR", equipment_name = "CHW Chiller" }, ] [connector-list."CHW Supply Connectors"] connector_1_object_type = "Connector:Splitter" connector_1_name = "CHW Supply Splitter" connector_2_object_type = "Connector:Mixer" connector_2_name = "CHW Supply Mixer" [connector-list."CHW Demand Connectors"] connector_1_object_type = "Connector:Splitter" connector_1_name = "CHW Demand Splitter" connector_2_object_type = "Connector:Mixer" connector_2_name = "CHW Demand Mixer" [connector.splitter."CHW Supply Splitter"] inlet_branch_name = "CHW Supply Inlet Branch" branches = [ { outlet_branch_name = "CHW Chiller Branch" }, { outlet_branch_name = "CHW Supply Bypass Branch" }, ] [connector.splitter."CHW Demand Splitter"] inlet_branch_name = "CHW Demand Inlet Branch" branches = [ { outlet_branch_name = "CHW Cooling Coil Branch" }, { outlet_branch_name = "CHW Demand Bypass Branch" }, ] [connector.mixer."CHW Supply Mixer"] outlet_branch_name = "CHW Supply Outlet Branch" branches = [ { inlet_branch_name = "CHW Chiller Branch" }, { inlet_branch_name = "CHW Supply Bypass Branch" }, ] [connector.mixer."CHW Demand Mixer"] outlet_branch_name = "CHW Demand Outlet Branch" branches = [ { inlet_branch_name = "CHW Cooling Coil Branch" }, { inlet_branch_name = "CHW Demand Bypass Branch" }, ] [pump.variable-speed."CHW Pump"] inlet_node_name = "CHW Supply Inlet Node" outlet_node_name = "CHW Pump Outlet Node" design_maximum_flow_rate = 0.0006 design_pump_head = 1000.0 design_power_consumption = 1.0 motor_efficiency = 0.9 fraction_of_motor_inefficiencies_to_fluid_stream = 0.0 coefficient_1_of_the_part_load_performance_curve = 0.0 coefficient_2_of_the_part_load_performance_curve = 1.0 coefficient_3_of_the_part_load_performance_curve = 0.0 coefficient_4_of_the_part_load_performance_curve = 0.0 design_minimum_flow_rate = 0.0 pump_control_type = "Intermittent" [chiller.electric.eir."CHW Chiller"] reference_capacity = 20000.0 reference_cop = 3.0 reference_leaving_chilled_water_temperature = 6.67 reference_entering_condenser_fluid_temperature = 35.0 reference_chilled_water_flow_rate = 0.0006 cooling_capacity_function_of_temperature_curve_name = "CHW Chiller Cap FT" electric_input_to_cooling_output_ratio_function_of_temperature_curve_name = "CHW Chiller EIR FT" electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name = "CHW Chiller EIR FPLR" minimum_part_load_ratio = 0.1 maximum_part_load_ratio = 1.0 optimum_part_load_ratio = 1.0 minimum_unloading_ratio = 0.2 chilled_water_inlet_node_name = "CHW Chiller Inlet Node" chilled_water_outlet_node_name = "CHW Chiller Outlet Node" condenser_inlet_node_name = "CHW Chiller Condenser Inlet Node" condenser_outlet_node_name = "CHW Chiller Condenser Outlet Node" condenser_type = "AirCooled" condenser_fan_power_ratio = 0.0 fraction_of_compressor_electric_consumption_rejected_by_condenser = 1.0 leaving_chilled_water_lower_temperature_limit = 2.0 chiller_flow_mode = "ConstantFlow" [curve.biquadratic."CHW Chiller Cap FT"] coefficient1_constant = 0.507883 coefficient2_x = 0.145228 coefficient3_x_2 = -0.00625644 coefficient4_y = -0.0011178 coefficient5_y_2 = -0.0001296 coefficient6_x_y = -0.00028188 minimum_value_of_x = 5.0 maximum_value_of_x = 10.0 minimum_value_of_y = 24.0 maximum_value_of_y = 35.0 input_unit_type_for_x = "Temperature" input_unit_type_for_y = "Temperature" output_unit_type = "Dimensionless" [curve.biquadratic."CHW Chiller EIR FT"] coefficient1_constant = 1.03076 coefficient2_x = -0.103536 coefficient3_x_2 = 0.00710208 coefficient4_y = 0.0093186 coefficient5_y_2 = 0.00031752 coefficient6_x_y = -0.00104328 minimum_value_of_x = 5.0 maximum_value_of_x = 10.0 minimum_value_of_y = 24.0 maximum_value_of_y = 35.0 input_unit_type_for_x = "Temperature" input_unit_type_for_y = "Temperature" output_unit_type = "Dimensionless" [curve.quadratic."CHW Chiller EIR FPLR"] coefficient1_constant = 0.088065 coefficient2_x = 1.137742 coefficient3_x_2 = -0.225806 minimum_value_of_x = 0.0 maximum_value_of_x = 1.0 [pipe.adiabatic."CHW Supply Bypass Pipe"] inlet_node_name = "CHW Supply Bypass Inlet Node" outlet_node_name = "CHW Supply Bypass Outlet Node" [pipe.adiabatic."CHW Supply Outlet Pipe"] inlet_node_name = "CHW Supply Outlet Pipe Inlet Node" outlet_node_name = "CHW Supply Outlet Node" [pipe.adiabatic."CHW Demand Inlet Pipe"] inlet_node_name = "CHW Demand Inlet Node" outlet_node_name = "CHW Demand Inlet Pipe Outlet Node" [pipe.adiabatic."CHW Demand Bypass Pipe"] inlet_node_name = "CHW Demand Bypass Inlet Node" outlet_node_name = "CHW Demand Bypass Outlet Node" [pipe.adiabatic."CHW Demand Outlet Pipe"] inlet_node_name = "CHW Demand Outlet Pipe Inlet Node" outlet_node_name = "CHW Demand Outlet Node" [[output.variable-dictionary]] key_field = "IDF" [[output.variable]] key_value = "*" variable_name = "Zone Air System Sensible Heating Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "*" variable_name = "Zone Air System Sensible Cooling Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "*" variable_name = "Zone Total Internal Latent Gain Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "*" variable_name = "Zone Mean Air Temperature" reporting_frequency = "Timestep" [[output.variable]] key_value = "*" variable_name = "Heating Coil Heating Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "*" variable_name = "Cooling Coil Total Cooling Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "*" variable_name = "Cooling Coil Sensible Cooling Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "*" variable_name = "Site Outdoor Air Barometric Pressure" reporting_frequency = "Timestep" [[output.variable]] key_value = "SZ Supply Fan" variable_name = "Fan Electricity Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "SZ Return Fan" variable_name = "Fan Electricity Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "Zone Exhaust Fan" variable_name = "Fan Air Mass Flow Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "SZ Air Loop" variable_name = "Air System Outdoor Air Economizer Status" reporting_frequency = "Timestep" [[output.variable]] key_value = "SZ Air Loop" variable_name = "Air System Outdoor Air Flow Fraction" reporting_frequency = "Timestep" [[output.variable]] key_value = "Outdoor Air Inlet Node" variable_name = "System Node Temperature" reporting_frequency = "Timestep" [[output.variable]] key_value = "Outdoor Air Inlet Node" variable_name = "System Node Humidity Ratio" reporting_frequency = "Timestep" [[output.variable]] key_value = "Outdoor Air Inlet Node" variable_name = "System Node Mass Flow Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "Mixed Air Node" variable_name = "System Node Temperature" reporting_frequency = "Timestep" [[output.variable]] key_value = "Mixed Air Node" variable_name = "System Node Humidity Ratio" reporting_frequency = "Timestep" [[output.variable]] key_value = "Mixed Air Node" variable_name = "System Node Mass Flow Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "Heating Coil Outlet Node" variable_name = "System Node Temperature" reporting_frequency = "Timestep" [[output.variable]] key_value = "Heating Coil Outlet Node" variable_name = "System Node Humidity Ratio" reporting_frequency = "Timestep" [[output.variable]] key_value = "Heating Coil Outlet Node" variable_name = "System Node Mass Flow Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "Cooling Coil Outlet Node" variable_name = "System Node Temperature" reporting_frequency = "Timestep" [[output.variable]] key_value = "Cooling Coil Outlet Node" variable_name = "System Node Humidity Ratio" reporting_frequency = "Timestep" [[output.variable]] key_value = "Cooling Coil Outlet Node" variable_name = "System Node Mass Flow Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "Zone One Supply Inlet" variable_name = "System Node Temperature" reporting_frequency = "Timestep" [[output.variable]] key_value = "Zone One Supply Inlet" variable_name = "System Node Humidity Ratio" reporting_frequency = "Timestep" [[output.variable]] key_value = "Zone One Supply Inlet" variable_name = "System Node Mass Flow Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "Zone One Air Node" variable_name = "System Node Temperature" reporting_frequency = "Timestep" [[output.variable]] key_value = "Zone One Air Node" variable_name = "System Node Humidity Ratio" reporting_frequency = "Timestep" [[output.variable]] key_value = "Zone One Air Node" variable_name = "System Node Mass Flow Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "Air Loop Inlet Node" variable_name = "System Node Temperature" reporting_frequency = "Timestep" [[output.variable]] key_value = "Air Loop Inlet Node" variable_name = "System Node Humidity Ratio" reporting_frequency = "Timestep" [[output.variable]] key_value = "Air Loop Inlet Node" variable_name = "System Node Mass Flow Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "Return Fan Outlet Node" variable_name = "System Node Temperature" reporting_frequency = "Timestep" [[output.variable]] key_value = "Return Fan Outlet Node" variable_name = "System Node Humidity Ratio" reporting_frequency = "Timestep" [[output.variable]] key_value = "Return Fan Outlet Node" variable_name = "System Node Mass Flow Rate" reporting_frequency = "Timestep" [run-period."AE245 Run"] begin_month = 1 begin_day_of_month = 1 end_month = 1 end_day_of_month = 7 use_weather_file_holidays_and_special_days = "No" use_weather_file_daylight_saving_period = "No" apply_weekend_holiday_rule = "No" use_weather_file_rain_indicators = "Yes" use_weather_file_snow_indicators = "Yes"