Validation · ANSI/ASHRAE Standard 140-2023
Tested against Standard 140
SIMsara is a building energy simulation engine written in Rust. This site reports how it performs on the ASHRAE Standard 140 test suites: which cases were run, where each result sits against the reference results, and the input files and modeler reports behind every number.
- Software
- SIMsara 0.1.0
- Standard
- ANSI/ASHRAE 140-2023
- Run date
- 2026-10-05
- Suites run
- 6 of 7
- Cases
- 124, plus 3 diagnostic
124 cases in 6 suites
Weather, envelope, cooling, heating and air-side tests, plus 3 diagnostic runs. Each suite page lists every reported quantity next to the range of the example programs.
Modeler reports included
Each suite carries its Standard 140 modeler report: methods used, equivalent inputs, omitted cases and any result outside the example range.
Inputs you can inspect
Every case links to its input file with a checksum, and the method page describes how the results were produced.
Annex A3
Acceptance criteria
Standard 140 sets a range for selected results and a minimum number that must fall inside it for each group. The white tick marks that minimum.
Thermal Fabric Low Mass
21of 21
Minimum 18
PassThermal Fabric High Mass
19of 19
Minimum 17
PassCooling Equipment
14of 14
Minimum 12
PassHeating Equipment
6of 6
Minimum 5
PassAir-side Equipment
54of 54
Minimum 48
PassCounts use the Annex A3 tables of Standard 140-2023 as published. Addendum a (2025) revises the thermal fabric tables. Weather drivers and ground coupling have no Annex A3 criteria.
Results
Test suites
Open a suite for its results table, acceptance ranges, modeler report, input files and downloads.
| Suite | Standard 140 | Cases run | Values compared | Outside example range | Acceptance |
|---|---|---|---|---|---|
| Weather drivers | Section 6 | 6 | 246 | 5 | No A3 criteria |
| Thermal fabric | Section 7 | 49 +3 diagnostic | 1616 | 161 | 21 of 2119 of 19 |
| Ground coupling | Section 8 | Omitted | |||
| Space cooling A | Sections 9.2.1 to 9.2.2 | 14 | 266 | 28 | No A3 criteria |
| Space cooling B | Sections 9.2.3 to 9.2.4 | 20 | 783 | 178 | 14 of 14 |
| Space heating | Section 10 | 11 | 48 | 12 | 6 of 6 |
| Air-side equipment | Section 11 | 24 | 1371 | 249 | 54 of 54 |
The example range is the spread of the simulation programs published with the standard. It is informative; falling outside it is explained in the suite's modeler report and is not, by itself, a failure.