Sections 9.2.3 to 9.2.4 · Space cooling B

Case CE540

Values compared
23
Outside example range
13
Run time
1.91 s
Input file
CE540.toml, 18.3 kB

Against the example programs

Each reported quantity next to the spread of the simulation programs published with the standard.

Position in the example range
Example rangeSIMsara
Energy Consumption Compr + Both Fans WhCE b annual hourly maxima
8,677.48,985
Above range
Energy Consumption Compr + Both Fans Wh, CE b annual hourly maxima: SIMsara 9,127.7 · range 8,677.4 to 8,985
CE b annual hourly maximaWh
18,79419,799
Above range
CE b annual hourly maxima, Wh: SIMsara 19,830.4 · range 18,794 to 19,799
CE b annual hourly maximaWh
01,655.0
In range
CE b annual hourly maxima, Wh: SIMsara 4.24e-12 · range 0 to 1,655.0
Sensible + Latent WhCE b annual hourly maxima
18,79419,799
Above range
Sensible + Latent Wh, CE b annual hourly maxima: SIMsara 19,830.4 · range 18,794 to 19,799
Cooling Energy Consumption Total (kWh)CE b annual results
19,061.120,164
Above range
Cooling Energy Consumption Total (kWh), CE b annual results: SIMsara 20,277.7 · range 19,061.1 to 20,164
Compressor (kWh)CE b annual results
15,020.716,751.9
In range
Compressor (kWh), CE b annual results: SIMsara 15,856.3 · range 15,020.7 to 16,751.9
Cond Fan (kWh)CE b annual results
1,872.31,940
In range
Cond Fan (kWh), CE b annual results: SIMsara 1,893.1 · range 1,872.3 to 1,940
Indoor Fan (kWh)CE b annual results
2,2582,573
In range
Indoor Fan (kWh), CE b annual results: SIMsara 2,528.2 · range 2,258 to 2,573
Evaporator Coil Load Total (kWh)CE b annual results
44,979.847,462
Above range
Evaporator Coil Load Total (kWh), CE b annual results: SIMsara 47,507.7 · range 44,979.8 to 47,462
Sensible (kWh)CE b annual results
44,976.747,460
Above range
Sensible (kWh), CE b annual results: SIMsara 47,507.7 · range 44,976.7 to 47,460
Latent (kWh)CE b annual results
0.9798106.98
Below range
Latent (kWh), CE b annual results: SIMsara −2.94e-14 · range 0.9798 to 106.98
CE b annual resultsCOP2
2.6402.823
In range
CE b annual results, COP2: SIMsara 2.677 · range 2.640 to 2.823
CE b annual resultsIDB (°C)
13.28914.980
In range
CE b annual results, IDB (°C): SIMsara 14.080 · range 13.289 to 14.980
Zone Humidity Ratio (kg/kg)CE b annual results
0.0038550.004630
Below range
Zone Humidity Ratio (kg/kg), CE b annual results: SIMsara 0.002841 · range 0.003855 to 0.004630
Zone Relative Humidity (%)CE b annual results
40.05148.521
Below range
Zone Relative Humidity (%), CE b annual results: SIMsara 29.054 · range 40.051 to 48.521
CE b COP2, IDB, humidity and RH extremesCOP2
3.4553.696
In range
CE b COP2, IDB, humidity and RH extremes, COP2: SIMsara 3.478 · range 3.455 to 3.696
CE b COP2, IDB, humidity and RH extremesCOP2
2.1432.383
In range
CE b COP2, IDB, humidity and RH extremes, COP2: SIMsara 2.268 · range 2.143 to 2.383
CE b COP2, IDB, humidity and RH extremes°C
1516.146
In range
CE b COP2, IDB, humidity and RH extremes, °C: SIMsara 15.002 · range 15 to 16.146
CE b COP2, IDB, humidity and RH extremes°C
7.89014.950
In range
CE b COP2, IDB, humidity and RH extremes, °C: SIMsara 10.754 · range 7.890 to 14.950
CE b COP2, IDB, humidity and RH extremeskg/kg
0.0032560.006776
Below range
CE b COP2, IDB, humidity and RH extremes, kg/kg: SIMsara 0.002841 · range 0.003256 to 0.006776
CE b COP2, IDB, humidity and RH extremeskg/kg
0.0032530.004200
Below range
CE b COP2, IDB, humidity and RH extremes, kg/kg: SIMsara 0.002841 · range 0.003253 to 0.004200
CE b COP2, IDB, humidity and RH extremes%
39.96061.275
Below range
CE b COP2, IDB, humidity and RH extremes, %: SIMsara 36.008 · range 39.960 to 61.275
CE b COP2, IDB, humidity and RH extremes%
3139.740
Below range
CE b COP2, IDB, humidity and RH extremes, %: SIMsara 26.737 · range 31 to 39.740
TableQuantitySIMsaraMinMaxMeanStatus
CE b annual hourly maximaEnergy Consumption Compr + Both Fans Wh9,127.78,677.48,9858,848.2Above range
CE b annual hourly maximaDateJul 20
CE b annual hourly maximaHour15
CE b annual hourly maximaWh19,830.418,79419,79919,571.1Above range
CE b annual hourly maximaSensible DateJul 20
CE b annual hourly maximaEvaporatorCoilLoads Hour15
CE b annual hourly maximaWh4.24e-1201,655.0718.02In range
CE b annual hourly maximaLatent DateAug 12
CE b annual hourly maximaHour16
CE b annual hourly maximaSensible + Latent Wh19,830.418,79419,79919,571.1Above range
CE b annual hourly maximaDateJul 20
CE b annual hourly maximaHour15
CE b annual resultsCooling Energy Consumption Total (kWh)20,277.719,061.120,16419,657.3Above range
CE b annual resultsCompressor (kWh)15,856.315,020.716,751.915,659.6In range
CE b annual resultsCond Fan (kWh)1,893.11,872.31,9401,913.1In range
CE b annual resultsIndoor Fan (kWh)2,528.22,2582,5732,403.4In range
CE b annual resultsEvaporator Coil Load Total (kWh)47,507.744,979.847,46246,517.9Above range
CE b annual resultsSensible (kWh)47,507.744,976.747,46046,479.8Above range
CE b annual resultsLatent (kWh)−2.94e-140.9798106.9838.098Below range
CE b annual resultsCOP22.6772.6402.8232.695In range
CE b annual resultsIDB (°C)14.08013.28914.98013.951In range
CE b annual resultsZone Humidity Ratio (kg/kg)0.0028410.0038550.0046300.004323Below range
CE b annual resultsZone Relative Humidity (%)29.05440.05148.52144.675Below range
CE b COP2, IDB, humidity and RH extremesCOP23.4783.4553.6963.570In range
CE b COP2, IDB, humidity and RH extremesMaximum DateMar 16
CE b COP2, IDB, humidity and RH extremesC O P 2 Hour10
CE b COP2, IDB, humidity and RH extremesCOP22.2682.1432.3832.264In range
CE b COP2, IDB, humidity and RH extremesMinimum DateJul 30
CE b COP2, IDB, humidity and RH extremesHour12
CE b COP2, IDB, humidity and RH extremes°C15.0021516.14615.236In range
CE b COP2, IDB, humidity and RH extremesIndoor Drybulb Temperature Maximum DateOct 29
CE b COP2, IDB, humidity and RH extremesHour5
CE b COP2, IDB, humidity and RH extremes°C10.7547.89014.9509.420In range
CE b COP2, IDB, humidity and RH extremesMinimum* DateDec 21
CE b COP2, IDB, humidity and RH extremesHour6
CE b COP2, IDB, humidity and RH extremeskg/kg0.0028410.0032560.0067760.005626Below range
CE b COP2, IDB, humidity and RH extremesHumidity Ratio Maximum DateDec 30
CE b COP2, IDB, humidity and RH extremesHour22
CE b COP2, IDB, humidity and RH extremeskg/kg0.0028410.0032530.0042000.003845Below range
CE b COP2, IDB, humidity and RH extremesMinimum* DateApr 1
CE b COP2, IDB, humidity and RH extremesHour1
CE b COP2, IDB, humidity and RH extremes%36.00839.96061.27550.854Below range
CE b COP2, IDB, humidity and RH extremesRelative Humidity Maximum* DateDec 20
CE b COP2, IDB, humidity and RH extremesHour11
CE b COP2, IDB, humidity and RH extremes%26.7373139.74035.804Below range
CE b COP2, IDB, humidity and RH extremesMinimum* DateApr 18
CE b COP2, IDB, humidity and RH extremesHour17

Reported outputs

The values the engine wrote for this case, before they are placed in the output template.

OutputValue
Annual · total (kWh)20,277.7
Annual · compressor (kWh)15,856.3
Annual · cond fan (kWh)1,893.1
Annual · indoor fan (kWh)2,528.2
Annual · coil total (kWh)47,507.7
Annual · coil sensible (kWh)47,507.7
Annual · coil latent (kWh)−2.94e-14
Annual · cop2 mean2.677
Annual · idb mean14.080
Annual · w mean0.002841
Annual · rh mean29.054
Annual · odb mean19.914
Annual · ow mean0.01161
Annual · edb mean14.080
Annual · hours8,760
Maxima · total · value9,127.7
Maxima · total · month7
Maxima · total · day20
Maxima · total · hour15
Maxima · total · date37,092
Maxima · total · monJul
Maxima · cs · value19,830.4
Maxima · cs · month7
Maxima · cs · day20
Maxima · cs · hour15
Maxima · cs · date37,092
Maxima · cs · monJul
Maxima · cl · value4.24e-12
Maxima · cl · month8
Maxima · cl · day12
Maxima · cl · hour16
Maxima · cl · date37,115
Maxima · cl · monAug
Maxima · ct · value19,830.4
Maxima · ct · month7
Maxima · ct · day20
Maxima · ct · hour15
Maxima · ct · date37,092
Maxima · ct · monJul
Extremes · cop2 max · value3.478
Extremes · cop2 max · month3
Extremes · cop2 max · day16
Extremes · cop2 max · hour10
Extremes · cop2 max · date36,966
Extremes · cop2 max · monMar
Extremes · cop2 min · value2.268
Extremes · cop2 min · month7
Extremes · cop2 min · day30
Extremes · cop2 min · hour12
Extremes · cop2 min · date37,102
Extremes · cop2 min · monJul
Extremes · idb max · value15.002
Extremes · idb max · month10
Extremes · idb max · day29
Extremes · idb max · hour5
Extremes · idb max · date37,193
Extremes · idb max · monOct
Extremes · idb min · value10.754
Extremes · idb min · month12
Extremes · idb min · day21
Extremes · idb min · hour6
Extremes · idb min · date37,246
Extremes · idb min · monDec
Extremes · w max · value0.002841
Extremes · w max · month12
Extremes · w max · day30
Extremes · w max · hour22
Extremes · w max · date37,255
Extremes · w max · monDec
Extremes · w min · value0.002841
Extremes · w min · month4
Extremes · w min · day1
Extremes · w min · hour1
Extremes · w min · date36,982
Extremes · w min · monApr
Extremes · rh max · value36.008
Extremes · rh max · month12
Extremes · rh max · day20
Extremes · rh max · hour11
Extremes · rh max · date37,245
Extremes · rh max · monDec
Extremes · rh min · value26.737
Extremes · rh min · month4
Extremes · rh min · day18
Extremes · rh min · hour17
Extremes · rh min · date36,999
Extremes · rh min · monApr
Extreme window apr dectrue
Hours above setpoint 0p5k0

Input file

sha256 c9e5db48555c338f9eed4799c70c5d7102b53e7548c327334d0b3c25cbaa2ba7

CE540.tomlDownload
[version]
version_identifier = "26.1"

[simulation-control]
do_zone_sizing_calculation = "No"
do_system_sizing_calculation = "No"
do_plant_sizing_calculation = "No"
run_simulation_for_sizing_periods = "No"
run_simulation_for_weather_file_run_periods = "Yes"
do_hvac_sizing_simulation_for_sizing_periods = "No"
maximum_number_of_hvac_sizing_simulation_passes = 1

[building."Standard 140 CE540 (SIMsara)"]
north_axis = 0.0
terrain = "Suburbs"
loads_convergence_tolerance_value = 0.04
temperature_convergence_tolerance_value = 0.004
solar_distribution = "MinimalShadowing"
maximum_number_of_warmup_days = 50
minimum_number_of_warmup_days = 6

[timestep]
number_of_timesteps_per_hour = 6

[heat-balance-algorithm]
algorithm = "ConductionTransferFunction"

[surface.convection.algorithm.inside]
algorithm = "TARP"

[surface.convection.algorithm.outside]
algorithm = "SimpleCombined"

[global-geometry-rules]
starting_vertex_position = "UpperLeftCorner"
vertex_entry_direction = "Counterclockwise"
coordinate_system = "Relative"

[site.location."CE b Site"]
latitude = 30.0
longitude = -90.3
time_zone = -6.0
elevation = 3.0

[schedule-type-limits."Fraction"]
lower_limit_value = 0.0
upper_limit_value = 1.0
numeric_type = "Continuous"

[schedule-type-limits."Any Number"]

[schedule-type-limits."Temperature"]
lower_limit_value = -60.0
upper_limit_value = 200.0
numeric_type = "Continuous"
unit_type = "Temperature"

[schedule-type-limits."Control Type"]
lower_limit_value = 0.0
upper_limit_value = 4.0
numeric_type = "Discrete"

[schedule.compact."Always On"]
schedule_type_limits_name = "Fraction"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 1.0 },
]

[schedule.compact."Cooling Only Control"]
schedule_type_limits_name = "Control Type"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 2.0 },
]

[schedule.compact."CE Sensible Gain Schedule"]
schedule_type_limits_name = "Fraction"
data = [
  { field = "Through: 3/10" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 0.0 },
  { field = "Through: 4/10" },
  { field = "For: AllDays" },
  { field = "Until: 09:00" },
  { field = 0.0 },
  { field = "Until: 16:00" },
  { field = 0.3749866723531293 },
  { field = "Until: 24:00" },
  { field = 0.0 },
  { field = "Through: 4/11" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 0.0 },
  { field = "Through: 4/20" },
  { field = "For: AllDays" },
  { field = "Until: 08:00" },
  { field = 0.0 },
  { field = "Until: 17:00" },
  { field = 0.5 },
  { field = "Until: 24:00" },
  { field = 0.0 },
  { field = "Through: 10/11" },
  { field = "For: AllDays" },
  { field = "Until: 08:00" },
  { field = 0.3749866723531293 },
  { field = "Until: 12:00" },
  { field = 0.5 },
  { field = "Until: 14:00" },
  { field = 0.7500266552937414 },
  { field = "Until: 16:00" },
  { field = 1.0 },
  { field = "Until: 20:00" },
  { field = 0.5 },
  { field = "Until: 24:00" },
  { field = 0.3749866723531293 },
  { field = "Through: 10/18" },
  { field = "For: AllDays" },
  { field = "Until: 08:00" },
  { field = 0.0 },
  { field = "Until: 14:00" },
  { field = 0.5 },
  { field = "Until: 24:00" },
  { field = 0.0 },
  { field = "Through: 11/5" },
  { field = "For: AllDays" },
  { field = "Until: 08:00" },
  { field = 0.0 },
  { field = "Until: 12:00" },
  { field = 0.5 },
  { field = "Until: 14:00" },
  { field = 0.7500266552937414 },
  { field = "Until: 16:00" },
  { field = 1.0 },
  { field = "Until: 20:00" },
  { field = 0.5 },
  { field = "Until: 24:00" },
  { field = 0.3749866723531293 },
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 0.0 },
]

[schedule.compact."Cooling Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 15.0 },
]

[schedule.compact."CE Fan Mode"]
schedule_type_limits_name = "Any Number"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 0.0 },
]

[schedule.compact."CE Heating Off"]
schedule_type_limits_name = "Fraction"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 0.0 },
]

[material.no-mass."CE Insulation Outer Half"]
roughness = "VerySmooth"
thermal_resistance = 162.33766233766235
thermal_absorptance = 0.9
solar_absorptance = 0.1
visible_absorptance = 0.1

[material.no-mass."CE Insulation Inner Half"]
roughness = "VerySmooth"
thermal_resistance = 162.33766233766235
thermal_absorptance = 0.9
solar_absorptance = 0.6
visible_absorptance = 0.6

[construction."CE Envelope"]
outside_layer = "CE Insulation Outer Half"
layer_2 = "CE Insulation Inner Half"

[output.variable-dictionary."Output:VariableDictionary"]
key_field = "IDF"

[run-period."CE540"]
begin_month = 1
begin_day_of_month = 1
end_month = 12
end_day_of_month = 31
day_of_week_for_start_day = "Sunday"
use_weather_file_holidays_and_special_days = "No"
use_weather_file_daylight_saving_period = "No"
apply_weekend_holiday_rule = "No"
use_weather_file_rain_indicators = "Yes"
use_weather_file_snow_indicators = "Yes"

[building.surface.detailed."CE Zone South Wall"]
surface_type = "Wall"
zone_name = "CE Zone"
construction_name = "CE Envelope"
outside_boundary_condition = "Outdoors"
sun_exposure = "SunExposed"
wind_exposure = "WindExposed"
view_factor_to_ground = 0.5
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 },
]

[building.surface.detailed."CE Zone East Wall"]
surface_type = "Wall"
zone_name = "CE Zone"
construction_name = "CE Envelope"
outside_boundary_condition = "Outdoors"
sun_exposure = "SunExposed"
wind_exposure = "WindExposed"
view_factor_to_ground = 0.5
vertices = [
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 },
]

[building.surface.detailed."CE Zone North Wall"]
surface_type = "Wall"
zone_name = "CE Zone"
construction_name = "CE Envelope"
outside_boundary_condition = "Outdoors"
sun_exposure = "SunExposed"
wind_exposure = "WindExposed"
view_factor_to_ground = 0.5
vertices = [
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 },
]

[building.surface.detailed."CE Zone West Wall"]
surface_type = "Wall"
zone_name = "CE Zone"
construction_name = "CE Envelope"
outside_boundary_condition = "Outdoors"
sun_exposure = "SunExposed"
wind_exposure = "WindExposed"
view_factor_to_ground = 0.5
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 },
]

[building.surface.detailed."CE Zone Floor"]
surface_type = "Floor"
zone_name = "CE Zone"
construction_name = "CE Envelope"
outside_boundary_condition = "Outdoors"
sun_exposure = "SunExposed"
wind_exposure = "WindExposed"
view_factor_to_ground = 0.0
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
]

[building.surface.detailed."CE Zone Roof"]
surface_type = "Roof"
zone_name = "CE Zone"
construction_name = "CE Envelope"
outside_boundary_condition = "Outdoors"
sun_exposure = "SunExposed"
wind_exposure = "WindExposed"
view_factor_to_ground = 0.0
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 },
]

[zone."CE Zone"]
direction_of_relative_north = 0.0
x_origin = 0.0
y_origin = 0.0
z_origin = 0.0
type = 1
multiplier = 1
ceiling_height = 3.0
volume = 588.0
floor_area = 196.0
part_of_total_floor_area = "Yes"

[electric-equipment."CE Sensible Gains"]
zone_or_zonelist_or_space_or_spacelist_name = "CE Zone"
schedule_name = "CE Sensible Gain Schedule"
design_level_calculation_method = "EquipmentLevel"
design_level = 18758.0
fraction_latent = 0.0
fraction_radiant = 0.0
fraction_lost = 0.0
end_use_subcategory = "General"

[thermostat.setpoint.single-cooling."CE Cooling Setpoint"]
setpoint_temperature_schedule_name = "Cooling Setpoint"

[zone.control.thermostat."CE Thermostat"]
zone_or_zonelist_name = "CE Zone"
control_type_schedule_name = "Cooling Only Control"
control_1_object_type = "ThermostatSetpoint:SingleCooling"
control_1_name = "CE Cooling Setpoint"

[air-loop-hvac."CE Air Loop"]
availability_manager_list_name = "CE Availability"
design_supply_air_flow_rate = 1.8877777777777778
branch_list_name = "CE Branches"
supply_side_inlet_node_name = "CE Loop Inlet"
demand_side_outlet_node_name = "CE Zone Equipment Outlet"
demand_side_inlet_node_names = "CE Zone Equipment Inlet"
supply_side_outlet_node_names = "CE Loop Outlet"
design_return_air_flow_fraction_of_supply_air_flow = 1.0

[branch-list."CE Branches"]
branches = [
  { branch_name = "CE Main Branch" },
]

[branch."CE Main Branch"]
components = [
  { component_object_type = "AirLoopHVAC:UnitaryHeatCool", component_name = "CE Unitary", component_inlet_node_name = "CE Loop Inlet", component_outlet_node_name = "CE Loop Outlet" },
]

[availability-manager-assignment-list."CE Availability"]
managers = [
  { availability_manager_object_type = "AvailabilityManager:Scheduled", availability_manager_name = "CE Avail" },
]

[availability.manager.scheduled."CE Avail"]
schedule_name = "Always On"

[air.loop.hvac.unitary-heat-cool."CE Unitary"]
availability_schedule_name = "Always On"
unitary_system_air_inlet_node_name = "CE Loop Inlet"
unitary_system_air_outlet_node_name = "CE Loop Outlet"
supply_air_fan_operating_mode_schedule_name = "CE Fan Mode"
maximum_supply_air_temperature = 50.0
cooling_supply_air_flow_rate = 1.8877777777777778
heating_supply_air_flow_rate = 1.8877777777777778
no_load_supply_air_flow_rate = 1.8877777777777778
controlling_zone_or_thermostat_location = "CE Zone"
supply_fan_object_type = "Fan:OnOff"
supply_fan_name = "CE Supply Fan"
fan_placement = "DrawThrough"
heating_coil_object_type = "Coil:Heating:Electric"
heating_coil_name = "CE Heating Coil"
cooling_coil_object_type = "Coil:Cooling:DX:SingleSpeed"
cooling_coil_name = "CE Cooling Coil"
dehumidification_control_type = "None"

[coil.heating.electric."CE Heating Coil"]
availability_schedule_name = "CE Heating Off"
efficiency = 1.0
nominal_capacity = 1000.0
air_inlet_node_name = "CE Coil Outlet"
air_outlet_node_name = "CE Heating Coil Outlet"

[curve.biquadratic."CE b CapFT"]
coefficient1_constant = 0.8421792790769599
coefficient2_x = 0.013597330340468002
coefficient3_x_2 = 0.0005425555274330542
coefficient4_y = -0.0046779772346486545
coefficient5_y_2 = -1.892890987340474e-05
coefficient6_x_y = -0.0001833613310964283
minimum_value_of_x = -20.0
maximum_value_of_x = 50.0
minimum_value_of_y = -20.0
maximum_value_of_y = 60.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.biquadratic."CE b EIRFT"]
coefficient1_constant = 0.6296349141804827
coefficient2_x = -0.01194173030834857
coefficient3_x_2 = 0.00013564228411874153
coefficient4_y = 0.014620794633169055
coefficient5_y_2 = 0.0001647879385125572
coefficient6_x_y = -0.00023849947842266334
minimum_value_of_x = -20.0
maximum_value_of_x = 50.0
minimum_value_of_y = -20.0
maximum_value_of_y = 60.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.quadratic."CE b CapFFF"]
coefficient1_constant = 1.0
coefficient2_x = 0.0
coefficient3_x_2 = 0.0
minimum_value_of_x = 0.0
maximum_value_of_x = 1.5

[curve.quadratic."CE b EIRFFF"]
coefficient1_constant = 1.0
coefficient2_x = 0.0
coefficient3_x_2 = 0.0
minimum_value_of_x = 0.0
maximum_value_of_x = 1.5

[curve.quadratic."CE b PLF"]
coefficient1_constant = 0.771
coefficient2_x = 0.229
coefficient3_x_2 = 0.0
minimum_value_of_x = 0.0
maximum_value_of_x = 1.0

[coil.cooling.dx.single-speed."CE Cooling Coil"]
availability_schedule_name = "Always On"
gross_rated_total_cooling_capacity = 33277.1085
gross_rated_sensible_heat_ratio = 0.7825956753424054
gross_rated_cooling_cop = 3.0426175825180586
rated_air_flow_rate = 1.8877777777777778
air_inlet_node_name = "CE Loop Inlet"
air_outlet_node_name = "CE Coil Outlet"
total_cooling_capacity_function_of_temperature_curve_name = "CE b CapFT"
total_cooling_capacity_function_of_flow_fraction_curve_name = "CE b CapFFF"
energy_input_ratio_function_of_temperature_curve_name = "CE b EIRFT"
energy_input_ratio_function_of_flow_fraction_curve_name = "CE b EIRFFF"
part_load_fraction_correlation_curve_name = "CE b PLF"
minimum_outdoor_dry_bulb_temperature_for_compressor_operation = -25.0
nominal_time_for_condensate_removal_to_begin = 0.0
ratio_of_initial_moisture_evaporation_rate_and_steady_state_latent_capacity = 0.0
maximum_cycling_rate = 0.0
latent_capacity_time_constant = 0.0
condenser_type = "AirCooled"
crankcase_heater_capacity = 0.0
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater_operation = 10.0

[fan.on-off."CE Supply Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 1.0
pressure_rise = 657.9164214243673
maximum_flow_rate = 1.8877777777777778
motor_efficiency = 1.0
motor_in_airstream_fraction = 1.0
air_inlet_node_name = "CE Heating Coil Outlet"
air_outlet_node_name = "CE Loop Outlet"
end_use_subcategory = "General"

[air.loop.hvac.supply-path."CE Supply Path"]
supply_air_path_inlet_node_name = "CE Zone Equipment Inlet"
components = [
  { component_object_type = "AirLoopHVAC:ZoneSplitter", component_name = "CE Splitter" },
]

[air.loop.hvac.zone-splitter."CE Splitter"]
inlet_node_name = "CE Zone Equipment Inlet"
nodes = [
  { outlet_node_name = "CE Terminal Inlet" },
]

[air.terminal.single.duct.constant.volume.no-reheat."CE Terminal"]
availability_schedule_name = "Always On"
air_inlet_node_name = "CE Terminal Inlet"
air_outlet_node_name = "CE Zone Supply Inlet"
maximum_air_flow_rate = 1.8877777777777778

[zone.hvac.air-distribution-unit."CE ADU"]
air_distribution_unit_outlet_node_name = "CE Zone Supply Inlet"
air_terminal_object_type = "AirTerminal:SingleDuct:ConstantVolume:NoReheat"
air_terminal_name = "CE Terminal"
nominal_upstream_leakage_fraction = 0.0
constant_downstream_leakage_fraction = 0.0

[air.loop.hvac.return-path."CE Return Path"]
return_air_path_outlet_node_name = "CE Zone Equipment Outlet"
components = [
  { component_object_type = "AirLoopHVAC:ZoneMixer", component_name = "CE Mixer" },
]

[air.loop.hvac.zone-mixer."CE Mixer"]
outlet_node_name = "CE Zone Equipment Outlet"
nodes = [
  { inlet_node_name = "CE Zone Return Outlet" },
]

[zone.hvac.equipment-list."CE Equipment"]
load_distribution_scheme = "SequentialLoad"
equipment = [
  { zone_equipment_object_type = "ZoneHVAC:AirDistributionUnit", zone_equipment_name = "CE ADU", zone_equipment_cooling_sequence = 1, zone_equipment_heating_or_no_load_sequence = 1 },
]

[[zone.hvac.equipment-connections]]
zone_name = "CE Zone"
zone_conditioning_equipment_list_name = "CE Equipment"
zone_air_inlet_node_or_nodelist_name = "CE Zone Supply Inlet"
zone_air_node_name = "CE Zone Air Node"
zone_return_air_node_or_nodelist_name = "CE Zone Return Outlet"

[[output.variable]]
key_value = "Environment"
variable_name = "Site Outdoor Air Drybulb Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Environment"
variable_name = "Site Outdoor Air Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Environment"
variable_name = "Site Outdoor Air Barometric Pressure"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Zone"
variable_name = "Zone Mean Air Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Zone"
variable_name = "Zone Air Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Cooling Coil"
variable_name = "Cooling Coil Electricity Energy"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Cooling Coil"
variable_name = "Cooling Coil Runtime Fraction"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Cooling Coil"
variable_name = "Cooling Coil Total Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Cooling Coil"
variable_name = "Cooling Coil Sensible Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Cooling Coil"
variable_name = "Cooling Coil Latent Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Supply Fan"
variable_name = "Fan Electricity Energy"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Loop Inlet"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Loop Inlet"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"