MODELING NOTES FOR ASHRAE STANDARD 140 =============================================================================== INTRODUCTION =============================================================================== This document shall include supplemental information about the ASHRAE Standard 140 tests performed. One S140outNotes document shall be provided for each set of tests (e.g., one for the building thermal and fabric load tests of Section 7.2; one for the space cooling equipment analytical verification tests of Sections 9.2; etc.) The types of information listed below shall be provided in this document, each in a separate section: a. Software information b. Alternative modeling methods c. Equivalent modeling methods d. Nonspecified inputs e. Omitted test cases and results f. Changes made to source code for the purpose of running the tests, where such changes are not available in publicly released versions of the software g. Anomalous results. Notes in this document shall be limited to the topics shown above. Notes must be factual and objective and shall only refer to the software being tested. Notes shall not refer to any other software program. INFORMATIVE NOTE: Text at the start of each section describes the content of the section for the reader and provides instructions for supplying the content. Sample notes are provided in a separate document (S140outNotes_Examples.TXT). =============================================================================== A. SOFTWARE INFORMATION =============================================================================== CONTENT: This section shall include reference information for the software - the vendor, name, and version of the software, plus operating system and computer hardware requirements. INSTRUCTIONS: Information for items 1 through 7 below shall be provided. Information for Item 8 shall be permitted but is not required. 1. SOFTWARE VENDOR: Jared Bell, Roots Ontological Technologies, LLC 2. SOFTWARE NAME: SIMsara 3. SOFTWARE VERSION (unique software version identifier): SIMsara 0.1.0 4. OPERATING SYSTEM REQUIREMENTS: macOS 13 or later on Apple silicon (arm64). This is the build that was tested; other targets are listed only when they have been built and run for these tests. 5. APPROX HARD DISK SPACE REQUIRED FOR INSTALLATION: About 6.3 MB: the release binary s140_run, which needs no other runtime files beyond the TOML input and the EPW weather file. 6. MINIMUM RAM REQUIRED FOR SOFTWARE OPERATION: 16 MB: the largest peak resident memory of any submitted test case, measured with /usr/bin/time -l on the tested build. 7. MINIMUM DISPLAY MONITOR REQUIREMENTS: None. SIMsara is a command-line program with no graphical display. 8. OTHER HARDWARE OR SOFTWARE-RELATED REQUIREMENTS: Input is TOML (docs/TOML-INPUT.md in the source distribution) with EPW weather. Building from source needs Rust 1.98.1. The Standard 140 harness scripts that generate the test inputs and fill the output templates need Python 3.11 or later, standard library only. INFORMATIVE NOTE: Item 8 can be used to supply additional relevant information. =============================================================================== B. REPORT BLOCK FOR ALTERNATIVE MODELING METHODS =============================================================================== CONTENT: If the software being tested provides alternative modeling methods or algorithms for performing the tests, this section shall describe modeling methods used for the tests. INSTRUCTIONS: If alternative modeling methods are applicable, a separate note for each alternative modeling method or algorithm situation shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If alternative modeling methods are not applicable, specify "NONE" in place of the information below. NOTE 1 - Unitary System Parent (Section 5.1.1.4, 9.2.3.10 and 9.2.4.2.2) --------------------------------------------------------- 1.1 Describe the Effect Being Simulated: How the DX coil and the indoor fan follow the zone load in every case, and whether the economizer can be locked out while the compressor runs (CE410). 1.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 1.2.1 AirLoopHVAC:UnitaryHeatCool Physical Meaning: Heat-cool unitary on an air loop: supply fan, DX cooling coil and heating coil controlled to the load of one zone; it requests the economizer lockout of Controller:OutdoorAir LockoutWithCompressor whenever its compressor runs. 1.2.2 AirLoopHVAC:UnitarySystem Physical Meaning: Generic unitary system with load or setpoint control and multi-speed fans and coils; with a single-speed DX coil it does not request the economizer lockout. 1.2.3 ZoneHVAC:PackagedTerminalAirConditioner Physical Meaning: Packaged terminal unit serving the zone directly, without an air loop or an economizer. 1.3 Setting or Capability Used: AirLoopHVAC:UnitaryHeatCool in all 20 cases, CE300-CE545: one modeling method for all cases (5.1.1.4), and the parent that can model the nonintegrated compressor of CE410 (9.2.4.2.2), which needs the economizer locked out while the compressor runs. Its heating coil is never available (heat off). NOTE 2 - Cooling Coil Model (Section 9.2.3.10) --------------------------------------------------------- 2.1 Describe the Effect Being Simulated: Total, sensible and latent capacity and compressor power at each entering condition, and so every consumption, coil-load, COP2 and humidity result. 2.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 2.2.1 Coil:Cooling:DX:SingleSpeed Physical Meaning: Rated gross capacity, sensible heat ratio, COP and flow with capacity and energy-input-ratio curves of entering wet bulb and outdoor dry bulb; the sensible and latent split by the apparatus dew point and bypass factor method, with a dry-coil branch when the entering air is dry. 2.2.2 Other DX coil objects Physical Meaning: Multi-speed, variable-speed and performance-table coils (not used). 2.3 Setting or Capability Used: Coil:Cooling:DX:SingleSpeed, with the bypass factor derived by the program at the rated point and applied through the apparatus dew point method. NOTE 3 - Fan Operation and Part-Load Degradation (Section 9.2.3.10.4, 9.2.3.10.5 and 9.2.4.3.1.2) --------------------------------------------------------- 3.1 Describe the Effect Being Simulated: Indoor-fan energy, fan heat and compressor energy at part load. 3.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 3.2.1 Fan operating mode schedule Physical Meaning: 1: the supply fan runs continuously at the rated flow while the compressor cycles; 0: the fan cycles with the compressor. 3.2.2 Part-load fraction curve Physical Meaning: PLF(PLR) divides the runtime fraction of the compressor and of the fans that cycle with it. 3.3 Setting or Capability Used: Continuous fan (schedule 1) in CE300-CE440 and cycling fan (schedule 0) in CE500-CE545; the outdoor fan always cycles with the compressor. PLF = 1 - Cd (1 - PLR) with Cd 0.229, so the runtime fraction is PLR / PLF. NOTE 4 - Outdoor Air and Infiltration (Section 9.2.3.10.6, 9.2.4.1 and 9.2.4.2) --------------------------------------------------------- 4.1 Describe the Effect Being Simulated: Outdoor-air and infiltration loads of CE300-CE360, and the economizer cooling of CE400-CE440. 4.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 4.2.1 Controller:OutdoorAir Physical Meaning: Fixed or proportional minimum outdoor air with a minimum-flow schedule; economizer controls: differential dry bulb or enthalpy (outdoor against return air), fixed dry-bulb, enthalpy or dew-point limits, electronic enthalpy; modulate-flow or minimum-flow-with-bypass action; lockout with heating or with the compressor, or no lockout. 4.2.2 SetpointManager:MixedAir Physical Meaning: The mixed-air temperature the economizer holds: a reference supply setpoint less the fan temperature rise. 4.2.3 SetpointManager:SingleZone:Cooling Physical Meaning: The supply temperature that meets the zone's cooling load, between a minimum and a maximum. 4.2.4 ZoneInfiltration:DesignFlowRate Physical Meaning: Scheduled design flow with constant, temperature and wind terms. 4.3 Setting or Capability Used: A fixed minimum outdoor-air flow with its schedule; no economizer in CE300-CE360. In CE400-CE440 the economizer modulates the outdoor air between that minimum and the whole supply flow to hold a mixed-air setpoint: CE400 differential dry bulb, CE420 a fixed 20 C outdoor dry-bulb limit, CE430 differential enthalpy, CE440 differential enthalpy with a 47.25 kJ/kg outdoor enthalpy limit; no lockout. CE410 is CE400 with the economizer locked out while the compressor runs (LockoutWithCompressor): in a step where the compressor must run, the step is simulated again with the outdoor air at its minimum (decided per ten-minute step, Block C note 7). The mixed-air setpoint is the supply temperature that meets the zone's cooling load (single-zone cooling setpoint manager, 1.46-50 C) less the draw-through fan rise, so the outdoor air cools as far as the load needs and, except in CE410, the compressor meets the rest. Infiltration as a scheduled design flow with the constant term only. NOTE 5 - Surface Convection, Time Step and Initialization (Section 9.2.3.8, 9.2.3.9 and 5.1.1.7.2) --------------------------------------------------------- 5.1 Describe the Effect Being Simulated: Heat gain through the R 325 envelope, thermostat resolution, and the zone state at the start of the year. 5.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 5.2.1 Inside: Simple, TARP, CeilingDiffuser, Adaptive, ASTMC1340 Physical Meaning: Constant or correlation-based interior coefficients. 5.2.2 Outside: SimpleCombined, TARP, DOE-2, MoWiTT Physical Meaning: A combined coefficient to the outdoor air, or convection with explicit long-wave exchange. 5.2.3 Zone time steps per hour; warmup days Physical Meaning: 1 to 60 steps; warmup repeats the first day until loads and temperatures converge (up to the maximum number of warmup days). 5.3 Setting or Capability Used: TARP inside; SimpleCombined outside; 6 zone steps per hour; warmup of at least 6 and at most 50 days, starting from zone air at the outdoor conditions of January 1. In CE500-CE545 the zone has no gains, fan heat, outdoor air or infiltration before March 11, and the near-adiabatic zone does not converge within 50 warmup days (the program reports it); it floats from its warmup state until the gains begin. =============================================================================== C. REPORT BLOCK FOR EQUIVALENT MODELING METHODS =============================================================================== CONTENT: This section shall describe equivalent modeling methods used to perform the tests. When the software does not model an effect exactly as stated in the standard or does not permit the input values required, equivalent modeling methods shall be permitted to perform the test. INSTRUCTIONS: If equivalent modeling methods are applied, a separate note for each instance of equivalent modeling shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If equivalent modeling methods are not applicable, specify "NONE" in place of the information below. NOTE 1 - Unitary Split System Modeled as a Heat-Cool Unitary with Heat Always Off (Section 9.2.3.10 and Figure 9-7) ------------------------------------------------------------------------------- 1.1 Describe the Effect Being Simulated: All results. 1.2 Section(s) of the Standard where Relevant Inputs are Specified: A single-speed split air conditioner with an air-cooled condenser, an outdoor-air mixing system, a draw-through indoor fan, the outdoor fan cycling with the compressor, heat always off. 1.3 Equivalent Input(s) Used: One air loop whose branch holds an AirLoopHVAC:UnitaryHeatCool, controlled to the zone's load, in every case (one modeling method for all cases, 5.1.1.4): a Coil:Cooling:DX:SingleSpeed, then a Coil:Heating:Electric whose availability schedule is 0 all year, then a draw-through Fan:OnOff of 1242 W at the rated flow (total and motor efficiency 1, all heat to the air, 9.2.3.10.5.1.2); cooling, heating and no-load supply flows are the rated flow and dehumidification control is none. An outdoor-air system with a mixer precedes the unit in every case with outdoor air (CE300, CE310, CE330, CE340, CE350, CE360 and CE400-CE440); CE320 and CE500-CE545 have none (9.2.4.1.2.2, 9.2.4.3.1.3). A constant-volume terminal without reheat delivers the air. The thermostat is ThermostatSetpoint:SingleCooling (non-proportional, 9.2.1.10.2.4). This unit has no minimum supply air temperature input; the 1.46 C of 9.2.3.10.3.3 is entered only in CE400-CE440, as the lower limit of the economizer's supply-temperature setpoint manager. 1.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: Same components, arrangement and control as the specified unit; heating is never called for and the heating coil is never available, so it adds no energy and no load. NOTE 2 - Expanded Performance Map Fitted to Curves (Section 9.2.3.10.3 (Tables 9-16 and 9-17; CE300MAP.xls sheet ExpSI)) ------------------------------------------------------------------------------- 2.1 Describe the Effect Being Simulated: Capacity and power at every operating point. 2.2 Section(s) of the Standard where Relevant Inputs are Specified: The expanded performance map of Table 9-16 (CE300MAP.xls), its rating row and its compressor envelope; extrapolation by the program (9.2.3.10.3.1). 2.3 Equivalent Input(s) Used: The map's gross total capacity and compressor-plus-outdoor-fan power are fitted to biquadratics in entering wet bulb and outdoor dry bulb, normalized and anchored at the rating row (SIMsara's scripts/s140/fit.py, least squares), over the 31 wet-coil points inside the compressor envelope at the rated entering dry bulb of 26.67 C. Fit errors: capacity RMS 0.354 percent, maximum 0.951 percent; power RMS 0.320 percent, maximum 0.723 percent; the rated point exactly. Rated values from the map: gross capacity 33277 W, gross SHR 0.7826, coil COP 3.043 (compressor and outdoor fan), flow 1.88778 m3/s (6796 m3/h, 9.2.3.10.5.1). The flow-fraction curves are 1. The curve form has no entering dry-bulb term: at an entering dry bulb of 15.56 C the fitted model exceeds the map's wet-coil capacity by 3.8 percent on average, and at 35 C it is 1.35 percent below, which bears on CE520, CE522 and CE525; the dry-coil cases use the model's dry-coil branch. The curves are entered without clamping; the weather file has 1623 hours below the lowest fitted outdoor dry bulb (12.78 C). The bypass factor is derived by the program from the rated SHR (9.2.3.10.3.2). 2.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The curve form is the program's; the fit reproduces the map within the stated errors at the rated entering dry bulb. NOTE 3 - Weather Data Converted from TMY2 (Section 9.2.3.1 and Annex A1, A1.2.2 and Table A1-7) ------------------------------------------------------------------------------- 3.1 Describe the Effect Being Simulated: Outdoor dry bulb and humidity of every case. 3.2 Section(s) of the Standard where Relevant Inputs are Specified: CE300.TM2. 3.3 Equivalent Input(s) Used: SIMsara reads EPW. SIMsara's converter (scripts/s140/wx/tm2.py) writes CE300.TM2 as an EPW; the processed file is archived with its sha256. The location line carries the site of Table A1-7 (30.0 N, 90.3 W, time zone 6, 3 m), not the station of the file header. The program interpolates the hourly records to the ten-minute steps, so hourly means of the outdoor conditions differ slightly from the hourly records. 3.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The dry bulb and humidity are carried over unchanged (plan WP1); the annual means and maxima of outdoor dry bulb and humidity ratio lie within the weather-check tolerances. NOTE 4 - Compressor and Condenser Fan Split; Coil Loads, COP2, RH and EWB Post-Processed (Section 9.3.2 and Section 3.1 (COP2)) ------------------------------------------------------------------------------- 4.1 Describe the Effect Being Simulated: Reported compressor, condenser-fan and coil-load energies, COP2, relative humidity and entering wet bulb. 4.2 Section(s) of the Standard where Relevant Inputs are Specified: Annual, May-September, hourly-maximum, June 28 hourly and daily outputs. 4.3 Equivalent Input(s) Used: The DX coil reports one electricity energy for compressor plus outdoor fan: the condenser fan is 930 W times the coil runtime fraction times the step length, and the compressor is the remainder. The coil loads are the reported total, sensible and latent cooling rates times the step length. COP2 is the evaporator coil total load divided by the compressor plus condenser-fan energy (9.3.2.1.2): the annual and daily values are ratios of the totals, the maxima, minima and June 28 values hourly. Zone relative humidity is computed hourly from the zone air temperature and humidity ratio at the step's barometric pressure, and the entering wet bulb from the coil-inlet node state, with the program's psychrometric relations. Hourly values are the time averages or sums of the six steps; the daily outputs are the day's energies over 24 hours and the day's means (9.3.2.5). The CE500-CE545 minimum IDB and humidity ratio and the RH extremes are taken from April 1 to December 31 (9.3.2.3.2). 4.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: Exact for quantities held constant within each step; the COP2 definition reproduces the COP2 column of every example sheet from its own energy columns (within 0.32 percent). NOTE 5 - Outdoor Air, Infiltration and Internal Gain Schedules (Section 9.2.3.5, 9.2.3.6, 9.2.3.10.6 and 9.2.4.1-9.2.4.3 (Tables 9-15, 9-20 to 9-23)) ------------------------------------------------------------------------------- 5.1 Describe the Effect Being Simulated: Internal gains of every case; outdoor-air and infiltration loads of CE300-CE440. 5.2 Section(s) of the Standard where Relevant Inputs are Specified: Hourly internal gains in watts by period; outdoor air as a fraction of the supply flow; infiltration in m3/h; the CE350 set-up schedule. 5.3 Equivalent Input(s) Used: The gains are two ElectricEquipment objects (sensible, and latent with latent fraction 1), 100 percent convective, each with a design level equal to the table's largest hourly value and a Schedule:Compact of the listed watts over it, so every hour carries the listed value; April 11 and November 6 - December 31 repeat the January 1 - March 10 schedule (footnote b). The outdoor air is the controller's fixed minimum (the case's largest outdoor-air fraction times the supply flow, 15 percent = 0.28317 m3/s) times a schedule of the fraction over that peak: CE330 and CE340 rise to 100 and 50 percent from 08:00 to 20:00, April 21 - October 12. In CE400-CE440 the economizer's maximum outdoor-air flow is the supply flow. The infiltration of CE320 and CE340 is ZoneInfiltration:DesignFlowRate with the listed m3/h as a scheduled design flow (constant term only). The CE350 set point is 35 C from 00:00 to 07:00 and 20:00 to 24:00, April 21 - October 12, and 25 C otherwise. Time 0:00-8:00 in the tables is read as hours 1 to 8 (hour 1 runs from 0:00 to 1:00, 9.3.2.2.2). 5.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: As specified; the outdoor-air and infiltration mass flows use the program's air density (Block D note 1). NOTE 6 - Simulation Period (Section 5.1.1.7.2, 5.1.1.8.1 and 9.3.2) ------------------------------------------------------------------------------- 6.1 Describe the Effect Being Simulated: Annual results. 6.2 Section(s) of the Standard where Relevant Inputs are Specified: Full annual simulation with preconditioning; May-September, April-December and daily extracts. 6.3 Equivalent Input(s) Used: Run January 1 to December 31 after warmup; the extracts are taken from the annual run. 6.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: As specified. NOTE 7 - Nonintegrated Economizer of CE410 Decided per Ten-Minute Step (Section 9.2.4.2.2, 9.2.4.2.2.1 and 9.2.4.2.1.1) ------------------------------------------------------------------------------- 7.1 Describe the Effect Being Simulated: CE410: in which steps and hours the economizer and the compressor run, and so CE410's consumption, coil loads, COP2 and zone humidity. 7.2 Section(s) of the Standard where Relevant Inputs are Specified: CE410 is CE400 except that the compressor may not run while the economizer operates, and the economizer operates only when it alone can meet the whole cooling load (9.2.4.2.2 and 9.2.4.2.2.1). Economizer and compressor ON and OFF are those of CE400 and hold for the hour: the economizer ON supplies outdoor air as needed above the 15 percent minimum, OFF keeps the minimum, and the compressor OFF does not run in that hour (9.2.4.2.1.1). 7.3 Equivalent Input(s) Used: The CE400 inputs with Controller:OutdoorAir Lockout Type LockoutWithCompressor on the AirLoopHVAC:UnitaryHeatCool parent (Block B note 1). The program decides the control once per ten-minute system step, not per hour: in a step where the compressor runs, the parent requests the lockout and the step is simulated again with the outdoor air at its minimum, so the compressor meets that step's whole load; in a step where the outdoor air alone meets the load, the compressor stays off. The hour of 9.2.4.2.1.1 is read as the ten-minute step. No system step has the economizer and the compressor on together (0 of 52,928 steps), but in 357 of 8,760 hours the economizer runs above its minimum in some steps and the compressor in other steps of the same hour (CE400, whose compressor runs together with the economizer: 2,204 hours). The compressor runs 62.7 of its 2,169.0 hours of runtime in those hours. 7.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The program has no hourly control decision. Per step, the control keeps the intent of 9.2.4.2.2: the economizer runs above its minimum only when it alone meets the load, and never while the compressor runs. An hourly decision would hold the outdoor air at its minimum for the whole of each of those hours, so the compressor would also meet the load that the outdoor air meets in their economizer steps; CE410's compressor energy and coil loads are lower than an hourly decision would give by that part. =============================================================================== D. REPORT BLOCK FOR USE OF NON-SPECIFIED INPUTS =============================================================================== CONTENT: This section shall describe nonspecified inputs used to perform the tests. Use of nonspecified inputs shall be permitted only for the following specified sections relating to the following topics: * Alternative constant exterior surface coefficients in Sections 7.2.1.9.3, 7.2.3.1.4.3, 7.2.3.3.2, and 9.2.1.8 * Alternative constant interior surface coefficients in Sections 7.2.1.10.3, 7.2.3.1.4.4, 7.2.3.2.2, and 9.2.1.9 * Alternative constant interior solar distribution fractions in Sections 7.2.1.12, 7.2.2.1.2.2, 7.2.2.1.6.2, 7.2.2.1.7.2, 7.2.2.2.7.4, 7.2.3.9.3, 7.2.3.10.2, and 7.2.3.12.2 * Air density given at specific altitudes for the space-cooling and space- heating equipment cases in Sections 9.2.1.4.3, 9.2.3.4.3, and 10.2.1.4.3. INSTRUCTIONS: If nonspecified inputs are applied, a separate note for each use of nonspecified inputs shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If nonspecified inputs are not applied, specify "NONE" in place of the information below. NOTE 1 - Air Density and Envelope Inputs (Section 9.2.3.4.2, 9.2.3.4.3, 9.2.3.8, 9.2.3.9) ------------------------------------------------------------------------------- 1.1 Describe the Effect Being Simulated: Fan mass flow and power; outdoor-air and infiltration mass flow; envelope heat gain. 1.2 Section(s) of the Standard where Relevant Inputs are Specified: Air density at the site altitude; the constant combined surface coefficients. 1.3 Nonspecified Input(s) Used: The program converts the rated volume flow to mass flow with the density of dry air at 20 C and the standard pressure of the site elevation, and uses the state-dependent density elsewhere (9.2.3.4.3 lets a program that calculates air density skip the 1.201 kg/m3). The combined surface coefficients of 8.29 and 29.3 W/m2K are not entered; the envelope uses the algorithms of Block B (9.2.3.8 and 9.2.3.9), with the single R 325 insulation layer entered as two Material:NoMass layers of R 162.3 (no thermal or moisture capacitance, 9.2.3.4.2) so that the inner face carries solar absorptance 0.6 and the outer 0.1, infrared emittance 0.9 on both (Table 9-3). 1.4 Physical, Mathematical or Logical Justification for Use of the Nonspecified Input(s) � provide supporting calculations, if relevant: The insulation resistance dominates the overall U-value (0.00308 W/m2K), so the film coefficients change the envelope gain by well under 1 W. NOTE 2 - Readings of the Economizer Specification and of the Gain Tables (Section 9.2.4.2 and Tables 9-15, 9-20 to 9-23) ------------------------------------------------------------------------------- 2.1 Describe the Effect Being Simulated: CE400, CE420, CE430 and CE440; the hourly gains of every case. 2.2 Section(s) of the Standard where Relevant Inputs are Specified: The economizer and compressor control strategies of CE400, CE420, CE430 and CE440, and the listed watts against the frac v. max columns. 2.3 Nonspecified Input(s) Used: The economizer modulates the outdoor air to hold a mixed-air temperature equal to the supply temperature that meets the zone load less the fan rise, so outdoor air is supplied as needed up to 100 percent and is at 100 percent whenever the compressor must also run (9.2.4.2.1.1). CE420 uses a fixed 20 C outdoor dry-bulb limit without the return-air comparison, as its strategy list 9.2.4.2.3.1 states (with IDB above 25 C the comparison always holds). CE440 keeps the CE430 enthalpy comparison and adds the 47.25 kJ/kg outdoor limit, as 9.2.4.2.5 states (exactly as CE430 except for the limit); its strategy list 9.2.4.2.5.1 names only the limit, and the two readings differ only in hours with the return air enthalpy below the outdoor enthalpy and the outdoor enthalpy at or below the limit. The enthalpy is that of moist air per kg of dry air with dry air at 0 C as the zero, for which 47.25 kJ/kg is the SI value of 28.0 Btu/lb. The gains use the listed watts; the frac v. max columns, given for convenience, differ from them by rounding only (under 1 W). 2.4 Physical, Mathematical or Logical Justification for Use of the Nonspecified Input(s) � provide supporting calculations, if relevant: The text of 9.2.4.2 and of the table notes. =============================================================================== =============================================================================== E. REPORT BLOCK FOR OMITTED TEST CASES AND RESULTS =============================================================================== CONTENT: This section shall describe test cases that were omitted and/or individual results of test cases that were omitted along with the reason for the omission. INSTRUCTIONS: If test cases were omitted, a separate note to describe each type of omission shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If there are no omitted test cases, specify "NONE" in place of the information below. NONE =============================================================================== F. REPORT BLOCK FOR CHANGES TO SOURCE CODE FOR THE PURPOSE OF RUNNING THE TESTS, WHERE SUCH CHANGES ARE NOT AVAILABLE IN PUBLICLY RELEASED VERSIONS OF THE SOFTWARE =============================================================================== CONTENT: This section shall describe changes to software source code made to allow the software to run a test, where such changes are not available in a publicly released version of the software. INFORMATIVE NOTE: This section addresses special situations where a change to source code is necessary to activate a feature or to permit inputs needed for a test when these features are not available in the publicly released version of the software. INSTRUCTIONS: If changes to the source code for the purpose of running a test are applied, separate notes to describe each source code modification shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If changes to source code are not applied, specify "NONE" in place of the information below. NONE =============================================================================== G. REPORT BLOCK FOR ANOMALOUS RESULTS =============================================================================== CONTENT: Describing anomalous results shall be permitted but is not required. If anomalous test results are described, this section shall be used. INSTRUCTIONS: If anomalous test results are described, each type of anomalous result shall be described in a separate note. The standard format shown below and a separate number and title for each note item shall be applied. If anomalous results are not discussed, it shall be permitted to specify "NONE" in place of the information below. NOTE 1 - Zone Humidity of the Dry-Coil Cases and Its Effect on Capacity (Section 9.2.4.3 (Informative Annex B16.5.2)) ------------------------------------------------------------------------------- 1.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: CE530, CE540 and CE545: zone humidity ratio and relative humidity (annual, daily and extremes, 1.7 to 58 percent below the example results), consumption (0.6 to 3.4 percent above), indoor and condenser fan energy (3 to 9.4 percent above), COP2 (0.6 to 2.1 percent below), coil loads (0.1 to 0.3 percent above), their hourly maxima and the CE530 daily values; CE540 coil latent load (zero). 1.2 Explanation of Reason for the Anomalous Results: These cases have no latent gain, outdoor air or infiltration and the coil stays dry, so nothing adds or removes moisture: the zone humidity ratio keeps its initial value all year. The program starts the zone at the outdoor conditions of January 1 hour 1, 0.00284 kg/kg, and applies its preconditioning (5.1.1.7.2); Section 9 prescribes no initial zone humidity. The value is below the example results. The lower entering wet bulb lowers the dry-coil capacity of the fitted curves, so the unit runs longer. In a diagnostic run (not submitted; made before the WP11 view-factor fix) with a moisture source in the first week only, the CE530 zone humidity ratio is 0.0065 kg/kg, COP2 lies inside the example range and the consumption is 0.85 percent above it. The coil latent load is zero because the coil is dry. NOTE 2 - Zone Humidity of the No-Outdoor-Air Wet-Coil Cases (Section 9.2.4.3 (Informative Annex B16.5.2)) ------------------------------------------------------------------------------- 2.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: CE500, CE520, CE522 and CE525 annual mean zone humidity ratio (1.4 to 2.6 percent below) and relative humidity (4.1 to 5.3 percent below); CE500 April 30 humidity ratio; the humidity-ratio and relative-humidity extremes of CE500 to CE525 (0.6 to 14 percent outside, mostly CE520). 2.2 Explanation of Reason for the Anomalous Results: From January 1 to March 10 these cases have no gains and the zone keeps the initial humidity of Block G note 1, which lowers the annual means. The humidity during operation follows the apparatus dew point and bypass factor split at the entering dry bulb of each case; at 15 C and 20 C (CE520, CE522) the curves, fitted at 26.67 C without an entering dry-bulb term, depart from the map (Block C note 2), which moves the dehumidification and the humidity extremes. NOTE 3 - Consumption at Low Entering Dry Bulb (Section 9.2.4.3 (Informative Annex B16.5.2)) ------------------------------------------------------------------------------- 3.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: CE520 and CE522 annual consumption (0.21 and 0.22 percent above the example results) and the CE520 hourly maximum consumption (1.0 percent above). 3.2 Explanation of Reason for the Anomalous Results: The entering dry bulb of 15 C and 20 C lies below the 26.67 C at which the curves are fitted (Block C note 2); the capacity and power there are extrapolated by the curve form. NOTE 4 - Cycling Fan Energy (Section 9.2.4.3 (Informative Annex B16.5.2)) ------------------------------------------------------------------------------- 4.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: CE500 annual and May-September indoor and condenser fan energy and consumption, the CE500 June 25 daily values, and the hourly maxima of CE500, CE510 and CE525 (0.01 to 0.6 percent above the example results). 4.2 Explanation of Reason for the Anomalous Results: With a cycling fan both fans run for the runtime fraction PLR / PLF of the degradation curve (Block B note 2), so the fan energy includes the cycling loss. NOTE 5 - Results at the Thermostat Setpoint (Section 9.3.2 (Informative Annex B16.5.2)) ------------------------------------------------------------------------------- 5.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: Mean and maximum IDB and entering dry bulb at or within 0.04 percent of the edge of the example range (CE340, CE350, CE500 May-September and daily, CE530 daily, CE300 June 28). 5.2 Explanation of Reason for the Anomalous Results: The zone temperature overshoots the setpoint by less than 0.001 K within the ten-minute step, and the entering dry bulb of the continuous-fan cases carries the fan-off part of each step; the values are within 0.04 percent of the range. NOTE 6 - Hourly Maxima and CE300 June 28 Hourly Values (Section 9.3.2 (Informative Annex B16.5.2)) ------------------------------------------------------------------------------- 6.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: Hourly maxima of consumption and coil loads of CE300, CE310 and CE350 (0.01 to 0.58 percent above), the CE300 outdoor humidity maximum (0.09 percent below), the CE320 annual sensible coil load (0.46 percent below), COP2 extremes of CE300, CE310 and CE350 (0.2 to 0.3 percent), the CE350 maximum relative humidity (0.7 percent below) and CE300 June 28 hourly values (0.01 to 5.2 percent, the largest in the latent load of two hours). 6.2 Explanation of Reason for the Anomalous Results: Single hours depend on the fitted curves (fit error up to 0.95 percent, Block C note 2), on the sensible and latent split of the bypass-factor method, on the cycling of the compressor within the hour, and on the weather interpolated to ten-minute steps, so hourly outdoor values are means of the interpolated steps rather than the hourly records. NOTE 7 - Economizer Cases CE400, CE420, CE430 and CE440 (Section 9.2.4.2 (Informative Annex B16.5.2)) ------------------------------------------------------------------------------- 7.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: Hourly maxima of consumption and coil loads of CE400-CE440 (up to 0.51 percent above; the CE440 latent maximum 1.6 percent above), the annual sensible coil load of CE400 and CE420 (0.19 and 0.05 percent below), the CE440 mean relative humidity (0.04 percent below), the CE420 minimum COP2 (0.19 percent below) and the CE430 maximum relative humidity (0.11 percent above). Every annual consumption lies inside the range of the example results. 7.2 Explanation of Reason for the Anomalous Results: The hourly maxima occur in hot hours with the economizer closed, so they equal CE300's maxima, which the note Hourly Maxima and CE300 June 28 Hourly Values explains; the example ranges of these cases are narrower than CE300's. The annual sensible coil load falls because the economizer meets the sensible load of cool hours with outdoor air; the program meets exactly the load that remains, and the fitted-curve and bypass-factor effects of that note apply to it. The economizer's mixed-air setpoint and the CE420 and CE440 limit readings are those of Block D note 2. NOTE 8 - Nonintegrated Economizer Case CE410 (Section 9.2.4.2.2 (Informative Annex B16.5.2)) ------------------------------------------------------------------------------- 8.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: CE410 annual consumption, compressor and condenser fan energy and evaporator coil total load (0.05 to 1.2 percent above the example results), annual mean zone humidity ratio and relative humidity (0.6 percent below), the hourly maxima of consumption, sensible and total coil load (0.8 to 2.8 percent above), the maximum and minimum COP2 (2.9 percent above and 0.35 percent below), the maximum IDB (0.4 percent below) and the maximum humidity ratio and relative humidity (2.4 and 1.0 percent below). 8.2 Explanation of Reason for the Anomalous Results: The economizer and the compressor are decided per ten-minute step (Block C note 7): in a step where the outdoor air at up to 100 percent cannot meet the load, the step is simulated again with the outdoor air at its 15 percent minimum and the compressor meets the whole load, so no system step has both on (0 of 52,928), while in 357 of 8,760 hours the economizer runs above its minimum in some steps and the compressor in others. Against CE400 the compressor runs about 6 percent longer and the consumption is 2.8 percent higher; more of the load passes the coil, which dries the zone. The compressor takes over whenever the economizer cannot hold the set point, so the zone air never exceeds 25 C by more than 0.01 K. The hourly maxima and the minimum COP2 fall in hot hours with the economizer closed and equal CE300's (note Hourly Maxima and CE300 June 28 Hourly Values); the maximum IDB, equal to CE300's too, falls in a mild October afternoon hour in which the lockout keeps the outdoor air at its minimum while the compressor runs. The maximum COP2 and the humidity maxima are single hours of the spring, where the outdoor air the economizer brings in sets the coil's entering humidity. =============================================================================== ===============================================================================