Sections 9.2.3 to 9.2.4 · Space cooling B

Case CE545

Values compared
23
Outside example range
14
Run time
2.22 s
Input file
CE545.toml, 18.3 kB

Against the example programs

Each reported quantity next to the spread of the simulation programs published with the standard.

Position in the example range
Example rangeSIMsara
Energy Consumption Compr + Both Fans WhCE b annual hourly maxima
7,204.87,762.8
Above range
Energy Consumption Compr + Both Fans Wh, CE b annual hourly maxima: SIMsara 7,935.6 · range 7,204.8 to 7,762.8
CE b annual hourly maximaWh
18,75920,075.2
In range
CE b annual hourly maxima, Wh: SIMsara 19,576.1 · range 18,759 to 20,075.2
CE b annual hourly maximaWh
04
In range
CE b annual hourly maxima, Wh: SIMsara 4.85e-12 · range 0 to 4
Sensible + Latent WhCE b annual hourly maxima
18,76420,075.2
In range
Sensible + Latent Wh, CE b annual hourly maxima: SIMsara 19,576.1 · range 18,764 to 20,075.2
Cooling Energy Consumption Total (kWh)CE b annual results
15,687.116,635.7
Above range
Cooling Energy Consumption Total (kWh), CE b annual results: SIMsara 17,052.5 · range 15,687.1 to 16,635.7
Compressor (kWh)CE b annual results
12,621.914,764.8
In range
Compressor (kWh), CE b annual results: SIMsara 13,637.1 · range 12,621.9 to 14,764.8
Cond Fan (kWh)CE b annual results
1,301.81,337
Above range
Cond Fan (kWh), CE b annual results: SIMsara 1,462.4 · range 1,301.8 to 1,337
Indoor Fan (kWh)CE b annual results
1,5011,870.9
Above range
Indoor Fan (kWh), CE b annual results: SIMsara 1,953.0 · range 1,501 to 1,870.9
Evaporator Coil Load Total (kWh)CE b annual results
44,775.146,668
Above range
Evaporator Coil Load Total (kWh), CE b annual results: SIMsara 46,740.0 · range 44,775.1 to 46,668
Sensible (kWh)CE b annual results
44,775.146,668
Above range
Sensible (kWh), CE b annual results: SIMsara 46,740.0 · range 44,775.1 to 46,668
Latent (kWh)CE b annual results
025.500
In range
Latent (kWh), CE b annual results: SIMsara 8.19e-14 · range 0 to 25.500
CE b annual resultsCOP2
3.1573.236
Below range
CE b annual results, COP2: SIMsara 3.095 · range 3.157 to 3.236
CE b annual resultsIDB (°C)
26.60530.690
In range
CE b annual results, IDB (°C): SIMsara 27.711 · range 26.605 to 30.690
Zone Humidity Ratio (kg/kg)CE b annual results
0.0062270.007220
Below range
Zone Humidity Ratio (kg/kg), CE b annual results: SIMsara 0.002841 · range 0.006227 to 0.007220
Zone Relative Humidity (%)CE b annual results
29.20038.631
Below range
Zone Relative Humidity (%), CE b annual results: SIMsara 15.891 · range 29.200 to 38.631
CE b COP2, IDB, humidity and RH extremesCOP2
4.1564.428
Below range
CE b COP2, IDB, humidity and RH extremes, COP2: SIMsara 4.121 · range 4.156 to 4.428
CE b COP2, IDB, humidity and RH extremesCOP2
2.6602.733
Below range
CE b COP2, IDB, humidity and RH extremes, COP2: SIMsara 2.605 · range 2.660 to 2.733
CE b COP2, IDB, humidity and RH extremes°C
3535.672
In range
CE b COP2, IDB, humidity and RH extremes, °C: SIMsara 35.000 · range 35 to 35.672
CE b COP2, IDB, humidity and RH extremes°C
7.94033.010
In range
CE b COP2, IDB, humidity and RH extremes, °C: SIMsara 11.051 · range 7.940 to 33.010
CE b COP2, IDB, humidity and RH extremeskg/kg
0.0066890.01220
Below range
CE b COP2, IDB, humidity and RH extremes, kg/kg: SIMsara 0.002841 · range 0.006689 to 0.01220
CE b COP2, IDB, humidity and RH extremeskg/kg
0.0062080.007000
Below range
CE b COP2, IDB, humidity and RH extremes, kg/kg: SIMsara 0.002841 · range 0.006208 to 0.007000
CE b COP2, IDB, humidity and RH extremes%
24.14097
In range
CE b COP2, IDB, humidity and RH extremes, %: SIMsara 35.272 · range 24.140 to 97
CE b COP2, IDB, humidity and RH extremes%
17.12420.140
Below range
CE b COP2, IDB, humidity and RH extremes, %: SIMsara 8.102 · range 17.124 to 20.140
TableQuantitySIMsaraMinMaxMeanStatus
CE b annual hourly maximaEnergy Consumption Compr + Both Fans Wh7,935.67,204.87,762.87,414.3Above range
CE b annual hourly maximaDateJul 20
CE b annual hourly maximaHour15
CE b annual hourly maximaWh19,576.118,75920,075.219,470.0In range
CE b annual hourly maximaSensible DateJul 20
CE b annual hourly maximaEvaporatorCoilLoads Hour15
CE b annual hourly maximaWh4.85e-12040.6667In range
CE b annual hourly maximaLatent DateJul 15
CE b annual hourly maximaHour15
CE b annual hourly maximaSensible + Latent Wh19,576.118,76420,075.219,470.8In range
CE b annual hourly maximaDateJul 20
CE b annual hourly maximaHour15
CE b annual resultsCooling Energy Consumption Total (kWh)17,052.515,687.116,635.716,007.6Above range
CE b annual resultsCompressor (kWh)13,637.112,621.914,764.813,212.7In range
CE b annual resultsCond Fan (kWh)1,462.41,301.81,3371,323.6Above range
CE b annual resultsIndoor Fan (kWh)1,953.01,5011,870.91,691.7Above range
CE b annual resultsEvaporator Coil Load Total (kWh)46,740.044,775.146,66845,918.7Above range
CE b annual resultsSensible (kWh)46,740.044,775.146,66845,910.2Above range
CE b annual resultsLatent (kWh)8.19e-14025.5008.501In range
CE b annual resultsCOP23.0953.1573.2363.207Below range
CE b annual resultsIDB (°C)27.71126.60530.69027.823In range
CE b annual resultsZone Humidity Ratio (kg/kg)0.0028410.0062270.0072200.006732Below range
CE b annual resultsZone Relative Humidity (%)15.89129.20038.63135.333Below range
CE b COP2, IDB, humidity and RH extremesCOP24.1214.1564.4284.241Below range
CE b COP2, IDB, humidity and RH extremesMaximum DateMar 16
CE b COP2, IDB, humidity and RH extremesC O P 2 Hour10
CE b COP2, IDB, humidity and RH extremesCOP22.6052.6602.7332.708Below range
CE b COP2, IDB, humidity and RH extremesMinimum DateJul 30
CE b COP2, IDB, humidity and RH extremesHour12
CE b COP2, IDB, humidity and RH extremes°C35.0003535.67235.112In range
CE b COP2, IDB, humidity and RH extremesIndoor Drybulb Temperature Maximum DateJul 8
CE b COP2, IDB, humidity and RH extremesHour18
CE b COP2, IDB, humidity and RH extremes°C11.0517.94033.01012.520In range
CE b COP2, IDB, humidity and RH extremesMinimum* DateDec 21
CE b COP2, IDB, humidity and RH extremesHour6
CE b COP2, IDB, humidity and RH extremeskg/kg0.0028410.0066890.012200.008747Below range
CE b COP2, IDB, humidity and RH extremesHumidity Ratio Maximum DateDec 31
CE b COP2, IDB, humidity and RH extremesHour12
CE b COP2, IDB, humidity and RH extremeskg/kg0.0028410.0062080.0070000.006667Below range
CE b COP2, IDB, humidity and RH extremesMinimum* DateApr 1
CE b COP2, IDB, humidity and RH extremesHour10
CE b COP2, IDB, humidity and RH extremes%35.27224.1409777.063In range
CE b COP2, IDB, humidity and RH extremesRelative Humidity Maximum* DateDec 20
CE b COP2, IDB, humidity and RH extremesHour11
CE b COP2, IDB, humidity and RH extremes%8.10217.12420.14018.873Below range
CE b COP2, IDB, humidity and RH extremesMinimum* DateApr 18
CE b COP2, IDB, humidity and RH extremesHour17

Reported outputs

The values the engine wrote for this case, before they are placed in the output template.

OutputValue
Annual · total (kWh)17,052.5
Annual · compressor (kWh)13,637.1
Annual · cond fan (kWh)1,462.4
Annual · indoor fan (kWh)1,953.0
Annual · coil total (kWh)46,740.0
Annual · coil sensible (kWh)46,740.0
Annual · coil latent (kWh)8.19e-14
Annual · cop2 mean3.095
Annual · idb mean27.711
Annual · w mean0.002841
Annual · rh mean15.891
Annual · odb mean19.914
Annual · ow mean0.01161
Annual · edb mean27.713
Annual · hours8,760
Maxima · total · value7,935.6
Maxima · total · month7
Maxima · total · day20
Maxima · total · hour15
Maxima · total · date37,092
Maxima · total · monJul
Maxima · cs · value19,576.1
Maxima · cs · month7
Maxima · cs · day20
Maxima · cs · hour15
Maxima · cs · date37,092
Maxima · cs · monJul
Maxima · cl · value4.85e-12
Maxima · cl · month7
Maxima · cl · day15
Maxima · cl · hour15
Maxima · cl · date37,087
Maxima · cl · monJul
Maxima · ct · value19,576.1
Maxima · ct · month7
Maxima · ct · day20
Maxima · ct · hour15
Maxima · ct · date37,092
Maxima · ct · monJul
Extremes · cop2 max · value4.121
Extremes · cop2 max · month3
Extremes · cop2 max · day16
Extremes · cop2 max · hour10
Extremes · cop2 max · date36,966
Extremes · cop2 max · monMar
Extremes · cop2 min · value2.605
Extremes · cop2 min · month7
Extremes · cop2 min · day30
Extremes · cop2 min · hour12
Extremes · cop2 min · date37,102
Extremes · cop2 min · monJul
Extremes · idb max · value35.000
Extremes · idb max · month7
Extremes · idb max · day8
Extremes · idb max · hour18
Extremes · idb max · date37,080
Extremes · idb max · monJul
Extremes · idb min · value11.051
Extremes · idb min · month12
Extremes · idb min · day21
Extremes · idb min · hour6
Extremes · idb min · date37,246
Extremes · idb min · monDec
Extremes · w max · value0.002841
Extremes · w max · month12
Extremes · w max · day31
Extremes · w max · hour12
Extremes · w max · date37,256
Extremes · w max · monDec
Extremes · w min · value0.002841
Extremes · w min · month4
Extremes · w min · day1
Extremes · w min · hour10
Extremes · w min · date36,982
Extremes · w min · monApr
Extremes · rh max · value35.272
Extremes · rh max · month12
Extremes · rh max · day20
Extremes · rh max · hour11
Extremes · rh max · date37,245
Extremes · rh max · monDec
Extremes · rh min · value8.102
Extremes · rh min · month4
Extremes · rh min · day18
Extremes · rh min · hour17
Extremes · rh min · date36,999
Extremes · rh min · monApr
Extreme window apr dectrue
Hours above setpoint 0p5k0

Input file

sha256 2a014084481f6b81e5b398f9ac0de2422e31630e67b2ee2ee439c08228aa659d

CE545.tomlDownload
[version]
version_identifier = "26.1"

[simulation-control]
do_zone_sizing_calculation = "No"
do_system_sizing_calculation = "No"
do_plant_sizing_calculation = "No"
run_simulation_for_sizing_periods = "No"
run_simulation_for_weather_file_run_periods = "Yes"
do_hvac_sizing_simulation_for_sizing_periods = "No"
maximum_number_of_hvac_sizing_simulation_passes = 1

[building."Standard 140 CE545 (SIMsara)"]
north_axis = 0.0
terrain = "Suburbs"
loads_convergence_tolerance_value = 0.04
temperature_convergence_tolerance_value = 0.004
solar_distribution = "MinimalShadowing"
maximum_number_of_warmup_days = 50
minimum_number_of_warmup_days = 6

[timestep]
number_of_timesteps_per_hour = 6

[heat-balance-algorithm]
algorithm = "ConductionTransferFunction"

[surface.convection.algorithm.inside]
algorithm = "TARP"

[surface.convection.algorithm.outside]
algorithm = "SimpleCombined"

[global-geometry-rules]
starting_vertex_position = "UpperLeftCorner"
vertex_entry_direction = "Counterclockwise"
coordinate_system = "Relative"

[site.location."CE b Site"]
latitude = 30.0
longitude = -90.3
time_zone = -6.0
elevation = 3.0

[schedule-type-limits."Fraction"]
lower_limit_value = 0.0
upper_limit_value = 1.0
numeric_type = "Continuous"

[schedule-type-limits."Any Number"]

[schedule-type-limits."Temperature"]
lower_limit_value = -60.0
upper_limit_value = 200.0
numeric_type = "Continuous"
unit_type = "Temperature"

[schedule-type-limits."Control Type"]
lower_limit_value = 0.0
upper_limit_value = 4.0
numeric_type = "Discrete"

[schedule.compact."Always On"]
schedule_type_limits_name = "Fraction"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 1.0 },
]

[schedule.compact."Cooling Only Control"]
schedule_type_limits_name = "Control Type"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 2.0 },
]

[schedule.compact."CE Sensible Gain Schedule"]
schedule_type_limits_name = "Fraction"
data = [
  { field = "Through: 3/10" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 0.0 },
  { field = "Through: 4/10" },
  { field = "For: AllDays" },
  { field = "Until: 09:00" },
  { field = 0.0 },
  { field = "Until: 16:00" },
  { field = 0.3749866723531293 },
  { field = "Until: 24:00" },
  { field = 0.0 },
  { field = "Through: 4/11" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 0.0 },
  { field = "Through: 4/20" },
  { field = "For: AllDays" },
  { field = "Until: 08:00" },
  { field = 0.0 },
  { field = "Until: 17:00" },
  { field = 0.5 },
  { field = "Until: 24:00" },
  { field = 0.0 },
  { field = "Through: 10/11" },
  { field = "For: AllDays" },
  { field = "Until: 08:00" },
  { field = 0.3749866723531293 },
  { field = "Until: 12:00" },
  { field = 0.5 },
  { field = "Until: 14:00" },
  { field = 0.7500266552937414 },
  { field = "Until: 16:00" },
  { field = 1.0 },
  { field = "Until: 20:00" },
  { field = 0.5 },
  { field = "Until: 24:00" },
  { field = 0.3749866723531293 },
  { field = "Through: 10/18" },
  { field = "For: AllDays" },
  { field = "Until: 08:00" },
  { field = 0.0 },
  { field = "Until: 14:00" },
  { field = 0.5 },
  { field = "Until: 24:00" },
  { field = 0.0 },
  { field = "Through: 11/5" },
  { field = "For: AllDays" },
  { field = "Until: 08:00" },
  { field = 0.0 },
  { field = "Until: 12:00" },
  { field = 0.5 },
  { field = "Until: 14:00" },
  { field = 0.7500266552937414 },
  { field = "Until: 16:00" },
  { field = 1.0 },
  { field = "Until: 20:00" },
  { field = 0.5 },
  { field = "Until: 24:00" },
  { field = 0.3749866723531293 },
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 0.0 },
]

[schedule.compact."Cooling Setpoint"]
schedule_type_limits_name = "Temperature"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 35.0 },
]

[schedule.compact."CE Fan Mode"]
schedule_type_limits_name = "Any Number"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 0.0 },
]

[schedule.compact."CE Heating Off"]
schedule_type_limits_name = "Fraction"
data = [
  { field = "Through: 12/31" },
  { field = "For: AllDays" },
  { field = "Until: 24:00" },
  { field = 0.0 },
]

[material.no-mass."CE Insulation Outer Half"]
roughness = "VerySmooth"
thermal_resistance = 162.33766233766235
thermal_absorptance = 0.9
solar_absorptance = 0.1
visible_absorptance = 0.1

[material.no-mass."CE Insulation Inner Half"]
roughness = "VerySmooth"
thermal_resistance = 162.33766233766235
thermal_absorptance = 0.9
solar_absorptance = 0.6
visible_absorptance = 0.6

[construction."CE Envelope"]
outside_layer = "CE Insulation Outer Half"
layer_2 = "CE Insulation Inner Half"

[output.variable-dictionary."Output:VariableDictionary"]
key_field = "IDF"

[run-period."CE545"]
begin_month = 1
begin_day_of_month = 1
end_month = 12
end_day_of_month = 31
day_of_week_for_start_day = "Sunday"
use_weather_file_holidays_and_special_days = "No"
use_weather_file_daylight_saving_period = "No"
apply_weekend_holiday_rule = "No"
use_weather_file_rain_indicators = "Yes"
use_weather_file_snow_indicators = "Yes"

[building.surface.detailed."CE Zone South Wall"]
surface_type = "Wall"
zone_name = "CE Zone"
construction_name = "CE Envelope"
outside_boundary_condition = "Outdoors"
sun_exposure = "SunExposed"
wind_exposure = "WindExposed"
view_factor_to_ground = 0.5
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 },
]

[building.surface.detailed."CE Zone East Wall"]
surface_type = "Wall"
zone_name = "CE Zone"
construction_name = "CE Envelope"
outside_boundary_condition = "Outdoors"
sun_exposure = "SunExposed"
wind_exposure = "WindExposed"
view_factor_to_ground = 0.5
vertices = [
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 },
]

[building.surface.detailed."CE Zone North Wall"]
surface_type = "Wall"
zone_name = "CE Zone"
construction_name = "CE Envelope"
outside_boundary_condition = "Outdoors"
sun_exposure = "SunExposed"
wind_exposure = "WindExposed"
view_factor_to_ground = 0.5
vertices = [
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 },
]

[building.surface.detailed."CE Zone West Wall"]
surface_type = "Wall"
zone_name = "CE Zone"
construction_name = "CE Envelope"
outside_boundary_condition = "Outdoors"
sun_exposure = "SunExposed"
wind_exposure = "WindExposed"
view_factor_to_ground = 0.5
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 },
]

[building.surface.detailed."CE Zone Floor"]
surface_type = "Floor"
zone_name = "CE Zone"
construction_name = "CE Envelope"
outside_boundary_condition = "Outdoors"
sun_exposure = "SunExposed"
wind_exposure = "WindExposed"
view_factor_to_ground = 0.0
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 },
]

[building.surface.detailed."CE Zone Roof"]
surface_type = "Roof"
zone_name = "CE Zone"
construction_name = "CE Envelope"
outside_boundary_condition = "Outdoors"
sun_exposure = "SunExposed"
wind_exposure = "WindExposed"
view_factor_to_ground = 0.0
vertices = [
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 },
  { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 },
]

[zone."CE Zone"]
direction_of_relative_north = 0.0
x_origin = 0.0
y_origin = 0.0
z_origin = 0.0
type = 1
multiplier = 1
ceiling_height = 3.0
volume = 588.0
floor_area = 196.0
part_of_total_floor_area = "Yes"

[electric-equipment."CE Sensible Gains"]
zone_or_zonelist_or_space_or_spacelist_name = "CE Zone"
schedule_name = "CE Sensible Gain Schedule"
design_level_calculation_method = "EquipmentLevel"
design_level = 18758.0
fraction_latent = 0.0
fraction_radiant = 0.0
fraction_lost = 0.0
end_use_subcategory = "General"

[thermostat.setpoint.single-cooling."CE Cooling Setpoint"]
setpoint_temperature_schedule_name = "Cooling Setpoint"

[zone.control.thermostat."CE Thermostat"]
zone_or_zonelist_name = "CE Zone"
control_type_schedule_name = "Cooling Only Control"
control_1_object_type = "ThermostatSetpoint:SingleCooling"
control_1_name = "CE Cooling Setpoint"

[air-loop-hvac."CE Air Loop"]
availability_manager_list_name = "CE Availability"
design_supply_air_flow_rate = 1.8877777777777778
branch_list_name = "CE Branches"
supply_side_inlet_node_name = "CE Loop Inlet"
demand_side_outlet_node_name = "CE Zone Equipment Outlet"
demand_side_inlet_node_names = "CE Zone Equipment Inlet"
supply_side_outlet_node_names = "CE Loop Outlet"
design_return_air_flow_fraction_of_supply_air_flow = 1.0

[branch-list."CE Branches"]
branches = [
  { branch_name = "CE Main Branch" },
]

[branch."CE Main Branch"]
components = [
  { component_object_type = "AirLoopHVAC:UnitaryHeatCool", component_name = "CE Unitary", component_inlet_node_name = "CE Loop Inlet", component_outlet_node_name = "CE Loop Outlet" },
]

[availability-manager-assignment-list."CE Availability"]
managers = [
  { availability_manager_object_type = "AvailabilityManager:Scheduled", availability_manager_name = "CE Avail" },
]

[availability.manager.scheduled."CE Avail"]
schedule_name = "Always On"

[air.loop.hvac.unitary-heat-cool."CE Unitary"]
availability_schedule_name = "Always On"
unitary_system_air_inlet_node_name = "CE Loop Inlet"
unitary_system_air_outlet_node_name = "CE Loop Outlet"
supply_air_fan_operating_mode_schedule_name = "CE Fan Mode"
maximum_supply_air_temperature = 50.0
cooling_supply_air_flow_rate = 1.8877777777777778
heating_supply_air_flow_rate = 1.8877777777777778
no_load_supply_air_flow_rate = 1.8877777777777778
controlling_zone_or_thermostat_location = "CE Zone"
supply_fan_object_type = "Fan:OnOff"
supply_fan_name = "CE Supply Fan"
fan_placement = "DrawThrough"
heating_coil_object_type = "Coil:Heating:Electric"
heating_coil_name = "CE Heating Coil"
cooling_coil_object_type = "Coil:Cooling:DX:SingleSpeed"
cooling_coil_name = "CE Cooling Coil"
dehumidification_control_type = "None"

[coil.heating.electric."CE Heating Coil"]
availability_schedule_name = "CE Heating Off"
efficiency = 1.0
nominal_capacity = 1000.0
air_inlet_node_name = "CE Coil Outlet"
air_outlet_node_name = "CE Heating Coil Outlet"

[curve.biquadratic."CE b CapFT"]
coefficient1_constant = 0.8421792790769599
coefficient2_x = 0.013597330340468002
coefficient3_x_2 = 0.0005425555274330542
coefficient4_y = -0.0046779772346486545
coefficient5_y_2 = -1.892890987340474e-05
coefficient6_x_y = -0.0001833613310964283
minimum_value_of_x = -20.0
maximum_value_of_x = 50.0
minimum_value_of_y = -20.0
maximum_value_of_y = 60.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.biquadratic."CE b EIRFT"]
coefficient1_constant = 0.6296349141804827
coefficient2_x = -0.01194173030834857
coefficient3_x_2 = 0.00013564228411874153
coefficient4_y = 0.014620794633169055
coefficient5_y_2 = 0.0001647879385125572
coefficient6_x_y = -0.00023849947842266334
minimum_value_of_x = -20.0
maximum_value_of_x = 50.0
minimum_value_of_y = -20.0
maximum_value_of_y = 60.0
input_unit_type_for_x = "Temperature"
input_unit_type_for_y = "Temperature"
output_unit_type = "Dimensionless"

[curve.quadratic."CE b CapFFF"]
coefficient1_constant = 1.0
coefficient2_x = 0.0
coefficient3_x_2 = 0.0
minimum_value_of_x = 0.0
maximum_value_of_x = 1.5

[curve.quadratic."CE b EIRFFF"]
coefficient1_constant = 1.0
coefficient2_x = 0.0
coefficient3_x_2 = 0.0
minimum_value_of_x = 0.0
maximum_value_of_x = 1.5

[curve.quadratic."CE b PLF"]
coefficient1_constant = 0.771
coefficient2_x = 0.229
coefficient3_x_2 = 0.0
minimum_value_of_x = 0.0
maximum_value_of_x = 1.0

[coil.cooling.dx.single-speed."CE Cooling Coil"]
availability_schedule_name = "Always On"
gross_rated_total_cooling_capacity = 33277.1085
gross_rated_sensible_heat_ratio = 0.7825956753424054
gross_rated_cooling_cop = 3.0426175825180586
rated_air_flow_rate = 1.8877777777777778
air_inlet_node_name = "CE Loop Inlet"
air_outlet_node_name = "CE Coil Outlet"
total_cooling_capacity_function_of_temperature_curve_name = "CE b CapFT"
total_cooling_capacity_function_of_flow_fraction_curve_name = "CE b CapFFF"
energy_input_ratio_function_of_temperature_curve_name = "CE b EIRFT"
energy_input_ratio_function_of_flow_fraction_curve_name = "CE b EIRFFF"
part_load_fraction_correlation_curve_name = "CE b PLF"
minimum_outdoor_dry_bulb_temperature_for_compressor_operation = -25.0
nominal_time_for_condensate_removal_to_begin = 0.0
ratio_of_initial_moisture_evaporation_rate_and_steady_state_latent_capacity = 0.0
maximum_cycling_rate = 0.0
latent_capacity_time_constant = 0.0
condenser_type = "AirCooled"
crankcase_heater_capacity = 0.0
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater_operation = 10.0

[fan.on-off."CE Supply Fan"]
availability_schedule_name = "Always On"
fan_total_efficiency = 1.0
pressure_rise = 657.9164214243673
maximum_flow_rate = 1.8877777777777778
motor_efficiency = 1.0
motor_in_airstream_fraction = 1.0
air_inlet_node_name = "CE Heating Coil Outlet"
air_outlet_node_name = "CE Loop Outlet"
end_use_subcategory = "General"

[air.loop.hvac.supply-path."CE Supply Path"]
supply_air_path_inlet_node_name = "CE Zone Equipment Inlet"
components = [
  { component_object_type = "AirLoopHVAC:ZoneSplitter", component_name = "CE Splitter" },
]

[air.loop.hvac.zone-splitter."CE Splitter"]
inlet_node_name = "CE Zone Equipment Inlet"
nodes = [
  { outlet_node_name = "CE Terminal Inlet" },
]

[air.terminal.single.duct.constant.volume.no-reheat."CE Terminal"]
availability_schedule_name = "Always On"
air_inlet_node_name = "CE Terminal Inlet"
air_outlet_node_name = "CE Zone Supply Inlet"
maximum_air_flow_rate = 1.8877777777777778

[zone.hvac.air-distribution-unit."CE ADU"]
air_distribution_unit_outlet_node_name = "CE Zone Supply Inlet"
air_terminal_object_type = "AirTerminal:SingleDuct:ConstantVolume:NoReheat"
air_terminal_name = "CE Terminal"
nominal_upstream_leakage_fraction = 0.0
constant_downstream_leakage_fraction = 0.0

[air.loop.hvac.return-path."CE Return Path"]
return_air_path_outlet_node_name = "CE Zone Equipment Outlet"
components = [
  { component_object_type = "AirLoopHVAC:ZoneMixer", component_name = "CE Mixer" },
]

[air.loop.hvac.zone-mixer."CE Mixer"]
outlet_node_name = "CE Zone Equipment Outlet"
nodes = [
  { inlet_node_name = "CE Zone Return Outlet" },
]

[zone.hvac.equipment-list."CE Equipment"]
load_distribution_scheme = "SequentialLoad"
equipment = [
  { zone_equipment_object_type = "ZoneHVAC:AirDistributionUnit", zone_equipment_name = "CE ADU", zone_equipment_cooling_sequence = 1, zone_equipment_heating_or_no_load_sequence = 1 },
]

[[zone.hvac.equipment-connections]]
zone_name = "CE Zone"
zone_conditioning_equipment_list_name = "CE Equipment"
zone_air_inlet_node_or_nodelist_name = "CE Zone Supply Inlet"
zone_air_node_name = "CE Zone Air Node"
zone_return_air_node_or_nodelist_name = "CE Zone Return Outlet"

[[output.variable]]
key_value = "Environment"
variable_name = "Site Outdoor Air Drybulb Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Environment"
variable_name = "Site Outdoor Air Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "Environment"
variable_name = "Site Outdoor Air Barometric Pressure"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Zone"
variable_name = "Zone Mean Air Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Zone"
variable_name = "Zone Air Humidity Ratio"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Cooling Coil"
variable_name = "Cooling Coil Electricity Energy"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Cooling Coil"
variable_name = "Cooling Coil Runtime Fraction"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Cooling Coil"
variable_name = "Cooling Coil Total Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Cooling Coil"
variable_name = "Cooling Coil Sensible Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Cooling Coil"
variable_name = "Cooling Coil Latent Cooling Rate"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Supply Fan"
variable_name = "Fan Electricity Energy"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Loop Inlet"
variable_name = "System Node Temperature"
reporting_frequency = "Timestep"

[[output.variable]]
key_value = "CE Loop Inlet"
variable_name = "System Node Humidity Ratio"
reporting_frequency = "Timestep"
← CE54020 of 20