Sections 9.2.3 to 9.2.4 · Space cooling B
Case CE510
- Values compared
- 23
- Outside example range
- 2
- Run time
- 1.16 s
- Input file
- CE510.toml, 20.1 kB
Against the example programs
Each reported quantity next to the spread of the simulation programs published with the standard.
Position in the example range
Example rangeSIMsara
Energy Consumption Compr + Both Fans WhCE b annual hourly maxima
11,18611,590
In rangeEnergy Consumption Compr + Both Fans Wh, CE b annual hourly maxima: SIMsara 11,454.8 · range 11,186 to 11,590
CE b annual hourly maximaWh
21,12122,513
In rangeCE b annual hourly maxima, Wh: SIMsara 22,237.7 · range 21,121 to 22,513
CE b annual hourly maximaWh
8,7238,954.8
Above rangeCE b annual hourly maxima, Wh: SIMsara 8,955.6 · range 8,723 to 8,954.8
Sensible + Latent WhCE b annual hourly maxima
29,94831,188
In rangeSensible + Latent Wh, CE b annual hourly maxima: SIMsara 31,111.4 · range 29,948 to 31,188
CE510 MAY-SEP · Cooling Energy Consumption Total (kWh)CE b annual results
34,608.835,971
In rangeCE510 MAY-SEP · Cooling Energy Consumption Total (kWh), CE b annual results: SIMsara 35,811.2 · range 34,608.8 to 35,971
CE510 MAY-SEP · Compressor (kWh)CE b annual results
27,747.931,669.2
In rangeCE510 MAY-SEP · Compressor (kWh), CE b annual results: SIMsara 28,674.7 · range 27,747.9 to 31,669.2
CE510 MAY-SEP · Cond Fan (kWh)CE b annual results
2,937.73,061
In rangeCE510 MAY-SEP · Cond Fan (kWh), CE b annual results: SIMsara 3,055.7 · range 2,937.7 to 3,061
CE510 MAY-SEP · Indoor Fan (kWh)CE b annual results
3,923.24,099
In rangeCE510 MAY-SEP · Indoor Fan (kWh), CE b annual results: SIMsara 4,080.8 · range 3,923.2 to 4,099
CE510 MAY-SEP · Evaporator Coil Load Total (kWh)CE b annual results
108,974114,018
In rangeCE510 MAY-SEP · Evaporator Coil Load Total (kWh), CE b annual results: SIMsara 112,822 · range 108,974 to 114,018
CE510 MAY-SEP · Sensible (kWh)CE b annual results
77,489.482,305.7
In rangeCE510 MAY-SEP · Sensible (kWh), CE b annual results: SIMsara 81,341.9 · range 77,489.4 to 82,305.7
CE510 MAY-SEP · Latent (kWh)CE b annual results
31,21731,712.2
In rangeCE510 MAY-SEP · Latent (kWh), CE b annual results: SIMsara 31,479.6 · range 31,217 to 31,712.2
CE510 MAY-SEP · COP2CE b annual results
3.5303.577
In rangeCE510 MAY-SEP · COP2, CE b annual results: SIMsara 3.556 · range 3.530 to 3.577
CE510 MAY-SEP · IDB (°C)CE b annual results
24.96025.817
In rangeCE510 MAY-SEP · IDB (°C), CE b annual results: SIMsara 25.000 · range 24.960 to 25.817
CE510 MAY-SEP · Zone Humidity Ratio (kg/kg)CE b annual results
0.010900.01140
In rangeCE510 MAY-SEP · Zone Humidity Ratio (kg/kg), CE b annual results: SIMsara 0.01099 · range 0.01090 to 0.01140
CE510 MAY-SEP · Zone Relative Humidity (%)CE b annual results
54.70057.436
In rangeCE510 MAY-SEP · Zone Relative Humidity (%), CE b annual results: SIMsara 55.566 · range 54.700 to 57.436
CE b COP2, IDB, humidity and RH extremesCOP2
4.5307.367
In rangeCE b COP2, IDB, humidity and RH extremes, COP2: SIMsara 4.704 · range 4.530 to 7.367
CE b COP2, IDB, humidity and RH extremesCOP2
2.6522.900
In rangeCE b COP2, IDB, humidity and RH extremes, COP2: SIMsara 2.781 · range 2.652 to 2.900
CE b COP2, IDB, humidity and RH extremes°C
25.00026.100
In rangeCE b COP2, IDB, humidity and RH extremes, °C: SIMsara 25.009 · range 25.000 to 26.100
CE b COP2, IDB, humidity and RH extremes°C
7.94024.040
In rangeCE b COP2, IDB, humidity and RH extremes, °C: SIMsara 11.010 · range 7.940 to 24.040
CE b COP2, IDB, humidity and RH extremeskg/kg
0.011500.01190
Below rangeCE b COP2, IDB, humidity and RH extremes, kg/kg: SIMsara 0.01138 · range 0.01150 to 0.01190
CE b COP2, IDB, humidity and RH extremeskg/kg
0.0068280.01050
In rangeCE b COP2, IDB, humidity and RH extremes, kg/kg: SIMsara 0.008094 · range 0.006828 to 0.01050
CE b COP2, IDB, humidity and RH extremes%
57.510100
In rangeCE b COP2, IDB, humidity and RH extremes, %: SIMsara 100 · range 57.510 to 100
CE b COP2, IDB, humidity and RH extremes%
52.08855.288
In rangeCE b COP2, IDB, humidity and RH extremes, %: SIMsara 53.248 · range 52.088 to 55.288
| Table | Quantity | SIMsara | Min | Max | Mean | Status |
|---|---|---|---|---|---|---|
| CE b annual hourly maxima | Energy Consumption Compr + Both Fans Wh | 11,454.8 | 11,186 | 11,590 | 11,387.0 | In range |
| CE b annual hourly maxima | Date | Jul 20 | ||||
| CE b annual hourly maxima | Hour | 15 | ||||
| CE b annual hourly maxima | Wh | 22,237.7 | 21,121 | 22,513 | 22,072.6 | In range |
| CE b annual hourly maxima | Sensible Date | Jul 20 | ||||
| CE b annual hourly maxima | EvaporatorCoilLoads Hour | 15 | ||||
| CE b annual hourly maxima | Wh | 8,955.6 | 8,723 | 8,954.8 | 8,836.2 | Above range |
| CE b annual hourly maxima | Latent Date | Jun 17 | ||||
| CE b annual hourly maxima | Hour | 14 | ||||
| CE b annual hourly maxima | Sensible + Latent Wh | 31,111.4 | 29,948 | 31,188 | 30,865.3 | In range |
| CE b annual hourly maxima | Date | Jun 17 | ||||
| CE b annual hourly maxima | Hour | 14 | ||||
| CE b annual results | CE510 MAY-SEP · Cooling Energy Consumption Total (kWh) | 35,811.2 | 34,608.8 | 35,971 | 35,496.0 | In range |
| CE b annual results | CE510 MAY-SEP · Compressor (kWh) | 28,674.7 | 27,747.9 | 31,669.2 | 28,943.5 | In range |
| CE b annual results | CE510 MAY-SEP · Cond Fan (kWh) | 3,055.7 | 2,937.7 | 3,061 | 3,016.8 | In range |
| CE b annual results | CE510 MAY-SEP · Indoor Fan (kWh) | 4,080.8 | 3,923.2 | 4,099 | 4,038.3 | In range |
| CE b annual results | CE510 MAY-SEP · Evaporator Coil Load Total (kWh) | 112,822 | 108,974 | 114,018 | 111,927 | In range |
| CE b annual results | CE510 MAY-SEP · Sensible (kWh) | 81,341.9 | 77,489.4 | 82,305.7 | 80,454.4 | In range |
| CE b annual results | CE510 MAY-SEP · Latent (kWh) | 31,479.6 | 31,217 | 31,712.2 | 31,472.1 | In range |
| CE b annual results | CE510 MAY-SEP · COP2 | 3.556 | 3.530 | 3.577 | 3.558 | In range |
| CE b annual results | CE510 MAY-SEP · IDB (°C) | 25.000 | 24.960 | 25.817 | 25.166 | In range |
| CE b annual results | CE510 MAY-SEP · Zone Humidity Ratio (kg/kg) | 0.01099 | 0.01090 | 0.01140 | 0.01129 | In range |
| CE b annual results | CE510 MAY-SEP · Zone Relative Humidity (%) | 55.566 | 54.700 | 57.436 | 56.526 | In range |
| CE b COP2, IDB, humidity and RH extremes | COP2 | 4.704 | 4.530 | 7.367 | 5.211 | In range |
| CE b COP2, IDB, humidity and RH extremes | Maximum Date | Oct 5 | ||||
| CE b COP2, IDB, humidity and RH extremes | C O P 2 Hour | 1 | ||||
| CE b COP2, IDB, humidity and RH extremes | COP2 | 2.781 | 2.652 | 2.900 | 2.834 | In range |
| CE b COP2, IDB, humidity and RH extremes | Minimum Date | Mar 31 | ||||
| CE b COP2, IDB, humidity and RH extremes | Hour | 17 | ||||
| CE b COP2, IDB, humidity and RH extremes | °C | 25.009 | 25.000 | 26.100 | 25.223 | In range |
| CE b COP2, IDB, humidity and RH extremes | Indoor Drybulb Temperature Maximum Date | Jul 30 | ||||
| CE b COP2, IDB, humidity and RH extremes | Hour | 15 | ||||
| CE b COP2, IDB, humidity and RH extremes | °C | 11.010 | 7.940 | 24.040 | 11.009 | In range |
| CE b COP2, IDB, humidity and RH extremes | Minimum* Date | Dec 21 | ||||
| CE b COP2, IDB, humidity and RH extremes | Hour | 6 | ||||
| CE b COP2, IDB, humidity and RH extremes | kg/kg | 0.01138 | 0.01150 | 0.01190 | 0.01176 | Below range |
| CE b COP2, IDB, humidity and RH extremes | Humidity Ratio Maximum Date | Jul 20 | ||||
| CE b COP2, IDB, humidity and RH extremes | Hour | 15 | ||||
| CE b COP2, IDB, humidity and RH extremes | kg/kg | 0.008094 | 0.006828 | 0.01050 | 0.007810 | In range |
| CE b COP2, IDB, humidity and RH extremes | Minimum* Date | Dec 20 | ||||
| CE b COP2, IDB, humidity and RH extremes | Hour | 12 | ||||
| CE b COP2, IDB, humidity and RH extremes | % | 100 | 57.510 | 100 | 89.377 | In range |
| CE b COP2, IDB, humidity and RH extremes | Relative Humidity Maximum* Date | Dec 12 | ||||
| CE b COP2, IDB, humidity and RH extremes | Hour | 20 | ||||
| CE b COP2, IDB, humidity and RH extremes | % | 53.248 | 52.088 | 55.288 | 53.632 | In range |
| CE b COP2, IDB, humidity and RH extremes | Minimum* Date | May 4 | ||||
| CE b COP2, IDB, humidity and RH extremes | Hour | 4 |
Reported outputs
The values the engine wrote for this case, before they are placed in the output template.
| Output | Value |
|---|---|
| Annual · total (kWh) | 43,154.2 |
| Annual · compressor (kWh) | 34,483.4 |
| Annual · cond fan (kWh) | 3,712.7 |
| Annual · indoor fan (kWh) | 4,958.2 |
| Annual · coil total (kWh) | 136,630 |
| Annual · coil sensible (kWh) | 98,508.6 |
| Annual · coil latent (kWh) | 38,121.3 |
| Annual · cop2 mean | 3.577 |
| Annual · idb mean | 21.005 |
| Annual · w mean | 0.009240 |
| Annual · rh mean | 56.516 |
| Annual · odb mean | 19.914 |
| Annual · ow mean | 0.01161 |
| Annual · edb mean | 21.006 |
| Annual · hours | 8,760 |
| Maxima · total · value | 11,454.8 |
| Maxima · total · month | 7 |
| Maxima · total · day | 20 |
| Maxima · total · hour | 15 |
| Maxima · total · date | 37,092 |
| Maxima · total · mon | Jul |
| Maxima · cs · value | 22,237.7 |
| Maxima · cs · month | 7 |
| Maxima · cs · day | 20 |
| Maxima · cs · hour | 15 |
| Maxima · cs · date | 37,092 |
| Maxima · cs · mon | Jul |
| Maxima · cl · value | 8,955.6 |
| Maxima · cl · month | 6 |
| Maxima · cl · day | 17 |
| Maxima · cl · hour | 14 |
| Maxima · cl · date | 37,059 |
| Maxima · cl · mon | Jun |
| Maxima · ct · value | 31,111.4 |
| Maxima · ct · month | 6 |
| Maxima · ct · day | 17 |
| Maxima · ct · hour | 14 |
| Maxima · ct · date | 37,059 |
| Maxima · ct · mon | Jun |
| Extremes · cop2 max · value | 4.704 |
| Extremes · cop2 max · month | 10 |
| Extremes · cop2 max · day | 5 |
| Extremes · cop2 max · hour | 1 |
| Extremes · cop2 max · date | 37,169 |
| Extremes · cop2 max · mon | Oct |
| Extremes · cop2 min · value | 2.781 |
| Extremes · cop2 min · month | 3 |
| Extremes · cop2 min · day | 31 |
| Extremes · cop2 min · hour | 17 |
| Extremes · cop2 min · date | 36,981 |
| Extremes · cop2 min · mon | Mar |
| Extremes · idb max · value | 25.009 |
| Extremes · idb max · month | 7 |
| Extremes · idb max · day | 30 |
| Extremes · idb max · hour | 15 |
| Extremes · idb max · date | 37,102 |
| Extremes · idb max · mon | Jul |
| Extremes · idb min · value | 11.010 |
| Extremes · idb min · month | 12 |
| Extremes · idb min · day | 21 |
| Extremes · idb min · hour | 6 |
| Extremes · idb min · date | 37,246 |
| Extremes · idb min · mon | Dec |
| Extremes · w max · value | 0.01138 |
| Extremes · w max · month | 7 |
| Extremes · w max · day | 20 |
| Extremes · w max · hour | 15 |
| Extremes · w max · date | 37,092 |
| Extremes · w max · mon | Jul |
| Extremes · w min · value | 0.008094 |
| Extremes · w min · month | 12 |
| Extremes · w min · day | 20 |
| Extremes · w min · hour | 12 |
| Extremes · w min · date | 37,245 |
| Extremes · w min · mon | Dec |
| Extremes · rh max · value | 100 |
| Extremes · rh max · month | 12 |
| Extremes · rh max · day | 12 |
| Extremes · rh max · hour | 20 |
| Extremes · rh max · date | 37,237 |
| Extremes · rh max · mon | Dec |
| Extremes · rh min · value | 53.248 |
| Extremes · rh min · month | 5 |
| Extremes · rh min · day | 4 |
| Extremes · rh min · hour | 4 |
| Extremes · rh min · date | 37,015 |
| Extremes · rh min · mon | May |
| Extreme window apr dec | true |
| Hours above setpoint 0p5k | 0 |
| May sep · total (kWh) | 35,811.2 |
| May sep · compressor (kWh) | 28,674.7 |
| May sep · cond fan (kWh) | 3,055.7 |
| May sep · indoor fan (kWh) | 4,080.8 |
| May sep · coil total (kWh) | 112,822 |
| May sep · coil sensible (kWh) | 81,341.9 |
| May sep · coil latent (kWh) | 31,479.6 |
| May sep · cop2 mean | 3.556 |
| May sep · idb mean | 25.000 |
| May sep · w mean | 0.01099 |
| May sep · rh mean | 55.566 |
| May sep · odb mean | 25.981 |
| May sep · ow mean | 0.01589 |
| May sep · edb mean | 25.000 |
| May sep · hours | 3,672 |
Input file
sha256 ba77c7aa2ff637d1f42820227507c24c64b724820f5ac9ff4aa9e2e90d541d47
[version] version_identifier = "26.1" [simulation-control] do_zone_sizing_calculation = "No" do_system_sizing_calculation = "No" do_plant_sizing_calculation = "No" run_simulation_for_sizing_periods = "No" run_simulation_for_weather_file_run_periods = "Yes" do_hvac_sizing_simulation_for_sizing_periods = "No" maximum_number_of_hvac_sizing_simulation_passes = 1 [building."Standard 140 CE510 (SIMsara)"] north_axis = 0.0 terrain = "Suburbs" loads_convergence_tolerance_value = 0.04 temperature_convergence_tolerance_value = 0.004 solar_distribution = "MinimalShadowing" maximum_number_of_warmup_days = 50 minimum_number_of_warmup_days = 6 [timestep] number_of_timesteps_per_hour = 6 [heat-balance-algorithm] algorithm = "ConductionTransferFunction" [surface.convection.algorithm.inside] algorithm = "TARP" [surface.convection.algorithm.outside] algorithm = "SimpleCombined" [global-geometry-rules] starting_vertex_position = "UpperLeftCorner" vertex_entry_direction = "Counterclockwise" coordinate_system = "Relative" [site.location."CE b Site"] latitude = 30.0 longitude = -90.3 time_zone = -6.0 elevation = 3.0 [schedule-type-limits."Fraction"] lower_limit_value = 0.0 upper_limit_value = 1.0 numeric_type = "Continuous" [schedule-type-limits."Any Number"] [schedule-type-limits."Temperature"] lower_limit_value = -60.0 upper_limit_value = 200.0 numeric_type = "Continuous" unit_type = "Temperature" [schedule-type-limits."Control Type"] lower_limit_value = 0.0 upper_limit_value = 4.0 numeric_type = "Discrete" [schedule.compact."Always On"] schedule_type_limits_name = "Fraction" data = [ { field = "Through: 12/31" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 1.0 }, ] [schedule.compact."Cooling Only Control"] schedule_type_limits_name = "Control Type" data = [ { field = "Through: 12/31" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 2.0 }, ] [schedule.compact."CE Sensible Gain Schedule"] schedule_type_limits_name = "Fraction" data = [ { field = "Through: 3/10" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 0.0 }, { field = "Through: 4/10" }, { field = "For: AllDays" }, { field = "Until: 09:00" }, { field = 0.0 }, { field = "Until: 16:00" }, { field = 0.33331753779083545 }, { field = "Until: 24:00" }, { field = 0.0 }, { field = "Through: 4/11" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 0.0 }, { field = "Through: 4/20" }, { field = "For: AllDays" }, { field = "Until: 08:00" }, { field = 0.0 }, { field = "Until: 17:00" }, { field = 0.4444391792636118 }, { field = "Until: 24:00" }, { field = 0.0 }, { field = "Through: 10/11" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 1.0 }, { field = "Through: 10/18" }, { field = "For: AllDays" }, { field = "Until: 08:00" }, { field = 0.0 }, { field = "Until: 14:00" }, { field = 0.4444391792636118 }, { field = "Until: 24:00" }, { field = 0.0 }, { field = "Through: 11/5" }, { field = "For: AllDays" }, { field = "Until: 08:00" }, { field = 0.0 }, { field = "Until: 12:00" }, { field = 0.4444391792636118 }, { field = "Until: 14:00" }, { field = 0.6666824622091646 }, { field = "Until: 16:00" }, { field = 0.8888783585272236 }, { field = "Until: 20:00" }, { field = 0.4444391792636118 }, { field = "Until: 24:00" }, { field = 0.33331753779083545 }, { field = "Through: 12/31" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 0.0 }, ] [schedule.compact."CE Latent Gain Schedule"] schedule_type_limits_name = "Fraction" data = [ { field = "Through: 3/10" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 0.0 }, { field = "Through: 4/10" }, { field = "For: AllDays" }, { field = "Until: 09:00" }, { field = 0.0 }, { field = "Until: 16:00" }, { field = 0.33337221509389947 }, { field = "Until: 24:00" }, { field = 0.0 }, { field = "Through: 4/11" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 0.0 }, { field = "Through: 4/20" }, { field = "For: AllDays" }, { field = "Until: 08:00" }, { field = 0.0 }, { field = "Until: 17:00" }, { field = 0.4444185232707337 }, { field = "Until: 24:00" }, { field = 0.0 }, { field = "Through: 10/11" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 1.0 }, { field = "Through: 10/18" }, { field = "For: AllDays" }, { field = "Until: 08:00" }, { field = 0.0 }, { field = "Until: 14:00" }, { field = 0.4444185232707337 }, { field = "Until: 24:00" }, { field = 0.0 }, { field = "Through: 11/5" }, { field = "For: AllDays" }, { field = "Until: 08:00" }, { field = 0.0 }, { field = "Until: 12:00" }, { field = 0.4444185232707337 }, { field = "Until: 14:00" }, { field = 0.6666277849061005 }, { field = "Until: 16:00" }, { field = 0.8889536918231657 }, { field = "Until: 20:00" }, { field = 0.4444185232707337 }, { field = "Until: 24:00" }, { field = 0.33337221509389947 }, { field = "Through: 12/31" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 0.0 }, ] [schedule.compact."Cooling Setpoint"] schedule_type_limits_name = "Temperature" data = [ { field = "Through: 12/31" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 25.0 }, ] [schedule.compact."CE Fan Mode"] schedule_type_limits_name = "Any Number" data = [ { field = "Through: 12/31" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 0.0 }, ] [schedule.compact."CE Heating Off"] schedule_type_limits_name = "Fraction" data = [ { field = "Through: 12/31" }, { field = "For: AllDays" }, { field = "Until: 24:00" }, { field = 0.0 }, ] [material.no-mass."CE Insulation Outer Half"] roughness = "VerySmooth" thermal_resistance = 162.33766233766235 thermal_absorptance = 0.9 solar_absorptance = 0.1 visible_absorptance = 0.1 [material.no-mass."CE Insulation Inner Half"] roughness = "VerySmooth" thermal_resistance = 162.33766233766235 thermal_absorptance = 0.9 solar_absorptance = 0.6 visible_absorptance = 0.6 [construction."CE Envelope"] outside_layer = "CE Insulation Outer Half" layer_2 = "CE Insulation Inner Half" [output.variable-dictionary."Output:VariableDictionary"] key_field = "IDF" [run-period."CE510"] begin_month = 1 begin_day_of_month = 1 end_month = 12 end_day_of_month = 31 day_of_week_for_start_day = "Sunday" use_weather_file_holidays_and_special_days = "No" use_weather_file_daylight_saving_period = "No" apply_weekend_holiday_rule = "No" use_weather_file_rain_indicators = "Yes" use_weather_file_snow_indicators = "Yes" [building.surface.detailed."CE Zone South Wall"] surface_type = "Wall" zone_name = "CE Zone" construction_name = "CE Envelope" outside_boundary_condition = "Outdoors" sun_exposure = "SunExposed" wind_exposure = "WindExposed" view_factor_to_ground = 0.5 vertices = [ { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 }, ] [building.surface.detailed."CE Zone East Wall"] surface_type = "Wall" zone_name = "CE Zone" construction_name = "CE Envelope" outside_boundary_condition = "Outdoors" sun_exposure = "SunExposed" wind_exposure = "WindExposed" view_factor_to_ground = 0.5 vertices = [ { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 }, { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 }, ] [building.surface.detailed."CE Zone North Wall"] surface_type = "Wall" zone_name = "CE Zone" construction_name = "CE Envelope" outside_boundary_condition = "Outdoors" sun_exposure = "SunExposed" wind_exposure = "WindExposed" view_factor_to_ground = 0.5 vertices = [ { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 }, { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 }, ] [building.surface.detailed."CE Zone West Wall"] surface_type = "Wall" zone_name = "CE Zone" construction_name = "CE Envelope" outside_boundary_condition = "Outdoors" sun_exposure = "SunExposed" wind_exposure = "WindExposed" view_factor_to_ground = 0.5 vertices = [ { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 }, ] [building.surface.detailed."CE Zone Floor"] surface_type = "Floor" zone_name = "CE Zone" construction_name = "CE Envelope" outside_boundary_condition = "Outdoors" sun_exposure = "SunExposed" wind_exposure = "WindExposed" view_factor_to_ground = 0.0 vertices = [ { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 0.0 }, { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 0.0 }, ] [building.surface.detailed."CE Zone Roof"] surface_type = "Roof" zone_name = "CE Zone" construction_name = "CE Envelope" outside_boundary_condition = "Outdoors" sun_exposure = "SunExposed" wind_exposure = "WindExposed" view_factor_to_ground = 0.0 vertices = [ { vertex_x_coordinate = 0.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 }, { vertex_x_coordinate = 14.0, vertex_y_coordinate = 0.0, vertex_z_coordinate = 3.0 }, { vertex_x_coordinate = 14.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 }, { vertex_x_coordinate = 0.0, vertex_y_coordinate = 14.0, vertex_z_coordinate = 3.0 }, ] [zone."CE Zone"] direction_of_relative_north = 0.0 x_origin = 0.0 y_origin = 0.0 z_origin = 0.0 type = 1 multiplier = 1 ceiling_height = 3.0 volume = 588.0 floor_area = 196.0 part_of_total_floor_area = "Yes" [electric-equipment."CE Sensible Gains"] zone_or_zonelist_or_space_or_spacelist_name = "CE Zone" schedule_name = "CE Sensible Gain Schedule" design_level_calculation_method = "EquipmentLevel" design_level = 21103.0 fraction_latent = 0.0 fraction_radiant = 0.0 fraction_lost = 0.0 end_use_subcategory = "General" [electric-equipment."CE Latent Gains"] zone_or_zonelist_or_space_or_spacelist_name = "CE Zone" schedule_name = "CE Latent Gain Schedule" design_level_calculation_method = "EquipmentLevel" design_level = 8573.0 fraction_latent = 1.0 fraction_radiant = 0.0 fraction_lost = 0.0 end_use_subcategory = "General" [thermostat.setpoint.single-cooling."CE Cooling Setpoint"] setpoint_temperature_schedule_name = "Cooling Setpoint" [zone.control.thermostat."CE Thermostat"] zone_or_zonelist_name = "CE Zone" control_type_schedule_name = "Cooling Only Control" control_1_object_type = "ThermostatSetpoint:SingleCooling" control_1_name = "CE Cooling Setpoint" [air-loop-hvac."CE Air Loop"] availability_manager_list_name = "CE Availability" design_supply_air_flow_rate = 1.8877777777777778 branch_list_name = "CE Branches" supply_side_inlet_node_name = "CE Loop Inlet" demand_side_outlet_node_name = "CE Zone Equipment Outlet" demand_side_inlet_node_names = "CE Zone Equipment Inlet" supply_side_outlet_node_names = "CE Loop Outlet" design_return_air_flow_fraction_of_supply_air_flow = 1.0 [branch-list."CE Branches"] branches = [ { branch_name = "CE Main Branch" }, ] [branch."CE Main Branch"] components = [ { component_object_type = "AirLoopHVAC:UnitaryHeatCool", component_name = "CE Unitary", component_inlet_node_name = "CE Loop Inlet", component_outlet_node_name = "CE Loop Outlet" }, ] [availability-manager-assignment-list."CE Availability"] managers = [ { availability_manager_object_type = "AvailabilityManager:Scheduled", availability_manager_name = "CE Avail" }, ] [availability.manager.scheduled."CE Avail"] schedule_name = "Always On" [air.loop.hvac.unitary-heat-cool."CE Unitary"] availability_schedule_name = "Always On" unitary_system_air_inlet_node_name = "CE Loop Inlet" unitary_system_air_outlet_node_name = "CE Loop Outlet" supply_air_fan_operating_mode_schedule_name = "CE Fan Mode" maximum_supply_air_temperature = 50.0 cooling_supply_air_flow_rate = 1.8877777777777778 heating_supply_air_flow_rate = 1.8877777777777778 no_load_supply_air_flow_rate = 1.8877777777777778 controlling_zone_or_thermostat_location = "CE Zone" supply_fan_object_type = "Fan:OnOff" supply_fan_name = "CE Supply Fan" fan_placement = "DrawThrough" heating_coil_object_type = "Coil:Heating:Electric" heating_coil_name = "CE Heating Coil" cooling_coil_object_type = "Coil:Cooling:DX:SingleSpeed" cooling_coil_name = "CE Cooling Coil" dehumidification_control_type = "None" [coil.heating.electric."CE Heating Coil"] availability_schedule_name = "CE Heating Off" efficiency = 1.0 nominal_capacity = 1000.0 air_inlet_node_name = "CE Coil Outlet" air_outlet_node_name = "CE Heating Coil Outlet" [curve.biquadratic."CE b CapFT"] coefficient1_constant = 0.8421792790769599 coefficient2_x = 0.013597330340468002 coefficient3_x_2 = 0.0005425555274330542 coefficient4_y = -0.0046779772346486545 coefficient5_y_2 = -1.892890987340474e-05 coefficient6_x_y = -0.0001833613310964283 minimum_value_of_x = -20.0 maximum_value_of_x = 50.0 minimum_value_of_y = -20.0 maximum_value_of_y = 60.0 input_unit_type_for_x = "Temperature" input_unit_type_for_y = "Temperature" output_unit_type = "Dimensionless" [curve.biquadratic."CE b EIRFT"] coefficient1_constant = 0.6296349141804827 coefficient2_x = -0.01194173030834857 coefficient3_x_2 = 0.00013564228411874153 coefficient4_y = 0.014620794633169055 coefficient5_y_2 = 0.0001647879385125572 coefficient6_x_y = -0.00023849947842266334 minimum_value_of_x = -20.0 maximum_value_of_x = 50.0 minimum_value_of_y = -20.0 maximum_value_of_y = 60.0 input_unit_type_for_x = "Temperature" input_unit_type_for_y = "Temperature" output_unit_type = "Dimensionless" [curve.quadratic."CE b CapFFF"] coefficient1_constant = 1.0 coefficient2_x = 0.0 coefficient3_x_2 = 0.0 minimum_value_of_x = 0.0 maximum_value_of_x = 1.5 [curve.quadratic."CE b EIRFFF"] coefficient1_constant = 1.0 coefficient2_x = 0.0 coefficient3_x_2 = 0.0 minimum_value_of_x = 0.0 maximum_value_of_x = 1.5 [curve.quadratic."CE b PLF"] coefficient1_constant = 0.771 coefficient2_x = 0.229 coefficient3_x_2 = 0.0 minimum_value_of_x = 0.0 maximum_value_of_x = 1.0 [coil.cooling.dx.single-speed."CE Cooling Coil"] availability_schedule_name = "Always On" gross_rated_total_cooling_capacity = 33277.1085 gross_rated_sensible_heat_ratio = 0.7825956753424054 gross_rated_cooling_cop = 3.0426175825180586 rated_air_flow_rate = 1.8877777777777778 air_inlet_node_name = "CE Loop Inlet" air_outlet_node_name = "CE Coil Outlet" total_cooling_capacity_function_of_temperature_curve_name = "CE b CapFT" total_cooling_capacity_function_of_flow_fraction_curve_name = "CE b CapFFF" energy_input_ratio_function_of_temperature_curve_name = "CE b EIRFT" energy_input_ratio_function_of_flow_fraction_curve_name = "CE b EIRFFF" part_load_fraction_correlation_curve_name = "CE b PLF" minimum_outdoor_dry_bulb_temperature_for_compressor_operation = -25.0 nominal_time_for_condensate_removal_to_begin = 0.0 ratio_of_initial_moisture_evaporation_rate_and_steady_state_latent_capacity = 0.0 maximum_cycling_rate = 0.0 latent_capacity_time_constant = 0.0 condenser_type = "AirCooled" crankcase_heater_capacity = 0.0 maximum_outdoor_dry_bulb_temperature_for_crankcase_heater_operation = 10.0 [fan.on-off."CE Supply Fan"] availability_schedule_name = "Always On" fan_total_efficiency = 1.0 pressure_rise = 657.9164214243673 maximum_flow_rate = 1.8877777777777778 motor_efficiency = 1.0 motor_in_airstream_fraction = 1.0 air_inlet_node_name = "CE Heating Coil Outlet" air_outlet_node_name = "CE Loop Outlet" end_use_subcategory = "General" [air.loop.hvac.supply-path."CE Supply Path"] supply_air_path_inlet_node_name = "CE Zone Equipment Inlet" components = [ { component_object_type = "AirLoopHVAC:ZoneSplitter", component_name = "CE Splitter" }, ] [air.loop.hvac.zone-splitter."CE Splitter"] inlet_node_name = "CE Zone Equipment Inlet" nodes = [ { outlet_node_name = "CE Terminal Inlet" }, ] [air.terminal.single.duct.constant.volume.no-reheat."CE Terminal"] availability_schedule_name = "Always On" air_inlet_node_name = "CE Terminal Inlet" air_outlet_node_name = "CE Zone Supply Inlet" maximum_air_flow_rate = 1.8877777777777778 [zone.hvac.air-distribution-unit."CE ADU"] air_distribution_unit_outlet_node_name = "CE Zone Supply Inlet" air_terminal_object_type = "AirTerminal:SingleDuct:ConstantVolume:NoReheat" air_terminal_name = "CE Terminal" nominal_upstream_leakage_fraction = 0.0 constant_downstream_leakage_fraction = 0.0 [air.loop.hvac.return-path."CE Return Path"] return_air_path_outlet_node_name = "CE Zone Equipment Outlet" components = [ { component_object_type = "AirLoopHVAC:ZoneMixer", component_name = "CE Mixer" }, ] [air.loop.hvac.zone-mixer."CE Mixer"] outlet_node_name = "CE Zone Equipment Outlet" nodes = [ { inlet_node_name = "CE Zone Return Outlet" }, ] [zone.hvac.equipment-list."CE Equipment"] load_distribution_scheme = "SequentialLoad" equipment = [ { zone_equipment_object_type = "ZoneHVAC:AirDistributionUnit", zone_equipment_name = "CE ADU", zone_equipment_cooling_sequence = 1, zone_equipment_heating_or_no_load_sequence = 1 }, ] [[zone.hvac.equipment-connections]] zone_name = "CE Zone" zone_conditioning_equipment_list_name = "CE Equipment" zone_air_inlet_node_or_nodelist_name = "CE Zone Supply Inlet" zone_air_node_name = "CE Zone Air Node" zone_return_air_node_or_nodelist_name = "CE Zone Return Outlet" [[output.variable]] key_value = "Environment" variable_name = "Site Outdoor Air Drybulb Temperature" reporting_frequency = "Timestep" [[output.variable]] key_value = "Environment" variable_name = "Site Outdoor Air Humidity Ratio" reporting_frequency = "Timestep" [[output.variable]] key_value = "Environment" variable_name = "Site Outdoor Air Barometric Pressure" reporting_frequency = "Timestep" [[output.variable]] key_value = "CE Zone" variable_name = "Zone Mean Air Temperature" reporting_frequency = "Timestep" [[output.variable]] key_value = "CE Zone" variable_name = "Zone Air Humidity Ratio" reporting_frequency = "Timestep" [[output.variable]] key_value = "CE Cooling Coil" variable_name = "Cooling Coil Electricity Energy" reporting_frequency = "Timestep" [[output.variable]] key_value = "CE Cooling Coil" variable_name = "Cooling Coil Runtime Fraction" reporting_frequency = "Timestep" [[output.variable]] key_value = "CE Cooling Coil" variable_name = "Cooling Coil Total Cooling Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "CE Cooling Coil" variable_name = "Cooling Coil Sensible Cooling Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "CE Cooling Coil" variable_name = "Cooling Coil Latent Cooling Rate" reporting_frequency = "Timestep" [[output.variable]] key_value = "CE Supply Fan" variable_name = "Fan Electricity Energy" reporting_frequency = "Timestep" [[output.variable]] key_value = "CE Loop Inlet" variable_name = "System Node Temperature" reporting_frequency = "Timestep" [[output.variable]] key_value = "CE Loop Inlet" variable_name = "System Node Humidity Ratio" reporting_frequency = "Timestep"