MODELING NOTES FOR ASHRAE STANDARD 140 =============================================================================== INTRODUCTION =============================================================================== This document shall include supplemental information about the ASHRAE Standard 140 tests performed. One S140outNotes document shall be provided for each set of tests (e.g., one for the building thermal and fabric load tests of Section 7.2; one for the space cooling equipment analytical verification tests of Sections 9.2; etc.) The types of information listed below shall be provided in this document, each in a separate section: a. Software information b. Alternative modeling methods c. Equivalent modeling methods d. Nonspecified inputs e. Omitted test cases and results f. Changes made to source code for the purpose of running the tests, where such changes are not available in publicly released versions of the software g. Anomalous results. Notes in this document shall be limited to the topics shown above. Notes must be factual and objective and shall only refer to the software being tested. Notes shall not refer to any other software program. INFORMATIVE NOTE: Text at the start of each section describes the content of the section for the reader and provides instructions for supplying the content. Sample notes are provided in a separate document (S140outNotes_Examples.TXT). =============================================================================== A. SOFTWARE INFORMATION =============================================================================== CONTENT: This section shall include reference information for the software - the vendor, name, and version of the software, plus operating system and computer hardware requirements. INSTRUCTIONS: Information for items 1 through 7 below shall be provided. Information for Item 8 shall be permitted but is not required. 1. SOFTWARE VENDOR: Jared Bell, Roots Ontological Technologies, LLC 2. SOFTWARE NAME: SIMsara 3. SOFTWARE VERSION (unique software version identifier): SIMsara 0.1.0 4. OPERATING SYSTEM REQUIREMENTS: macOS 13 or later on Apple silicon (arm64). This is the build that was tested; other targets are listed only when they have been built and run for these tests. 5. APPROX HARD DISK SPACE REQUIRED FOR INSTALLATION: About 6.4 MB: the release binary s140_run, which needs no other runtime files beyond the TOML input and the EPW weather file. 6. MINIMUM RAM REQUIRED FOR SOFTWARE OPERATION: 16 MB: the largest peak resident memory of any submitted test case, measured with /usr/bin/time -l on the tested build. 7. MINIMUM DISPLAY MONITOR REQUIREMENTS: None. SIMsara is a command-line program with no graphical display. 8. OTHER HARDWARE OR SOFTWARE-RELATED REQUIREMENTS: Input is TOML (docs/TOML-INPUT.md in the source distribution) with EPW weather. Building from source needs Rust 1.98.1. The Standard 140 harness scripts that generate the test inputs and fill the output templates need Python 3.11 or later, standard library only. INFORMATIVE NOTE: Item 8 can be used to supply additional relevant information. =============================================================================== B. REPORT BLOCK FOR ALTERNATIVE MODELING METHODS =============================================================================== CONTENT: If the software being tested provides alternative modeling methods or algorithms for performing the tests, this section shall describe modeling methods used for the tests. INSTRUCTIONS: If alternative modeling methods are applicable, a separate note for each alternative modeling method or algorithm situation shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If alternative modeling methods are not applicable, specify "NONE" in place of the information below. NOTE 1 - Interior Surface Convection (Section 10.2.1.7) --------------------------------------------------------- 1.1 Describe the Effect Being Simulated: Heat transfer between the zone air and the inside faces, and so the building heat loss the furnace meets. 1.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 1.2.1 User Value (SurfaceProperty:ConvectionCoefficients) Physical Meaning: A constant coefficient entered per surface, or per surface class through the MultipleSurface form; the HeatBalanceAlgorithm minimum surface convection coefficient bounds it from below. 1.2.2 Simple Physical Meaning: Constant coefficients by orientation and heat-flow direction (4.040 W/m2K for upward flow at a ceiling, 3.076 vertical, 0.948 downward). 1.2.3 TARP Physical Meaning: Natural-convection correlations of temperature difference and tilt. 1.2.4 CeilingDiffuser, AdaptiveConvectionAlgorithm, ASTMC1340 Physical Meaning: Room-air-flow and adaptive correlations. 1.3 Setting or Capability Used: User Value on every inside face: 20 W/m2K on the roof, 1e-6 W/m2K on the walls and floor (Block C note 1). The zone default (Simple) applies to no surface. NOTE 2 - Exterior Surface Convection (Section 10.2.1.7) --------------------------------------------------------- 2.1 Describe the Effect Being Simulated: Heat transfer between the outside faces and the outdoor air. 2.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 2.2.1 User Value (SurfaceProperty:ConvectionCoefficients) Physical Meaning: A constant convection coefficient entered per surface or surface class; long-wave exchange stays explicit. 2.2.2 SimpleCombined Physical Meaning: A combined convection and radiation coefficient D + E V + F V^2 by roughness (8.23 W/m2K for a very smooth surface at zero wind); a face with a user value keeps it, and such faces are reported in a mixed-algorithms Severe message. 2.2.3 TARP, DOE-2, MoWiTT Physical Meaning: Separate convection correlations with explicit long-wave exchange. 2.3 Setting or Capability Used: User Value on every outside face: 20 W/m2K on the roof, 1e-6 W/m2K on the walls and floor (Block C note 1), with DOE-2 as the zone default, which applies to no surface; every surface NoWind. NOTE 3 - Time Step (Section 10.2.1.10.4) --------------------------------------------------------- 3.1 Describe the Effect Being Simulated: Resolution of the thermostat, burner cycling and part-load calculation. 3.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 3.2.1 Zone time steps per hour Physical Meaning: 1 to 60 steps per hour; the HVAC system may sub-step. 3.3 Setting or Capability Used: 6 steps per hour (10 minutes). The furnace cycles within a step through its part-load ratio (no on-off simulation within the step). NOTE 4 - Circulating Fan Heat (Section 10.2.2.5) --------------------------------------------------------- 4.1 Describe the Effect Being Simulated: Where the circulating fan's electric power ends up. 4.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 4.2.1 Motor in the airstream fraction Physical Meaning: Fraction 0 to 1 of the motor losses added to the air; the shaft power always heats the air. 4.3 Setting or Capability Used: Fraction 1: all 200 W of fan power is added to the supply air, upstream of the burner (blow-through), as 10.2.2.5 and 10.2.1.10.1 g specify. =============================================================================== C. REPORT BLOCK FOR EQUIVALENT MODELING METHODS =============================================================================== CONTENT: This section shall describe equivalent modeling methods used to perform the tests. When the software does not model an effect exactly as stated in the standard or does not permit the input values required, equivalent modeling methods shall be permitted to perform the test. INSTRUCTIONS: If equivalent modeling methods are applied, a separate note for each instance of equivalent modeling shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If equivalent modeling methods are not applicable, specify "NONE" in place of the information below. NOTE 1 - Roof Heat Loss with Fixed Surface Coefficients (Section 10.2.1.3, 10.2.1.4, 10.2.1.7, 10.2.1.8 and Table 10-1) ------------------------------------------------------------------------------- 1.1 Describe the Effect Being Simulated: The building heat loss that drives every furnace load. 1.2 Section(s) of the Standard where Relevant Inputs are Specified: Inside and outside convection coefficients of 20 W/m2K on the roof and approaching 0 on the walls and floor (combined coefficients where radiation and convection are modeled together), emissivity and solar absorptivity approaching 0, walls and floor of R 100 and a 48 m2 roof of R 0.14006: a building UA of 199.953 W/K, all of it through the roof. 1.3 Equivalent Input(s) Used: The surface coefficients are entered as fixed convection coefficients (SurfaceProperty:ConvectionCoefficients, type Value). The roof, the Figure 10-1 roof over the floor, carries an Inside and an Outside Value of 20 W/m2K. Every wall and the floor carry 1e-6 W/m2K inside and outside (two SurfaceProperty:ConvectionCoefficients:MultipleSurface objects, AllExteriorWalls and AllExteriorFloors) for the specified 0, which cannot be entered: the HeatBalanceAlgorithm minimum surface convection coefficient, also set to 1e-6 W/m2K, must be above 0 and bounds every user value from below. Any value above 0 is admitted, so 1e-6 W/m2K is a chosen effective 0, not a program limit. These are convection coefficients, not the combined coefficients of 10.2.1.7.2: radiation stays explicit; every surface is NoSun and NoWind, with thermal absorptance 1e-7 (for the specified 0) and solar absorptance 0. The outside default algorithm is DOE-2 and the inside default Simple; neither applies to any surface. Layers are Material:NoMass with R = thickness / k (10.2.1.4.2: no thermal or moisture capacitance). Site:HeightVariation sets the outdoor air temperature gradient to 0, so every face sees the weather file dry-bulb, as the analytical solution does (by default the outdoor air would cool with height above the weather station). The zone volume (129.6 m3), floor area (48 m2) and ceiling height (2.7 m) are entered explicitly. The infiltration method of 10.2.1.9 is not used: it is for programs without direct input of constant convection coefficients. 1.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The building is the specified one but for the 0 coefficients. At 1e-6 W/m2K on both faces the walls and floor are nearly decoupled from the zone air and float near their initial temperature; as a steady conduction path they would add at most 6.2e-5 W/K to the roof's 199.953 W/K (0.31 parts per million), convection and conduction only (their long-wave exchange, at the 1e-7 emissivity, is of the same order). Re-running every case with 1e-9 W/m2K in place of 1e-6 W/m2K moves every furnace load, input, fuel and fan result by at most 9.3e-8 relative and the hourly zone temperatures by at most 1.2e-5 K, so the chosen value acts as 0. The design loss at the HE100 temperature difference is 9997.7 W. The HE100 furnace load is 77.7387 GJ, 0.002 percent from the analytical value, and the HE120 and HE140 loads are 0.011 and 0.012 percent from theirs. NOTE 2 - Furnace Modeled as a Heat-Only Unitary System (Section 10.2.1.10, 10.2.2.5-10.2.2.7, 10.2.3) ------------------------------------------------------------------------------- 2.1 Describe the Effect Being Simulated: Burner, part-load, circulating fan and draft fan performance. 2.2 Section(s) of the Standard where Relevant Inputs are Specified: A sealed-combustion fuel-fired furnace of 10 kW (HE230: 5 kW), a capacity that does not include fan heat, 80 percent full-load efficiency (HE100: 100 percent), the part-load curve PLF = PLR / HIR(PLR) with the cubic HIR of 10.2.1.10.4, a 200 W circulating fan (0.355 m3/s, motor in the airstream) continuous or cycling with the burner, and a 50 W draft fan cycling with the burner whose heat goes up the flue. The base case simulates both fans at 0 W. 2.3 Equivalent Input(s) Used: A single-zone AirLoopHVAC without an outdoor-air system whose branch holds one AirLoopHVAC:UnitarySystem under Load control of the zone thermostat, with Coil:Heating:Fuel (NaturalGas) at the full 10,000 W (5,000 W) in every case, a blow-through Fan:OnOff in HE150-HE230 (operating-mode schedule 1 for continuous, 0 for cycling) and no fan object in HE100-HE140, whose 0 W fans carry neither power nor heat. The draft fan is the coil's on-cycle parasitic electric load, which never heats the air. The fan is 200 W at 0.355 m3/s (pressure rise 563.38 Pa, total and motor efficiency 1). The part-load curve enters as the coil's part-load fraction PLF, with fuel = full-load fuel x PLR / PLF, so PLF = PLR / HIR; that rational function has no supported curve form, and every case uses the Curve:Cubic that equals PLR / HIR exactly at PLR 0.1, 0.4, 0.7 and 1.0 (within 1.3 percent between 0.1 and 1). 2.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: Same components and control as the specified furnace. The cubic is exact at the HE120 part-load ratio and at full load; for HE140 it gives a furnace input 0.45 percent below the quasi-analytical value. At 100 percent full-load efficiency the HE100 furnace input (77.7372 GJ) is 0.002 percent below its load (77.7387 GJ): the furnace runs at a part-load ratio of about 0.9997, where the specified HIR gives PLR / HIR = 1.00003 (HIR(1) = 0.99995) and the cubic gives 1.00002, so the input falls just below the load with the specified curve itself. NOTE 3 - Weather Data Converted from WYEC2 (Section 10.2.1.1, Annex A1 A1.2.3 and A1.7) ------------------------------------------------------------------------------- 3.1 Describe the Effect Being Simulated: Outdoor dry-bulb temperature of every case. 3.2 Section(s) of the Standard where Relevant Inputs are Specified: The WYEC2 files HE100W, HE120W, HE130W, HE140W and HE210W (Table A1-8), in the format of Table A1-18, at the site of Table A1-9 (45.32 N, 75.67 W, 115 m, time zone 5). 3.3 Equivalent Input(s) Used: SIMsara reads EPW. SIMsara's converter (scripts/s140/wx/wy2.py) writes each WYEC2 file as an EPW with 8760 records, reading the data positions of Table A1-18; the LOCATION line carries the Table A1-9 site. The processed files are archived with their sha256. With every surface NoSun and NoWind only the dry-bulb temperature and the station pressure affect the results. 3.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The dry-bulb temperatures are carried over unchanged; the converter is checked field by field (plan WP1). NOTE 4 - Furnace Load Integrated from the Heating-Coil Rate (Section 10.3.1 and 10.3.2) ------------------------------------------------------------------------------- 4.1 Describe the Effect Being Simulated: The reported total furnace load. 4.2 Section(s) of the Standard where Relevant Inputs are Specified: Total furnace load (the load at the furnace coil), total furnace input, fuel consumption at 38 MJ/m3 over 7.776e6 s, and the energy of both fans, January through March. 4.3 Equivalent Input(s) Used: The decks request the fuel coil's heating rate (W) at each time step, and the load is the rate times the step length summed over the 90 days (SIMsara's Heating Coil Heating Energy, available on request, is the same product): the burner heat at the coil, without the circulating fan's heat. The furnace input is the summed NaturalGas energy; the fuel volume is input / (38 MJ/m3 x 7.776e6 s); fan energy is the circulating fan plus the coil's parasitic (draft fan) electricity. 4.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: Exact for a quantity held constant within each step. =============================================================================== D. REPORT BLOCK FOR USE OF NON-SPECIFIED INPUTS =============================================================================== CONTENT: This section shall describe nonspecified inputs used to perform the tests. Use of nonspecified inputs shall be permitted only for the following specified sections relating to the following topics: * Alternative constant exterior surface coefficients in Sections 7.2.1.9.3, 7.2.3.1.4.3, 7.2.3.3.2, and 9.2.1.8 * Alternative constant interior surface coefficients in Sections 7.2.1.10.3, 7.2.3.1.4.4, 7.2.3.2.2, and 9.2.1.9 * Alternative constant interior solar distribution fractions in Sections 7.2.1.12, 7.2.2.1.2.2, 7.2.2.1.6.2, 7.2.2.1.7.2, 7.2.2.2.7.4, 7.2.3.9.3, 7.2.3.10.2, and 7.2.3.12.2 * Air density given at specific altitudes for the space-cooling and space- heating equipment cases in Sections 9.2.1.4.3, 9.2.3.4.3, and 10.2.1.4.3. INSTRUCTIONS: If nonspecified inputs are applied, a separate note for each use of nonspecified inputs shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If nonspecified inputs are not applied, specify "NONE" in place of the information below. NONE =============================================================================== =============================================================================== E. REPORT BLOCK FOR OMITTED TEST CASES AND RESULTS =============================================================================== CONTENT: This section shall describe test cases that were omitted and/or individual results of test cases that were omitted along with the reason for the omission. INSTRUCTIONS: If test cases were omitted, a separate note to describe each type of omission shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If there are no omitted test cases, specify "NONE" in place of the information below. NONE =============================================================================== F. REPORT BLOCK FOR CHANGES TO SOURCE CODE FOR THE PURPOSE OF RUNNING THE TESTS, WHERE SUCH CHANGES ARE NOT AVAILABLE IN PUBLICLY RELEASED VERSIONS OF THE SOFTWARE =============================================================================== CONTENT: This section shall describe changes to software source code made to allow the software to run a test, where such changes are not available in a publicly released version of the software. INFORMATIVE NOTE: This section addresses special situations where a change to source code is necessary to activate a feature or to permit inputs needed for a test when these features are not available in the publicly released version of the software. INSTRUCTIONS: If changes to the source code for the purpose of running a test are applied, separate notes to describe each source code modification shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If changes to source code are not applied, specify "NONE" in place of the information below. NONE =============================================================================== G. REPORT BLOCK FOR ANOMALOUS RESULTS =============================================================================== CONTENT: Describing anomalous results shall be permitted but is not required. If anomalous test results are described, this section shall be used. INSTRUCTIONS: If anomalous test results are described, each type of anomalous result shall be described in a separate note. The standard format shown below and a separate number and title for each note item shall be applied. If anomalous results are not discussed, it shall be permitted to specify "NONE" in place of the information below. NOTE 1 - Furnace Input, Fuel and Fan Energy above the Example Range (HE210-HE230) (Section 10.3.1.2, 10.3.1.3 and 10.3.2.1) ------------------------------------------------------------------------------- 1.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: HE220 and HE230 furnace input 49.532 and 43.254 GJ (0.133 and 0.081 percent above the largest example result) and HE210, HE220 and HE230 fuel 1.772e-4, 1.676e-4 and 1.464e-4 m3/s (0.016, 0.135 and 0.124 percent above it); HE230 fan energy 480.70 kWh (0.479 percent above it). 1.2 Explanation of Reason for the Anomalous Results: The input and fuel follow from the part-load curve, entered as a cubic through PLR / HIR (Block C note 2), which each program represents in its own way. The undersized HE230 burner of 5 kW, which excludes the fan heat, runs at full load for long periods, and the fan runs with it. The furnace input and fan energy of HE210, HE220 - HE210 and HE230 - HE220 are inside the Annex A3 Tables A3-6 and A3-7 ranges (6 of 6). NOTE 2 - Results at the Edge of the Example Range (Section 10.3.1.1 and 10.3.2.1) ------------------------------------------------------------------------------- 2.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: HE100 and HE110 furnace load 77.739 GJ (0.002 percent from the analytical value, 0.015 percent below the example range); HE120 and HE140 furnace load 31.097 and 31.096 GJ (0.011 and 0.012 percent from the analytical values, 0.011 and 0.012 percent below the example range); HE160 fan energy 169.98 kWh (0.129 percent below the example range); HE170 fan energy 473.05 kWh (0.028 percent from the quasi-analytical value, 0.011 percent below the example range). 2.2 Explanation of Reason for the Anomalous Results: HE100 and HE110 match the analytical load to 0.002 percent, HE120 and HE140 theirs to 0.011 and 0.012 percent, and HE170 the quasi-analytical fan energy to 0.028 percent. In HE160 the 10 kW capacity excludes the fan heat (10.2.1.10.3), so burner and cycling fan deliver 10.2 kW together and run for the load over 10.2 kW; the informative quasi-analytical solution runs the fan for the load over 10 kW and counts its heat in the furnace load, so its fan energy and load are 10.2 / 10 of SIMsara's reading (SIMsara's HE160 load and fan are within 0.02 and 0.36 percent of the scaled values). =============================================================================== ===============================================================================