MODELING NOTES FOR ASHRAE STANDARD 140 =============================================================================== INTRODUCTION =============================================================================== This document shall include supplemental information about the ASHRAE Standard 140 tests performed. One S140outNotes document shall be provided for each set of tests (e.g., one for the building thermal and fabric load tests of Section 7.2; one for the space cooling equipment analytical verification tests of Sections 9.2; etc.) The types of information listed below shall be provided in this document, each in a separate section: a. Software information b. Alternative modeling methods c. Equivalent modeling methods d. Nonspecified inputs e. Omitted test cases and results f. Changes made to source code for the purpose of running the tests, where such changes are not available in publicly released versions of the software g. Anomalous results. Notes in this document shall be limited to the topics shown above. Notes must be factual and objective and shall only refer to the software being tested. Notes shall not refer to any other software program. INFORMATIVE NOTE: Text at the start of each section describes the content of the section for the reader and provides instructions for supplying the content. Sample notes are provided in a separate document (S140outNotes_Examples.TXT). =============================================================================== A. SOFTWARE INFORMATION =============================================================================== CONTENT: This section shall include reference information for the software - the vendor, name, and version of the software, plus operating system and computer hardware requirements. INSTRUCTIONS: Information for items 1 through 7 below shall be provided. Information for Item 8 shall be permitted but is not required. 1. SOFTWARE VENDOR: Jared Bell, Roots Ontological Technologies, LLC 2. SOFTWARE NAME: SIMsara 3. SOFTWARE VERSION (unique software version identifier): SIMsara 0.1.0 4. OPERATING SYSTEM REQUIREMENTS: macOS 13 or later on Apple silicon (arm64). This is the build that was tested; other targets are listed only when they have been built and run for these tests. 5. APPROX HARD DISK SPACE REQUIRED FOR INSTALLATION: About 6.3 MB: the release binary s140_run, which needs no other runtime files beyond the TOML input and the EPW weather file. 6. MINIMUM RAM REQUIRED FOR SOFTWARE OPERATION: 16 MB: the largest peak resident memory of any submitted test case, measured with /usr/bin/time -l on the tested build. 7. MINIMUM DISPLAY MONITOR REQUIREMENTS: None. SIMsara is a command-line program with no graphical display. 8. OTHER HARDWARE OR SOFTWARE-RELATED REQUIREMENTS: Input is TOML (docs/TOML-INPUT.md in the source distribution) with EPW weather. Building from source needs Rust 1.98.1. The Standard 140 harness scripts that generate the test inputs and fill the output templates need Python 3.11 or later, standard library only. INFORMATIVE NOTE: Item 8 can be used to supply additional relevant information. =============================================================================== B. REPORT BLOCK FOR ALTERNATIVE MODELING METHODS =============================================================================== CONTENT: If the software being tested provides alternative modeling methods or algorithms for performing the tests, this section shall describe modeling methods used for the tests. INSTRUCTIONS: If alternative modeling methods are applicable, a separate note for each alternative modeling method or algorithm situation shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If alternative modeling methods are not applicable, specify "NONE" in place of the information below. NOTE 1 - Unitary System Parent (Section 5.1.1.4 and 9.2.1.10) --------------------------------------------------------- 1.1 Describe the Effect Being Simulated: How the DX coil and the indoor fan follow the zone load, and which loads the program reports for the zone. 1.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 1.2.1 AirLoopHVAC:UnitaryHeatCool Physical Meaning: Heat-cool unitary on an air loop: supply fan, DX cooling coil and heating coil controlled to the load of one zone. 1.2.2 AirLoopHVAC:UnitarySystem Physical Meaning: Generic unitary system with load or setpoint control and multi-speed fans and coils. 1.2.3 ZoneHVAC:PackagedTerminalAirConditioner Physical Meaning: Packaged terminal unit serving the zone directly, without an air loop; it reports the cooling it delivers to the zone. 1.3 Setting or Capability Used: AirLoopHVAC:UnitaryHeatCool on an air loop without outdoor air, the parent of the CE b cases (CE300-CE545), so that all Section 9 cases use one modeling method (5.1.1.4). Its heating coil is never available (heat off). NOTE 2 - Cooling Coil Model (Section 9.2.1.10.3) --------------------------------------------------------- 2.1 Describe the Effect Being Simulated: Total, sensible and latent capacity and compressor power of the unit at each entering condition, and so every consumption, coil-load, COP and humidity result. 2.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 2.2.1 Coil:Cooling:DX:SingleSpeed Physical Meaning: Rated gross capacity, sensible heat ratio, COP and flow with capacity and energy-input-ratio curves of entering wet bulb and outdoor dry bulb; the sensible and latent split by the apparatus dew point and bypass factor method, with a dry-coil branch when the entering air is dry. 2.2.2 Other DX coil objects Physical Meaning: Multi-speed, variable-speed and performance-table coils (not used). 2.3 Setting or Capability Used: Coil:Cooling:DX:SingleSpeed, with the bypass factor derived by the program at the rated point and applied through the apparatus dew point method, independent of the part-load ratio (9.2.1.10.3.3 lets a program that calculates the bypass factor skip that input; 9.2.1.10.4.4). NOTE 3 - Cycling Fan and Part-Load Degradation (Section 9.2.1.10.1 d and e, and 9.2.1.10.4) --------------------------------------------------------- 3.1 Describe the Effect Being Simulated: Compressor and fan energy at part load. 3.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 3.2.1 Fan operating mode Physical Meaning: Cycling with the compressor (operating-mode schedule 0) or continuous (1). 3.2.2 Part-load fraction curve Physical Meaning: PLF(PLR) divides the runtime fraction; the indoor fan runs for the same runtime fraction. 3.3 Setting or Capability Used: Cycling fan; PLF = 1 - Cd (1 - PLR) with Cd 0.229, the COP degradation factor of Figure 9-3, so the runtime fraction is PLR / PLF (9.2.1.10.4.2) for the compressor, the outdoor fan and the indoor fan; PLR on the gross basis of Equation 9-2. NOTE 4 - Surface Convection and Time Step (Section 9.2.1.8, 9.2.1.9) --------------------------------------------------------- 4.1 Describe the Effect Being Simulated: Heat gain through the R 100 envelope (a few percent of the load in the low-load cases) and the resolution of the thermostat. 4.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 4.2.1 Inside: Simple, TARP, CeilingDiffuser, Adaptive, ASTMC1340 Physical Meaning: Constant or correlation-based interior coefficients. 4.2.2 Outside: SimpleCombined, TARP, DOE-2, MoWiTT Physical Meaning: A combined convection and radiation coefficient to the outdoor air (SimpleCombined), or convection with explicit long-wave exchange to sky and ground. 4.2.3 Zone time steps per hour Physical Meaning: 1 to 60. 4.3 Setting or Capability Used: TARP inside; SimpleCombined outside, the form of the specified combined exterior coefficient (exchange with the outdoor air only); 6 zone steps per hour, the unit cycling within each step through its part-load ratio. =============================================================================== C. REPORT BLOCK FOR EQUIVALENT MODELING METHODS =============================================================================== CONTENT: This section shall describe equivalent modeling methods used to perform the tests. When the software does not model an effect exactly as stated in the standard or does not permit the input values required, equivalent modeling methods shall be permitted to perform the test. INSTRUCTIONS: If equivalent modeling methods are applied, a separate note for each instance of equivalent modeling shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If equivalent modeling methods are not applicable, specify "NONE" in place of the information below. NOTE 1 - Split System Modeled as a Heat-Cool Unitary with Heat Always Off (Section 9.2.1.10) ------------------------------------------------------------------------------- 1.1 Describe the Effect Being Simulated: All results. 1.2 Section(s) of the Standard where Relevant Inputs are Specified: A single-speed split air conditioner with an air-cooled condenser, a draw-through indoor fan, indoor and outdoor fans cycling with the compressor, no outdoor air, heat always off. 1.3 Equivalent Input(s) Used: One air loop without outdoor air whose branch holds an AirLoopHVAC:UnitaryHeatCool, controlled to the zone's load (the parent of the CE b cases, Block B note 1): a Coil:Cooling:DX:SingleSpeed, then a Coil:Heating:Electric that the unit object requires, with an availability schedule of 0, then a draw-through Fan:OnOff of 230 W at the rated flow (total and motor efficiency 1, so that the power is exactly the specified 230 W, all heat to the air as 9.2.1.10.6.1.2 specifies; the specified 0.5 efficiency and 271 Pa give 230.2 W at this flow) with an operating-mode schedule of 0 (cycling); cooling, heating and no-load supply flows are the rated flow and dehumidification control is none. A constant-volume terminal without reheat delivers the air and the zone air returns to the unit. The thermostat is ThermostatSetpoint:SingleCooling (non-proportional). 1.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: Same components, arrangement and control as the specified unit; the heating coil never operates. NOTE 2 - Performance Map Fitted to Curves (Section 9.2.1.10.3 (Tables 9-5 to 9-10; CE100MAP.xls)) ------------------------------------------------------------------------------- 2.1 Describe the Effect Being Simulated: Capacity and power at every operating point. 2.2 Section(s) of the Standard where Relevant Inputs are Specified: Tables 9-5 to 9-10 in their electronic file CE100MAP.xls (Table 9-7, gross capacities in SI units, is fitted) and the rated block. 2.3 Equivalent Input(s) Used: The map's gross total capacity and compressor-plus-outdoor-fan power are fitted to biquadratics in entering wet bulb and outdoor dry bulb, normalized and anchored at the rated point (SIMsara's scripts/s140/fit.py, standard least squares). Fit errors over the 24 wet-coil points: capacity RMS 0.120 percent, maximum 0.214 percent; power RMS 0.232 percent, maximum 0.549 percent; the rated point exactly. Rated values from the map: gross capacity 8181 W, gross SHR 0.778, coil COP 4.161 (compressor and outdoor fan), flow 0.42475 m3/s. The flow-fraction curves are 1 (constant flow). The curves are entered without clamping: the dry-coil cases evaluate them at an entering wet bulb of 13.9 to 14.8 C, slightly below the 15.0 C lowest map point, as 9.2.1.10.3.1 requires (the program extrapolates the performance data). 2.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The curve form is the program's; the fit reproduces the map within the stated errors. NOTE 3 - Weather Data Converted from TMY2 (Section 9.2.1.1 and Annex A1.2.1 (Tables A1-4 and A1-6)) ------------------------------------------------------------------------------- 3.1 Describe the Effect Being Simulated: Outdoor dry bulb and humidity of every case. 3.2 Section(s) of the Standard where Relevant Inputs are Specified: CE100A.TM2, CE110A.TM2, CE165A.TM2 and CE200A.TM2. 3.3 Equivalent Input(s) Used: SIMsara reads EPW. SIMsara's converter (scripts/s140/wx/tm2.py) writes each TM2 file as an EPW; the processed files are archived with their sha256. The location line carries the site of Table A1-6: latitude 25.8 N, longitude 80.3 W, altitude 2 m, time zone 5 (75 W). 3.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The dry bulb and humidity are carried over unchanged (plan WP1). NOTE 4 - Compressor and Condenser Fan Split; Coil Loads from Rates (Section 9.3.1) ------------------------------------------------------------------------------- 4.1 Describe the Effect Being Simulated: Reported compressor, condenser-fan and coil-load energies. 4.2 Section(s) of the Standard where Relevant Inputs are Specified: February compressor and condenser-fan consumption and evaporator coil loads. 4.3 Equivalent Input(s) Used: The DX coil reports one electricity energy for compressor plus outdoor fan: the condenser fan is 108 W times the coil runtime fraction times the time step, and the compressor is the remainder. The DX coil reports its total, sensible and latent cooling rates but no energies, so the coil loads are the rates times the step length summed over February. The unit reports no zone loads (9.3.1.3): the zone sensible load is the sensible cooling the supply air delivers to the zone (the zone's air-system sensible cooling rate), the zone latent load is the coil's latent cooling rate, since with no outdoor air and no infiltration the coil removes all the moisture that leaves the zone, and the zone total load is their sum, each times the step length summed over February. COP is the net refrigeration effect over the total cooling energy consumption (9.3.1.4 a): the evaporator coil total load less the indoor fan energy, divided by compressor plus both fans (Section 3); the February mean is the ratio of the February totals and the maximum and minimum are hourly. 4.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: Exact for quantities held constant within each step; the COP definition reproduces the COP columns of the analytical solutions from their own energy columns. NOTE 5 - Simulation Period (Section 5.1.1.8.3) ------------------------------------------------------------------------------- 5.1 Describe the Effect Being Simulated: Initialization. 5.2 Section(s) of the Standard where Relevant Inputs are Specified: At least the first two months; results for February. 5.3 Equivalent Input(s) Used: Run January 1 to February 28 with warmup to convergence; February reported. 5.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: As specified. =============================================================================== D. REPORT BLOCK FOR USE OF NON-SPECIFIED INPUTS =============================================================================== CONTENT: This section shall describe nonspecified inputs used to perform the tests. Use of nonspecified inputs shall be permitted only for the following specified sections relating to the following topics: * Alternative constant exterior surface coefficients in Sections 7.2.1.9.3, 7.2.3.1.4.3, 7.2.3.3.2, and 9.2.1.8 * Alternative constant interior surface coefficients in Sections 7.2.1.10.3, 7.2.3.1.4.4, 7.2.3.2.2, and 9.2.1.9 * Alternative constant interior solar distribution fractions in Sections 7.2.1.12, 7.2.2.1.2.2, 7.2.2.1.6.2, 7.2.2.1.7.2, 7.2.2.2.7.4, 7.2.3.9.3, 7.2.3.10.2, and 7.2.3.12.2 * Air density given at specific altitudes for the space-cooling and space- heating equipment cases in Sections 9.2.1.4.3, 9.2.3.4.3, and 10.2.1.4.3. INSTRUCTIONS: If nonspecified inputs are applied, a separate note for each use of nonspecified inputs shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If nonspecified inputs are not applied, specify "NONE" in place of the information below. NOTE 1 - Air Density and Envelope Inputs (Section 9.2.1.4.3, 9.2.1.8, 9.2.1.9) ------------------------------------------------------------------------------- 1.1 Describe the Effect Being Simulated: Fan mass flow and power; envelope heat gain. 1.2 Section(s) of the Standard where Relevant Inputs are Specified: Air density at the site altitude; the constant combined surface coefficients. 1.3 Nonspecified Input(s) Used: The program converts the rated volume flow to mass flow with the density of dry air at 20 C and the standard pressure of the site elevation, and uses the state-dependent density elsewhere (9.2.1.4.3 lets a program that calculates air density skip the 1.201 kg/m3). The combined surface coefficients of 8.29 and 29.3 W/m2K are not entered (9.2.1.8 and 9.2.1.9 let a program that calculates surface radiation and convection skip them); the envelope uses the algorithms of Block B, with the single R 100 insulation layer entered as two Material:NoMass layers of R 50 so that the inner face carries solar absorptance 0.6 and the outer 0.1 (infrared emittance 0.9 on both, Table 9-3), because the materials have no thermal capacitance (9.2.1.4.2). 1.4 Physical, Mathematical or Logical Justification for Use of the Nonspecified Input(s) � provide supporting calculations, if relevant: The insulation resistance dominates the overall U-value (0.010 W/m2K), so the film coefficients change the envelope gain by well under 1 W. =============================================================================== =============================================================================== E. REPORT BLOCK FOR OMITTED TEST CASES AND RESULTS =============================================================================== CONTENT: This section shall describe test cases that were omitted and/or individual results of test cases that were omitted along with the reason for the omission. INSTRUCTIONS: If test cases were omitted, a separate note to describe each type of omission shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If there are no omitted test cases, specify "NONE" in place of the information below. NONE =============================================================================== F. REPORT BLOCK FOR CHANGES TO SOURCE CODE FOR THE PURPOSE OF RUNNING THE TESTS, WHERE SUCH CHANGES ARE NOT AVAILABLE IN PUBLICLY RELEASED VERSIONS OF THE SOFTWARE =============================================================================== CONTENT: This section shall describe changes to software source code made to allow the software to run a test, where such changes are not available in a publicly released version of the software. INFORMATIVE NOTE: This section addresses special situations where a change to source code is necessary to activate a feature or to permit inputs needed for a test when these features are not available in the publicly released version of the software. INSTRUCTIONS: If changes to the source code for the purpose of running a test are applied, separate notes to describe each source code modification shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If changes to source code are not applied, specify "NONE" in place of the information below. NONE =============================================================================== G. REPORT BLOCK FOR ANOMALOUS RESULTS =============================================================================== CONTENT: Describing anomalous results shall be permitted but is not required. If anomalous test results are described, this section shall be used. INSTRUCTIONS: If anomalous test results are described, each type of anomalous result shall be described in a separate note. The standard format shown below and a separate number and title for each note item shall be applied. If anomalous results are not discussed, it shall be permitted to specify "NONE" in place of the information below. NOTE 1 - Coil Sensible Load of the Wet-Coil Cases (Section 9.3.1 (Annex B16, Section B16.5.1; evaporator coil sensible load)) ------------------------------------------------------------------------------- 1.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: CE150, CE160, CE165 and CE180 evaporator coil sensible load (0.12 to 0.74 percent below the example results); CE180 consumption (0.09 percent above) and maximum COP (0.41 percent below). 1.2 Explanation of Reason for the Anomalous Results: The sensible and latent split of a wet coil follows the apparatus dew point and bypass factor method with the bypass factor derived at the rated point, so the split at other entering conditions differs slightly from the map's own sensible capacities; CE180 has the lowest sensible heat ratio. The coil total and latent loads lie within 0.3 percent of the analytical solutions. NOTE 2 - Low Part-Load COP and Results at the Edge of the Example Range (Section 9.3.1 (Annex B16, Section B16.5.1)) ------------------------------------------------------------------------------- 2.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: CE130, CE190 and CE195 mean and maximum COP (0.16 to 0.54 percent below the example results, inside or within 0.23 percent of the analytical range); zone sensible and total loads of CE110, CE150, CE160, CE180 and CE200 (0.001 to 0.005 percent above); mean and minimum IDB of CE130, CE140, CE190 and CE195 (22.2000 to 22.2002 C, against a setpoint of 22.2 C); CE180 mean humidity ratio (0.023 percent below). 2.2 Explanation of Reason for the Anomalous Results: At part-load ratios below 0.1 the COP depends on the degradation curve and on how the indoor fan's runtime is counted; SIMsara runs both fans for the runtime fraction PLR / PLF. The other items are within 0.005 percent of the range and within 0.005 percent of the analytical solutions; the zone temperature overshoots the setpoint by less than 0.001 K within the ten-minute step. =============================================================================== ===============================================================================