MODELING NOTES FOR ASHRAE STANDARD 140 =============================================================================== INTRODUCTION =============================================================================== This document shall include supplemental information about the ASHRAE Standard 140 tests performed. One S140outNotes document shall be provided for each set of tests (e.g., one for the building thermal and fabric load tests of Section 7.2; one for the space cooling equipment analytical verification tests of Sections 9.2; etc.) The types of information listed below shall be provided in this document, each in a separate section: a. Software information b. Alternative modeling methods c. Equivalent modeling methods d. Nonspecified inputs e. Omitted test cases and results f. Changes made to source code for the purpose of running the tests, where such changes are not available in publicly released versions of the software g. Anomalous results. Notes in this document shall be limited to the topics shown above. Notes must be factual and objective and shall only refer to the software being tested. Notes shall not refer to any other software program. INFORMATIVE NOTE: Text at the start of each section describes the content of the section for the reader and provides instructions for supplying the content. Sample notes are provided in a separate document (S140outNotes_Examples.TXT). =============================================================================== A. SOFTWARE INFORMATION =============================================================================== CONTENT: This section shall include reference information for the software - the vendor, name, and version of the software, plus operating system and computer hardware requirements. INSTRUCTIONS: Information for items 1 through 7 below shall be provided. Information for Item 8 shall be permitted but is not required. 1. SOFTWARE VENDOR: Jared Bell, Roots Ontological Technologies, LLC 2. SOFTWARE NAME: SIMsara 3. SOFTWARE VERSION (unique software version identifier): SIMsara 0.1.0 4. OPERATING SYSTEM REQUIREMENTS: macOS 13 or later on Apple silicon (arm64). This is the build that was tested; other targets are listed only when they have been built and run for these tests. 5. APPROX HARD DISK SPACE REQUIRED FOR INSTALLATION: About 7.2 MB: the release binary s140_run, which needs no other runtime files beyond the TOML input and the EPW weather file. 6. MINIMUM RAM REQUIRED FOR SOFTWARE OPERATION: 16 MB: the largest peak resident memory of any submitted test case, measured with /usr/bin/time -l on the tested build. 7. MINIMUM DISPLAY MONITOR REQUIREMENTS: None. SIMsara is a command-line program with no graphical display. 8. OTHER HARDWARE OR SOFTWARE-RELATED REQUIREMENTS: Input is TOML (docs/TOML-INPUT.md in the source distribution) with EPW weather. Building from source needs Rust 1.98.1. The Standard 140 harness scripts that generate the test inputs and fill the output templates need Python 3.11 or later, standard library only. INFORMATIVE NOTE: Item 8 can be used to supply additional relevant information. =============================================================================== B. REPORT BLOCK FOR ALTERNATIVE MODELING METHODS =============================================================================== CONTENT: If the software being tested provides alternative modeling methods or algorithms for performing the tests, this section shall describe modeling methods used for the tests. INSTRUCTIONS: If alternative modeling methods are applicable, a separate note for each alternative modeling method or algorithm situation shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If alternative modeling methods are not applicable, specify "NONE" in place of the information below. NOTE 1 - Exterior Surface Convection (Section 7.2.1.9) --------------------------------------------------------- 1.1 Describe the Effect Being Simulated: Exterior convective heat transfer of all opaque surfaces, with exterior infrared exchange to the sky, the ground and the air computed separately at each time step. 1.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 1.2.1 SimpleCombined Physical Meaning: combined convective and radiative coefficient from wind speed and roughness 1.2.2 TARP Physical Meaning: natural and wind-driven convection by surface orientation and roughness 1.2.3 DOE-2 Physical Meaning: TARP natural convection combined with a roughness-corrected MoWiTT forced term 1.2.4 MoWiTT Physical Meaning: natural and forced convection correlations for smooth surfaces 1.3 Setting or Capability Used: DOE-2, with explicit time-step long-wave exchange to sky, ground and air. Cases 450 and 470 enter the constant exterior combined coefficients instead (Block C). NOTE 2 - Interior Surface Convection (Section 7.2.1.10) --------------------------------------------------------- 2.1 Describe the Effect Being Simulated: Interior convective heat transfer of all surfaces; interior infrared exchange is computed separately. 2.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 2.2.1 Simple Physical Meaning: constant natural-convection coefficients by orientation 2.2.2 TARP Physical Meaning: variable natural convection from the surface-to-air temperature difference and tilt 2.2.3 CeilingDiffuser Physical Meaning: correlations for mixed convection with a ceiling diffuser 2.2.4 AdaptiveConvectionAlgorithm Physical Meaning: correlation chosen from the flow regime 2.2.5 ASTMC1340 Physical Meaning: correlations of ASTM C1340 for attic surfaces 2.3 Setting or Capability Used: TARP. Cases 450 and 460 enter the constant interior combined coefficients instead (Block C). NOTE 3 - Interior Solar Distribution (Section 7.2.1.12 and 7.2.2.2.7.4) --------------------------------------------------------- 3.1 Describe the Effect Being Simulated: Distribution of the solar radiation transmitted by the windows among the interior surfaces of every windowed case, and the part of it lost back out through the windows. 3.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 3.2.1 FullInteriorAndExterior Physical Meaning: beam radiation projected onto the interior surfaces it strikes 3.2.2 FullExterior Physical Meaning: all entering beam radiation falls on the floor 3.2.3 MinimalShadowing Physical Meaning: as FullExterior, without exterior shading by other surfaces 3.3 Setting or Capability Used: Full interior and exterior distribution. The beam radiation entering each window is projected, from the sun position of each hour, onto the interior surfaces it strikes (the floor, the walls and the other windows). The diffuse radiation transmitted by each window first reaches each interior surface in proportion to its view factor from the window and is absorbed there by the surface's solar absorptance. The reflected beam radiation and the reflected remainder of the diffuse radiation are distributed over all interior surfaces in proportion to area times solar absorptance; the share falling on a window is absorbed in its panes or transmitted back out. The interior solar absorptances are the specified ones; no distribution fractions are entered (the alternative of Section 5.1.1.6 c is not used). NOTE 4 - Exterior Shading by Overhangs and Fins (Section 7.2.2.1.1 and 7.2.2.1.3) --------------------------------------------------------- 4.1 Describe the Effect Being Simulated: Beam, sky diffuse and ground-reflected solar radiation on the windows and walls of the shaded cases 610, 630, 910, 930, 290 and 310. 4.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 4.2.1 Simple sky diffuse modeling Physical Meaning: sky diffuse shading ratios computed once, for devices whose transmittance does not vary 4.2.2 Detailed sky diffuse modeling Physical Meaning: sky diffuse shading ratios recomputed when a device transmittance varies in time 4.2.3 With reflections Physical Meaning: solar reflected by the devices and the ground traced to each surface (not used) 4.3 Setting or Capability Used: Simple sky diffuse modeling, without reflections. Each overhang and fin is a shading surface of zero thickness, opaque to solar radiation, that shades with both faces, reflects nothing and has no heat balance. The sunlit part of each window and wall is found by polygon clipping of the shadows of the devices for every time step of a representative day, updated every day. Of the anisotropic sky diffuse radiation, the isotropic part is reduced by a constant ratio for each surface (the shaded to unshaded sky radiation summed over 144 sky patches, 6 altitudes by 24 azimuths), the horizon band by its own ratio, and the circumsolar part by the beam sunlit fraction. The ground-reflected radiation is not reduced by the devices, and no reflection from the devices is calculated. NOTE 5 - Window Model (Section 7.2.1.11, 7.2.2.1.6.1 and 7.2.2.1.7.1) --------------------------------------------------------- 5.1 Describe the Effect Being Simulated: Optical and thermal behavior of every window: transmitted and absorbed solar radiation and the heat flow through the glazing. 5.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 5.2.1 Layer by layer Physical Meaning: panes and gaps from their own properties; angular properties derived by the program 5.2.2 Simple glazing system Physical Meaning: the whole window from a U-factor, solar heat gain coefficient and visible transmittance 5.3 Setting or Capability Used: Layer by layer. Each pane is entered with its specified thickness, conductivity, normal-incidence solar transmittance, front and back solar reflectances and front and back infrared emittances (Tables 7-10, 7-17 and 7-21; the low-emissivity coating on the inside face of the outer pane), and the gap with its fill gas and width. The program derives the angle-dependent optical properties of each pane and of the glazing system from the normal-incidence values, and solves the pane and gap heat balance at every time step with temperature-dependent fill-gas properties. The visible properties the input asks for are not specified; they enter only daylighting, which no case uses, and are set to the solar values. NOTE 6 - Sky Long-Wave Radiation (Section 7.2.1.1.1 and 7.2.1.8.2) --------------------------------------------------------- 6.1 Describe the Effect Being Simulated: Sky temperature for exterior infrared exchange, and the reported Case 600 sky temperature. 6.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 6.2.1 Weather-file infrared Physical Meaning: sky emissivity from the horizontal infrared radiation field when present 6.2.2 Clark-Allen Physical Meaning: sky emissivity from dew point and opaque sky cover (Walton cloud correction) 6.3 Setting or Capability Used: Clark-Allen with the opaque-sky-cover correction, computed at run time, because the converted weather file carries no horizontal infrared radiation. The surrounding ground surface temperature is the outdoor air temperature of each time step. NOTE 7 - Time Step, Solar Geometry and Preconditioning (Section 5.1.1.7 and 7.2.1) --------------------------------------------------------- 7.1 Describe the Effect Being Simulated: Numerical resolution of all cases. 7.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 7.2.1 Time steps per hour Physical Meaning: 1 to 60 zone time steps per hour 7.2.2 Solar update frequency Physical Meaning: days between solar geometry updates 7.3 Setting or Capability Used: Six zone time steps per hour; solar geometry, the sunlit areas and the interior projection of the entering beam radiation (polygon clipping) updated every day (Periodic, frequency 1); warmup of at least 6 days until the loads and zone temperatures converge; conduction transfer functions for every opaque construction. NOTE 8 - Infiltration Air Density and Floor-to-Ground Infrared Exchange (Section 7.2.1.6 and 7.2.1.5) --------------------------------------------------------- 8.1 Describe the Effect Being Simulated: Infiltration mass flow at altitude; long-wave exchange of the raised floor underside. 8.2 Optional Settings or Modeling Capabilities (list setting or capability and its physical meaning): 8.2.1 Air density Physical Meaning: from the weather-file station pressure (automatic) or at sea level 8.2.2 View factor to ground Physical Meaning: geometric from the surface tilt, or a user value 8.3 Setting or Capability Used: Automatic altitude adjustment: the infiltration rate is entered in air changes per hour and converted to mass flow with the outdoor air density at the weather-file station pressure (adjustment factor 1.0). The floor underside exchanges infrared radiation with the ground only (view factor to ground 1, geometric for a downward-facing surface). =============================================================================== C. REPORT BLOCK FOR EQUIVALENT MODELING METHODS =============================================================================== CONTENT: This section shall describe equivalent modeling methods used to perform the tests. When the software does not model an effect exactly as stated in the standard or does not permit the input values required, equivalent modeling methods shall be permitted to perform the test. INSTRUCTIONS: If equivalent modeling methods are applied, a separate note for each instance of equivalent modeling shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If equivalent modeling methods are not applicable, specify "NONE" in place of the information below. NOTE 1 - Weather Data Conversion (Section 7.2.1.1.1 and Annex A1) ------------------------------------------------------------------------------- 1.1 Describe the Effect Being Simulated: Weather input of every thermal fabric case. 1.2 Section(s) of the Standard where Relevant Inputs are Specified: 7.2.1.1.1 (normative 725650TY.csv, TMY3) and Annex A1 Table A1-1 (site). 1.3 Equivalent Input(s) Used: 725650TY.csv was converted to EPW by the SIMsara converter scripts/s140/wx/tmy3.py, mapping fields by name (pressure mbar to Pa, visibility m to km, precipitable water cm to mm; -9900 to the EPW missing code). The LOCATION line carries the specified site (Table A1-1: latitude, longitude, time zone and elevation). Horizontal infrared radiation is not in TMY3 and is left missing, so the program computes the sky emissivity (Block B, Sky Long-Wave Radiation). The converted file is archived with its sha256. 1.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The dry bulb, dew point, humidity, pressure, radiation, wind, sky cover and albedo fields are identical hour by hour to the source; the program computes the sky temperature by its stated method. NOTE 2 - High-Conductance Wall Element Air Gap and Floor Insulation (Section 7.2.3.1.4 and 7.2.1.5) ------------------------------------------------------------------------------- 2.1 Describe the Effect Being Simulated: Cases 200-250, 400-430 and 800 (air gap); every case (floor insulation). 2.2 Section(s) of the Standard where Relevant Inputs are Specified: 7.2.3.1.4.2 and Table 7-36; 7.2.1.4 Table 7-2, 7.2.2.2.1.1 Table 7-27, Table 7-31, 7.2.2.2.7.3 and 7.2.1.5 (140-2017a Tables 5-36, 5-2 and 5-27). 2.3 Equivalent Input(s) Used: The high-conductance elements are two opaque 3 m x 2 m subsurfaces in the south wall, each a construction of two panes with the Table 7-36 properties around an air gap entered as its specified constant resistance without mass. The floor insulation is a resistance without mass: the Table 7-2 resistance for every low-mass floor, and the Table 7-27 (and Table 7-31) resistance for every high-mass floor (Cases 800, 810, 900, 920, 940, 950, 980, 985 and 995, the Case 960 sun zone, and Cases 900FF, 950FF and 980FF). 2.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: Table 7-36 fixes the air gap properties as constant; its heat capacity (about 16 J/(m2 K)) is negligible. Section 7.2.1.5 asks for the minimum insulation density and specific heat the program allows. NOTE 3 - Night Ventilation Fan Entered as Scheduled Outdoor Air (Section 7.2.2.1.5) ------------------------------------------------------------------------------- 3.1 Describe the Effect Being Simulated: Cases 650, 950, 650FF and 950FF. 3.2 Section(s) of the Standard where Relevant Inputs are Specified: 7.2.2.1.5.1, 7.2.2.1.5.2 and Table 7-16 (vent fan flow, hours of operation, no fan heat gain). 3.3 Equivalent Input(s) Used: The vent fan is entered as a second outdoor-air infiltration input of the zone: the specified constant volume flow, scheduled on during the specified night hours and off otherwise, beside the continuous infiltration of Case 600. The volume flow is converted to mass flow with the outdoor air density at the weather-file station pressure, as the infiltration is (Block B). 3.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The specified fan brings outdoor air into the zone at a fixed flow with no fan heat; the scheduled infiltration input adds exactly that outdoor-air mass flow, at the outdoor air temperature, to the zone air heat balance. NOTE 4 - Shading Surfaces Opaque to Infrared Radiation (Section 7.2.2.1.1.2) ------------------------------------------------------------------------------- 4.1 Describe the Effect Being Simulated: The exterior infrared exchange of the surfaces that see a shading device (the shaded cases 610, 630, 910, 930, 290 and 310). 4.2 Section(s) of the Standard where Relevant Inputs are Specified: 7.2.2.1.1.2.1 b (infrared emittance of the shading devices). 4.3 Equivalent Input(s) Used: No input: the program treats shading surfaces as opaque to infrared radiation. The view of a shading surface reduces a surface's sky view factor, and that part of its view is counted as ground at the outdoor air temperature, whatever emittance the shading surface has. The specified infrared emittance of the devices is therefore not entered. 4.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The shading devices exchange no infrared radiation of their own in the specification; the program's treatment removes their share of the sky view and replaces it by radiation at the outdoor air temperature. NOTE 5 - Glass Density and Specific Heat Not Entered (Section 7.2.1.11, 7.2.2.1.6.1 and 7.2.2.1.7.1) ------------------------------------------------------------------------------- 5.1 Describe the Effect Being Simulated: Every window. 5.2 Section(s) of the Standard where Relevant Inputs are Specified: Tables 7-10, 7-17 and 7-21 (density and specific heat of the glass). 5.3 Equivalent Input(s) Used: Not entered. The program solves the window heat balance at each time step without thermal storage in the panes, so its window input has no glass density or specific heat: these are nonapplicable inputs (Section 5.1.1.3). 5.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: The panes are thin single sheets of glass; their heat capacity is small beside that of the zone, and the program's window model has no input for it. NOTE 6 - Constant Combined Surface Coefficients Entered as Convective Coefficients (Section 7.2.3.21 to 7.2.3.23) ------------------------------------------------------------------------------- 6.1 Describe the Effect Being Simulated: Cases 450, 460 and 470. 6.2 Section(s) of the Standard where Relevant Inputs are Specified: 7.2.3.21.1 and 7.2.3.21.2 with Table 7-46 (Case 450), 7.2.3.22.1 (Case 460, interior side) and 7.2.3.23.1 (Case 470, exterior side), and the informative note 1 of each. 6.3 Equivalent Input(s) Used: The program takes a constant convective coefficient per surface but has no input for a constant combined convective and radiative coefficient. Each Table 7-46 value is entered as the constant convective coefficient of every wall, the roof, the raised floor or the windows, on the interior side (Cases 450 and 460) or the exterior side (Cases 450 and 470), and the infrared emittance of every face that carries one is set to 0.000001 (the program accepts any value above zero; at this value the long-wave exchange of those faces is about a millionth of its usual size, see the justification): the inside or outside face of each opaque surface, and the inner face of the inner pane or the outer face of the outer pane of each window. The pane faces toward the window gap keep their specified emittance, and the other side of each surface keeps the Case 600 calculation (Block B). 6.4 Physical, Mathematical or Logical Justification of the Equivalent Input(s) � provide supporting calculations, if relevant: With these emittances the long-wave exchange of the affected faces with the sky, the ground, the air and the other zone surfaces is about a millionth of its usual size, so each face exchanges heat with the adjacent air at its constant coefficient alone, as a combined coefficient does. With the inside emittances near zero (Cases 450 and 460) the radiative part of the internal gains is absorbed by the zone surfaces in proportion to their areas. =============================================================================== D. REPORT BLOCK FOR USE OF NON-SPECIFIED INPUTS =============================================================================== CONTENT: This section shall describe nonspecified inputs used to perform the tests. Use of nonspecified inputs shall be permitted only for the following specified sections relating to the following topics: * Alternative constant exterior surface coefficients in Sections 7.2.1.9.3, 7.2.3.1.4.3, 7.2.3.3.2, and 9.2.1.8 * Alternative constant interior surface coefficients in Sections 7.2.1.10.3, 7.2.3.1.4.4, 7.2.3.2.2, and 9.2.1.9 * Alternative constant interior solar distribution fractions in Sections 7.2.1.12, 7.2.2.1.2.2, 7.2.2.1.6.2, 7.2.2.1.7.2, 7.2.2.2.7.4, 7.2.3.9.3, 7.2.3.10.2, and 7.2.3.12.2 * Air density given at specific altitudes for the space-cooling and space- heating equipment cases in Sections 9.2.1.4.3, 9.2.3.4.3, and 10.2.1.4.3. INSTRUCTIONS: If nonspecified inputs are applied, a separate note for each use of nonspecified inputs shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If nonspecified inputs are not applied, specify "NONE" in place of the information below. NONE =============================================================================== =============================================================================== E. REPORT BLOCK FOR OMITTED TEST CASES AND RESULTS =============================================================================== CONTENT: This section shall describe test cases that were omitted and/or individual results of test cases that were omitted along with the reason for the omission. INSTRUCTIONS: If test cases were omitted, a separate note to describe each type of omission shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If there are no omitted test cases, specify "NONE" in place of the information below. NONE =============================================================================== F. REPORT BLOCK FOR CHANGES TO SOURCE CODE FOR THE PURPOSE OF RUNNING THE TESTS, WHERE SUCH CHANGES ARE NOT AVAILABLE IN PUBLICLY RELEASED VERSIONS OF THE SOFTWARE =============================================================================== CONTENT: This section shall describe changes to software source code made to allow the software to run a test, where such changes are not available in a publicly released version of the software. INFORMATIVE NOTE: This section addresses special situations where a change to source code is necessary to activate a feature or to permit inputs needed for a test when these features are not available in the publicly released version of the software. INSTRUCTIONS: If changes to the source code for the purpose of running a test are applied, separate notes to describe each source code modification shall be provided. The standard format shown below and a separate number and title for each note shall be applied. If changes to source code are not applied, specify "NONE" in place of the information below. NOTE 1 - Program Changes Made for These Tests; All Cases Re-run (Section 5.1.1.9) ------------------------------------------------------------------------------- 1.1 List the Change(s) to the Source Code: While these tests were prepared the program gained the layer-by-layer window model (Block B), exterior shading surfaces with polygon clipping, the full interior and exterior solar distribution (Block B), sky-diffuse shading ratios with the exterior infrared view factors derived from them, and constant convective coefficients on window faces (Block C, Cases 450 to 470). Each was verified against a reference implementation of the same algorithms run on identical inputs, never against the example results. 1.2 List the Test Case(s) Relevant to the Change(s) in the Source Code: Every reported case was run with the tested build. The 14 opaque cases (195, 200 to 250, 395 to 430 and 800) and the Case 600 incident solar radiation and sky temperature, first run before these changes, were re-run with the tested build: their results are unchanged to the last digit. 1.3 Explanation of Why the Change is Not Included in the Publicly Released Version of the Software: The tested build carries these changes but no tagged public release includes them yet. =============================================================================== G. REPORT BLOCK FOR ANOMALOUS RESULTS =============================================================================== CONTENT: Describing anomalous results shall be permitted but is not required. If anomalous test results are described, this section shall be used. INSTRUCTIONS: If anomalous test results are described, each type of anomalous result shall be described in a separate note. The standard format shown below and a separate number and title for each note item shall be applied. If anomalous results are not discussed, it shall be permitted to specify "NONE" in place of the information below. NOTE 1 - Case 600 Sky Temperature at the Edge of the Example Range (Section 7.2.1.1; 140-2017a 6.2.1.2.3) ------------------------------------------------------------------------------- 1.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: Case 600 annual mean and minimum sky temperature (C178, D178), and hourly sky temperatures on Feb 1, May 4 and July 14 (I230-K253) lie just outside the range of the example results, beyond the example value that forms the bound of the range. 1.2 Explanation of Reason for the Anomalous Results: SIMsara lies beyond the bounding example value by at most 0.14 C (annual mean 0.004 C, minimum 0.124 C, hourly values at most 0.14 C). The cause is the sky long-wave route: the converted TMY3 file carries no horizontal infrared radiation, so SIMsara computes it with the Clark-Allen correlation at run time. Run on the informative 725650TYCST.epw, which carries the infrared field, SIMsara's annual mean and minimum lie within 0.005 C of those bounding example values. NOTE 2 - Case 600 Hourly Incident Solar Radiation at the Edge of the Example Range (Section 7.2.1; 140-2017a 6.2.1.8) ------------------------------------------------------------------------------- 2.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: Case 600 hourly incident solar radiation on May 4 and July 14 (cells in D247-E248 and F234-H245) lies just outside the range of the example results. 2.2 Explanation of Reason for the Anomalous Results: In each of these hours SIMsara lies beyond the bounding example value by at most 0.05 Wh/m2 (0.04 percent), a difference in the last digits of the hourly integration; the annual incident solar radiation on all five surfaces lies inside the range. NOTE 3 - Windowed-Case Results at the Edge of the Example Range (Section 7.3) ------------------------------------------------------------------------------- 3.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: Annual sensible cooling of Cases 670, 695, 270, 300 and 320 (D77, D80, D99, D102, D104); peak cooling of Cases 960 and 440 (I87, I110); monthly peak loads of Cases 600 and 900 (E190, M190, H191, E195, H195, H198); hourly transmitted solar radiation of Cases 600, 660 and 670 on February 1, May 4 and July 14 (cells in L234-T248); hourly loads on February 1 and July 14 (cells in C270-V282) and the Case 640 zone temperature at hour 19 of February 1 (Y280); hourly free-float temperatures of Cases 650FF and 950FF on July 14 (E302-F307). 3.2 Explanation of Reason for the Anomalous Results: Each value lies beyond the bounding example value by a small margin: annual cooling loads by at most 0.015 MWh (0.22 percent), peak cooling loads by at most 0.001 kW (0.02 percent), monthly peak loads by at most 0.004 kW (0.11 percent), hourly transmitted solar radiation by at most 0.03 Wh/m2 (0.02 percent), hourly loads by at most 0.14 kWh (up to 6 percent of the bounding value, in the cooling hours around noon of February 1), the Case 640 zone temperature by 0.19 C and the free-float temperatures by at most 0.06 C. These results follow from the specified inputs through the program's layer-by-layer window model and its full interior and exterior solar distribution (Block B); no input was adjusted toward the example results (Section 5.1.1.9). Every evaluated Annex A3 range in which these cases appear holds the program's result; the example results are informative. NOTE 4 - Shaded-Case Results at the Edge of the Example Range (Section 7.2.3.11, 7.2.3.13 and 7.3) ------------------------------------------------------------------------------- 4.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: Annual sensible cooling of Case 290 (D101) and peak heating of Case 310 (E103) lie just outside the range of the example results, beyond the example value that forms the bound of the range. 4.2 Explanation of Reason for the Anomalous Results: Case 290 lies beyond the bounding example value by less than 0.002 MWh (0.04 percent) and Case 310 by less than 0.0001 kW (0.002 percent). The overhangs and fins are entered as nearly as the program allows (Figures 7-3, 7-5 and 7-6; Section 7.2.2.1.1.2; the infrared emittance of 7.2.2.1.1.2.1 b has no input, Block C), and the results follow through the program's polygon-clipping shading, sky-diffuse shading ratios, the treatment of the devices' sky view as ground at outdoor air temperature (Block C) and full interior and exterior solar distribution (Block B); no input was adjusted toward the example results (Section 5.1.1.9). Every Annex A3 range in which the shaded cases appear holds the program's result; the example results are informative. NOTE 5 - Constant-Coefficient Case Results at the Edge of the Example Range (Section 7.2.3.21 to 7.2.3.23 and 7.3) ------------------------------------------------------------------------------- 5.1 Test Case(s) and Specific Results from the Case(s) that are Anomalous: Peak heating of Case 450 (E111), peak cooling of Case 460 (I112), and annual heating and peak cooling of Case 470 (C113, I113) lie just outside the range of the example results, beyond the example value that forms the bound of the range. 5.2 Explanation of Reason for the Anomalous Results: Case 450 lies beyond the bounding example value by less than 0.0001 kW (0.001 percent), Case 460 by less than 0.002 kW (0.02 percent), and Case 470 by less than 0.002 MWh (0.03 percent) and 0.001 kW (0.01 percent). The constant combined coefficients are entered as constant convective coefficients with near-zero infrared emittance on the faces they apply to, the input the informative notes of Sections 7.2.3.21.1 and 7.2.3.21.2 describe (Block C); no input was adjusted toward the example results (Section 5.1.1.9). No Annex A3 range includes these cases; the example results are informative. =============================================================================== ===============================================================================